AD1400B-AD900B-AD900C Circolatore d'aria ad alte portate
INDICE
1 AVVERTENZE GENERALI 2 AVVERTENZE PARTICOLARI 3 TIPOLOGIA 4 CARATTERISTICHE PRINCIPALI 5 DATI 6 DIMENSIONI E DISTANZE 7 COMPONENTI 8 INSTALLAZIONE 9 SCHEMI COLLEGAMENTO ELETTRICO
9.1 CTRL-A (accessorio a richiesta) AD1400B-AD900B 9.2 CTRL-A2 (accessorio a richiesta) AD1400B-AD900B 9.3 COMANDO CON POTENZIOMETRO ESTERNO (non fornito) AD1400B-AD900B 9.4 CTRL-XWS (accessorio a richiesta) AD1400B-AD900B 9.5 CTRL-XTHI (accessorio a richiesta) AD1400B-AD900B 9.6 AD900C 10 PULIZIA 11 DICHIARAZIONE DI CONFORMITÀ E INCORPORAZIONE

Istruzioni Originali
2 2 2 3 3 3 4 4 6 6 7 8 8 9 10 10 11

1 AVVERTENZE GENERALI
Leggere attentamente le istruzioni contenute nel manuale. Questo Manuale Specifico deve essere letto unitamente al "Manuale Generale di Installazione, Uso e Manutenzione". Nota: conservare il manuale per future consultazioni. Ci riserviamo il diritto di perfezionare e modificare il manuale, i prodotti e gli accessori senza l'obbligo di aggiornare i manuali e i ventilatori prodotti precedentemente a tali eventuali revisioni. L'installazione, i collegamenti elettrici e la manutenzione della macchina devono essere effettuate da un installatore qualificato e autorizzato e in accordo con le regole locali

2 AVVERTENZE PARTICOLARI
Oltre alle precauzioni contenute nel "Manuale Generale di Installazione, Uso e Manutenzione" è necessario prestare particolare attenzione alle seguenti note:
- il ventilatore deve essere installato ad un'altezza non inferiore a 2,7m dal pavimento sottostante. L'installazione ad un'altezza inferiore è considerata "uso improprio". In caso di "uso improprio" il produttore declina ogni responsabilità in relazione a qualsiasi danno che possa essere causato a persone o cose, e qualsiasi tipo di garanzia sarà considerata invalidata.

COPPIE DI SERRAGGIO BULLONERIA TE E TCEI FILETTATURA METRICA PROFILO TRIANGOLARE PASSO GROSSO - CLASSE 8.8

Dimensioni M6

M8

M10 M12 M14 M16

Nm

9,5

23

46

79

127 198

Tabella 1 Utilizzare i valori riportati in tabella per il serraggio di tutta la viteria.

- Controllare almeno annualmente il serraggio di tutta la viteria. - Il ventilatore non deve lavorare in condizioni d'elevata ventosità ( 6m/s).

L'installatore e il proprietario della struttura sono responsabili della posa corretta e in sicurezza del ventilatore, secondo le norme vigenti nel luogo di installazione.

3 TIPOLOGIA
Ventilatori assiali per installazione in sospensione o a parete progettati per applicazioni industriali, civili e zootecniche, in cui sono richieste alte prestazioni.

2

4 CARATTERISTICHE PRINCIPALI
· Struttura resistente e robusta (Acciaio zincato) · Connessioni elettriche semplificate · Temperatura max +50°C · Assenza di riduttore ad ingranaggi a vantaggio di silenziosità
e nessuna manutenzione ordinaria
5 DATI

· Versione B : Motore EC brushless monofase ad alta efficienza, 220/277Vac, 50/60Hz, IP55, provvisto di elettronica di controllo integrata e filtri EMC, velocità regolabile e adatto per servizio continuo S1
· Versione C: Motore AC a induzione trifase, TEFC, 230400Vac, 50Hz, IP55, adatto per servizio continuo S1

Modello

Diam. ventola

AD1400B (1) AD900B (1) AD900C (2)

1170 800 800

Velocità rotazione
max
r/min
500 1200 920

Potenza assorbita
max
kW
1,40 0,99 0,62

Spinta max
N
105 56 36

Portata max AMCA 230-15

cfm
20551 10300 8240

m3/h
34917 17500 14000

SPI(3) W/(m3/s) 144,3
203,7
159,4

Portata max AMCA 230-99

cfm
29064 14567 11653

m3/h
49380 24749 19799

SPI(3) W/(m3/s) 102,1
144,0
112,7

(1) Dati @230Vac, 50 Hz (2) Dati @400Vac, 50 Hz (3) Potenza max assorbita / portata max

6 DIMENSIONI E DISTANZE

13B82 11C90

27F0

Ø10

2E10

1273

1382 1190

270

210

Punti di sospensione

1273

o fissaggio

2G08

13A82

208

aeraul iqa

1200
12D00

1273

1382

1273 1200 1382

478

h min

Modello

A

B

C

D

E

mm

mm

mm

mm

mm

AD1400B

1382

1382

1189

1200

210

AD900B

951

951

819

780

210

AD900C

951

951

819

780

210

47I 8

478

F

G

mm

mm

270

208

270

120681

270

132

I

h (min)* Peso

mm

mm

kg

478

2700aeraul iq5a2

431 aerau2l iq7a00

40

402

2700

36

*ATTENZIONE: Il ventilatore deve essere installato ad un'altezza non inferiore a 2,7m dal pavimento sottostante.

1190

210

1273

ATTENZIONE: Prevedere una distanza minima di 11,3582m tra il ventilatore ed even27t0uali pareti/ostacoli e tra un ventilatore e l'altro

in caso si tratti si installazione in linea di più macchine.

distanza m?inima 1,5m

dismtainn.zdaistmanicnei=m1a5010,5m







3

7 COMPONENTI
2
1

3
Fig. XII

Fig. XII
44

5235 2636

Fig. XII 23

Pos.

Descrizione

Q.tà

1

GIRANTE

1

2

CARCASSA

1

3

MOTORE

1

4

GOLFARE M10

4

5

RONDELLA

8

6

VITE M10x25

4

8 INSTALLAZIONE
ATTENZIONE: Assicurarsi che l'interruttore generale dell'impianto sia spento prima di qualsiasi operazione di installazione, manutenzione o collegamento elettrico! Il ventilatore deve essere installato ad un'altezza non inferiore a 2,7m dal pavimento sottostante. Il ventilatore dovrà essere installato con uno spazio circostante sufficiente per effettuare le normali operazioni di montaggio/ smontaggio, pulizia e manutenzione.

ATTENZIONE: l'installatore e il proprietario della struttura sono responsabili della posa corretta e in sicurezza del ventilatore, secondo le norme vigenti nel luogo di installazione.

Il ventilatore può essere installato a parete o in sospensione.

Nei casi di installazione in sospensione fare attenzione alle seguenti indicazioni.

DETTAGLIO B SCALA 1 : 1

Utilizzare dei golfari in dotazione installandoli come in Fig.I, distribuendo il carico uniformemente. Evitare rotazioni fuori controllo. Prevedere catene o funi adeguate. Si prescrive come minima adozione una sospensione avente carico di lavoro di 2 kN min e carico di rottura 5 kN min.

Fig. I In caso d'installazione fissa prevedere un ancoraggio meccanico ad espansione su struttura cementizia o viteria metrica passante su strutture metalliche o lignee, utilizzando tutto il diametro disponibile dei fori predisposti nei punti di fissaggio.
4

45° 45,00°

45° 45,00°

45° 45,00°

Le catene di sospensione

devono essere installate con un

45° 45,00°

angolo di 45° come indicato in fig.II-A.

Il ventilatore si inclinerà

naturalmente all'indietro durante

il funzionamento.

Se si usano catene molto lunghe

per sospendere l'unità, potrebbe

verificarsi un effetto pendolo.

In questo caso, devono essere

previste delle catene aggiuntive

da attaccare agli angoli

posteriori inferiori per evitare

questo effetto.

Fig. II-A

vista laterale

30°

vista frontale
30°

Se il ventilatore viene inclinato le catene devono essere fissate ai golfari preventivamente installati nei punti di fissaggio.

Fig. II-B

5

9 SCHEMI COLLEGAMENTO ELETTRICO
Assicurarsi che la macchina non sia alimentata durante ogni operazione di installazione, manutenzione o servizio! L'installazione, i collegamenti elettrici e la manutenzione della macchina devono essere fatte da un installatore autorizzato e in accordo con le regole locali. Il ventilatore deve essere collegato all'impianto di messa a terra.

9.1 CTRL-A (accessorio a richiesta)
cavo a 6 fili

AD1400B

GIALLO ROSSO MARRONE
BIANCO +10V BLU 0-10V NERO GND

CTRL - A POTENZIOMETRO
+ U -

INTERRUTTORE BIPOLARE

MARRONE

L

cavo a 3 fili

BLU

N

GIALLO-VERDE

cavo a 6 fili

AD900B

BIANCO ROSSO MARRONE
GIALLO +10V BLU 0-10V NERO GND

CTRL - A POTENZIOMETRO
+ U -

INTERRUTTORE BIPOLARE

MARRONE

L

cavo a 3 fili

BLU

N

GIALLO-VERDE

6

9.2 CTRL-A2 (accessorio a richiesta)

cavo a 6 fili

AD1400B

GIALLO ROSSO MARRONE
BIANCO +10V BLU 0-10V NERO GND

CTRL - A2 POTENZIOMETRO
+ U -

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

INTERRUTTORE BIPOLARE
L N

SERRANDA

3

BIANCO MARRONE

2 BLU

1

L N

cavo a 6 fili

AD900B

BIANCO ROSSO MARRONE
GIALLO +10V BLU 0-10V NERO GND

CTRL - A2 POTENZIOMETRO
+ U -

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

INTERRUTTORE BIPOLARE
L N

SERRANDA

3 2

GIALLO MARRONE
BIANCO

1

L N

7

9.3 COMANDO CON POTENZIOMETRO ESTERNO (non fornito) AD1400B

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

cavo a 6 fili

GIALLO ROSSO MARRONE
BIANCO +10V BLU 0-10V NERO GND

L N
POTENZIOMETRO ESTERNO 10k
(NON FORNITO)

AD900B

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

cavo a 6 fili

BIANCO ROSSO MARRONE
GIALLO +10V BLU 0-10V NERO GND

L N
POTENZIOMETRO ESTERNO 10k
(NON FORNITO)

9.4 CTRL-XWS (accessorio a richiesta)

AD1400B

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

cavo a 6 fili

BLU 0-10V NERO GND
BIANCO +10V
GIALLO ROSSO MARRONE

SENSORE DI TEMPERATURA

SONDA AGGIUNTIIVA (ACCESSORIO)

L N
CTRL-XWS + 19 - 18

3

4

5

1

6

2

8

AD900B

cavo a 3 fili

MARRONE BLU
GIALLO-VERDE

cavo a 6 fili

BLU 0-10V NERO GND
GIALLO +10V
BIANCO ROSSO MARRONE

SENSORE DI TEMPERATURA

SONDA AGGIUNTIIVA (ACCESSORIO)

L N
CTRL-XWS + 19 - 18

3

4

5

1

6

2

9.5 CTRL-XTHI (accessorio a richiesta)

AD1400B

MARRONE

L

cavo a 3 fili

BLU

N

GIALLO-VERDE

cavo a 6 fili

BLU 0-10V NERO GND
BIANCO +10V
GIALLO ROSSO MARRONE

SENSORE DI TEMPERATURA
SONDA UMIDITÀ (ACCESSORIO)

DOCCETTE H2O

GND SIGNAL +12V
NO COMUNE NC

CTRL-XTHI
+ 19 - 18

3

4

5

1

6

2

12 13 14

AD900B

MARRONE

L

cavo a 3 fili

BLU

N

GIALLO-VERDE

cavo a 6 fili

BLU 0-10V NERO GND
GIALLO +10V
BIANCO ROSSO MARRONE

SENSORE DI TEMPERATURA
SONDA UMIDITÀ (ACCESSORIO)

DOCCETTE H2O

GND SIGNAL +12V
NO COMUNE NC

CTRL-XTHI
+ 19 - 18

3

4

5

1

6

2

12 13 14

9

9.6 AD900C

AD900C

V2

W1

L3

U2

V1

L2

W2

U1

L1

COLLEGAMENTO A STELLA Y TENSIONE PIÙ ALTA IN TARGA

V2

W1

L3

U2

V1

L2

W2

U1

L1

COLLEGAMENTO A TRIANGOLO TENSIONE PIÙ BASSA IN TARGA

10 PULIZIA
ATTENZIONE: Assicurarsi che l'interruttore generale dell'impianto sia spento prima di qualsiasi operazione di installazione, manutenzione o collegamento elettrico!
Effettuare le operazioni di pulizia periodicamente. La macchina (IP55) può essere lavata con un getto d'acqua a bassa pressione per non danneggare il girante.

10

11 DICHIARAZIONE DI CONFORMITÀ E INCORPORAZIONE

DICHIARAZIONE UE DI
CONFORMITA'/INCORPORAZIONE
Costruttore:
AERAULIQA SRL Via Mario Calderara 39/41 - 25018 Montichiari (BS) - ITALY

DICHIARAZIONE UE DI CONFORMITA'

DICHIARAZIONE DI INCORPORAZIONE
In accordo alla Direttiva Macchine 2006/42/EC.

Dichiariamo qui di seguito che I prodotti della gamma:
Ventilatori assiali AD
MARCHIO: AERAULIQA MODELLI: AD1400A, AD1400B AD900B, AD900C

Dichiariamo qui di seguito che I prodotti della gamma:
Ventilatori assiali AD
MARCHIO: AERAULIQA MODELLI: AD1400A, AD1400B AD900B, AD900C

sulla base del loro progetto e costruzione come quasimacchine immesse sul mercato, sono progettati in conformità con I requisiti pertinenti di salute e sicurezza delle seguenti Direttive:
2014/35/UE - Low Voltage Directive (LVD) 2014/30/UE ­ Electromagnetic Compatibility (EMC) 2009/125/EC ­ Energy Related Products (ErP)
In caso di alterazioni apportate ai prodotti senza il previo consenso del costruttore, la validità della presente dichiarazione decade. La presente dichiarazione di conformità è rilasciata sotto la responsabilità esclusiva del fabbricante.

sulla base del loro progetto e costruzione come quasimacchine, sono progettati in conformità con I Requisiti Essenziali di Salute e Sicurezza (EHSRs) dell'ALLEGATO I, sezioni 1.1.2 (Integrazione della sicurezza), 1.1.5 (Movimentazione), 1.4.1 (Dispositivi di protezione), 1.5.1 (Elettricità) della Direttiva Macchine 2006/42/EC.
Il macchinario è incompleto e non deve essere messo in servizio finché esso non sia stato incorporato in una macchina, la quale sia stata valutata e dichiarata in conformità con i requisiti della Direttiva Macchine 2006/42/EC.
Ci impegniamo a trasmettere, a seguito di ragionata richiesta da parte di pertinenti autorità nazionali, le informazioni rilevanti relative alle quasi-macchine sopraccitate.

Montichiari, 01/05/2024

11

EN

Translated from Original Instructions

AD1400B-AD900B-AD900C High volume circulation fans

INDEX

1 GENERAL INFORMATION

12

2 PRECAUTIONS

12

3 TYPE AXIAL FANS

12

4 MAIN FEATURES

13

5 DATA

13

6 DIMENSIONS AND CLEARANCES

13

7 COMPONENTS

14

8 INSTALLATION

14

9 ELECTRIC WIRING DIAGRAM

16

9.1 CTRL-A (accessory on request) AD1400B-AD900B

16

9.2 CTRL-A2 (accessory on request) AD1400B-AD900B

17

9.3 CONTROL WITH EXTERNAL POTENTIOMETER (not supplied) AD1400B-AD900B

18

9.4 CTRL-XWS (accessory on request) AD1400B-AD900B

18

9.5 CTRL-XTHI (accessory on request) AD1400B-AD900B

19

9.6 AD900C

20

10 CLEANING

20

11 DECLARATION OF CONFORMITY AND INCORPORATION

21

1 GENERAL INFORMATION
Carefully read the instructions contained in this manual. This Specific Manual MUST be read in conjunction with the "Installation, Operation and Maintance General Manual". Note: store the manual for future reference. We reserve the right to improve and make changes to the manual, products and accessories without any obligation to update previous productions and manuals. The installation, electric wiring and service of the unit must be performed by an authorized installer and in accordance with local rules and regulations.

2 PRECAUTIONS
In addition to the precautions indicated in the "Installation, Operation and Maintenance General Manual" special attention should be paid to the following warning notes:
-The fan must be installed at a height of not less than 2.7m from the floor below. Installation at a lower height is considered "improper use". In case of "improper use" the manufacturer declines all responsibility for any damage that may be caused to persons or property, and any warranty will be considered invalid.

RECOMMENDED BOLT TORQUE FOR COARSE THREADED METRIC STEEL BOLTS TE-TCEI GRADE 8.

Dimensions M6

M8

M10 M12 M14 M16

Nm

9,5

23

46

79

127 198

Table 1 Use the values shown in the table to tighten all the screws.

- Check/inspect and eventually retighten all the fixing annually. - Fans should not operate in case of strong wind ( 6m/s). The installer and the building owner are responsible to ensure the safety of the fan mounting system and that the fan installation is correct, in compliance with any national and local regulations.

3. TYPE AXIAL FANS
Ceiling fan with EC brushless motor suitable for wall installation or suspended at ceiling, designed for industrial, civil and zootechnical applications, where high performances are required.

12

4 MAIN FEATURES
· Strong and robust design and manufacturing (galvanised steel)
· Simplified electrical wiring connection · Max temperature +50°C · Gearless for silent operation and maintenance free

· B version: high efficient one-phase EC Brushless motor, 220/277Vac, 50/60Hz, IP55, with integrated electronic system and EMC filters, speed controllable and suitable for S1 continuous service
· C version: three-phase AC Motor, 220/277Vac, TEFC, 50Hz, IP55, suitable for S1 continuous service

5 DATA

Model

Fan diam.

Max speed rotation

Max absorbed
power

Max Thrust

r/min

kW

N

AD1400B (1) AD900B (1) AD900C (2)

1170 800 800

500 1200 920

1,40

105

0,99

56

0,62

36

(1) Data @230Vac, 50 Hz (2) Data @400Vac, 50 Hz (3) Max. absorbed power / max. airflow
6 DIMENSIONS AND CLEARANCES

13B82 11C90

Max airflow AMCA 230-15

cfm
20551 10300 8240

m3/h
34917 17500 14000

SPI(3) W/(m3/s) 144,3
203,7
159,4

27F0

Ø10

2E10

Max airflow AMCA 230-99

cfm
29064 14567 11653

m3/h
49380 24749 19799

SPI(3) W/(m3/s) 102,1
144,0
112,7

1273

1382 1190

270

210

Points for

1273

suspension or fixed

installation

2G08

13A82

208

aeraul iqa

1200
12D00

1273

1382

1273 1200 1382

478

h min

Model

A

B

C

D

E

mm

mm

mm

mm

mm

AD1400B

1382

1382

1189

1200

210

AD900B

951

951

819

780

210

AD900C

951

951

819

780

210

47I 8

478

F

G

mm

mm

270

208

270

120681

270

132

I

h (min)* Weight

mm

mm

kg

478

2700aeraul iq5a2

431 aerau2l i7q0a0

40

402

2700

36

*ATTENTION: The fan must be installed at a height of not less than 2.7m from the floor below

ATTENTION:

A

minimum

air

space

in

front

and

behi1n19d0 1382

the

fan

of

1.5m

is

requi22r71e00 d

(from

wall

or

similar

obst1a27c3 le

and

between

each fan in case of in-line installation of multiple units)

minimum di?stance 1.5m

mmiinn.dimistuanmced=i1s5ta00nce 1.5m







13

7 COMPONENTS
2
1

3
Fig. XII

Fig. XII
44

5235 2636

Fig. XII 23

Pos.

Description

Q.ty

1

IMPELLER

1

2

CASING

1

3

MOTOR

1

4

M10 EYEBOLT

4

5

WASHER

8

6

M10x25 SCREW

4

8 INSTALLATION
ATTENTION: Make sure that the main supply to the unit is disconnected before performing any installation, service, maintenance or electrical work! The fan must be installed at a height of not less than 2.7m from the floor below. The fan must be installed with sufficient surrounding space for assembly/disassembly, cleaning and maintenance.

ATTENTION: the installer and the building owner are responsible to ensure the safety of the fan mounting system and that the fan installation is correct, in compliance with any national and local regulations.

The fan can be wall installed or suspended at ceiling.

For suspended installation pay attention to the following indications.

DETTAGLIO B SCALA 1 : 1

Eyebolts are provided for units which are to be suspended, as per Fig.I: the weight has to be evenly distributed. Avoid spinning of the unit out of control. Provide suitable chains or ropes. It is recommended to use a suspension means with a workload of at least 2 kN and breaking load of at least 5 kN.

Fig. I In the case of fixed installation, provide a mechanical expansion anchor intended for use in solid concrete, or metric screws for use in metal or wooden structures using the entire available diameter of the holes in the fixing points.
14

45° 45,00°

45° 45,00°

45° 45,00°

The suspension chains must be

installed at an angle of approx.

45° 45,00°

45° as shown in Fig. II-A. The fan will naturally tilt back under

operation. If very long chains

are used to suspend the unit,

a pendulum effect may occur.

In this case, additional chains

should be attached to the

bottom rear corners to prevent

this effect.

Fig. II-A

side view

30°

front view
30°

If the fan is tilted, the chains must be attached to the eyebolts previously mounted on the fixing points.

Fig. II-B

15

9 ELECTRIC WIRING DIAGRAM
Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintance or electrical work! The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations. Fan must be earthed.

9.1 CTRL-A (accessory on request)
6-core cable

AD1400B

YELLOW RED BROWN
BIANCO +10V BLU 0-10V BLACK GND

CTRL - A POTENTIOMETER
+ U -

BIPOLAR SWITCH

BROWN

L

3-core cable

BLUE

N

YELLOW-GREEN

6-core cable

AD900B

WHITE RED BROWN
YELLOW +10V BLUE 0-10V BLACK GND

CTRL - A POTENTIOMETER
+ U -

BIPOLAR SWITCH

BROWN

L

3-core cable

BLUE

N

YELLOW-GREEN

16

9.2 CTRL-A2 (accessory on request)

6-core cable

AD1400B

YELLOW RED BROWN
WHITE +10V BLUE 0-10V BLACK GND

CTRL - A2
POTENTIOMETER
+ U -

3-core cable

BROWN BLUE
YELLOW-GREEN

BIPOLAR SWITCH
L N

SHUTTER

3

WHITE BROWN

2 BLUE

1

L N

6-core cable

AD900B

WHITE RED BROWN
YELLOW +10V BLUE 0-10V BLACK GND

CTRL - A2
POTENTIOMETER
+ U -

3-core cable

BROWN BLUE
YELLOW-GREEN

BIPOLAR SWITCH
L N

SHUTTER

3 2

YELLOW BROWN
WHITE

1

L N

17

9.3 CONTROL WITH EXTERNAL POTENTIOMETER (not supplied) AD1400B

3-core cable

BROWN BLUE
YELLOW-GREEN

6-core cable

YELLOW RED BROWN
WHITE +10V BLUE 0-10V BLACK GND

L N
EXTERNAL POTENTIOMETER
10k (NOT SUPPLIED)

AD900B

3-core cable

BROWN BLUE
YELLOW-GREEN

6-core cable

WHITE RED BROWN
YELLOW +10V BLUE 0-10V BLACK GND

L N
EXTERNAL POTENTIOMETER
10k (NOT SUPPLIED)

9.4 CTRL-XWS (accessory on request)

AD1400B

3-core cable

BROWN BLUE
YELLOW-GREEN

6-core cable

BLUE 0-10V BLACK GND
WHITE +10V
YELLOW RED BROWN

TEMPERATURE SENSOR

ADDITIONAL SENSOR (ACCESSORY)

L N
CTRL-XWS + 19 - 18

3

4

5

1

6

2

18

AD900B

3-core cable

BROWN BLUE
YELLOW-GREEN

6-core cable

BLUE 0-10V BLACK GND
YELLOW +10V
WHITE RED BROWN

TEMPERATURE SENSOR

ADDITIONAL SENSOR (ACCESSORY)

L N
CTRL-XWS + 19 - 18

3

4

5

1

6

2

9.5 CTRL-XTHI (accessory on request)

AD1400B

BROWN

L

3-core cable

BLUE

N

YELLOW-GREEN

6-core cable

BLUE 0-10V BLACK GND WHITE +10V
YELLOW RED BROWN
TEMPERATURE SENSOR
HUMIDTY PROBE (ACCESSORY)

SPRINKLER H2O

GND SIGNAL +12V
NO COMMON NC

CTRL-XTHI
+ 19 - 18

3

4

5

1

6

2

12 13 14

AD900B

BROWN

L

3-core cable

BLUE

N

YELLOW-GREEN

6-core cable

BLUE 0-10V BLACK GND YELLOW +10V
WHITE RED BROWN
TEMPERATURE SENSOR
HUMIDTY PROBE (ACCESSORY

SPRINKLER H2O

GND SIGNAL +12V
NO COMMON NC

CTRL-XTHI
+ 19 - 18

3

4

5

1

6

2

12 13 14

19

9.6 AD900C

AD900C

V2

W1

L3

U2

V1

L2

W2

U1

L1

CONNECTION STAR Y HIGHEST VOLTAGE ON PLATE

V2

W1

L3

U2

V1

L2

W2

U1

L1

CONNECTION DELTA LOWER VOLTAGE ON PLATE

10 CLEANING
ATTENTION Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintenance or electrical work!
Carry out cleaning operations periodically. The unit (IP55) can be washed with a low-pressure water jet to avoid damaging the impeller.

20

11 DECLARATION OF CONFORMITY AND INCORPORATION

UE DECLARATION OF
CONFORMITY/INCORPORATION Manufacturer: AERAULIQA SRL
Via Mario Calderara 39/41 - 25018 Montichiari (BS) - ITALY

UE DECLARATION OF CONFORMITY

UE DECLARATION OF INCORPORATION
In accordance with the Machinery Directive 2006/42/EC.

We herewith declare that the following range:
AD axial fans
BRAND: AERAULIQA MODELS: AD1400A, AD1400B AD900B, AD900C
on the basis of its design and construction as partly completed machines brought onto the market, is designed in compliance within relevant health and safety requirements of the following Directives:
2014/35/UE - Low Voltage Directive (LVD) 2014/30/UE ­ Electromagnetic Compatibility (EMC) 2009/125/EC ­ Energy Related Products (ErP)
in the event that alterations are made to the machinery without prior consent with the manufacturer, this declaration becomes invalid.
This declaration is issued under the sole responsibility of the manufacturer.

We herewith declare that the following range:
AD axial fans
BRAND: AERAULIQA MODELS: AD1400A, AD1400B AD900B, AD900C
on the basis of its design and construction of partly completed machines, is designed in compliance with the Essential Health and Safety Requirements (EHSRs) of ANNEX l, sections 1.1.2 (Safety integration), 1.1.5 (Handling), 1.4.1 (Protective devices), 1.5.1 (Electricity) of EC Machinery Directive 2006/42/EC.
The machinery is incomplete and must not be put into service until such time as the machinery which is partly complete is to be incorporated and has been assessed and declared in conformity with the provisions of the Machinery Directive 2006/42/EC.
We undertake to transmit, upon reasoned request by appropriate national authorities, relevant information on the partly completed machinery identified above.

Montichiari, 01/05/2024

21

NOTE

NOTE

Durante l'installazione, si raccomanda di scrivere il numero di serie dell'unità in questo manuale e conservarlo in luogo accessibile al servizio di manutenzione.
During installation, it is recommended to write the serial number of the unit in this manual and keep it safe for maintenance service.
SERIAL NUMBER
Aerauliqa S.r.l. - via Mario Calderara 39/41, 25018 Montichiari (Bs) C.F. e P.IVA/VAT 03369930981 - REA BS-528635 - Tel: +39 030 674681 - Fax: +39 030 6872149 - www.aerauliqa.it - www.aerauliqa.com - info@aerauliqa.it
Aerauliqa S.r.l. si riserva il diritto di modificare/apportare migliorie ai prodotti e/o alle istruzioni di questo manuale in qualsiasi momento e senza preavviso. Aerauliqa S.r.l. reserves the right to modify/make improvements to products and/or this instruction manual at any time and without prior notice.