Danfoss KP 15 Pressure Switch Installation Guide
Installation guide for the Pressure switch KP 15 with goldplated contacts.
Refrigerants
The following refrigerants are approved for use with the KP 15:
- R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A
For a complete list of approved refrigerants, visit: http://products.danfoss.com/all-products/
Technical Specifications
Temperature Limits:
- Minimum operating temperature (t₁ min.): -40 °C (-40 °F)
- Maximum operating temperature (t₁ max.): 65 °C (149 °F)
Pressure Connections:
- LP (Low Pressure) connection: 7/16 in SAE flare
- HP (High Pressure) connection: 7/16 in SAE flare
Maximum Test Pressure:
- LP: 14 bar (203 psig)
- HP: 35 bar (510 psig)
Electrical Connections
Caution: Disconnect power supply before making wiring connections or performing service to avoid possible electrical shock or damage to equipment. Never touch live parts with fingers or tools.
Contact Load:
- Max: 30 mA/30 V DC
- Min: 1 mA/5 V DC
Regulation Ratings:
- AC1: 10 A, 400 V
- AC3: 6 A, 400 V
- AC15: 4 A, 400 V
- DC13: 12 W, 220 V
Alarm (Au surface is burnt away):
- SPDT + LP signal
Diagrams illustrating wiring for LP and HP connections, including cut-in and cut-out differential settings, are provided.
Manual Trip Function
The pressure switch features a manual trip function for testing purposes. The diagram shows how to activate the manual trip using the test button. Note: Use fingers only for the test function; do not use a screwdriver.
Pressure Adjustment
The pressure switch allows for adjustment of both the LP and HP setpoints and their differentials. The diagrams illustrate the adjustment process for both low and high pressure sides.
Adjustment Specifications:
Type | Range | Max. working pressure PS/MWP |
---|---|---|
KP 15 | LP: -0.2 - 7.5 bar HP: 8 - 32 bar |
17 bar/245 psig (LP) 32 bar/465 psig (HP) |
Reset | LP: -0.2 - 7.5 bar HP: 8 - 32 bar |
17 bar/245 psig (LP) 32 bar/465 psig (HP) |
Enclosure Types
The KP 15 is available with different enclosure types:
- A: 8-32 UNC (M4)
- B: Enclosure IP30 (EN 60529)
- C: Enclosure IP44 (EN 60529)
A maximum enclosure opening of 3 mm (1/8 in) is indicated.
UK Customer Information
For UK customers, please contact Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB.