VKPI EC 2 www.ventilation-system.com CONTENTS This user's manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the VKPI EC unit and

Inline centrifugal sound- and heat insulated fan VKPI 500х250 L1 EC | VENTS


File Info : application/pdf, 16 Pages, 2.06MB

PDF preview unavailable. Download the PDF instead.

v210en a4 01 preview
USER'S MANUAL
VKPI EC
Inline centrifugal fan in sound insulated casing

CONTENTS
Safety requirements..................................................................................................................................................................... 3 Purpose................................................................................................................................................................................................ 5 Delivery set........................................................................................................................................................................................ 5 Designation key.............................................................................................................................................................................. 5 Technical data.................................................................................................................................................................................. 6 Mounting and set-up.................................................................................................................................................................. 8 Connection to power mains .................................................................................................................................................. 9 Technical maintenance.............................................................................................................................................................. 10 Troubleshooting............................................................................................................................................................................. 11 Storage and transportation regulations.......................................................................................................................... 11 Manufacturer's warranty........................................................................................................................................................... 12 Certificate of acceptance ........................................................................................................................................................ 13 Seller information.......................................................................................................................................................................... 13 Installation certificate.................................................................................................................................................................. 13 Warranty card ................................................................................................................................................................................. 13

VKPI EC

This user's manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the VKPI EC unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country. The information in this user's manual is correct at the time of the document's preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.

2

www.ventilation-system.com

SAFETY REQUIREMENTS
· Please read the user's manual carefully prior to installing and operating the unit. · All user's manual requirements as well as the provisions of all the applicable local and national
construction, electrical, and technical norms and standards must be observed when installing and operating the unit. · The warnings contained in the user's manual must be considered most seriously since they contain vital personal safety information. · Failure to follow the rules and safety precautions noted in this user's manual may result in an injury or unit damage. · After a careful reading of the manual, keep it for the entire service life of the unit. · While transferring the unit control, the user's manual must be turned over to the receiving operator.

UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS

· Disconnect the unit from power mains prior to any installation operations.

· Unpack the unit with care.

· The unit must be grounded!
· Do not change the power cable length at your own discretion.
· Do not bend the power cable. · Avoid damaging the power
cable. · Do not put any foreign objects
on the power cable.
· Do not use damaged equipment or cables when connecting the unit to power mains.
· Do not touch the unit controls with wet hands.
· Do not carry out the installation and maintenance operations with wet hands.

· While installing the unit, follow the safety regulations specific to the use of electric tools.
· Do not lay the power cable of the unit in close proximity to heating equipment.
· Do not operate the unit outside the temperature range stated in the user's manual.
· Do not operate the unit in aggressive or explosive environments.
· Do not wash the unit with water.
· Protect the electric parts of the unit against ingress of water.

www.ventilation-system.com

3

· Do not allow children to operate the unit.
· Do not store any explosive or highly flammable substances in close proximity to the unit.
· Do not open the unit during operation.
· Do not block the air duct when the unit is switched on.
· Do not sit on the unit and avoid placing foreign objects on it.

VKPI EC
· Disconnect the unit from power mains prior to any technical maintenance.
· When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.
· Do not direct the air flow produced by the unit towards open flame or ignition sources.
· In case of continuous operation of the unit, periodically check the security of mounting.
· Use the unit only for its intended purpose.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

4

www.ventilation-system.com

PURPOSE
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN.
The centrifugal fan in a sound insulated casing is designed for supply and exhaust ventilation of domestic, public and industrial premises with high requirements to the noise level and with limited space for mounting. The unit is rated for continuous operation. The unit is a component part and is not designed for stand-alone operation. Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

DELIVERY SET
NAME Fan User's manual Packing box

NUMBER
1 pc. 1 pc. 1 pc.

DESIGNATION KEY
Designation example: VKPI XXXxXXX X X X
Series name
Rectangular duct size 300x150/400x200/500x250/500x300/ 600x300/600x350/700x400/800x500/
900x500/1000x500
Motor modification M: medium pressure motor
L: high pressure motor
Phases 1: single-phase 3: three-phase
Motor type EC: synchronous electronically
commutated motor

www.ventilation-system.com

5

VKPI EC
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from 0 °C up to +45 °C and relative humidity up to 80 %. The unit is rated as a Class I electrical appliance. Ingress protection rating against access to hazardous parts and water ingress is IPX4. The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

VKPI 300150 M1 EC
Unit voltage [V/50 (60) Hz] 1~230

VKPI 300150
L1 EC
1~230

VKPI 400200 M1 EC
1~230

VKPI 400200
L1 EC
1~230

VKPI 500250 M1 EC
1~230

VKPI 500250
L1 EC
1~230

VKPI 500300
L1 EC
1~230

VKPI 600300 M1 EC
1~230

Power [W]

97

101

91

192

252

555

553

326

Current [A]

0.73

0.80

0.69

1.43

1.85

4.10

4.20

2.45

Max. air flow [m³/h]

565

665

810

1190

1590

2480

2700

2545

RPM [min-1]

3300

3500

2470

3010

2500

3100

3100

2000

Sound pressure level at 3 m distance [dBA]

29

Transported air temperature [°]
Ingress protection rating

VKPI 600350 M1 EC

Unit voltage [V/50 (60) Hz] 1~230

30
VKPI 600350
L3 EC 3~400

33
VKPI 700400 M1 EC 1~230

30

34

-25...+50

IPX4

VKPI 700x400
L3 EC

VKPI 800500 3 EC

3~400

3~400

41
VKPI 800x500
L3 EC 3~400

43

34

VKPI 900x500
L3 EC

VKPI 1000x500
L3 EC

3~400

3~400

Power [W]

361

1308

795

2748

2025

2925

3429

3429

Current [A]

2.62

2.35

3.48

2.80

2.01

3.05

5.00

5.00

Max. air flow [m³/h]

2815

4290

5710

6810

8395

8535

11190

11190

RPM [min-1]

2000

3160

1400

2530

1470

2400

1800

1800

Sound pressure level at 3 m distance [dBA]

38

40

37

43

43

42

47

47

Transported air temperature [°]
Ingress protection rating

-25...+50 IPX4

6

www.ventilation-system.com

H 3 H 1 H
H 3 H 2 H 1 H k

9

Model
VKPI 300x150 M1 EC VKPI 300x150 L1 EC VKPI 400x200 M1 EC VKPI 400x200 L1 EC VKPI 500x250 M1 EC VKPI 500x250 L1 EC VKPI 500x300 L1 EC

B

B1

L

B2

B3

OVERALL DIMENSIONS

Dimensions [mm]

Weight

B

B1

B2

B3

H

H1

H2

H3

L

[kg]

300

320

340

364

150

170

190

271

370

10.3

300

320

340

364

150

170

190

271

370

10.8

400

420

440

464

200

220

240

322

460

15.1

400

420

440

464

200

220

240

322

460

16.8

500

520

540

564

250

270

290

373

560

25.5

500

520

540

564

250

270

290

373

560

27.7

500

520

540

564

300

320

340

424

560

29

f 9

B

L

B1

B3

Model
VKPI 600x300 M1 EC VKPI 600x350 M1 EC VKPI 600x350 L3 EC VKPI 700x400 M1 EC VKPI 700x400 L3 EC VKPI 800x500 3 EC VKPI 800x500 L3 EC VKPI 900x500 L3 EC VKPI 1000x500 L3 EC

OVERALL DIMENSIONS

Dimensions [mm]

B

B1

B3

H

H1

H3

600

620

783

300

320

574

600

620

783

350

370

664

600

620

783

350

370

664

700

720

883

400

420

714

700

720

883

400

420

714

800

820

983

500

520

814

800

820

983

500

520

814

900

920

1083

500

520

814

1000 1020 1183

500

520

814

L

f

752

755

752

755

752

750

882

855

882

855

937

955

937

955

1037 1055

1037 1155

Weight

k

[kg]

450

52.9

450

56.6

450

59.3

742

82.6

742

83.4

797

108.4

797

99.8

800 125.0

800 132.0

www.ventilation-system.com

7

MOUNTING AND SET-UP
BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN OBJECTS (E.G. FOIL, PAPER).

VKPI EC

WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT MAINTENANCE AND REPAIR.
Check the fan power cables for integrity and make sure the impeller has smooth rotation prior to mounting. The VKPI 300x150 M1 E, VKPI 300x150 L1 E, VKPI 400x200 M1 E, VKPI 400x200 L1 E, VKPI 500x250 M1 E, VKPI 500x250 L1 E, and VKPI 500x300 L1 E fans are mounted between the rectangular air ducts and do not require special fastening if the connection is made directly to them. Connect the fan to air ducts with M8 bolts and nuts. The VKPI 600x300 M1 E, VKPI 600x350 M1 E, VKPI 600x350 L3 E, VKPI 700x400 M1 E, VKPI 700x400 L3 E, VKPI 800x500 M3 EC, VKPI 800x500 L3 E, VKPI 900x500 L3 E and VKPI 1000x500 L3 E fans are attached to the ceiling on anchors/studs or suspension brackets. The fan may be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing). Access for the fan maintenance shall be provided. The casing is equipped with a removable access cover for maintenance purposes.

1 3 4 8

2
www.ventilation-system.com

CONNECTION TO POWER MAINS

DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER'S MANUAL. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER'S LABEL.
The unit is rated for connection to 1~230 V/50 (60) Hz or 3~400 V/50 (60) Hz power mains according to the wiring diagram. The connection must be made using durable, insulated and heat-resistant conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method. The external power input must be equipped with an automatic circuit breaker QF built into the stationary wiring to open the circuit in the event of overload or short-circuit. The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit. The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the "Technical data" section or to the unit label). It is recommended to select the nominal current of the circuit breaker from the standard series, following the maximum current of the connected unit. The circuit breaker is not included in the delivery set and can be ordered separately.

Wiring diagram of the fan with a single-phase motor

M1

X1

1:1

~230V L 50/60Hz N
PE

1:2 1:3

black

blue

L N

yellow-green

PE

+10V
+10V
A1 0-10V CTR GND GND

2:1 red 2:2 yellow 2:3 blue 2:4 white

X2

+10V 0-10V GND Tacho

Wiring diagram of the fan with a three-phase motor

X1
L 1:1 ~400V L 1:2 50/60Hz N 1:3
PE 1:4

M1

brown

L1

blue

black

L2 L3

yellow-green

PE

+10V
+10V
A1 0-10V CTR GND GND

2:1 red 2:2 yellow 2:3 blue 2:4 white

X2

+10V 0-10V GND Tacho

www.ventilation-system.com

9

VKPI EC
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt. Use a soft brush or compressed air to remove dust from metal surfaces of the fan. Use a vacuum cleaner to remove dust from the sound insulating surface. The impeller blades require thorough cleaning once in 6 months. Detach air ducts from the fan before starting maintenance works. Clean the impeller blades with a soft cloth wetted in mild water detergent solution. Avoid liquid dripping on the motor. Wipe the fan surfaces dry after cleaning. While cleaning the fan make sure the balance counterweights are not shifted and the impeller is not misaligned.

1 3 5 10

2 4 6
www.ventilation-system.com

TROUBLESHOOTING

Problem The fan does not run.

Possible reasons No power supply.

Noisy operation.

Impeller imbalance.

Troubleshooting Check the automatic circuit breaker. Check the electric connections.
Clean the impeller.

STORAGE AND TRANSPORTATION REGULATIONS
· Store the unit in the manufacturer's original packaging box in a dry closed ventilated premise with temperature range from +5 ° to +40 ° and relative humidity up to 70 %.
· Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
· Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit. · Follow the handling requirements applicable for the particular type of cargo. · The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position. · Avoid sharp blows, scratches, or rough handling during loading and unloading. · Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least
3-4 hours.

www.ventilation-system.com

11

VKPI EC
MANUFACTURER'S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include: · routine technical maintenance · unit installation/dismantling · unit setup To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user's manual. Contact the Seller for warranty service.
The manufacturer's warranty does not apply to the following cases: · User's failure to submit the unit with the entire delivery package as stated in the user's manual including submission with missing
component parts previously dismounted by the user. · Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual. · User's failure to ensure timely technical maintenance of the unit. · External damage to the unit casing (excluding external modifications as required for installation) and internal components caused
by the user. · Redesign or engineering changes to the unit. · Replacement and use of any assemblies, parts and components not approved by the manufacturer. · Unit misuse. · Violation of the unit installation regulations by the user. · Violation of the unit control regulations by the user. · Unit connection to power mains with a voltage different from the one stated in the user's manual. · Unit breakdown due to voltage surges in power mains. · Discretionary repair of the unit by the user. · Unit repair by any persons without the manufacturer's authorization. · Expiration of the unit warranty period. · Violation of the unit transportation regulations by the user. · Violation of the unit storage regulations by the user. · Wrongful actions against the unit committed by third parties. · Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades). · Missing seals if provided by the user's manual. · Failure to submit the user's manual with the unit purchase date stamp. · Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE UNIT.

USER'S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER'S MANUAL
WITH THE PURCHASE DATE STAMP.

12

www.ventilation-system.com

CERTIFICATE OF ACCEPTANCE
Unit Type Model Serial Number Manufacture Date Quality Inspector's Stamp

Inline centrifugal fan in sound insulated casing VKPI _____________ EC

SELLER INFORMATION
Seller Address Phone Number E-mail Purchase Date This is to certify acceptance of the complete unit delivery with the user's manual. The warranty terms are acknowledged and accepted.
Customer's Signature

INSTALLATION CERTIFICATE

The VKPI _____________ EC unit is installed pursuant to the requirements stated in the present user's manual.

Company name

Address

Phone Number

Installation Technician's Full Name

Installation Date:

Signature:

The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.

Signature:

Seller's Stamp Installation Stamp

WARRANTY CARD
Unit Type Model Serial Number Manufacture Date Purchase Date Warranty Period
Seller

Inline centrifugal fan in sound insulated casing VKPI _____________ EC

Seller's Stamp

www.ventilation-system.com

13

VKPI EC

14

www.ventilation-system.com

www.ventilation-system.com

15