Installation Guide: Danfoss ECL Comfort 310, P501

Product Code: 087H3842

This guide provides detailed installation and wiring information for the Danfoss ECL Comfort 310 and P501 controllers, including various system configurations and component connections.

General Connections and Schematics

Basic Power and Communication Connections:

Diagram 1 (Top Left): Illustrates a 230 V AC power plug being inserted into a wall socket.

Diagram 2 (Top Middle): Shows a USB connection for ECL 210/310 controllers and an Internet connection for ECL 310 controllers.

Diagram 3 (Top Right): Depicts a 230 V AC power plug being inserted into a wall socket.

P501.1, Example a: System Schematic

This schematic illustrates a heating system configuration. It features the ECL 310 controller, an ECA 32/35 expansion module, and various sensors labeled S1 through S12. Actuators and valves are indicated by P1-P3 and V1-V2, with pumps labeled M1-M2. The diagram shows connections for heating circuits, domestic hot water (DHW), and potential solar thermal integration, showing the flow of water and control signals.

P501.1 System Schematics

P501.1, Example b: System Schematic

This schematic presents an alternative system configuration for P501.1, featuring the ECL 310 controller, ECA 32/35 module, and a similar array of sensors (S1-S12), actuators/valves (P1-P3, V1-V2), and pumps (M1-M2), arranged differently to suit specific system designs.

P501.1, Example c: System Schematic

This schematic shows another variation of the P501.1 system configuration, detailing the interconnections between the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.

P501.11 System Schematics

P501.11, Example a: System Schematic

This diagram illustrates a system configuration for P501.11, showing the ECL 310 controller, ECA 32/35 module, and associated components like sensors (S1-S12), actuators/valves (P1-P3, V1-V2), and pumps (M1-M2).

P501.12 System Schematics

P501.12, Example a: System Schematic

This schematic depicts a system configuration for P501.12, detailing the connections between the ECL 310 controller, ECA 32/35 module, sensors (S1-S12), actuators/valves (P1-P4, V2-V3), and pumps (M1-M3).

P501.12, Example b: System Schematic

This diagram shows another system configuration for P501.12, illustrating the integration of the ECL 310 controller, ECA 32/35 module, and various sensors, actuators, and pumps.

P501.12, Example c: System Schematic

This schematic presents a third system configuration example for P501.12, detailing the interconnections of the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.

P501.12, Example d: System Schematic

This diagram illustrates a system configuration for P501.12, showing the ECL 310 controller, ECA 32/35 module, and associated components like sensors (S1-S12), actuators/valves (P1-P3, V2-V4), and pumps (M1-M2).

P501.12, Example e: System Schematic

This schematic depicts a system configuration for P501.12, detailing the connections between the ECL 310 controller, ECA 32/35 module, sensors (S1-S12), actuators/valves (P1-P3, V2-V4), and pumps (M1-M2).

P501.12, Example f: System Schematic

This diagram shows another system configuration example for P501.12, illustrating the integration of the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.

ECL 310 Wiring and Module Compatibility

ECL 310, 230 V a.c. Wiring (P501.1)

This diagram details the wiring connections for the ECL 310 controller operating on 230 V AC. It shows connections to terminal blocks labeled R1-R6, N (Neutral), L (Line), M (Motor), P1-P4, B5, P6, S1-S12 (sensors), V1-V4 (valves), and M1-M2 (motors). The diagram also shows connections to external components like Tr1-Tr6 and a 230 V AC power source (L, N).

ECL 310, 230 V a.c. Wiring (P501.11, P501.12)

Further wiring diagrams for the ECL 310 controller on 230 V AC, applicable to P501.11 and P501.12 configurations, illustrating specific terminal connections.

ECA 32/35 Module Compatibility

Configuration ECA 32 ECA 35
P501.1XX
P501.11X
P501.12X

ECA 32/35 Connections (P7, B8, O1, A1)

This diagram illustrates specific connections for terminals P7, B8, O1, and A1 when using ECA 32/35 modules, showing their relationship with the ECL 310 controller and the ECA 35 module.

Analog and PWM Output Connections

ECA 35: PWM Out 1 & 2

Diagrams showing the wiring for Pulse Width Modulation (PWM) outputs 1 and 2 from the ECA 35 module, connecting to the ECL 310 controller.

ECA 32/35: P6/V1, Analog Out 1 (0-10 V)

This diagram illustrates the connection for Analog Output 1 (0-10 V) via terminal P6/V1, linking the ECA 32/35 module to the ECL 310 controller.

ECA 32/35: P7/V2, Analog Out 2 (0-10 V)

Diagram showing the connection for Analog Output 2 (0-10 V) via terminal P7/V2, connecting the ECA 32/35 module to the ECL 310 controller.

ECA 32: V1, Analog Out 1 (0-10 V)

This diagram illustrates the connection for Analog Output 1 (0-10 V) via terminal V1, linking the ECA 32 module to the ECL 310 controller.

ECA 32: V3, Analog Out 3 (0-10 V)

Diagram showing the connection for Analog Output 3 (0-10 V) via terminal V3, connecting the ECA 32 module to the ECL 310 controller.

P501.12 ECA 35 Output Configurations

ECA 35: V1, V2, V3 (0-10 V)

Diagrams illustrating the connections for analog outputs V1, V2, and V3 (0-10 V) from the ECA 35 module to the ECL 310 controller.

ECA 35: V2, V3, V4 (PWM)

Diagrams showing the connections for Pulse Width Modulation (PWM) outputs V2, V3, and V4 from the ECA 35 module to the ECL 310 controller.

Safety Thermostat Wiring

230 V a.c. / 24 V a.c., Safety Thermostat (1-step closing)

Wiring diagrams for 230 V AC / 24 V AC safety thermostats with 1-step closing functionality, shown for ECL 210/310/311 and ECL 210/310 controllers. These diagrams illustrate connections to the controller terminals and the thermostat (ST), along with power supply (L, N) and motor connections (M1).

230 V a.c. / 24 V a.c., Safety Thermostat (2-step closing)

Wiring diagrams for 230 V AC / 24 V AC safety thermostats with 2-step closing functionality, shown for ECL 210/310/311 and ECL 210/310 controllers. These diagrams detail the thermostat (ST, ST1) connected to controller terminals, power supply (L, N), and motor connections (M1, M2).

Pt 1000 Sensor Connections and Data

Pt 1000 Sensor Wiring

Diagrams illustrating the wiring for Pt 1000 temperature sensors. They show connections to the ECL 310 controller, ECA 32, and ECA 35 modules, detailing how sensors S1-S10 connect to specific pins and terminals on these devices.

Pt 1000 Compatibility Table

Configuration S1S2S3S4S5S6S7S8S9S10
P501.1XXXXXXXXXX
P501.11XXXXXXXXXX
P501.12XXXXXXXXXX

Pt 1000 Temperature-Resistance Data

Pt 1000 (1000 Ω / 0°C) Table

°CΩ
-50803
-40843
-30882
-20922
-10961
01000
101039
201078
301117
401155
501194
601232
701271
801309
901347
1001385
1101423
1201461
1301498
1401535
1501573

Pt 1000 Temperature vs. Resistance Graph

This graph visually represents the relationship between temperature (°C) on the x-axis and resistance (Ω) on the y-axis for a Pt 1000 sensor, as per IEC 751B standard. It shows a linear increase in resistance as temperature rises from -50°C to 150°C.

Communication Protocols

Modbus Connections

Diagrams illustrating the Modbus communication setup for ECL controllers, showing connections to the ECL 210/296/310/311 controller terminals.

M-bus Connections

Diagrams detailing the M-bus communication setup for ECL controllers, including connections to ECL 296/310/311 terminals and specific configurations for P501.1, P501.11, P501.12 with F1 + F2 M-bus.

Installation Steps for ECA 30

The following steps describe the installation process for the ECA 30 unit:

  1. Step 1: Prepare the wall opening and mounting plate.
  2. Step 2: Insert the ECA 30 unit into the wall mounting plate.
  3. Step 3: Secure the ECA 30 unit to the mounting plate.
  4. Step 4: Attach the ECA 30 unit to the wall, ensuring correct orientation.
  5. Step 5: Connect the necessary wiring cable to the ECA 30 unit.
  6. Step 6: Connect the ECA 30 unit to the power source or system.
  7. Step 7: Complete the final mounting of the ECA 30 unit.
  8. Step 8: The ECA 30 unit is now installed.

Further Information

For more details and resources:

Danfoss A/S
Climate Solutions
danfoss.com
+45 7488 2222

Models: 087H3842, ECL Comfort 310, Controller, ECL Comfort 310 Controller, ECL Comfort P501

File Info : application/pdf, 20 Pages, 2.74MB

PDF preview unavailable. Download the PDF instead.

AN19798647125300-000701

References

Danfoss A/S Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Danfoss ECL Comfort 310, A362 Installation Guide
Comprehensive installation guide for Danfoss ECL Comfort 310 and A362 controllers, detailing wiring, system configurations, and operational parameters for HVAC systems. Includes diagrams and technical specifications.
Preview Danfoss ECL Comfort 210/296/310, A232/A332 Installation Guide
Comprehensive installation guide for Danfoss ECL Comfort 210, 296, and 310 controllers, and A232/A332 series devices. Includes system schematics, wiring diagrams, electrical specifications, and communication protocol details for various configurations.
Preview Danfoss ECL Comfort 210/296/310, A231/A331 Installation Guide
Comprehensive installation guide for Danfoss ECL Comfort 210, 296, 310, A231, and A331 controllers, detailing electrical connections, wiring diagrams, sensor inputs, communication interfaces, and installation procedures.
Preview Navod k obsluze ECL Comfort 210/296/310, aplikace A230
Tato uživatelská příručka poskytuje komplexní informace o regulátorech Danfoss ECL Comfort řady 210, 296 a 310 při použití s aplikací A230. Dokument je určen pro uživatele a techniky, kteří potřebují detailní pokyny k instalaci, konfiguraci a každodennímu provozu těchto pokročilých systémů řízení vytápění a chlazení.
Preview Danfoss ECL Comfort 210/296/310 Operating Guide: Application A237/A337
Official operating guide for Danfoss ECL Comfort 210, 296, and 310 controllers with application A237/A337. Learn about installation, daily use, settings, and system integration for HVAC and building automation. Includes safety and technical details.
Preview Danfoss ECA 30/31 Remote Control Units Operating Guide
This document provides an operating guide for the Danfoss ECA 30 and ECA 31 Remote Control Units, detailing their functions, installation, settings, and troubleshooting for use with ECL Comfort controllers.
Preview Danfoss ECL Comfort 310, P501 Installation Guide
Installation guide for the Danfoss ECL Comfort 310 and P501 controllers, providing detailed wiring diagrams and configuration information for various applications.
Preview Danfoss ECA 60/61/62/63 Mounting and Wiring Guide
Official mounting and wiring guide for Danfoss ECA 60, ECA 61, ECA 62, and ECA 63 controllers, including connections for ECL Comfort systems. Provides step-by-step instructions and terminal layouts.