NDR 480 SPEC
480W Single Output Industrial DIN RAIL

NDR-480 series
User's Manual

 Features

THOM AS SAMUEL

THOMAASS SSAAMMUEL

IS13252 R33100 (except 48V) RoHS

Bauart gepruft Sicherheit
egelma ge od o s be wac g
www.tuv.com ID 2000000000
TPTC004 BS EN/EN62368-1 IEC62368-1
 Applications

Universal AC input / Full range

Industrial control system

Built-in active PFC function

Factory automation

Protections: Short circuit / Overload / Over voltage / Over temperature

Electro-mechanical apparatus

Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved

 GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level

100% full load burn-in test

3 years warranty

 Description
NDR-480 is one economical slim 480W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 85.5mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. NDR-480 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 92.5%, the entire series can operate at the ambient temperature between -20 and 70 under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make NDR-480 a very competitive power supply solution for industrial applications.

 Model Encoding NDR - 480- 24
Output voltage Output wattage Series name

File Name:NDR-480-SPEC 2024-07-15

480W Single Output Industrial DIN RAIL

NDR-480 series

SPECIFICATION

MODEL

NDR-480-24

NDR-480-48

DC VOLTAGE

24V

48V

RATED CURRENT

20A

10A

CURRENT RANGE

0 ~ 20A

0 ~ 10A

RATED POWER

480W

480W

RIPPLE & NOISE (max.) Note.2 150mVp-p

150mVp-p

OUTPUT

VOLTAGE ADJ. RANGE

24 ~ 28V

VOLTAGE TOLERANCE Note.3 ±1.0%

LINE REGULATION

±0.5%

LOAD REGULATION

±1.0%

48 ~ 55V ±1.0% ±0.5% ±1.0%

SETUP, RISE TIME

1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load

HOLD UP TIME (Typ.)

16ms/230VAC 16ms/115VAC at full load

VOLTAGE RANGE Note.4 90 ~ 264VAC 127 ~ 370VDC

FREQUENCY RANGE

47 ~ 63Hz

POWER FACTOR (Typ.)

PF>0.98/115VAC, PF>0.94/230VAC at full load

INPUT EFFICIENCY (Typ.)

92.5%

92.5%

AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

4.8A/115VAC 20A/115VAC

2.4A/230VAC 35A/230VAC

LEAKAGE CURRENT

<2mA / 240VAC

OVERLOAD

105 ~ 130% rated output power Protection type : Constant current limiting, unit will shut down after 3 sec., re-power on to recover

PROTECTION OVER VOLTAGE

29 ~ 33V

56 ~ 65V

Protection type : Shut down o/p voltage, re-power on to recover

OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION

Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing -40 ~ +85, 10 ~ 95% RH ±0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY STANDARDS

Ul508, TUV BS EN/EN62368-1, EAC TP TC 004 , BSMI CNS14336-1 , IS13252(Part1)/IEC60950-1(except for 48V) approved; (meet BS EN/EN60204-1)

SAFETY & WITHSTAND VOLTAGE

EMC (Note 4)

ISOLATION RESISTANCE EMC EMISSION

I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to BS EN/EN55032 (CISPR32),BS EN/EN61204-3 Class B,BS EN/EN61000-3-2,-3,EAC TP TC 020,CNS13438 Class B

EMC IMMUNITY MTBF

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11,BS EN/EN55035,BS EN/EN61000-6-2 (BS EN/EN50082-2),BS EN/EN61204-3, heavy industry level, EAC TP TC 020 1041.6K hrs min. Telcordia SR-332 (Bellcore) ; 146.8K hrs min. MIL-HDBK-217F (25)

OTHERS NOTE

DIMENSION

85.5*125.2*128.5mm (W*H*D)

PACKING

1.5Kg; 8pcs/13Kg/0.9CUFT

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1F & 47F parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.

In case the adjacent device is a heat source, 15mm clearance is recommended.

5. Derating may be needed under low input voltage. Please check the derating curve for more details.

6. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the

EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power supplies."

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf ) 7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than

2000m(6500ft).

 Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:NDR-480-SPEC 2024-07-15

480W Single Output Industrial DIN RAIL

NDR-480 series

Block Diagram

EMI FILTER

I/P

&

RECTIFIERS

PFC CIRCUIT

POWER SWITCHING

UVP

O.L.P.

FG

PFC

PWM

CONTROL

CONTROL

O.T.P.

RECTIFIERS &
FILTER

PFC fosc : 85KHz PWM fosc : 65KHz
+V -V O.C.P.
DETECTION CIRCUIT
O.V.P.

Derating Curve

Output derating VS input voltage

100
80
60 50 40
20

-20

0

10

20

30

40

50

60

70 (VERTICAL)

AMBIENT TEMPERATURE ()

100 90 80 70 60 50 40
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz

LOAD (%) LOAD (%)

File Name:NDR-480-SPEC 2024-07-15

480W Single Output Industrial DIN RAIL
Mechanical Specification

NDR-480 series
Case No.984D Unit:mm

128.5

Top View 85.5
1234
TB2

36 125.2

Side View
Installation Instruction

DC OK
+ +V ADJ TB1 123
Front View
Bottom View

Side View
Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 AC/N or DC 3 AC/L or DC +
Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 DC OUTPUT +V 3,4 DC OUTPUT-V

35

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.