User Manual for AJAX models including: FireProtect 2 Jeweller, FireProtect 2 Jeweller Wireless Fire Detector, Wireless Fire Detector, Fire Detector, Detector

Gebruikershandleiding van Ajax FireProtect 2 (Heat)

Ajax FireProtect 2 SB Wit met hitte sensors en ingebouwde batterijen - WebStore4


File Info : application/pdf, 29 Pages, 772.97KB

PDF preview unavailable. Download the PDF instead.

Gebruikershandleiding-van-FireProtect-2-Heat-Ajax-WebStore4
FireProtect 2 (Heat) Jeweller User manual
Updated August 4, 2023
FireProtect 2 (Heat) Jeweller is a wireless re detector with a built-in siren. Designed for indoor installation. Detects temperature rise. The detector also can work without a hub. It is available in two modi cations: with sealed batteries (has SB in the name) that run 10 years, and with replaceable ones (has RB in the name) that run up to 7 years.
A list of compatible hubs and range extenders is available here. FireProtect 2 (Heat) detector is compatible only with hubs on OS Malevich 2.15 and higher.
The detector operates as part of the Ajax system, communicating with the hub via the Jeweller secure radio protocol. The hub communication range is up to 1,700 meters without obstacles.
Buy FireProtect 2 (Heat)

Versions of the detector with other sensor combinations are also available. All Ajax re detectors are available here.
Functional elements
1. Detector front panel with Test/Mute button. To activate the button, press the center of the panel.
2. SmartBracket mounting panel. To remove the panel, turn it counterclockwise.
3. Device QR code and ID (serial number). It is used to add the detector to the Ajax system.
4. Tamper button. Triggers when an attempt is made to detach the detector from the surface or remove it from the mounting panel.
5. Power button. 6. Detector certi cation information.

7. Siren. 8. Green LED indicator. 9. Yellow LED indicator. 10. Red LED indicator. 11. First thermistor. Detects dangerous temperatures. 12. Second thermistor. Detects dangerous temperatures.
Operating principle

00:00

00:12

FireProtect 2 (Heat) is a wireless re detector designed for indoor installation. Available in two versions:

With sealed batteries. Such a detector has SB in its name. Built-in battery life is 10 years. After the batteries are discharged, the detector should be replaced with a new one.
With replaceable batteries. Such a detector has RB in its name. Pre-installed battery life is 7 years. When the batteries are discharged, they can be replaced with new ones.

The Battery Life Optimization feature must be enabled to ensure such a lifetime for builtin and pre-installed batteries.
Learn more

How to replace batteries in FireProtect 2 RB (Heat)
The detector is equipped with a siren (piezoelectric buzzer) for audible noti cation of alarms and events with a volume of up to 85 dB (at a distance of 3 m from the detector). The detector is always active and reacts to a re 24/7, regardless of the system's security mode.
FireProtect 2 is protected by tamper. The tamper controls the removal of the detector from the SmartBracket mounting panel: the detector reacts with LED indication and sends noti cations to users in Ajax apps and the security company monitoring station.
Ajax automation devices respond to FireProtect 2 alarms and perform userde ned actions using automation scenarios. For example, the WallSwitch relay can turn on the ventilation system and emergency lighting when an alarm occurs.
Heat sensor
Two built-in thermistors of A1 class detect a rapid rise and exceeding the temperature threshold in FireProtect 2. Such thermistors notify of alarm when a rapid temperature rise or static temperature is detected in the range of +54°C to +65°C.
FireProtect 2 reports that the temperature threshold has been exceeded as soon as its value exceeds +64°C. The detector reports a rapid temperature rise if the indicator increases by 10°C within one minute. If the temperature indicator rises sharply by 20°C or more, the detector alerts immediately.
Test/Mute button
o activate the Test/Mute button, press lightly on the centre of the front panel with your hand. Use a suitable item (mop handle) if you can't reach up the detector with your hand. Test/Mute is a mechanical button placed under the front panel of the detector.
The button performs several functions:
In normal mode, it starts the detector self-test.

In case of an alarm, it mutes the detector alarm or Interconnected Alarm of all re detectors in the system for 10 minutes.
In case of a fault or low battery level it mutes the sound and LED indication for 12 hours.
Interconnected Fire Detectors Alarms*
All re detectors of the FireProtect 2 product line support the Interconnected Alarm feature. This function activates the built-in sirens of all re detectors in the system as soon as at least one of the re detectors detects an alarm. Sirens of FireProtect 2 detectors are activated within 20 seconds after an alarm is detected. FireProtect and FireProtect Plus are activated over a detector ping interval set in the Jeweller (or Jeweller/Fibra) settings, but no later than 60 seconds after.
FireProtect 2 detectors have different sound and LED indications of alarm types to make it easier for users to distinguish between them. In case of interconnected alarm, FireProtect 2 detectors indicate exactly the alarm type detected by the initiating detector. The initiating detector additionally indicates the alarm by LED. Instead, FireProtect and FireProtect Plus detectors notify all types of alarms with the same sound.
How to set Interconnected Fire Detectors Alarms
How to mute Interconnected Fire Detectors Alarms
*The Interconnected Fire Detectors Alarm function is not certi ed according to EN 14604 and EN 50291
Sending events to the monitoring station
The Ajax system can transmit events and alarms to the PRO Desktop monitoring app as well as the Central Monitoring Station (CMS) via SurGard (Contact ID), SIA DC-09 (ADM-CID), ADEMCO 685, and other protocols. The list of supported protocols is available here.
Which CMSs Ajax connects to

Addressability of Ajax devices allows you to send not only events but also the type of the device, the name, virtual room, and security group assigned to it to the PRO Desktop and to the CMS. The list of transmitted parameters may differ depending on the type of the CMS and the selected communication protocol.
The ID and detector loop (zone) number are available in the detector States.
Adding to the system
Before adding a device
1. Install the Ajax app. 2. Create an account if you don't have one. 3. Add a hub compatible with the detector to your app. Set the required
settings and create at least one virtual room. 4. Make sure that the hub is on and has Internet access via Ethernet, Wi-Fi,
and/or mobile network. You can do this in the Ajax app or by looking at the LED indicator of the hub: it should light up white or green. 5. Make sure that the hub does not start updates and that it is disarmed by checking the status in the Ajax app.
A PRO or a user with system setup rights can connect the device to the hub.
To connect to the hub, the detector should be within the coverage area of the hub radio network. To operate via a radio signal range extender rst connect the detector to the hub and then to the range extender. You can do this in the range extender settings in Ajax apps.
How to connect FireProtect 2 to a hub
1. Open the Ajax app.

2. Select the hub if you have several of them or if you are using the Ajax PRO app.
3. Go to the Devices tab. Press Add Device. 4. Enter the name of the device. 5. Scan the QR code or enter the ID manually. QR code is located on the rear
part of the enclosure (under the mounting panel) and on the device packaging. The device ID can be found below the QR code. 6. Select the virtual room and security group (if the group mode is enabled). 7. Click Add; the countdown will begin.
If the maximum number of devices is added to the hub, when you add the device, you will get a noti cation about exceeding the device limit. The number of devices that you can connect to the hub depends on the central unit model.
8. Turn on the detector by holding the power button for 3 seconds. The hub connection request is sent only if the detector is enabled. If the detector fails to connect to the hub, try again in 5 seconds.
The detector cannot connect to the hub if they operate on different radio frequencies. The radio frequency range of the devices depends on the region of sale. Please contact technical support for information on the operating frequency range of your devices.
Once connected, FireProtect 2 will appear in the hub device list in the Ajax app. Device status update depends on the ping interval set in the Jeweller or Jeweller/Fibra settings. The default value is 36 seconds.
FireProtect 2 works with only one hub. When connected to a new hub, the detector stops transmitting data to the old hub. Once added to a new hub, FireProtect 2 is not removed from the list of devices of the old hub. This must be done manually in the Ajax app.
Autonomous operation mode

FireProtect 2 detectors can be used autonomously without connecting to an Ajax hub. In this case, the detector noti es of re with only a built-in siren and LED indication. Users don't receive noti cations on any Ajax apps, including Ajax Translator, or PRO Desktop. The Interconnected Fire Detectors Alarms feature is also unavailable for this operation mode.
To use the detector autonomously, follow these steps:
1. Select the optimal location of the detector using the recommendations in the Selection of installation place section.
2. Mount the detector on the SmartBracket panel as described in the Installation section.
3. Press the power button to switch on the detector. 4. Start a self-test with the Test/Mute button. Press the centre of the front
panel and hold it for 1.5 seconds.
During a self-test FireProtect 2 noti es about each step with a built-in siren and LED indication. Once a self-test is completed, the LED indication turns off, and the detector works autonomously.
In case of an alarm, press the Test/Mute button or eliminate the cause of the alarm to mute the siren.
Indication

00:00

00:06

LEDs and the built-in siren of the detector can report alarms as well as certain states of the detector.

LED indication
The red LED ashes continuously.

Sound indication
The siren sounds in time with the LED indication.

Event

Notes
The detector stops alarming as soon as its sources are eliminated.

Alarm by:
rapid temperature rise;
temperature threshold exceeding.

Also, you can mute the alarm by pressing
the Test/Mute button or in the Ajax
app.
The LED and sound indications resume if the source of the alarm is still present after the muting timer (10 minutes) has expired.

The red LED ashes

No.

every 4 seconds.

The red LED ashes 2 No. times in a row.

The yellow LED lights No. up for 1 second.

Muted alarm.
Restore after alarm.
Tamper alarm. The detector is removed from the SmartBracket mounting panel.

The detector stops alarming as soon as its source is eliminated.
If the source of the alarm is removed, the detector is restored automatically.

The green LED lights

up for 1 second.

No.

Green, yellow, and red No. LEDs light up in turn,

The detector is installed on the SmartBracket mounting panel.
Turning the detector on.

Turns on when the tamper is triggered.
To turn on the detector, hold the

then go off.

Green, yellow, and red

LEDs light up at the

same time, then go

No.

off in reverse order.

The green LED is

No.

permanently on.

The green LED ashes

6 times in a row.

No.

The yellow LED ashes 2 times in a
row every minute.

The siren beeps in time with the LED indication every minute.

power button for 1 second.

Turning the detector off.

To turn off the detector, hold the power button for 2 seconds.

Connection to the hub in progress.

The indication turns off after the detector connection to the hub.

The detector has been removed from the hub.

The indication turns on when the detector receives information that it has been removed from the hub.

Malfunction detected.

All malfunctions are displayed in the
detector states in
Ajax apps. Fields with malfunctions are highlighted in red.
If the detector needs to be repaired, contact
Technical Support.

The yellow LED ashes once per
minute.

The siren beeps in time with the LED indication once per minute.

Low battery level.

You can replace batteries in a detector with replaceable batteries only (has RB in its name). A detector with sealed batteries (with SB in the name) should be replaced with a new one after the batteries are discharged.
How to replace batteries in FireProtect 2 RB (Heat)

The yellow LED

No.

constantly ashes.

The battery is completely

You can replace batteries in a detector

discharged.

with replaceable batteries only (has RB in its name). A detector with sealed batteries (has SB in its name) should be replaced with a new one after the batteries are discharged.
How to replace batteries in FireProtect 2 RB (Heat)

The red LED ashes 5 times.

The siren beeps 5 times.

Performing a self-test.

The test can be started by pressing
the Test/Mute button or in the Ajax
app in the detector settings.

Detector testing
Functionality testing
The test allows you to check the status of the detector's sensors. You can run it in two ways: by pressing the Test/Mute button on the detector or in Ajax apps.
If the detector is in an alarm state, the self-test is not available.
To run the test using the Test/Mute button, press the center of the front panel and hold for 1.5 seconds. To run the test in the Ajax app:
1. Open the Ajax app.

2. Select the hub if you have several of them or if you are using the Ajax PRO app.
3. Go to the Devices menu. 4. Select FireProtect 2 (Heat). 5. Go to the settings by clicking on the gear icon . 6. Click on the Device Self-test eld.
After starting the test, the red LED of the detector ashes 5 times in a row. The detector's siren beeps in time with the LED indication. When the test is over, users receive a noti cation about the detector state in Ajax apps.
The detector also noti es about the test result with sound and LED indications. If the test is failed and a malfunction is detected, the detector starts to indicate a malfunction 3 seconds after the test is begun: the yellow LED ashes twice, and the siren beeps in time with the LED indication.
The self-test does not start immediately, but no later than 30 seconds after pressing the Test/Mute button or running from the Ajax app.
If no sound and LED indications occurred during the self-test, the detector may not be used. Contact our Technical Support.
Testing at the place of installation
Ajax system provides several tests to select the correct installation place of devices. Jeweller Signal Strength Test is available for FireProtect 2. The test determines the strength and stability of the signal at the intended location of the device.
To run the test in the Ajax app:
1. Select the hub if you have several of them or if you are using the Ajax PRO app.
2. Go to the Devices menu.

3. Select FireProtect 2 (Heat). 4. Go to the settings by clicking on the gear icon . 5. Select Jeweller Signal Strength Test. 6. Perform the test following the tips in the app
The test does not start immediately, but the waiting time does not exceed the duration of one detector ping interval. The default value is 36 seconds. You can change the detector ping interval in the Jeweller (or Jeweller/Fibra) menu in the hub settings.
Icons
The icons show some of the detector states. You can view them in Ajax apps in the Devices tab.

Icon

Meaning

Jeweller signal strength between the detector and the hub or the radio signal range extender. The recommended value is two or three bars.

Learn more

Battery charge level of the device.
Learn more

The Interconnected Fire Detectors Alarm feature is activated.
Learn more

The detector operates in the Always Active mode.
The icon is displayed permanently. FireProtect 2 is always active and responds to a re 24/7, regardless of the system's security mode.
Learn more

The detector operates through a radio signal range extender.

The detector is permanently deactivated.
Learn more
The detector has detected a rapid temperature rise. The detector has detected that the temperature threshold has been exceeded. The detector was removed from the SmartBracket mounting panel, or the enclosure integrity was violated in another way. Check the mounting of the detector. The detector's siren plays an alarm sound. Malfunction detected. A list of malfunctions is available in the detector
states.
The detector has tamper triggering events deactivated.
Learn more
States
The states include information about the device and its operating parameters. You can see FireProtect 2 (Heat) states in Ajax apps. To access them:
1. Open the Ajax app. 2. Select a hub if you have several of them or if you are using the Ajax PRO
app. 3. Go to the Devices tab. 4. Select the device from the list.
Ajax apps display three FireProtect 2 temperature parameters. The rst one shows the air temperature in the room where the detector is installed. The other two (Temperature Threshold Exceeded and Rapid Temperature Rise) show whether re-related temperature changes are detected. These values may differ from the temperature in the room.

Parameter Temperature Jeweller Signal Strength
Connection via Jeweller Battery Charge

Meaning
Air temperature in the premise where FireProtect 2 is installed. Measured in Celsius or Fahrenheit degrees depending on the app settings.
In the normal state, the temperature value is displayed in black.
When the temperature rises, the eld is highlighted with red.
Jeweller signal strength between FireProtect 2 and the hub or radio signal range extender.
The recommended value is two or three bars.
Jeweller is a protocol for transmitting FireProtect 2 events and alarms.
Connection status between FireProtect 2 and the hub or radio signal range extender via Jeweller:
Online -- the detector is connected to the hub or radio signal range extender. Normal state.
O ine -- no connection between the detector and the hub or radio signal range extender. Check the detector connection.
The battery power level of the device:
OK -- detector batteries have su cient charge. Normal state.
Battery low -- detector batteries are discharged.
When the batteries are discharged, users and the CMS receive a noti cation.
After the low battery noti cation, the detector is able to operate for another month under normal conditions. In case of an alarm, the battery

Lid
Temperature Threshold Exceeded Rapid Temperature Rise

power is enough to ensure 4 minutes of the sound and LED indication operation.
How the battery charge is displayed
Battery life calculator
You can replace batteries in a detector with replaceable batteries only (has RB in its name). A detector with sealed batteries (with SB in the name) should be replaced with a new one after the batteries are discharged.
How to replace batteries in FireProtect 2 RB (Heat)
The status of the detector`s tamper that responds to detachment of the device from the surface or opening of the enclosure:
Open -- the detector is removed from the SmartBracket mounting panel, or the enclosure integrity is violated in another way. Check the mounting of the detector.
Closed -- the detector is installed on the SmartBracket mounting panel. The integrity of the device enclosure and the mounting panel is not violated. Normal state.
Learn more
Alarm state if temperature threshold is exceeded:
No -- normal state, the detector does not detect a temperature threshold exceeding.
Alarm -- the detector has detected a temperature threshold exceeding.
If a temperature threshold exceeding is detected, the text eld highlights red.
Learn more
Alarm by rapid temperature rise:

Permanent Deactivation
Firmware Device ID Device No.

No -- normal state, the detector does not detect a rapid temperature rise.
Alarm -- the detector has detected a rapid temperature rise.
If a rapid temperature rise is detected, the text eld highlights red.
Learn more
Shows the status of the device permanent deactivation function:
No -- the device operates in normal mode.
Lid only -- detector's tamper triggering noti cations are disabled.
Entirely -- the detector does not execute system commands, does not participate in automation scenarios, and does not send noti cations of alarms, malfunctions, and other events to the CMS and system users. In this case, the detector will continue to operate autonomously and indicate alarms using the built-in siren.
Learn more
FireProtect 2 rmware version.
ID (serial number) of FireProtect 2. Also available on the detector's enclosure (under the mounting panel) below the QR code and on the packaging box.
The number of FireProtect 2 loop (zone). Events are sent to the CMS from this number.

Settings
To change FireProtect 2 (Heat) settings in the Ajax app: 1. Open the Ajax app.

2. Select the hub if you have several of them or if you are using the Ajax PRO app.
3. Go to the Devices tab. 4. Select the device from the list. 5. Go to Settings by clicking on the gear icon . 6. Set the required settings. 7. Click Back to save the settings.

Settings Name

Meaning
Detector name. Displayed in the list of hub devices, text of SMS and noti cations in the events feed.
To change the name, click on the text eld.
The name can contain up to 12 Cyrillic characters or up to 24 Latin characters.

Room

Selecting the virtual room to which FireProtect 2 is assigned.
The room name is displayed in the SMS text and noti cations of the events feed.
To change the room, click on the eld.

Alert with a siren

If the temperature threshold exceeded

When this option is enabled, the Ajax sirens
connected to the system are activated when the detector detects a temperature threshold exceeding.

If rapid temperature rise detected

When the option is enabled, the Ajax sirens
connected to the system are activated when the detector detects a rapid temperature rise.

Jeweller Signal Strength Test

Switches the detector to the Jeweller signal strength test mode. The test helps to determine the optimal place for installing FireProtect 2.

Device Self-test User Guide
Permanent Deactivation
Delete device

The test shows the signal strength between the detector and the hub or radio signal range extender via the Jeweller wireless data transfer protocol.
The recommended value is two or three divisions.
Learn more
Runs a detector self-test.
Learn more
Opens FireProtect 2 User Manual in the Ajax app.
Allows to deactivate the device without removing it from the system. Three options are available:
No -- the device operates in normal mode.
Lid only -- detector's tamper triggering noti cations are disabled.
Entirely -- the detector does not execute system commands, does not participate in automation scenarios, and does not send noti cations of alarms, malfunctions, and other events to the CMS and system users. In this case, the detector will continue to operate autonomously and indicate alarms using the built-in siren.
Learn more
Unpairs FireProtect 2 from the hub and deletes its settings.

Battery life optimization setting
The Battery Life Optimization feature is provided to save the detectors' battery charge. It is available only for hubs on OS Malevich 2.14 or higher with

FireProtect 2 detectors connected. This feature is enabled by default. When the Battery Life Optimization feature is enabled, the hub increases the ping interval for FireProtect 2 detectors.
This feature doesn't affect alarm noti cation delivery time.
To disable the Battery Life Optimization feature: 1. Open the Ajax app. 2. Select the hub with FireProtect 2 detectors connected. 3. Go to: Hub  Settings  Service  Fire Detectors Settings. 4. Disable the Battery Life Optimization toggle. 5. Click Back to save the settings.
If the Battery Life Optimization feature is disabled: FireProtect 2 SB (Heat) built-in battery life is 5 years (instead of 10). FireProtect 2 RB (Heat) pre-installed battery life is 3.5 years (instead of 7).
Selection of installation place
The detector is designed for indoor installation only.
The coverage area of one FireProtect 2 (Heat) is 50 to 60 m², depending on the type of premises.

The detector is suitable for installation in premises where the generation of gases/vapours/smoke is part of the operating process. For example, in a garage, kitchen, boiler house or boiler room. The detector is placed in the center of the ceiling at a distance of 30 cm from light xtures, chandeliers, or any other decorative objects that may interfere with alarm detection. If there are beams on the ceiling protruding 30 cm or more, the detector should be installed between every two beams. If the beams protrude by less than 30 cm, installation on a beam in the central part of the ceiling is allowed. In halls or narrow corridors, detectors should be installed at a distance of no more than 7.5 m from each other. If the ceiling is sloping, the detector is installed at a distance of 60 cm from the top point of the ceiling. To select an installation place, draw a straight line down from the top of the ceiling. Then, draw a perpendicular from this line to the sloping part of the ceiling. The detector is installed at this point.
We do not recommend mounting the detector on a wall. This installation is acceptable if closely spaced beams or other obstacles interfere with the installation of the detector. Wall mounting is possible only if the detector is placed at a distance of 15­30 cm below the ceiling but above the doorways.
When installing on the wall, ensure the LEDs are visible to the user. It means FireProtect 2 must be installed upside down.

When choosing the location of the detector, consider the parameters that affect its operation:
Jeweller signal strength. Distance between the detector and the hub. Presence of barriers for radio signal passage between devices: walls, inter oor ceilings, large objects located in the room.
Consider the placement recommendations when designing the project of Ajax system for the object. The security system must be designed and installed by specialists. The list of recommended Ajax partners is available here.
Signal strength
The Jeweller signal strength is determined by the ratio of the number of undelivered/corrupted data packets that are exchanged between the hub and the detector to expected ones within a certain period of time. Signal strength is indicated by the icon on the Devices tab:
Three bars -- excellent signal strength. Two bars -- good signal strength. One bar -- low signal strength; stable operation is not guaranteed. Crossed out icon -- no signal; stable operation is not guaranteed.
Check the Jeweller signal strength at the installation site. If the signal strength is as low as one or zero bars, we cannot guarantee stable operation of the device. In this case, move the device. Repositioning even by 20 cm can signi cantly improve the signal reception.
If after relocation the detector still has a low or unstable signal strength, use a radio signal range extender.
Do not install the detector
1. Outdoors. This can lead to the detector failure.

2. In places with low or unstable Jeweller signal strength. This can result in the connection loss.
3. Inside premises with temperature and humidity outside the permissible limits. This could damage the detector.
4. In places with fast air circulation. For example, near fans, vents, open windows, or doors. This may interfere with re detection.
5. Opposite any objects with rapidly changing temperature. For example, electric and gas heaters. This can lead to false alarms.
6. In the corners of the room. This may interfere with re detection. 7. In bathrooms, showers, or other areas where the temperature changes
rapidly. This can lead to false alarms. 8. Near lighting xtures, decorations, and other interior items that may
interfere with the circulation of air in the room. This may interfere with re detection. 9. On surfaces that are usually warmer or colder than the rest of the premise. For example, roof traps. Temperature uctuations can interfere with re detection. 10. In high or inconvenient places. Access to the Test/Mute button is required to mute the alarm and test the detector if it's used without connection to a hub.
Installation
Make sure that you have selected the optimal installation place, and it complies with the requirements of this manual.
Only a competent specialist should install this device.
To install the detector:
1. Remove the SmartBracket mounting panel from the detector. To remove the panel, turn it counterclockwise.

2. Fix the SmartBracket panel to a surface using double-sided adhesive tape or another temporary fastener. The mounting panel has the UP sign, which indicates the correct position.
Use double-sided adhesive tape for temporary xation only. The device xed by the adhesive tape can peel off the surface at any time, which can lead to damage if the device is dropped.
3. Run the Jeweller Signal Strength Test. The recommended value is two or three bars. If the signal strength is a single bar or lower, we cannot guarantee the stable operation of the detector. Consider to relocate the device as repositioning even by 20 cm can signi cantly improve the signal strength. If there is still low or unstable signal after the relocation, use a radio signal range extender.
4. Remove the detector from the mounting panel. 5. Attach the SmartBracket panel with the bundled screws using all xation
points. When using other fasteners, make sure they do not damage or deform the mounting panel. 6. Place the detector on the SmartBracket mounting panel. 7. Adjust the position of the detector, if it is necessary.
It is necessary to perform a Self-test after the installation is nished.
Actions to take in case of Fire alarm (Smoke/Heat)
NEVER IGNORE THE ALARM! Assume that it is a real re alarm, and you have to evacuate from the premises immediately, even if you doubt about the cause of the alarm signal.

1. Don't open the doors if you feel heat or smoke behind them. Check other entries and use an alternative way to escape. Close all doors behind you as you leave.
If heavy smoke enters a room, stay close to the oor and crawl out. If possible, breathe through a wet cloth or hold your breath. Please note that more people die because of smoke inhalation than re.
2. Evacuate as quickly as you can, don't panic. Save time, and don't pack your things. Arrange a meeting place outside for everybody in the building. Check if everyone got out safely.
3. Call the re department immediately by yourself or ask someone nearby. Remember, even the smallest re can spread quickly, so do not hesitate to call the re department. Call the re department even if the alarm is automatically transmitted to a monitoring station.
NEVER come back to the house on re.
Malfunctions

If FireProtect 2 malfunction is detected (for example, there is no connection with the hub), the malfunction counter is displayed in the device eld in the Ajax apps.
All malfunctions are displayed in the detector States. Fields with malfunctions will be highlighted in red.
The device can report malfunctions to the CMS, as well as to users through push noti cations and SMS.
FireProtect 2 (Heat) malfunctions:
There is no connection with the hub or radio signal range extender. The detector's enclosure is open. Low battery charge level. Hardware malfunction (failure of the sensor of the detector).
Maintenance
The detector has a self-test system and does not require the user or installer intervention. We recommend to periodically run a self-test to familiarize people with the alarm sound and LED indication.
FireProtect 2 devices connected to the Ajax hubs generally do not require routine testing. All connected devices are constantly monitored for possible Faults or Low battery. However, we encourage all users to test FireProtect 2 devices periodically (monthly)* to allow residents of the building to become familiar with the re alarm signals of the system. *Please be aware that your local regulation might require more frequent testing (e.g., weekly).
Clean the detector enclosure of dust, cobwebs, and other contaminants as they emerge. Use a soft dry cloth suitable for equipment care. Do not use substances that contain alcohol, acetone, gasoline, and other active solvents.

The service life of the detector is 10 years. After this period, the sensitivity of the sensors decreases. We recommend replacing the detector with a new one to ensure uninterrupted re protection at the premises. The version of the detector with replaceable batteries (has RB in the name) operates from pre-installed batteries for up to 7 years. When the batteries are discharged, replace them with new ones.
How to replace batteries in FireProtect 2 RB (Heat)
A detector with sealed batteries (has SB in the name) should be replaced with a new one after the batteries are discharged.
Buy FireProtect 2 SB (Heat)
Ensure the batteries are installed with the correct polarity. The polarity is marked inside the enclosure. Please run a self-test with Ajax apps or by pressing the Test/Mute button after the batteries are replaced to check the correct operation of the detector.
Technical speci cations
All technical speci cations of FireProtect 2 RB (Heat)
All technical speci cations of FireProtect 2 SB (Heat)
Compliance with standards
Complete set
For FireProtect 2 RB (Heat)
1. FireProtect 2 RB (Heat) Jeweller 2. SmartBracket mounting panel 3. Installation kit

4. 2 × CR123A battery (pre-installed) 5. Quick start guide
For FireProtect 2 SB (Heat)
1. FireProtect 2 SB (Heat) Jeweller 2. SmartBracket mounting panel 3. Installation kit 4. Quick start guide
Warranty
Warranty for the Limited Liability Company "Ajax Systems Manufacturing" products is valid for 2 years after the purchase. If the device does not function correctly, please contact the Ajax Technical Support rst. In most cases, technical issues can be resolved remotely.
Warranty obligations
User Agreement
Contact Technical Support: email Telegram

Subscribe to the newsletter about safe life. No spam

Email

Subscribe



References

Mozilla/5.0 (Windows NT 10.0; Win64; x64) AppleWebKit/537.36 (KHTML, like Gecko) Chrome/117.0.0.0 Safari/537.36 Skia/PDF m117