Owner's Manual for INTERTHERM models including: E3EB-010-H Series Downflow Upflow Electric Furances, E3EB-010-H Series, Downflow Upflow Electric Furances, Upflow Electric Furances, Electric Furances, Furances

TCPDF

Downflow, Upflow Electic Furnace

E3 Series Electric Furnace | Electric Furnace | Intertherm | Literature Library


File Info : application/pdf, 8 Pages, 745.39KB

PDF preview unavailable. Download the PDF instead.

936b
TECHNICAL SPECIFICATIONS

E3EB-xxx-HSeries
Downflow,Upflow ElectricFurnaces
The E3 Series furnace is designed for all sizes of manufactured and modular homes. These units incorporate reliability and low maintenance. Units may be installed free standing in a utility room or enclosed in an alcove or closet. E3 Series furnaces are A/C ready, with multiple blower combinations for cooling requirements.

FEATURESandBENEFITS
· ChoiceofAirConditioningOptions: From 2 to 5 tons A/C ready.
· EasyOpenDoor: Secures the door firmly for transit, yet allows easy removal for access.
· EffectiveAirFilter: Universal disposable filter is readily available and simple to replace.
· NichromeHeatingElements: Provide long lasting, efficient heating.
· ApplianceQualityDoor: Protects against rust and other corrosion. Baked enamel finish allows for easy cleaning.
· FullyInsulatedCabinet: Insures minimized heat loss and quiet operation.
· SafetyandDependability: Auto reset controls protect unit's electrical circuitry and helps ensure trouble free performance. Built in circuit breakers for extra safety.
· Adaptable: Unit can be adapted to provide dependable heating in either downflow or upflow mode.
· Versatile: Works with self-contained or split system air conditioners or heat pumps.

2

MODELIDENTIFICATION
E 3 EB - 010 H
Product Type E - Electric Furnace
Generation 3 - Third Series Product Identifier EB - A/C Blower Equipped Relay

Electrical Code H - 240-1-60

Primary Capacity

010 - 10 kw

012 - 12 kw

015 - 15 kw

017 - 17 kw

020 - 20 kw

023 - 23 kw

FurnacePartsIdentification

Indoor Coil (optional)
Coil Air Filters (used with indoor coil)
Furnace Air Filter (NOT used with
coil air filters)

Blower
Circuit Breakers Data Label
Control Panel Cover (left)

Control Panel Cover (right)

OptionalAccessories

Cabinet Insulation

20" (508 mm)

29" (737 mm)

23 3/4" (603 mm) Upflow Coil Cabinet

17.12

13.62

20.00
23.82 19.82
UpflowStand
3

UNITSPECIFICATIONS

ElectricFurnaceModels Rated Heating Output, Btuh (see note 1) Watts (Total kw, Heating Elements and Blower) Supply Voltage Heating Elements, No.(Total kw) Blower Wheel Size
Motor Speed, H.P. Rating, Amps
Test ESP, in. w.c. Max
Optional Cooling Available with factory installed blower Optional Heat Pump Available with factory installed blower Air Filter (Standard)
Furnace Dimensions

010H 35,000
10.4
2 (10.0)

012H 41,000
12.0
2 (11.6)

015H

E3EB 017H

020H

53,000 57,000 70,000

15.4

16.6

20.4

240 Volts/60Hz/1-Phase

3 (15.0) 3 (16.2) 10.5" Dia, 8" Wide

4 (20.0)

4 Speed, 1/3 HP, 2.9 0.3

2.0 - 4.0 Ton

023H 75,000
22.0

023H 5-Ton 75,000 22.0

4 (21.6)

4 (21.6)
11" Dia., 8" W 4 Spd, 3/4HP
3.8 Amps

2.0 - 5.0 Ton

2.0 - 4.0 Ton 16" x 20" x 1" (nominal) Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)

1. Heating output rated at listed voltage. For outputs at voltages other than 240V, multiply Btuh rating by the following factors: x 0.92 (230V), x 0.84 (220V), x 0.75 (208V)
2. Height is 56" with return air grille installed, 58" with coil cabinet and 72" with coil cabinet and upflow stand.

4

ELECTRICALSPECIFICATIONS

Model Number E3E(*)
-010H -012H
-015H
-017H
-020H
-023H

Supply Circuit Single Single Dual "A" Dual "B" Single Dual "A" Dual "B" Single Dual "A" Dual "B" Single Dual "A" Dual "B" Single Dual "A" Dual "B"

Total Amperes
44.6 51.2 27.1 24.2 65.4 44.6 20.8 70.4 47.9 22.5 86.2 44.6 41.7 93.8 45.5 48.0

Replacement furnace for E2E(*)-015HB

Maximum Over-current
Rating 60 70 40 30 90 60 30 90 60 30 125 60 60 125 60 60

Minimum Circuit
Ampacity 56 64 34 30 82 56 26 88 60 28 108 56 52 117 57 60

BlowerPerformance

4-Ton Blower with Coil and Coil Filters, @ 0.3" ESP

Pin No. #1 #2 #3 #4

Speed Low
Med.-Low Med.-High
High

CFM 880 1170 1310 1460

5-Ton Blower, with Coil and Coil Filters, @ 0.3" ESP

Pin No. #1 #2 #3 #4

Speed Low
Med.-Low Med.-High
High

CFM 990 1320 1620 1790

AnticipatorSettings

Furnace Model

Thermostat AnticipatorSetting

010, 012

0.2

015, 017, 020, 023

0.4

Clearances

ALLMODELS

CLOSET ALCOVE

Front 

6"

18"

Back

0"

0"

Sides

0"

0"

Top

0"

0"

Top and Sides of Duct

0"

0"

Bottom of Duct

0"

0"

 Service Clearance  For upflow application using upflow stand, 1" minimum per side.

5

AIRFLOwDATA

Coil
0.1 0.2 Static 0.3 (ESP) in W.C. 0.4 0.5 0.6

E3EB(010,012,015,017,020,023)H

High

Med High

Med Low

4-ton No Coil 3.5 ton No Coil 3-ton No Coil

1559 1503 1389 1362 1227 1203

1506 1458 1352 1330 1208 1174

1460 1414 1310 1291 1170 1146

1401 1352 1260 1241 1136 1103

1333 1282 1198 1179 1086 1055

1251 1208 1133 1113 1027

996

Low

2.5-ton None

923

885

906

863

880

831

845

798

805

758

757

707

Coil
0.1 0.2 Static 0.3 (ESP) in W.C. 0.4 0.5 0.6

E3EB023H-5TONand5tonaccessoryblower

High

Med High

Med Low

5-ton No Coil 5-ton No Coil 5-ton No Coil

1911 1886 1709 1679 1394 1373

1860 1821 1663 1630 1359 1333

1790 1768 1620 1585 1320 1296

1741 1700 1563 1526 1279 1252

1671 1643 1511 1473 1229 1201

1613 1584 1444 1400 1182 1147

Low

5-ton No Coil

1054 1032

1027 1004

880

970

952

928

912

884

864

824

6

ACCESSORIES
Description Blower, 2-4 Ton Blower, 5 Ton Heating Thermostat Intertherm (12 Pac) Heating Thermostat Miller (12 Pac) Thermostat Sub-Base Heating/Cooling Thermostat CM65 Intertherm/Miller (12 Pac) Heating/Cooling Thermostat GE Intertherm (12 Pac) Heating/Cooling Thermostat GE Miller (12 Pac) Automatic Damper for AC or HP Package Unit "VEE" Box Adapters (10") - 5 / carton Duct Connector 10" Dia. x 6" Long - 6 / carton "VEE" Box Adapters (12") - 5 / carton Single Wide Fitting Kit (12") Double Wide Fitting Kit (12") Single Wide Fitting Kit (14") Double Wide Fitting Kit (14") Y-Fitting (12") Y-Fitting (14") Fan Delay Kit (TDR) Top Grille/Frame Top Grille/Frame (4 pack) Wall Mount Top Grille (10 pack) Coil Cabinet Upflow Coil Cabinet Downflow (Front return) Upflow Stand Coil Cabinet, Downflow (Front and top return)

PartNumber
902993 902985 903188 (903182) 903189 (903183) 914146 903992 (903993) 903192 (903186) 903193 (903187) 901083 901985 902926 902149 911468A 911469A 914957 914956 911470 917195 911758 902989 903000 902988 902976 903891 904620 904067

7

ACCESSORYKITS
VentKits Soffit Air Inlet (for VentilAire III only) VentilAire III - Sloped 3/12 VentilAire IV - Sloped 3/12

PartNumber 917201A 914098 914229

PlenumConnectors 11.25 x 13.50 x 0.88 12 / carton 11.25 x 13.50 x 2.00 12 / carton 11.25 x 13.50 x 4.25 6 / carton 11.25 x 13.50 x 6.25 6 / carton 11.25 x 13.50 x 8.25 4 / carton 11.25 x 13.50 x 10.25 3 / carton 11.25 x 13.50 x 12.25 3 / carton 11.25 x 13.50 x 6.25 24 / carton

PartNumber 901987A 901988A 901989A 901990A 901991A 901992A 901993A 902681A

GENERAL TERMS OF LIMITED WARRANTY Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.
For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (1 /2015)

936B-1114 (Replaces 936B-0214)

www.intertherm.net

Trademark Intertherm® used under license.© Nortek Global HVAC, LLC.All Rights Reserved.

Powered by TCPDF (www.tcpdf.org)



References

TCPDF 6.0.003 (http://www.tcpdf.org)