Mitsubishi Electric CITY MULTI HYBRID Data Book

Models: PKFY-WL-VLM-E, PKFY-WL-VKM-E

1. Specifications

This section details the specifications for various models of the CITY MULTI HYBRID indoor units.

ModelPower SourceCooling Capacity (Nominal)Heating Capacity (Nominal)External FinishPower InputCurrent InputExternal Dimension (HxWxD)Net WeightHeat ExchangerFANWater VolumeExternal Static PressureMotor TypeMotor OutputDriving MechanismAirflow Rate (Low-Mid2-Mid1-High)Sound Pressure Level (measured in anechoic room)Insulation MaterialAir FilterProtection DeviceRefrigerant Control DeviceConnectable Outdoor Unit/HBC Controller/Hydro UnitWater Piping Diameter (Inlet/Outlet)Field Pipe Size (Inlet/Outlet)Field Drain Pipe Size (mm I.D.)Standard Attachment DocumentAccessoryOptional Parts
PKFY-WL10VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz1.2 kW (4,100 BTU/h)1.4 kW (4,800 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.20 kW0.15 A299x773x237 mm (11-25/32 x 30-7/16 x 9-11/32 in.)11 kg (25 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.6 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor3.3-3.8-4.1-4.5 m³/min (55-63-68-75 L/s, 117-134-145-159 cfm)22-26-28-30 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL15VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz1.7 kW (5,800 BTU/h)1.9 kW (6,500 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.20 kW0.15 A299x773x237 mm (11-25/32 x 30-7/16 x 9-11/32 in.)11 kg (25 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.6 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor3.3-3.8-4.3-4.9 m³/min (55-63-72-82 L/s, 117-134-152-173 cfm)22-26-29-32 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL20VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz2.2 kW (7,500 BTU/h)2.5 kW (8,500 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.25 kW0.20 A299x773x237 mm (11-25/32 x 30-7/16 x 9-11/32 in.)11 kg (25 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.6 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor3.3-3.8-4.3-4.9 m³/min (55-63-72-82 L/s, 117-134-152-173 cfm)22-28-33-36 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL25VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz2.8 kW (9,600 BTU/h)3.2 kW (10,900 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.35 kW0.30 A299x773x237 mm (11-25/32 x 30-7/16 x 9-11/32 in.)11 kg (25 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.7 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor4.0-5.4-7.0-8.4 m³/min (67-90-117-140 L/s, 141-191-247-297 cfm)22-30-36-41 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL32VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz3.6 kW (12,300 BTU/h)4.0 kW (13,600 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.35 kW0.30 A299x898x237 mm (11-25/32 x 35-3/8 x 9-11/32 in.)13 kg (29 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.7 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor4.0-5.4-7.0-8.4 m³/min (67-90-117-140 L/s, 141-191-247-297 cfm)29-34-38-41 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL40VLM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz4.5 kW (15,400 BTU/h)5.0 kW (17,100 BTU/h)Plastic, MUNSELL (0.7PB 9.2/0.4)0.45 kW0.40 A299x898x237 mm (11-25/32 x 35-3/8 x 9-11/32 in.)13 kg (29 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 10.7 L0 Pa (0 mmH2O)DC motor0.030 kWDirect-driven by motor6.3-7.6-9.0-10.4 m³/min (105-127-150-173 L/s, 226-290-353-420 cfm)30-36-41-45 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 3/4 screw20 mm (20 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15), Insulation, Tie bandDrain pump kit (PAC-SK01DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL50VKM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz5.6 kW (19,100 BTU/h)6.3 kW (21,500 BTU/h)Plastic, MUNSELL (1.0Y 9.2/0.2)0.46 kW0.40 A365x1170x295 mm (14-3/8 x 46-1/16 x 11-5/8 in.)20 kg (44 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 12.0 L0 Pa (0 mmH2O)DC motor0.069 kWDirect-driven by motor18-20 m³/min (300-333 L/s, 636-706 cfm)39-42 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 1-1/4 screw30 mm (30 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, L-shape connection pipe A/B, I-shape connection pipe A/B, Insulation, Tie bandDrain pump kit (PAC-SK19DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL63VKM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz7.1 kW (24,200 BTU/h)8.0 kW (27,300 BTU/h)Plastic, MUNSELL (1.0Y 9.2/0.2)0.56 kW0.50 A365x1170x295 mm (14-3/8 x 46-1/16 x 11-5/8 in.)20 kg (44 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 12.0 L0 Pa (0 mmH2O)DC motor0.069 kWDirect-driven by motor18-22 m³/min (300-367 L/s, 636-777 cfm)39-45 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 1-1/4 screw30 mm (30 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, L-shape connection pipe A/B, I-shape connection pipe A, Insulation, Tie bandDrain pump kit (PAC-SK19DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)
PKFY-WL80VKM-E1-phase 220-240V 50Hz, 1-phase 220V 60Hz9.0 kW (30,700 BTU/h)10.0 kW (34,100 BTU/h)Plastic, MUNSELL (1.0Y 9.2/0.2)0.76 kW0.70 A365x1170x295 mm (14-3/8 x 46-1/16 x 11-5/8 in.)20 kg (44 lbs)Cross fin (Aluminum fin and copper tube)Line flow fan x 12.0 L0 Pa (0 mmH2O)DC motor0.069 kWDirect-driven by motor18-26 m³/min (300-433 L/s, 636-918 cfm)39-49 dB(A)Polyethylene sheetPP honeycombFuse-HYBRID CITY MULTI/ CMB-WM-V-AA, CMB-WM-V-AB/ CMH-WM-V-ARC 1-1/4 screw30 mm (30 mm)I.D. 16(5/8)Installation Manual, Instruction BookMount board, Screw, Felt tape, L-shape connection pipe A/B, I-shape connection pipe A, Insulation, Tie bandDrain pump kit (PAC-SK19DM-E), Valve kit (PAC-SK35VK-E), Attachment plate (PAC-SK39AP-E), 6m Lead wire (PAC-SK40LW-E)

Notes:

2. External Dimensions

This section provides detailed diagrams of the external dimensions for the various models, including required installation clearances and piping hole details.

PKFY-WL10, 15, 20, 25VLM-E:

Diagrams show top, front, left, and right views, along with details for wall hole, piping cutouts, and terminal block locations. Key dimensions are provided.

PKFY-WL32, 40VLM-E:

Similar diagrams and dimensions are provided for these models, with noted differences in overall width and related dimensions.

PKFY-WL50, 63, 80VKM-E:

Diagrams and dimensions for the larger capacity models are presented, including details for water pipe connections and overall unit dimensions.

3. Center of Gravity

A table lists the center of gravity coordinates (W, D, H, X, Y, Z) for each model in millimeters.

ModelWDHXYZ
PKFY-WL10VLM-E773237299130340150
PKFY-WL15VLM-E773237299130340150
PKFY-WL20VLM-E773237299130340150
PKFY-WL25VLM-E773237299130340150
PKFY-WL32VLM-E898237299120390150
PKFY-WL40VLM-E898237299120390150
PKFY-WL50VKM-E1170295365190460190
PKFY-WL63VKM-E1170295365190460190
PKFY-WL80VKM-E1170295365190460190

4. Electrical Wiring Diagrams

Detailed wiring diagrams are provided for the PKFY-WL10, 15, 20, 25, 32, 40VLM-E models and the PKFY-WL50, 63, 80VKM-E models. These diagrams illustrate power supply connections, internal component wiring, and connections to optional accessories like drain pumps and valve kits.

Key components and their symbols are explained in a legend, including:

Notes on wiring include:

5. Sound Levels

5-1. Sound Levels

A table presents the sound levels in decibels (dB(A)) measured in an anechoic room for various models at different fan speeds (Low, Middle2, Middle1, High).

5-2. NC Curves

Noise Criteria (NC) curves are provided for each model, illustrating octave band pressure levels versus octave band center frequencies. These curves help in assessing the perceived loudness of the unit's noise.

6. Temperature/Airflow Distributions

6-1. Temperature Distributions

Contour plots show typical temperature distributions within a room for both cooling and heating modes, with horizontal and downward airflow respectively. These are provided for models PKFY-WL10VLM-E, PKFY-WL15VLM-E, PKFY-WL20VLM-E, PKFY-WL25VLM-E, PKFY-WL32VLM-E, PKFY-WL40VLM-E, and PKFY-P50, 63, 80VKM-E.

Note: Actual temperature distributions may vary based on installation conditions, room characteristics, and load.

6-2. Airflow Distributions

Similar contour plots illustrate typical airflow distributions (in m/s) for cooling and heating modes, showing the airflow patterns at different distances from the unit. These are provided for the same models as the temperature distributions.

Note: Actual airflow distributions may vary based on installation conditions, room characteristics, and load.

7. Electrical Characteristics

A table summarizes the electrical characteristics for each model, including voltage/frequency, power supply range, Maximum Circuit Amps (MCA), Indoor Fan Motor (IFM) output, and Full Load Amps (FLA).

ModelVolts/HzPower Supply Range +-10%MCA(A)IFM Output (kW)FLA(A)
PKFY-WL10VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.250.0300.20
PKFY-WL15VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.250.0300.20
PKFY-WL20VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.320.0300.25
PKFY-WL25VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.440.0300.35
PKFY-WL32VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.440.0300.35
PKFY-WL40VLM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.570.0300.45
PKFY-WL50VKM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.580.0690.46
PKFY-WL63VKM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.700.0690.56
PKFY-WL80VKM-E220-240V/50Hz, 220V/60HzMax.: 264V, Min.: 198V0.950.0690.76

8. Optional Parts

8-1. Optional Parts Lineup for the Indoor Unit

This table lists optional parts available for the PKFY-WL-VLM-E and PKFY-WL-VKM-E indoor units, including their description and model numbers:

8-2. Drain Pump

Details the installation and function of the PAC-SK01DM-E and PAC-SK19DM-E drain pumps, which can lift water up to 850mm. Includes a list of included items like screws and drain hoses.

8-3. Valve Kit

Explains the necessity of the valve kit for HVRF-Y and HVRF-R2 systems. A table shows the connectability between different outdoor and indoor unit types when using the valve kit.

8-4. Attachment Plate

Recommends the use of the attachment plate (PAC-SK39AP-E) for installing the valve kit on ceiling plates or when hanging from the ceiling.

8-5. 6m Lead Wire

Introduces the optional PAC-SK40LW-E (6m) lead wire for extending the connection distance to the valve kit, noting a maximum allowable piping distance of 5 meters.

Environmental Statement

Eco Changes: Mitsubishi Electric Group's environmental statement emphasizing commitment to environmental management and sustainable society.

Warning: Users are cautioned against using refrigerants other than those specified, as it may lead to unit damage, fire, or legal violations. Mitsubishi Electric is not responsible for issues arising from the use of incorrect refrigerants. The equipment uses R410A/R32 refrigerant.

PDF preview unavailable. Download the PDF instead.

MEES20K038 DATABOOK Adobe Acrobat Pro DC 20.13.20074 Adobe Acrobat Pro DC 20.13.20074

Related Documents

Preview Mitsubishi Electric PKFY-P VLM-E and VKM-E Wall-Mounted Air Conditioners
Detailed specifications and features of Mitsubishi Electric's PKFY-P VLM-E and VKM-E series wall-mounted air conditioning units, highlighting design, performance, and control options.
Preview Mitsubishi Electric Wall-Mounted Air Conditioners (VLM/VKM Series) - Specifications and Features
Detailed information on Mitsubishi Electric's PKFY-P VLM-E and PKFY-P VKM-E wall-mounted air conditioning units, covering their sophisticated design, improved airflow control, reduced noise levels, fan and vane control, optional parts, and comprehensive technical specifications.
Preview Mitsubishi Electric R32 Hybrid Pipe Connections Quick Reference Guide
This guide provides essential pipe connection specifications for Mitsubishi Electric's R32 Hybrid air conditioning indoor units, covering various models including PLFY, PEFY, PFFY, and PKFY series for ceiling, floor, and wall mounting.
Preview Mitsubishi Electric PKFY-P VLM-E Air Conditioning Systems - Product Flyer
Discover the Mitsubishi Electric PKFY-P VLM-E air conditioning unit, featuring a modern, compact design, reduced noise levels, and improved airflow control for enhanced comfort. Ideal for various spaces.
Preview Mitsubishi Electric CITY MULTI PEFY-P-NMHU-E2 / PEFY-P-NMHSU-E Data Book
Technical data book for Mitsubishi Electric CITY MULTI air conditioning systems, specifically the PEFY-P-NMHU-E2 and PEFY-P-NMHSU-E indoor units. Includes detailed specifications, external dimensions, center of gravity data, electrical wiring diagrams, sound levels, fan characteristics, and optional parts information.
Preview Mitsubishi Electric Hybrid CITY MULTI VRF Systems: Product Overview and Specifications
Explore Mitsubishi Electric's Hybrid CITY MULTI VRF air conditioning systems. This brochure details advanced features, energy efficiency, comfort, and a wide range of indoor and outdoor units for commercial applications.
Preview Mitsubishi Electric R32 Hybrid Catalogue: Next Generation VRF Heat Recovery Systems
Discover the Mitsubishi Electric City Multi R32 Hybrid Systems, featuring advanced 2-pipe VRF heat recovery technology with low GWP R32 refrigerant. These systems offer simultaneous heating and cooling, enhanced safety with water-based indoor units, reduced leak detection, and significant energy and cost efficiencies for commercial buildings.
Preview Mitsubishi Electric PKFY-P VLM-E Air Conditioning Systems Product Flyer
A product flyer for Mitsubishi Electric's PKFY-P VLM-E Air Conditioning Systems, detailing new design features, reduced noise levels, and advanced airflow control. Includes technical specifications and unit dimensions.