User Guide for VISIONIS models including: VS-AXESS-4D-DLX-PCB Commercial Access Control, VS-AXESS-4D-DLX-PCB, Commercial Access Control, Access Control, Control

VS-AXESS-4D-DLX-PCB-version2-manual-VISIONIS Four Doors Network Access Control PCB Controller Board

ASC-DE24;, Manual

www.visionistech.com

Manual

Visionis VS-AXESS-4D-DLX-PCB (Version 2.0) - Four Doors Network Acce


File Info : application/pdf, 1 Pages, 17.61MB

PDF preview unavailable. Download the PDF instead.

VS-AXESS-4D-DLX-PCB-version2-manual-VISIONIS
Device Parameter
Working Voltage: DC 12V Working Current: Non-loaded <200mA Working Temperature: -20°C - 50°C (-4°F - 122°F) Working Humidity: 10° - 90° Power Consumption: <3W Size: 178 x 120 x 20mm (7.0 x 6.69 x 0.79in.) Communication Mode: TCP/IP Communication Rate: 10/100M (TCP/IP) Extension Communication: RS485 Users Capacity: 20000 Record Capacity: 70000 Max. Doors: 4 Dry Contact Input: 5 Dry Contact Output: 12 Access Group: 200 Groups Default IP Address: 192.168.0.245 Default Communication Password: NULL
Basic Function
· First card open · Multi-card open · Anti-passback · Multi-door interlock · Card, password, card+password, card or
password open mode
· Different time differente open mode · Transmission encryption setup · Self-checking function · Remote control · Wiegand format can be self-defined · Add card without software · Multi-channel conection (max. 3 channels) · Real-time events active or passive upload · Arm/disarm by card · Arm/disarm by software · Relieve alarm by software · Multi-event linkage alarm · One event related to multi-relay trigger · Alarm delay turn off · Capacity can be expanded

IMPORTANT: These access control panels (Version 2.0) are only compatible with access control panels (Version 2.0) and with the Titan VSAxess software. They are not compatible with access control panels (Version 1.0) nor with VSAxess software.
· Self-defined door lock relay · Self-defined control door quantity · Door latch mode · Active door normal open mode by card · Timed automatic normal open mode · Timed invalid for exit button · Normal open time · Normal open holiday forbidden schedule · Access time schedule · Forbid access holiday schedule · Door lock delay setup · Access group setup · Threaten code setup · Force open/close door · Open door by software · Relieve normal open by card · Relieve card and card valid date setup · Expand RS485 communication · Real-time monitoring door and relay state

Commercial Access Control VS-AXESS-4D-DLX-PCB
User Guide
www.visionistech.com

Wiring Introduction

Wiring Position Power Supply - Access Controller Access Controller - Reader
Access Controller - Electric Lock Access Controller - Exit Button Access Controller - IR Alarm Access Controller - Sound-light Alarm RS485 Communication Cable TCP/IP Communication Cable

Wire Model RVV2*1.0
RVV4*0.5 RVV4*1.0 (Door-magnet feedback) RVV2*0.5 RVV2*1.0 RVV2*1.0
RVVP2*1.0
CAT-5

Remark Distance < 100M Distance 60M, max. can not over 100M.
Distance < 150M
Distance < 200M Distance < 200M Distance < 150M Distance < 1000M, shield layer connect to ground Distance < 100M

Disclaimer
The document provides information according to products specification. Visionis does not undertake any type of guarantee, express or implied warranties, including any implied merchantability, specific purposes or the infringement. The information in the document are changed without prior notice. Visionis and its associated sales agents special statement does not assume the result of the use of Visionis equipment of any and all direct, indirect, special, in general, by chance, inevitably, punitive damages. Any user's improper operation or use of the environment problem caused by direct or indirect losses, user pays full responsibility, equipment manufacturers and related sales agents does not undertake any responsability.

Connection

I/O Input Output Input Output Input Input Input

Device Reader Electric Lock Door-magnet Sound-light alarm IR Sensor/Smoke Sensor/Others Exit button RS485 device

Standard Wiegand 26-40 Switch Signal Switch Signal Switch Signal Switch Signal Switch Signal Communication

Quantity 2/4 2/4 2/4 1 2/4 2/4 1

Setup as function
as doors Support
Support

LED&Button Instruction

LED Two-door Four-door

RL1 Lock1 Lock1

RL2 Lock2 Lock2

RL3

RL4

RL5

Magnet Alarm1 Magnet Alarm2 Alarm Output1

Lock3

Lock4

Alarm (COM)

· Power: 12V power LED · RUN: Device run LED · RDOK: Read card status LED · 4DOOR: The status LED of 4 doors · RESET Key: It is used to reboot device and clear communication password. After power off, power on device
again and press RESET button for 3 seconds, then you can clear communication password

Wiring Diagram of Access Controller

Door Magnet

Door Magnet 3

Door Magnet 4

Door Magnet 1

Door Magnet 2

Alarm Output Lock
Lock 4
Lock 3 Fail-Secure
Lock 2

Lock 1

GND 485_B 485_A D_S4 GND D_S3 D_S2 GND D_S1 5NO 5NC 5C 4NO 4NC 4C 3NO 3NC 3C 3NO 2NC 2C 1NO 1NC 1C GND 12V

TITAN VSAxess
It applies to Windows 2000, Windows XP, Windows Server 2003, Windows Vista, Windows 7, Windows 10. Subsystem: · Access Control Management System · Attendance Management System · Real-time Monitor · Alarm

Bus Bar Diagram
1C 1NC 1NO 2C 2NC 2NO 3C 3NC 3NO 4C 4NC 4NO 5C 5NC 5NO D_S1 GND D_S2 D_S3 GND DS_4 ALR3 ALR2 GND ALR1 AN4 GND AN3 AN2 GND AN1 4RD1 4RD0 2RD+ 2RD- 3RD1 3RD0 2RD1 2RD0 1RD+ 1RD- 1RD1 1RD0 D_S1 GND D_S2 D_S3 GND DS_4 ALR3 ALR2 GND ALR1 AN4 GND AN3 AN2 GND AN1 4RD1 4RD0 2RD+ 2RD- 3RD1 3RD0 2RD1 2RD0 1RD+ 1RD- 1RD1 1RD0
1C 1NC 1NO 2C 2NC 2NO 3C 3NC 3NO 4C 4NC 4NO 5C 5NC 5NO

MODE

RESET

Port of Lamp Panel

1RD0 1RD1 1BUZ 1DR1RD+ 2RD0 2RD1 2BUZ 3RD0 3RD1 3BUZ 2RD2RD+ 4RD0 4RD1 4BUZ AN1 GND AN2 AN3 GND AN4 ALR1 GND ALR2 ALR3 GND ALR4

Green White Black Red

Keypad/Reader

Reader 1 VIS-3100

Green White Black Red

Reader 2 VIS-3100

Green White Black
Red

Reader 3 VIS-3000

Green White Black
Red

Reader 4 VIS-3000

Card reader state line

Exit Button 1 Exit Button 3

Exit Button 2
Exit Button
Exit Button 4

Battery

Smoke Alarm 1 (NO/NC)

Smoke Alarm 2 (NO/NC)
Alarm Input

IR Alarm 3 (NO/NC)

IR Alarm 4 (NO/NC)

Lamp Panel

Wire Hole at Top

Alarm Extensions Board

Bus Bar

Power Supply
Battery

Circuit Breaker

Quick Start

Controller List

Property Bar

Dynamic Help

Click to refresh All controllers in
LAN will be shown in the list, left click to choose device. Click Network Controller
Function Tree List

Here you can see device type, version and MAC address.

Here you can change the IP, sub-net mask and gateway.

Task Report

Communication setup-Network Controller

Notice:
1. Controller IP must be the same as you set. 2. Controller model must be the same as device type. You can detect controller and check the device type in task report. 3. Usually we can use ping command to test the device physical connection. 4. Controller Address is only valid when use MS series controller or TCP/IP to RS485 connector, otherwise, the default is 0. 5. Wrong time may no access and incorrect access record. Please adjust the time. 6. Initialize the controller will clear the device records, please make sure the records are saved.

Stop Button

Card List

Right Click Function Menu

Present card to the reader which connect to controller, card number and add card time will display in the card list.

Right click to choose the way of adding card.

To choose a controller add card in pull down menu.

Employee Setup-Card

Notice:
1. If there are employees with the same name, you can separate them by code. Code is unique. 2. Card number is decimal number. 3. Default administrator access group can pass anywhere anytime, it is the top authority. 4. Each employee can access with a separate 6-digit password. 5. Impor from Excel can quick register employees.

Click download setup

Device List Right Click Function Menu
Choose controller, then right click to download setup

Task Report
Current download process will be shown in the task report, green words mean successful.
Red words mean operation fail.
Other-Download Setup

1. Search Controller

Notice:
1. Search function is only valid in the same LAN, as adopt UDP communication protocol, across gateway will forbid communication. 2. When connect network cable to device, Ethernet port green light is on, yellow light flash. 3. Please note that IP address can not be the same. 4. Domain name can be used in the software.

Notice:

Once installed the Titan Vsaxess Login information is:

Username: Administrator

Password:

There is no default Password. Just click OK and you can login.

You can set a Password under "Platform" and "Change password".

2. Add Controller

3. Add Card

4. Add Employee

5. Download Setup

Notice:
1. Three download setup ways: Download setup, download all setups, smart download. Download setup refer to current device, download all setups and smart download refer to all devices. Smart download only download updated contents. Other two is download all setups. 2. When adopt smart download and download all setups, if there is a device offline, it will prompts error. 3. Default administrator access group can pass anywhere anytime, it is the top authority.

Controller List

Click disk icon to save.

Right Click Function Menu

Controller Property

Click controller
Right click to open function menu, choose add controller.

Choose detect controller in right click menu, the function is detect device connection.

Fill controller name model, door quantity and IP address, etc. Other property can refer to dynamic help.

If connection OK, device model, version and door number will be shown in the report.

Hardware Setup-Controller

Notice:
1. Three ways to add card, card distributor add card, controller add card and add card manually. Card distributor add card need to choose our card distributor. 2. Same card can only add once. 3. Please note that delete card will clear the card related to employee.

Employee List

Save!

Employee Property

Click employee

Right Click Function Menu

Right click and choose add employee

Input employee basic information.

Click to enter card base
Card Base
Choose undistributed card to employee
Employee Setup-Employee

The manual is a quick start for system, the user can refer to software help file or other technical files for details.

Important Notices
· Power off when wiring. · Power on when wiring OK. · Power supply output current must 1.3 times bigger than device work
current.
· Lock should better use a separate power. · All devices must be connected to common GND. · RS485 communication must use hand to hand connection. · Between different reader should have 10cm to avoid interference. · As it is a current weak system, strong and weak isolation must be done. · The wiring of strong and weak should not be parallel and distance at
least 20cm.
· RS485 line should connect the cable shield to GND to avoid
interference.
· When RS485 line interface more devices, user can add a 120
resistance between 485+ and 485- of last device.
· Reader can not nistall on the metal directly.

Alarm Extension Board Diagram

Dial Switch

RUN

AL1 AL2

1C 1NC 1NO ALRM1 GND

AL3

AL4

POWER

Fire Alarm Panel

Connect with DLX

485_A

485_B

controller series and

GND

RS485 communication

1C 1NC 1NO ALRM1 GND

Output 1

NO COM

Alarm Input1 (Fire Alarm Interface)

2C

2NC

Output 2

2NO

ALRM2 GND

Alarm Input 2

3C

3NC

Output 3

3NO

ALRM3 GND

Alarm Input 3

4C

4NC

Output 4

4NO

ALRM4 GND

Alarm Input 4

BZ1

Reader buzzer

BZ2 BZ3

(Break in trigger buzzer)

BZ4

12V GND

DC12V

