Installation Guide: Danfoss ECL Comfort 310, P501
Product Code: 087H3842
This guide provides detailed installation and wiring information for the Danfoss ECL Comfort 310 and P501 controllers, including various system configurations and component connections.
General Connections and Schematics
Basic Power and Communication Connections:
Diagram 1 (Top Left): Illustrates a 230 V AC power plug being inserted into a wall socket.
Diagram 2 (Top Middle): Shows a USB connection for ECL 210/310 controllers and an Internet connection for ECL 310 controllers.
Diagram 3 (Top Right): Depicts a 230 V AC power plug being inserted into a wall socket.
P501.1, Example a: System Schematic
This schematic illustrates a heating system configuration. It features the ECL 310 controller, an ECA 32/35 expansion module, and various sensors labeled S1 through S12. Actuators and valves are indicated by P1-P3 and V1-V2, with pumps labeled M1-M2. The diagram shows connections for heating circuits, domestic hot water (DHW), and potential solar thermal integration, showing the flow of water and control signals.
P501.1 System Schematics
P501.1, Example b: System Schematic
This schematic presents an alternative system configuration for P501.1, featuring the ECL 310 controller, ECA 32/35 module, and a similar array of sensors (S1-S12), actuators/valves (P1-P3, V1-V2), and pumps (M1-M2), arranged differently to suit specific system designs.
P501.1, Example c: System Schematic
This schematic shows another variation of the P501.1 system configuration, detailing the interconnections between the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.
P501.11 System Schematics
P501.11, Example a: System Schematic
This diagram illustrates a system configuration for P501.11, showing the ECL 310 controller, ECA 32/35 module, and associated components like sensors (S1-S12), actuators/valves (P1-P3, V1-V2), and pumps (M1-M2).
P501.12 System Schematics
P501.12, Example a: System Schematic
This schematic depicts a system configuration for P501.12, detailing the connections between the ECL 310 controller, ECA 32/35 module, sensors (S1-S12), actuators/valves (P1-P4, V2-V3), and pumps (M1-M3).
P501.12, Example b: System Schematic
This diagram shows another system configuration for P501.12, illustrating the integration of the ECL 310 controller, ECA 32/35 module, and various sensors, actuators, and pumps.
P501.12, Example c: System Schematic
This schematic presents a third system configuration example for P501.12, detailing the interconnections of the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.
P501.12, Example d: System Schematic
This diagram illustrates a system configuration for P501.12, showing the ECL 310 controller, ECA 32/35 module, and associated components like sensors (S1-S12), actuators/valves (P1-P3, V2-V4), and pumps (M1-M2).
P501.12, Example e: System Schematic
This schematic depicts a system configuration for P501.12, detailing the connections between the ECL 310 controller, ECA 32/35 module, sensors (S1-S12), actuators/valves (P1-P3, V2-V4), and pumps (M1-M2).
P501.12, Example f: System Schematic
This diagram shows another system configuration example for P501.12, illustrating the integration of the ECL 310 controller, ECA 32/35 module, sensors, actuators, and pumps.
ECL 310 Wiring and Module Compatibility
ECL 310, 230 V a.c. Wiring (P501.1)
This diagram details the wiring connections for the ECL 310 controller operating on 230 V AC. It shows connections to terminal blocks labeled R1-R6, N (Neutral), L (Line), M (Motor), P1-P4, B5, P6, S1-S12 (sensors), V1-V4 (valves), and M1-M2 (motors). The diagram also shows connections to external components like Tr1-Tr6 and a 230 V AC power source (L, N).
ECL 310, 230 V a.c. Wiring (P501.11, P501.12)
Further wiring diagrams for the ECL 310 controller on 230 V AC, applicable to P501.11 and P501.12 configurations, illustrating specific terminal connections.
ECA 32/35 Module Compatibility
Configuration | ECA 32 | ECA 35 |
---|---|---|
P501.1 | X | X |
P501.11 | X | |
P501.12 | X |
ECA 32/35 Connections (P7, B8, O1, A1)
This diagram illustrates specific connections for terminals P7, B8, O1, and A1 when using ECA 32/35 modules, showing their relationship with the ECL 310 controller and the ECA 35 module.
Analog and PWM Output Connections
ECA 35: PWM Out 1 & 2
Diagrams showing the wiring for Pulse Width Modulation (PWM) outputs 1 and 2 from the ECA 35 module, connecting to the ECL 310 controller.
ECA 32/35: P6/V1, Analog Out 1 (0-10 V)
This diagram illustrates the connection for Analog Output 1 (0-10 V) via terminal P6/V1, linking the ECA 32/35 module to the ECL 310 controller.
ECA 32/35: P7/V2, Analog Out 2 (0-10 V)
Diagram showing the connection for Analog Output 2 (0-10 V) via terminal P7/V2, connecting the ECA 32/35 module to the ECL 310 controller.
ECA 32: V1, Analog Out 1 (0-10 V)
This diagram illustrates the connection for Analog Output 1 (0-10 V) via terminal V1, linking the ECA 32 module to the ECL 310 controller.
ECA 32: V3, Analog Out 3 (0-10 V)
Diagram showing the connection for Analog Output 3 (0-10 V) via terminal V3, connecting the ECA 32 module to the ECL 310 controller.
P501.12 ECA 35 Output Configurations
ECA 35: V1, V2, V3 (0-10 V)
Diagrams illustrating the connections for analog outputs V1, V2, and V3 (0-10 V) from the ECA 35 module to the ECL 310 controller.
ECA 35: V2, V3, V4 (PWM)
Diagrams showing the connections for Pulse Width Modulation (PWM) outputs V2, V3, and V4 from the ECA 35 module to the ECL 310 controller.
Safety Thermostat Wiring
230 V a.c. / 24 V a.c., Safety Thermostat (1-step closing)
Wiring diagrams for 230 V AC / 24 V AC safety thermostats with 1-step closing functionality, shown for ECL 210/310/311 and ECL 210/310 controllers. These diagrams illustrate connections to the controller terminals and the thermostat (ST), along with power supply (L, N) and motor connections (M1).
230 V a.c. / 24 V a.c., Safety Thermostat (2-step closing)
Wiring diagrams for 230 V AC / 24 V AC safety thermostats with 2-step closing functionality, shown for ECL 210/310/311 and ECL 210/310 controllers. These diagrams detail the thermostat (ST, ST1) connected to controller terminals, power supply (L, N), and motor connections (M1, M2).
Pt 1000 Sensor Connections and Data
Pt 1000 Sensor Wiring
Diagrams illustrating the wiring for Pt 1000 temperature sensors. They show connections to the ECL 310 controller, ECA 32, and ECA 35 modules, detailing how sensors S1-S10 connect to specific pins and terminals on these devices.
Pt 1000 Compatibility Table
Configuration | S1 | S2 | S3 | S4 | S5 | S6 | S7 | S8 | S9 | S10 |
---|---|---|---|---|---|---|---|---|---|---|
P501.1 | X | X | X | X | X | X | X | X | X | X |
P501.11 | X | X | X | X | X | X | X | X | X | X |
P501.12 | X | X | X | X | X | X | X | X | X | X |
Pt 1000 Temperature-Resistance Data
Pt 1000 (1000 Ω / 0°C) Table
°C | Ω |
---|---|
-50 | 803 |
-40 | 843 |
-30 | 882 |
-20 | 922 |
-10 | 961 |
0 | 1000 |
10 | 1039 |
20 | 1078 |
30 | 1117 |
40 | 1155 |
50 | 1194 |
60 | 1232 |
70 | 1271 |
80 | 1309 |
90 | 1347 |
100 | 1385 |
110 | 1423 |
120 | 1461 |
130 | 1498 |
140 | 1535 |
150 | 1573 |
Pt 1000 Temperature vs. Resistance Graph
This graph visually represents the relationship between temperature (°C) on the x-axis and resistance (Ω) on the y-axis for a Pt 1000 sensor, as per IEC 751B standard. It shows a linear increase in resistance as temperature rises from -50°C to 150°C.
Communication Protocols
Modbus Connections
Diagrams illustrating the Modbus communication setup for ECL controllers, showing connections to the ECL 210/296/310/311 controller terminals.
M-bus Connections
Diagrams detailing the M-bus communication setup for ECL controllers, including connections to ECL 296/310/311 terminals and specific configurations for P501.1, P501.11, P501.12 with F1 + F2 M-bus.
Installation Steps for ECA 30
The following steps describe the installation process for the ECA 30 unit:
- Step 1: Prepare the wall opening and mounting plate.
- Step 2: Insert the ECA 30 unit into the wall mounting plate.
- Step 3: Secure the ECA 30 unit to the mounting plate.
- Step 4: Attach the ECA 30 unit to the wall, ensuring correct orientation.
- Step 5: Connect the necessary wiring cable to the ECA 30 unit.
- Step 6: Connect the ECA 30 unit to the power source or system.
- Step 7: Complete the final mounting of the ECA 30 unit.
- Step 8: The ECA 30 unit is now installed.
Further Information
For more details and resources:
- Visit the Danfoss website: www.danfoss.com
- Explore Danfoss Heating on YouTube: youtube.com/user/DanfossHeating
- Specifically, check the "How-to Videos" playlist for District Energy installation videos.
Danfoss A/S
Climate Solutions
danfoss.com
+45 7488 2222