SmartGen HGM1790N Genset Controller User Manual

1. Overview

The HGM1790N genset controller is suitable for single unit automation and monitoring control, and can also be used for pumping units. It enables manual start/stop of the genset and automatic start/stop via a remote start signal. The controller supervises and protects genset operation by gathering and analyzing data such as voltage, current, water temperature, and oil pressure, indicating fault conditions and facilitating maintenance. Its graphical LCD and touch-button operation provide a clear and intuitive user experience. Parameter thresholds and delay values can be adjusted via the front panel or a USB port connected to PC software.

2. Performance and Characteristics

3. Specification

Table 2 Technical Parameters

Item Content
Working Voltage DC8.0V to 35.0V, Continuous Power Supply
Power Consumption <1.2W (Standby mode: ≤0.5W)
Alternator Voltage Input AC 15V ~ AC 360 V (ph-N)
Alternator Frequency 50Hz/60Hz
Speed Sensor Voltage 1.0V to 24V (RMS)
Speed Sensor Frequency Max. 10,000Hz
Start Relay Output 1Amp DC28V DC B+ power supply
Fuel Relay Output 1Amp DC28V DC B+ power supply
Aux. Output 1 1Amp DC28V DC B+ power supply
Aux. Output 2 1Amp DC28V DC B+ power supply
Aux. Output 3 1Amp DC28V DC B+ power supply
Programmable Input Digital: Active when connected to B-
Case Dimensions 95mm x 86mm x 46.5mm
Panel Cutout 78mm x 66mm
CT Secondary Current Rated: 5A
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-25~+70)°C
Protection Level IP55: When waterproof rubber gasket installed between the controller and panel fascia.
Insulation Intensity Attach AC2.2kV voltage between AC high voltage terminal and low voltage terminal (leak current below 3mA in 1 minute).
Weight 0.18kg

4. Operation

4.1. Front Panel Description

The front panel features an LCD display, indicator lights, and touch buttons. Key components include:

4.2. Indicator Description

4.3. Panel Keys

Table 3 Key Descriptions

Key Definition Description
? Stop/Reset Stop/Reset In auto/manual mode, press to shutdown the genset. Resets shutdown alarms when the genset is in alarm status. Press and hold for over 3s in stop mode to test indicator lights and LCD icons. Press to immediately stop during a stop process. Press to quickly exit the parameter setting menu.
⚙️ Auto/Increase Auto/Increase Places the module into auto mode, controlling the genset by remote start signals. In the settings menu, moves the cursor up and increases the set value.
▶️ Start/Decrease Start/Decrease Starts the genset. In the settings menu, moves the cursor down and decreases the set value.
⬇️ Page Down Page Down Scrolls through the LCD monitor pages. Hold and press for over 2s to enter the settings menu. Moves the cursor and confirms setting information in the parameter setting menu.

4.4. LCD Icons

Table 4 LCD Icons

Icon Definition Icon Definition
Genset Start Indication FL Fuel Level Indication
Boot time is counting (reaching crank disconnect condition) L1 Generator Voltage Indication
Emergency Stop Alarm DC Battery Voltage Indication
Over Speed/Over Frequency Alarm kPa Oil Pressure Unit
Under Speed/Under Frequency Alarm A Current With Load Unit
High Temp. Alarm H Hours Count
Low Fuel Level Hz Frequency Unit
Auxiliary Alarm °C Temperature Unit
Low Oil Pressure rpm Speed Unit (revolutions per minute)
Fail to Start kW Active Power Unit
Fail to Stop V Voltage Unit
Voltage Abnormal % Percentage
Over Voltage
Under Voltage
Over Current With Load

4.5. Display Description

The LCD displays various parameters:

NOTE:

4.6. Auto Start/Stop Operation

Auto mode is selected by pressing the ⚙️ button, confirmed by an illuminated LED.

Automatic Start Sequence:

  1. When "Remote Start" is active (Terminal 6 connected to B-), "Start Delay" timer initiates.
  2. After "Start Delay", preheat relay energizes (if configured), and "Preheat Delay" starts counting.
  3. Following "Preheat Delay", the Fuel Relay (if configured) energizes, and one second later, the Start Relay engages. If the genset fails to fire during "Cranking Time", the fuel relay and start relay stop. "Crank Rest Time" begins, awaiting the next crank attempt.
  4. If the start sequence exceeds the set number of attempts, it terminates, displaying "Fail to Start" on the LCD with a blinking alarm indicator.
  5. Upon successful cranking, the "Safety On" timer activates, inhibiting Low Oil Pressure, High Temperature, and other alarms. "Start Idle" delay (if configured) initiates afterward.
  6. During "Start Idle" delay, under speed, under frequency, and under voltage alarms are inhibited. "Warming up" delay (if configured) initiates upon completion of "Start Idle" delay.
  7. Once "Warming up" delay is over, the genset starts normal running. Abnormal generator voltage or frequency triggers shutdown alarm signals.

Automatic Stop Sequence:

  1. When the "Remote Start" signal is removed, "Stop Delay" initiates.
  2. After "Stop Delay" expires, "Cooling Delay" initiates.
  3. During "Stop Idle" Delay (if configured), the idle relay energizes.
  4. "ETS Solenoid Hold" begins, energizing the ETS relay while the fuel relay de-energizes.
  5. "Fail to Stop Delay" begins; complete stop is detected automatically.
  6. The generator enters standby mode after its "After stop" delay. Otherwise, a "Fail to Stop" alarm is initiated (LCD display ).

NOTE:

4.7. Manual Start/Stop Operation

  1. MANUAL START: Press the ▶️ button to start the genset. Refer to Section 4.6 for detailed procedures. The controller protects the genset from high temperature, low oil pressure, over speed, and abnormal voltage during running.
  2. MANUAL STOP: Press the ? button to shut down the running genset. Refer to Section 4.6 for detailed procedures.

5. Protection

Table 5 Controller Alarms

Icons Alarms Type Triggering Condition
Emergency Shut Alarm Shut Alarm Controller sends alarms upon detecting emergency shutdown alarms.
Over Speed Shut Shut Alarm Controller sends alarms when genset speed exceeds the over speed threshold and lasts for over 2s.
Over Frequency Shut Shut Alarm Controller sends alarms when generator frequency exceeds the over frequency threshold and lasts for over 2s.
⬇️ Under Speed Shut Shut Alarm After warming up delay, controller sends alarms when speed is lower than the under speed threshold and lasts for over 10s.
⬇️ Under Frequency Shut Shut Alarm When genset is running normally, controller sends alarms once generator frequency falls below the under frequency threshold and lasts for over 10s.
?️ High Temp. Shut Shut Alarm After safe running delay, controller sends alarms once genset temperature is higher than the over temp. threshold and lasts for over 3s.
?️ High Temp. Input Shut Shut Alarm After safe running delay, controller sends alarms when high temperature input is active.
Temp. Sensor Open/Short Circuit Shut Shut Alarm After safe running delay, controller sends alarms when temperature sensor resistance value is above 60000 or under 50.
?️ Low Oil Pressure Shut Shut Alarm After safe running delay, controller sends alarms when genset oil temperature is lower than the low oil pressure threshold and lasts for over 2s.
?️ Low Oil Pressure Input Shut Alarm After safe running delay, controller sends alarms when low oil pressure input is active.
Oil Pressure Sensor Open/Short Circuit Shut Shut Alarm After safe running delay, controller sends alarms when oil pressure sensor resistance value is above 60000 or under 50.
Gen Over Current Warn Warn Alarm Controller sends alarms when generator current is higher than the preset value and over current action is selected as "Warn".
Gen Over Current Shut Shut Alarm Controller sends alarms when generator current is higher than the preset value and lasts for over the delay value (over current action is selected as "Shutdown").
Gen Over Current Cooling Shut Shut Alarm Controller sends alarms when generator current is higher than the preset value and lasts for over the delay value (over current action is selected as "Cooling Shutdown").
Gen Over Volt Shut Shut Alarm After safe running delay, controller sends alarms when generator voltage is higher than the over voltage threshold and lasts for over the voltage abnormal delay value.
Gen Low Volt Shut Shut Alarm After safe running delay, controller sends alarms when generator voltage is lower than the under voltage threshold and lasts for over the voltage abnormal delay value.
Fail to Start Shut Alarm Controller sends alarms when genset fails to start in preset attempts.
Auxiliary Shut Alarm Input Shut Alarm Controller sends alarms when auxiliary input port, configured as "auxiliary shutdown alarm input", is active.
?️ Low Fuel Level Warn Warn Alarm Controller sends alarms when fuel level is lower than the low fuel level threshold and lasts for over 10s.
?️ Low Fuel Level Input Warn Warn Alarm Controller sends alarms when low fuel level input is active.
Fuel Level Sensor Open/Short Circuit Warn Warn Alarm Controller sends alarms when fuel level sensor resistance value is above 60000 or under 50.
Fail to Stop Warn Alarm Controller sends alarms when genset fails to stop in stop duration.
Low Battery Volt Warn Warn Alarm Controller sends alarms when battery voltage is lower than the under voltage threshold and lasts for over 20s.
High Battery Volt Warn Warn Alarm Controller sends alarms when battery voltage is higher than the over voltage threshold and lasts for over 20s.

6. Wiring Connection

Fig.2 Controller Back Panel

The controller has multiple terminals for various connections:

NOTE: Type-B USB port is for PC software connection, parameter configuration, and data monitoring.

7. Parameter Range and Definition

7.1 Parameters Contents and Range

Table 7 Parameter Setting Contents and Range

No. Parameter Range Default Value Description
P00 Start Delay (0-3600)s 1 Time from remote start signal active to genset start.
P01 Stop Delay (0-3600)s 1 Time from remote start signal deactivated to genset stop.
P02 Start Attempts (1-10) times 3 Maximum number of crank attempts. Controller initiates fail to start alarm if none are successful.
P03 Preheat Time (0-300)s 0 Time of pre-powering heat plug before starter is powered up.
P04 Cranking Time (3-60)s 8 Time of powering up the starter for every crank attempt.
P05 Crank Rest Time (3-60)s 10 Waiting time before second power up when engine start fails.
P06 Safety On Delay (1-60)s 10 Alarms for low oil pressure, high temperature, under speed, under frequency, and under voltage are inactive during this period.
P07 Start Idle Time (0-3600)s 0 Idle running time of genset when starting.
P08 Warming Up Time (0-3600)s 10 Warming time between genset switch on and normal running.
P09 Cooling Time (3-3600)s 10 Radiating time before genset stop, after it unloads.
P10 Stop Idle Time (0-3600)s 0 Idle running time when genset stops.
P11 ETS Solenoid Hold (0-120)s 20 Time of powering up the electromagnet during stop procedure.
P12 Fail to Stop Delay (0-120)s 0 Time between ending of genset idle delay and stopped when "ETS output time" is set as 0.
Time between ending of ETS hold delay and stopped when "ETS output time" is not 0.
P13 Flywheel Teeth (1-300) 118 Tooth number of the engine for judging crank disconnect conditions and inspecting engine speed. Refer to installation instructions.
P14 Generator Poles (2-16) 4 Configuring numbers of generator poles.
P15 Generator Abnormal Time (0-20.0)s 10.0 Alarm delay for generator over and under voltage states.
P16 Generator Over Voltage (30-1000)V 264 When generator voltage exceeds this value and stays for "Generator Abnormal Time", it is regarded as over voltage and Generator Over Voltage shutdown alarm is initiated. If voltage is 1000V, over voltage signal is not initiated.
P17 Generator Under Voltage (30-1000)V 196 When voltage falls below this value and stays for "Generator Abnormal Time", it is regarded as under voltage and Generator Under Voltage shutdown alarm is initiated. If voltage is 30V, under voltage signal is not initiated.
P18 Engine Under Speed (0-6000)RPM 1200 When engine speed falls below this value and stays for 10s, it is regarded as under speed and under speed alarm shutdown signal is sent.
P19 Engine Over Speed (0-6000)RPM 1710 When engine speed exceeds this value and stays for 2s, it is regarded as over speed and over speed alarm shutdown signal is sent.
P20 Under Frequency (0-75.0)Hz 45.0 When generator frequency falls below this value and not 0, and stays for 10s, it is regarded as under frequency and under frequency alarm shutdown is initiated.
P21 Over Frequency (0-75.0)Hz 57.0 When generator frequency exceeds this value and stays for 2s, it is regarded as over frequency and over frequency alarm shutdown is initiated.
P22 High Temperature (80-140)°C 98 When external temperature sensor value exceeds this threshold, high temperature signal is sent. Detection starts after safety delay and concerns only the temperature sensor connected to the temperature sensor input port. If set value is 140, high temperature signal is not sent (concerns only temperature sensor, not high temperature signal via config. input port).
P23 Low Oil Pressure (0-400)kPa 103 When external pressure sensor value falls below this threshold, low oil pressure delay begins. Detection starts after safety on delay. If set value is 0, low oil pressure signal is not sent (concerns pressure sensor only, not low oil pressure warning signal via configurable input port).
P24 Low Liquid Level (0-100)% 10 When liquid level of external sensor falls below this value and stays for 10s, low liquid level signal is sent and warning without shutdown is initiated.
P25 Battery Over Volts (12-40)V 33.0 When battery voltage exceeds this value and stays for 20s, Battery Over Volts signal is sent and warning without shutdown is initiated.
P26 Battery Under Volts (4-30)V 8.0 When battery voltage falls below this value and stays for 20s, Battery Under Volts signal is sent and warning without shutdown is initiated.
P27 CT Ratio (5-6000)/5 500 Current transformer ratio default as 500:5.
P28 Full-load Current (5-1900)A 500 Rated current of generator, used for calculating over current with load.
P29 Over Current Percentage (50-130) 120 Over current delay starts when current with load is greater than value of full-load current multiply over current percentage.
P30 Over Current Delay (0-3600)s 60 When current with load exceeds preset value and stays so over delay time, over current alarm will be initiated.
P31 Action (0-2) 0 0: Warn 1: Shutdown 2: Cooling and Shutdown
P32 Aux. Output 3 (0-9) 3 Default: Common Alarm
P33 Digital Input (0-8) 4 Default: Auxiliary shutdown; if set value is 8, fuel level sensor type can be selected.
P34 Digital Input Delay (0-20.0)s 2.0 Active delay time for digital input ports.
P35 Power On Mode (0-2) 0 0: Stop 1: Manual 2: Auto
P36 Password Set (0-9999) 0318 See Table 11.
P37 Crank Disconnect Condition (0-6) 1 Starter disconnection condition. 3 conditions: speed, generator frequency, and oil pressure. Aims to separate the start motor and engine as soon as possible.
P38 Disconnect Engine Speed (0-3000) RPM 360 When speed is higher than the set value, starter will be disconnected.
P39 Disconnect Generator Freq (10.0-30.0) Hz 14.0 When generator frequency is higher than the set value, starter will be disconnected.
P40 Disconnect Oil Pressure (0-400) kPa 200 When generator oil pressure is higher than the set value, starter will be disconnected and oil engine crank successfully.
P41 AC System (0-3) 2 0: 3P4W 1: 2P3W 2: 1P2W 3: 3P3W. Used for calculating generator voltage and active power.
P42 Temp. Sensor (0-10) 06 SGD (120°C resistor type)
P43 OP Sensor (0-10) 06 SGD (10Bar resistor type)
P44 Fuel Level Sensor (0-7) 0 Not used. If fuel level sensor is used, digital input port must be set as "8 Multiplex Level Sensor".
P45 Disconnect Oil Pressure Delay (0-20.0)s 0.0s When crank disconnect condition including oil pressure, and engine oil pressure and delay value are higher than set values, starter will be disconnected and oil engine crank successfully.
P46 Aux. Output 1 (0-9) 3 Default: Idle Speed Output
P47 Aux. Output 2 (0-9) 2 Default: ETS Output

7.2 Definable Contents of Relay Outputs

Table 8 Definable Contents of Relay Outputs

No. Items Description
0 Not Used Output is not active.
1 Common Alarm Includes all shutdown alarms and warning alarms. Warning alarms are not self-latching, while shutdown alarms are self-latching and will not disappear until they are reset.
2 Energize to Stop Suitable for gensets with stop electromagnet. The electromagnet closes when stop idle is over and opens when EST delay is over.
3 Idle Control Used for machines with idles. Closes during cranking, disconnects during warming up, closes during stop idle delay, disconnects after complete stop.
4 Preheat Control Closes before starting and opens before starter is powered on.
5 Closing Gens Closes the breaker during normal operation of the generator.
6 High Speed Output Output when entering high speed warming up and disconnects after high speed cooling.
7 Rated Speed Output Output when speed is normal.
8 Over Speed Output Output when speed is over the set limit value.
9 Reserved

7.3 Definable Contents of Digital Inputs

Table 9 Definable Contents of Digital Inputs (Active When GND (B-) Connected)

No. Description Notes
0 Not Used
1 High Temperature Alarm If signals are activated after crank disconnect, shutdown alarm will be immediately initiated.
2 Low OP Alarm Only warning and not stops if this input is active.
3 Reserved
4 Auxiliary Shutdown Shutdown alarm will be immediately initiated if this input is active.
5 High Temperature Cooling Shutdown When the genset is working normally and this signal is activated, if there is a high temperature situation, the controller will first cool down the generator and then stop it. If the signal is deactivated and a high temperature situation occurs, the controller will shut down the genset without cooling down.
6 Reserved
7 Reserved
8 Multiplex Level Sensor Parameter P44 "Fuel Level Sensor" Input is active.

7.4 Sensor Selection

Table 10 Sensor Selection

No. Items Content Remark
1
Temperature
Sensor
0 Not used Digital input is digital signal; low or high electrical level can be selected to be active. Connecting to earth point means low electrical level is selected; hanging in air means high electrical level is selected. Cannot be connected to power supply positive. The range of user-defined resistor type sensor is 0-60000; by default SGD sensor is selected.
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 VDO
5 SGH (Huanghe sensor)
6 SGD (Dongkang sensor)
7 CURTIS
8 DATCON
9 VOLVO-EC
10 SGX 120 DEGREE
2
Oil Pressure
Sensor
0 Not used Digital input is digital signal; low or high electrical level can be selected to be active. Connecting to earth point means low electrical level is selected; hanging in air means high electrical level is selected. Cannot be connected to power supply positive. The range of user-defined resistor type sensor is 0-60000; by default SGD sensor is selected.
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 VDO 10Bar
5 SGH (Huanghe sensor)
6 SGD (Dongkang sensor)
7 CURTIS
8 DATCON 10Bar
9 VOLVO-EC
10 SGX 10Bar
3
Fuel Level
Sensor
0 Not used Digital input is digital signal; low or high electrical level can be selected to be active, connecting to earth point means low electrical level is selected, hang in air means high electrical level is selected; cannot be connected to power supply positive. The range of user-defined resistor type sensor is 0-60000, by default "Not used" is selected. Before selecting fuel level sensor type, digital input type must be set as 8.
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 SGH (Huanghe sensor)
5 SGD (Dongkang sensor)
6 Reserved 1
7 Reserved 2

7.5 Conditions of Crank Disconnect Selection

Table 11 Crank Disconnect Conditions Selection

No Content
0 Speed
1 Generator Frequency
2 Speed + Generator Frequency
3 Speed + Oil pressure
4 Generator Frequency + Oil pressure
5 Generator Frequency + Speed + Oil pressure
6 Oil pressure

1) There are 3 conditions to make the starter separate from the engine: Speed, generator frequency, and oil pressure. These can be used separately, but oil pressure is recommended to be used together with speed and generator frequency for faster starter disconnection.

2) The speed sensor is magnetic equipment installed in the starter for detecting flywheel teeth.

3) When setting by speed, ensure the number of flywheel teeth matches the setting; otherwise, "over speed shutdown" or "under speed shutdown" may occur.

4) If the genset does not have a speed sensor, do not select corresponding items, otherwise, "start fail" or "loss speed signal" may occur.

5) If the genset does not have an oil pressure sensor, do not select corresponding items.

6) If generator frequency is not selected in crank disconnect setting, the controller will not collect and display relative electric quantity (usable in water pump sets). If speed is not selected, the speed displayed is calculated by generator signal.

8. Controller Function Setting

8.1. Parameter Setting

Hold and press the ⚙️ button for 2s to enter the password interface. The first digit will blink.

Fig.3 Password Interface

1) Press the ▶️ button to increase the value of the blinking digit and the ⬇️ button to decrease it. Press ⚙️ to move the cursor.

2) Repeat the procedure for the 2nd to 4th digits.

3) If the password is correct, the parameter configuration interface appears. Press ⚙️ to scroll down and ⬇️ to scroll up through the set items and their parameters.

Fig.4 Parameter Configuration Interface

4) Press the ▶️ button to set the current item. When the first digit starts blinking, use the same method as for the password to enter the set value.

Attention:

8.2. LCD Contrast Adjustment

When the genset is in standby status, simultaneously hold and press the ⚙️ and ⬇️ keys for 2s to enter the LCD contrast adjustment interface. The LCD contrast increases one level every 1s without releasing the buttons. There are 6 levels to select.

Fig.5 LCD Contrast

8.3. Generator Flywheel Teeth Automatic Adjustment

In manual mode, if crank disconnect conditions are set to "2 Speed + Generator Frequency" or "5 Generator Frequency + Speed + Oil Pressure" (with generator frequency and speed not being 0), the controller will automatically adjust generator flywheel teeth based on gen frequency and poles when ⚙️ and ⬇️ are pressed simultaneously for 0.5s.

9. Sensor Settings

a) Sensors are all resistor types. Some standard sensor curves are available for selection via PC software (refer to Table 10).

b) When inputting sensor curves, the X value (resistance) must be entered from smallest to largest to avoid errors.

c) If the sensor type is set to "not used", the sensor curve will not function, and the LCD will display "---".

d) If only a low oil pressure alarm switch is present without an oil pressure sensor, the pressure sensor can be set as "low digital input is active" or "high digital input is active".

e) The headmost or backmost values in the vertical coordinates can be set as shown in the figure.

Fig.6 Sensor Curve

Table 12 Normal Pressure Unit Conversion Table

N/m² (pa) kgf/cm² bar psi
1Pa 1.02x10-5 1x10-5 1.45x10-4
1kgf/cm² 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1 psi 6.89x103 7.03x10-2 6.89x10-2 1

10. Commissioning

Ensure the following checks are made before commissioning:

  1. Verify all connections are correct and wire diameters are suitable.
  2. Ensure the controller's DC power has a fuse and that the positive and negative terminals are correctly connected to the starting battery.
  3. Take appropriate action to prevent engine crank success (e.g., remove the fuel valve connection wire). If checks are satisfactory, power on the starting battery, select manual mode, and the controller will execute its routine.
  4. Set the controller to manual mode, press the "start" button; the genset will start. After the set cranking time, the controller will send a "Start Failure" signal. Press "stop" to reset the controller.
  5. Reverse the action to prevent engine crank success (e.g., reconnect the fuel valve wire), press start again; the genset will start. If all goes well, the genset will run normally after idle running (if set). During this time, monitor the engine's running status and AC generator's voltage and frequency. If abnormal, stop the genset and check all wire connections according to this manual.
  6. For any further questions, please contact SmartGen service personnel.

11. Typical Application

Fig.7 HGM1790N Typical Application Diagram

CAUTION: Crank and fuel output ports should use extended large capacity relays.

CAUTION: When a sensor port is configured as "high digital input is active", hanging in air means a high electrical level; connecting to power supply positive is prohibited.

12. Installation

12.1. Fixing Clips

  1. The controller is designed for panel installation and is fixed by clips.
  2. Withdraw the fixing clip screw (turn anticlockwise) until it reaches the proper position.
  3. Pull the fixing clip backwards (towards the back of the module) to ensure both clips are inside their allotted slots.
  4. Turn the fixing clip screws clockwise until they are fixed on the panel.

NOTE: Be careful not to overtighten the screws of the fixing clips.

12.2. Overall Dimension

Fig.8 Overall and Cutout Dimensions

BATTERY VOLTAGE INPUT

The HGM1790N series controller supports a wide range of battery voltages (DC 8~35V). The negative terminal of the battery must be connected to the engine shell. The wire connecting the power supply to the battery must be over 1.5mm². If a floating charger is used, connect the charger's output wires to the battery's positive and negative terminals directly first, then connect the battery's positive and negative wires to the controller's positive and negative input ports to prevent charger interference with the controller's normal operation.

SPEED SENSOR INPUT

The speed sensor is magnetic equipment installed in the starter to detect flywheel teeth. Its connection wires to the controller should be a 2-core shielding line. The shielding layer should connect to Terminal 1 in the controller, while the other end is left in the air. The other two signal wires connect to Terminals 1 and 10 in the controller. The speed sensor's output voltage should be within AC(1~24)V (effective value) at full speed. AC12V is recommended (at rated speed). When installing the speed sensor, spin the sensor to contact the flywheel, then back out 1/3 lap, and finally lock the sensor nuts.

OUTPUT AND EXPAND RELAYS

All controller outputs are relay contact output types. If relays need to be expanded, add a freewheel diode to both ends of the expand relay's coils (for coils with DC current) or increase resistance-capacitance return circuit (for coils with AC current) to prevent disturbance to the controller or other equipment.

AC INPUT

The controller's current input must connect to an external current transformer. The current transformer's secondary side current must be 5A. Ensure the phases of the current transformer and input voltage are correct; otherwise, current collection and active power may be inaccurate.

WARNING: When there is load current, the transformer's secondary side must not be open-circuited.

WITHSTAND VOLTAGE TEST

If a high voltage test is required after the controller is installed in the control panel, disconnect all controller terminal connections to prevent high voltage from entering and damaging the controller.

13. Fault Finding

Table 13 Fault Finding

Symptoms Possible Solutions
Controller no response with power. Check starting batteries;
Check controller connection wirings;
Check DC fuse.
Genset shutdown Check the water/cylinder temperature is too high or not;
Check the genset AC voltage;
Check DC fuse.
Low oil pressure alarm after crank disconnect Check the oil pressure sensor and its connections.
High water temp. alarm after crank disconnect Check the temperature sensor and its connections.
Shutdown alarm in running Check related switch and its connections according to the information on LCD;
Check programmable inputs.
Crank not disconnect Check fuel circuit and its connections;
Check starting batteries;
Check speed sensor;
Refer to engine manual.
Starter no response Check starter connections;
Check starting batteries.
Models: HGM1790N, HGM1790N Genset Controller, Genset Controller, Controller

File Info : application/pdf, 29 Pages, 1.33MB

PDF preview unavailable. Download the PDF instead.

HGM1790N en

References

Microsoft Word 2016 Microsoft Word 2016

Related Documents

Preview SmartGen MGC100 Genset Controller User Manual
Comprehensive user manual for the SmartGen MGC100 Genset Controller, detailing its features, specifications, operation, connections, parameters, and troubleshooting for diesel and petrol generators.
Preview SmartGen HGM501 Genset Controller User Manual
User manual for the SmartGen HGM501 Genset Controller, detailing its features, technical specifications, operation, installation, and troubleshooting.
Preview SmartGen HGM6100LT Series Genset Controller User Manual
User manual for SmartGen HGM6100LT series genset controllers (HGM6110LT/HGM6120LT), detailing features, operation, specifications, and troubleshooting for automatic control and monitoring of generators in extreme environments.
Preview SmartGen HGM6100N Series Genset Controller User Manual
Comprehensive user manual for the SmartGen HGM6100N series genset controllers, detailing features, operation, specifications, and connections for automatic control and monitoring of single gensets.
Preview SmartGen MGC100 Genset Controller User Manual
User manual for the SmartGen MGC100 Genset Controller, detailing its features, specifications, operation, connections, parameters, and troubleshooting for genset management.
Preview SmartGen HGM501 Genset Controller User Manual
This user manual provides detailed information on the SmartGen HGM501 Genset Controller, covering its overview, performance, technical data, operation, auto-protection features, terminal connections, configurable parameters, commissioning, typical wiring diagram, installation, and troubleshooting.
Preview SmartGen HGM93XXMPU(CAN) Series Genset Controller User Manual
This user manual provides comprehensive information on the SmartGen HGM93XXMPU(CAN) series genset controllers. It details the features, specifications, operation, wiring, protection mechanisms, and troubleshooting for these advanced automatic genset control systems, designed for reliable and efficient generator management.
Preview SmartGen HGM6100N Series Genset Controller User Manual
Comprehensive user manual for SmartGen HGM6100N series genset controllers, covering operation, specifications, connections, and troubleshooting for models HGM6110N, HGM6120N, HGM6110NC, HGM6120NC, HGM6110CAN, and HGM6120CAN. Features include automatic start/stop, data measurement, alarm protection, and remote communication.