Installation Guide for SDC models including: EA Series, Door Prop Exit Alarm

Visio-INST-Door Prop.vsd

sdc-26

Visio-INST-Door Prop.vsd

Exit alarm on door opening. • Manual or automatic alarm reset. • Integral LED status indicator. • Local 85dB Piezo buzzer alarm. • Door prop alarm after ...

Installation

SDC , Datasheets, Installation Instructions, Templates, Pricesheets


File Info : application/pdf, 5 Pages, 1.18MB

PDF preview unavailable. Download the PDF instead.

INST-Door-Prop
SECURITY DOOR CONTROLS  WWW.SDCSECURITY.COM [t] 800.413.8783  805.494.0622  E-mail: service@sdcsecurity.com  801 Avenida Acaso, Camarillo, CA 93012  PO Box 3670, Camarillo, CA 93011
INSTALLATION INSTRUCTIONS
EA SERIES DOOR PROP/EXIT ALARM

Model EA-SN

Model EA-728

Model EA-708
(cylinder not included)

The SDC EA Series offers Exit Alarm, Forced Door Alarm, and Door Propped/Held Open Alarm monitoring capabilities to any controlled opening. It may be used as a standalone device or easily integrates with any access control system. Units are typically mounted adjacent to the opening, and provide local visual and audible alarm annunciation. An integral key switch is available for local bypass & alarm reset controls. A built-in alarm relay is also included for remote monitoring.

FEATURES
 Exit alarm on door opening  Door prop alarm after adjustable timed delay  Manual or automatic alarm reset  Local 85dB Piezo buzzer alarm  Integral LED status indicator

 Main relay output for remote alarm notification  Auxiliary relay output for door position status or
bypass/alarm status  Optional key reset/bypass switch
 Compact universal mounting

EA SERIES TECHNICAL SPECIFICATIONS

Input Power:

60mA @ 12 or 24VDC (Auto-sensing)

Mounting: EA-SN: Single Gang, 1/4" Thick aluminum plate w/ security screws

(2-1/8" depth recommended) EA-708, -728: Double Gang, 1/4" Thick aluminum plate w/ security screws

Alarm Sound Level:

85dB @ 3ft, Piezo Buzzer

Status Indicator:

Bi-color LED

Trigger (DPS) Input:

Dry, N/C or N/O, field selectable

Reset/Bypass (Control) Input:

Dry, N/O or N/C, field selectable

Alarm (Main) Output:

Form C, 2A @ 30VDC (Resistive)

Auxiliary Output:

Form C, 2A @ 30VDC (Resistive)

Wiring:

Screw terminals

Overall Dimensions:

EA-SN: 5"h x 3.25"w x 1.625" d

EA-708, -728: 5"h x 5"w x 1.875"d

P:\INST INSTRUCTIONS\CONTROLS - ANNUNCIATORS\INST-DOOR PROP Rev B 07-21 Page 1

Any suggestions or comments to this instruction or product are welcome. Please contact us through our website or email engineer@sdcsecurity.com

SECURITY DOOR CONTROLS  WWW.SDCSECURITY.COM [t] 800.413.8783  805.494.0622  E-mail: service@sdcsecurity.com  801 Avenida Acaso, Camarillo, CA 93012  PO Box 3670, Camarillo, CA 93011
EA Series Board Layout (Back View):

1

1

} PWR (-)

3

PWR (+)

2

2 3
4

}4

5
1s 60s

}5

NO C NC

}6 *The state of the Main & Aux. relays

are shown when the unit is not

NO C
NC

} powered. 7

1 Configuration Jumpers ­ Numbered 1 through 5. By default, all jumpers have been set to OFF. Use the (5) supplied
jumpers, as required. See the table below for a functional description of each jumper.

Configuration Jumpers 1= Latching Alarm

Jumper OFF

Jumper ON

Disabled (Alarm resets on

door closure)

Enabled. (Requires use of Control Input to reset an alarm OR Jumper #2)

2= Alarm Auto Reset Disabled

Auto-reset 60 sec. after door closure. (Requires Jumper #1 to be ON)

3= Control Input Polarity Normally Open

Normally Closed

4= DPS Input Polarity Normally Closed

Normally Open

5= Aux. Relay Function Follows DPS Input

Follows Bypass/Alarm State

2 Adjustable Alarm Timer ­ Determines the amount of time a door can be propped open before an alarm is activated.
Adjustable from 1 to 60 seconds. Turn clockwise to increase time.

3 Input Power Terminals ­ Requires a 12 or 24VDC +/- 10% power supply (auto-sensing).

4 Control Input Terminals ­ Dry input used for bypass & alarm reset. Field-selectable as normally open (default) or
normally closed. In a secure state, a held input will bypass the unit. In an alarm state, a momentary input will reset the alarm providing the door is closed. This input is factory pre-wired for key switch model EA-728.

5 Door Contact Input ­ Required for all models. Monitors the open/closed status of the door. Field-selectable as
normally open or normally closed (default).
6 Alarm Relay Output ­ Relay is energized when the unit is powered. An alarm state or loss of power will de-energize
the relay.
7 Auxiliary Relay Output ­ Relay may be configured to follow the DPS input OR to follow a bypass/alarm state.

P:\INST INSTRUCTIONS\CONTROLS - ANNUNCIATORS\INST-DOOR PROP Rev B 07-21 Page 2

SECURITY DOOR CONTROLS  WWW.SDCSECURITY.COM [t] 800.413.8783  805.494.0622  E-mail: service@sdcsecurity.com  801 Avenida Acaso, Camarillo, CA 93012  PO Box 3670, Camarillo, CA 93011

LED Status Indicator:

Door Status Closed Open Open Closed Open

Unit Condition

LED Status

Secure

Solid Green

G

Pre-alarm (1-60 sec.) Solid Green

G

Alarm

Solid Red

R

Bypassed

Flashing Green G

Bypassed

Flashing Green G

Aux. Relay*

Aux. Relay

Main Relay (Jumper 5 OFF) (Jumper 5 ON)

Energized De-energized Energized

Energized Energized

Energized

De-energized Energized

De-energized

Energized De-energized De-energized

Energized Energized

De-energized

*Relay state shown with N/C Door Contact
Key Switch Operation (EA-708 or 728 only):
NOTE: Unit must be Secure to be Bypassed. Door must be closed to reset an alarm condition.

EA-728

 Bypass (Maintained) ­ 90° Counter-clockwise. Key may be removed. Return to vertical position to re-secure.
 Alarm Reset (Momentary) ­ 45° Clockwise. Key returns to vertical position upon release.

EA-708

 See Page 5 for Mortise Key Cylinder installation
 Bypass (Maintained) ­ Turn counter-clockwise until ON/OFF switch is activated. Reactivate the switch to re-secure.
 Alarm Reset (Momentary) ­ Turn clockwise until momentary switch is activated.

EA Series Operational Modes:
Wiring Example #1 ­ Non-latching (auto-resetting) Exit Alarm or Door Prop Alarm.
Opening the door will initiate the pre-alarm timer. Closing the door before the timer expires resets the timer. If the door remains open and the timer expires, an audible alarm will sound and the Main Relay will trigger. Alarm resets on door closure. Bypass the alarm by activating the integral key switch or via remote bypass switch.

12 or 24VDC P.S.
N/C Alarm Relay for remote monitoring

Power Supply: SDC Model TR-12, TR-24, or 600 Series

N/O

EA-SN: Optional Remote Bypass; Pre-wired for model EA-728

Door Contact: SDC Model MC-4 or similar

Auxiliary Relay follow DPS input

(a) All jumpers are set OFF (default) (b) Adjust the alarm delay timer (1-60 seconds), as required. (c) Install & terminate a N/C door contact. (d) Install & terminate optional output relays, as needed. See page 2 for relay descriptions. (e) Apply power & test.
P:\INST INSTRUCTIONS\CONTROLS - ANNUNCIATORS\INST-DOOR PROP Rev B 07-21 Page 3

SECURITY DOOR CONTROLS  WWW.SDCSECURITY.COM [t] 800.413.8783  805.494.0622  E-mail: service@sdcsecurity.com  801 Avenida Acaso, Camarillo, CA 93012  PO Box 3670, Camarillo, CA 93011

Wiring Example #2 ­ Latching (Manually Reset) Exit Alarm/Door Prop Alarm.
Opening the door will initiate the pre-alarm timer. Closing the door before the timer expires resets the timer. If the door remains open and the timer expires, an audible alarm will sound and the Main Relay will trigger & latch. Alarm must be reset by using the integral key switch (EA-708 or EA-728 only), or by remote control switch. Bypass the alarm by
activating the integral key switch or via remote switch.

1
2 3 4 5
1s 60s

PWR (-) PWR (+)

12 or 24VDC P.S.

Power Supply: SDC Model TR-12, TR-24, or 600 Series

N/O

EA-SN: Requires Remote Reset Switch;

Pre-wired for model EA-728

N/C

NO

C

Alarm Relay for

NC

remote monitoring

Door Contact: SDC Model MC-4 or similar

NO

C

Auxiliary Relay changes state when the unit

enters bypass mode or alarm mode
NC

(a) Jumpers 1 & 5 are installed. Jumpers 2, 3, & 4 are set OFF. (b) Adjust the alarm delay timer (1-60 seconds), as required. (c) Install Remote reset switch. Required for EA-SN; Optional for EA-708 or EA-728. (d) Install & terminate a N/C door contact. (e) Install & terminate optional output relays, as needed. See page 2 for relay descriptions. (f) Apply power & test.

Wiring Example #3 ­ Double-Door Latching Exit Alarm/Door Prop Alarm with Timed Reset.
Opening the door will initiate the pre-alarm timer. Closing the door before the timer expires resets the timer. If the door remains open and the timer expires, an audible alarm will sound and the Main Relay will trigger & latch. The alarm will automatically reset 60 seconds after door closure. The alarm may also be reset by using the integral key switch (EA-708 or EA-728 only), or by remote control switch. Bypass the alarm by activating the integral key switch or via remote bypass switch.

1
2 3 4 5
1s 60s

PWR (-) PWR (+)

12 or 24VDC P.S.

Power Supply: SDC Model TR-12, TR-24, or 600 Series

N/O

EA-SN: Requires Remote Reset Switch;

Pre-wired for the EA-728

N/C

N/C

NO

C

Alarm Relay for

NC

remote monitoring

Door Contacts: SDC Model MC-4 (x2)

NO

C

Auxiliary Relay changes state when the unit

enters bypass mode or alarm mode

NC

(a) Jumpers 1, 2 & 5 are installed. Jumpers 3 & 4 are set OFF. (b) Adjust the alarm delay timer (1-60 seconds), as required. (c) Install Remote reset switch. Required for EA-SN; Optional for EA-708 or EA-728. (d) Install & terminate N/C door contacts in series. (e) Install & terminate optional output relays, as needed. See page 2 for relay descriptions. (f) Apply power & test.

P:\INST INSTRUCTIONS\CONTROLS - ANNUNCIATORS\INST-DOOR PROP Rev B 07-21 Page 4

SECURITY DOOR CONTROLS  WWW.SDCSECURITY.COM [t] 800.413.8783  805.494.0622  E-mail: service@sdcsecurity.com  801 Avenida Acaso, Camarillo, CA 93012  PO Box 3670, Camarillo, CA 93011

EA-708 Mortise Key Cylinder Installation:
ASSEMBLY DETAIL

SOUND DAMPENER All Exit Alarm Assemblies are shipped with a sound dampening cap loose in the box.
Install the unit without the cap for full volume.

Switch Mounting Bracket
triangular tabs
Locknut

Install the unit with the cap as shipped for complete dampening.
Install the unit with the center hole punched out for partial dampening

Key Cylinder SDC Part# CYL-KD
Or supply compatible 1" to 1-3/8" standard or interchangeable core mortise key cylinders (not included)
Use tailpiece supplied with SDC Part# CYL-KD, or Ilco 863G-00-10 Standard Cam equivalent.
Faceplate

CENTER HOLE AS SHIPPED

Adjustable Switch
Assembly

CENTER HOLE PUNCHED

Ensure that the cam makes contact with the center of the switch plunger

Complete the wiring connections by carefully routing the (2) white & (2) yellow wire leads behind the board. Terminate the (2) yellow wires to Control terminal "A". Terminate the (2) white wires to Control terminal "B".

SWITCH WIRING

(Reset) (Bypass)

A YEL B WHT

NO COM NO COM
WHT YEL
WHT YEL
P:\INST INSTRUCTIONS\CONTROLS - ANNUNCIATORS\INST-DOOR PROP Rev B 07-21 Page 5

