Instruction Manual for GTE models including: GSME-X22 Fire Gas Detector, GSME-X22, Fire Gas Detector, Gas Detector, Detector

Fire Gas Detector - GTE Industrieelektronik GmbH

28 feb 2023 — Supplementary Instruction Manual for GSME-X22. Fire Gas Detector ... ADICOS GME-X22 detectors are designed for operation in hazardous dust atmospheres of.

GTE Industrieelektronik GmbH


File Info : application/pdf, 16 Pages, 659.16KB

PDF preview unavailable. Download the PDF instead.

400-2410-002 en23 adicos gsme-x22 supplementary instructions
GSME-X22

EN

IP64

Supplementary Instruction Manual for GSME-X22
Fire Gas Detector

GTE Industrieelektronik GmbH | Helmholtzstr. 21, 38 ­ 40 41747 Viersen | Germany | +49 2162 3703-0 | info@gte.de

Supplementary Instructions for GSME-X22 Article number: 400-2410-002 Index: EN22 Release date: 10.01.2023
­ Translation ­

Manufacturer: GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 41747 Viersen GERMANY

Support hotline: +49 2162 3703-0 E-Mail: support.adicos@gte.de

© 2023 GTE Industrieelektronik GmbH ­ This document and all figures contained may not be copied, changed, or distributed without explicit approval by the manufacturer! Subject to technical changes!
ADICOS® and GSME® are registered trademarks of GTE Industrieelektronik GmbH.

2

400-2410-002 EN22

ADICOS GSME-X22

ABSTRACT
Abstract
The Advanced Discovery System (ADICOS®) is used for early detection of fires in industrial environments. It is comprised of various, separate detector units. By parameterizing and arranging the detectors appropriately, the system fulfills a predefined detection goal. The ADICOS system ensures reliable early detection of embers and smoldering fires even in adverse environments.
ADICOS GSME fire gas detectors detect at an early stage gases that are characteristic for developing fires. They detect both open and concealed smoldering fires. Highly sensitive and at the same time robust, they are ideal for fire gas detection in industrial environments ­ and already in the incipient stage. With the ADICOS software, all detector states and concentration curves can be displayed graphically. Sensitivities as well as alarm thresholds can be parameterized individually for each detector. The GSME fire gas detectors can be used in almost any indoor plant area, taking into account the air flow conditions.
Four parameterizable semiconductor gas sensors monitor and evaluate the concentration curve of these gases according to multi-criteria technology. This enables the GSME detectors to distinguish real fires from interference signals. In industrial environments, this often occurs under harsh conditions, e.g. due to vehicle exhaust fumes, dust, mist and vapor.
ADICOS GME-X22 detectors are designed for operation in hazardous dust atmospheres of ATEX zone 22.

ADICOS GSME-X22

400-2410-002 EN22

3

CONTENTS
Contents
1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Objective. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Explanation of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3 Storing the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2 Standards and regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3 Personnel Qualification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.4 Handling Electrical Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.5 Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.6 Accessories and Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.2 Cable assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.1 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 7 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.1 Detector replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 9 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.1 ID Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 10 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.1 ADICOS mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4

400-2410-002 EN22

ADICOS GSME-X22

About this mAnuAl
1 About this manual
1.1 Objective This manual describes the special requirements on installation, wiring, commissioning, and operation of ADICOS detectors for explosive atmospheres of ATEX zone 22. They are exclusively addressed to knowledgeable specialist personnel (­> Chap. 2, Safety instructions). 1.2 Explanation of Symbols This manual features a continuous structure for best possible comprehension. The following labels are used.
Warning signs The following types of notes are used through this manual.
DANGER! This combination of symbol and signal word indicates an immediately dangerous situation that will lead to death or severe injuries if not avoided.
WARNING! This combination of symbol and signal word indicates a possibly dangerous situation that could lead to death or severe injuries if not avoided.
Explosion Protection This information type signals measures that must be implemented for maintaining the Explosion protection.
Tips and recommendations Helpful tips and recommendations as well as information to ensure efficient and uninterrupted use.
1.3 Storing the Manual Store this manual easily reachable and in direct vicinity of the detector system to enable use as needed.

ADICOS GSME-X22

400-2410-002 EN22

5

sAfety instructions

2 Safety Instructions
ADICOS GSME-X22 detectors for explosive atmospheres up ATEX zone 22 ensure operational safety assuming proper installation, commissioning, operation, and maintenance. For this purpose, it is absolutely required to completely read, understand, and follow this manual and the safety information contained.
WARNING! Personal injury and property damage! Incorrect installation and operating errors can cause death, serious injury and damage to industrial equipment. · Read the entire manual and follow the instructions!
Explosion protection When using ADICOS detectors in potentially explosive atmospheres, follow the specifications of the ATEX operating directive.

2.1 Intended use
ADICOS GSME-X22 are designated for the detection of fire scenarios in explosive atmospheres of ATEX zone 22. In this context, the operating parameters described in Chap. 9, »Technical Data« must be met. Any deviating use requires prior consultation with the manufacturer.
Compliance with this manual as well as all applicable country-specific provisions is also part of the intended use.
2.2 Standards and regulations
The safety and accident prevention regulations applicable for the specific application must be observed during detector installation, commissioning, maintenance, and test.
The following standards and directives in their current version are of particular importance when handling potentially explosive atmospheres:

Standards and Regulations EN 60079-0 EN 60079-31 EN 60529 2014/34/EU
1999/92/EG

Description
Explosive atmospheres - Part 0: Equipment General requirements
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure ,,t"
Degrees of protection provided by enclosures (IP Code)
ATEX product directive (about equipment and protective systems intended for use in potentially explosive atmospheres)
ATEX operating directive (on safety and health protection of workers potentially at risk from explosive atmospheres)

6

400-2410-002 EN22

ADICOS GSME-X22

sAfety instructions
2.3 Personnel Qualification
Any work on ADICOS systems may only be performed by qualified personnel. Persons, who can perform work on electrical systems and recognize possible dangers based on their professional education, knowledge, and experience as well as knowledge of the applicable provisions, are considered qualified personnel.
WARNING! Personal injury and property damage! Improperly performed work on and with the device can lead to malfuctions.  Installation, startup, parameterization and maintenance may be
performed only by authorized and properly trained personnel.
2.4 Handling Electrical Voltage DANGER! Risk of explosion by electrical voltage in potentially explosive atmospheres! The electronics of ADICOS GSME-X22 detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! · De-energize the entire detector system and secure against unintentionally reactivation for all wiring work!
2.5 Modifications
WARNING! Property damage or detector failure by any form of unauthorized modification! Any form of unauthorized modification or extension can lead to a failure of the detector system. The warranty claim expires.  Never make unauthorized modifications on your own authority.
2.6 Accessories and Spare Parts
WARNING! Property damage due to short circuit or failure of the detector system The use of parts other than the manufacturer's original spare parts and original accessories may result in property damage due to short circuits.  Only use original spare parts and original accessories!  Original spare parts and accessories may only be in-
stalled by trained specialist personnel.  Qualified personnel are persons as described in Chap. 2.3.

ADICOS GSME-X22

400-2410-002 EN22

7

100

structure
3 Structure 3.1 Overview
3 2
1
100
No. Description  Enclosure  Display elements  Spray protection  Sinter metal filter  Cable gland

4 5
28

8

400-2410-002 EN22

ADICOS GSME-X22

structure

3.2 Cable Assignment

Wire
1 1 2 2 3 3 4 4

Color
black white black white black white black white

Signal

Limit value contact

Operating voltage DC 21.6 ... 40 V non-polarised
Relay output X6 e Relay output X6 a Relay output X7 a Relay output X7 e
M-Bus max. 40 V non-polarised

Alarm NO1 Alarm NO1 Fault NC Fault NC

1 with series resistor, standard 680 

Option fire panel interface

Wire
5 5 6 6

Color
black white black white

Interface module
Interface module A - in Interface module B - in Interface module A - out Interface module B - out

Siemens FDnet
FDnet (+) FDnet-A (-) FDnet (+) FDnet-B (-)

Bosch LSNi
LSN a in LSN b1 in LSN a out LSN b2 out

Option auxiliary relay

Wire

Color

5

black

5

white

6

black

6

white

Auxiliary relay Normally closed Normally open Common

ADICOS GSME-X22

400-2410-002 EN22

9

instAllAtion
4 Installation
4.1 Mounting
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! Mount the device with closed housing! · Use ADICOS mounting plate, if necessary!

10

400-2410-002 EN22

ADICOS GSME-X22

commissioning
4.2 Wiring Wiring according to chapter 3.2.
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! Mount the device with closed enclosure. · De-energize the entire detector system and secure against unintentionally
reactivation for all wiring work! · In the case of wiring within potentially explosive atmospheres, only use
Ex-protected connection boxes with respective approval! · Do not bend connection cable! Observe minimum bending radius!
(­> Chap. 9), Technical Data)
5 Commissioning
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Prior to switching on, check that all detectors are properly mounted and
wired!
6 Operation
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME X22 detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Never open the enclosure or loosen the cable gland during operation!

ADICOS GSME-X22

400-2410-002 EN22

11

mAintenAnce
7 Maintenance
7.1 Detector replacement
DANGER! Risk of explosion due to electrical voltage in hazardous areas. The electronics of ADICOS GSME-X22 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres. · Do not open enclosure! · De-energize the entire detector system and secure against unintentionally
reactivation for all wiring work! · Replace the closed detector including connection cable only!
8 Disposal
Return the device to the manufacturer when it reaches the end of its serviceable life. The manufacturer will ensure that the components are disposed of properly, in an environmentally friendly manner.

12

400-2410-002 EN22

ADICOS GSME-X22

technicAl DAtA

9 Technical Data

General Model: Item No.: Enclosure dimensions:
Weight (7 meter cable incl.): Degree of protection: Enclosure:

GSME-X22

408-2001-251

mm

128 x 100 x 100 (Length x Width x Depth)

(Length: cable gland incl.)

kg

2

IP64 Aluminum die-cast, powder-coated

Electrical properties
Voltage range:
Power consumption without heating: with heating
M-Bus voltage (signal):

V
VA VA V/mA

DC 21,6 ... 40
4 14 max. 40 V non-polarized / max. 30 mA

Thermal, physical data

Ambient temperature:

°C

­20 ... +50

Relative humidity:

%

 95 (non-condensing)

Optional communication modules (input parameters)

Interface module Siemens FDnet:

V

ADICOS

V

Interface module 4...20 mA:

Interface module Bosch LSN:

V

Pre-alarm relaiy module:

V

V

DC 33 V; max. 10 mA DC 35 V; max. 20 mA
DC 36 V; max. 20 mA DC 40 V; max. 10 mA DC 24 V; max. 20 mA

Sensor Data Sensor combination: Reaction time: Detection szenarios:

CO ­ H2 ­ HC ­ NOx

s

> 30

Smoldering fires according to EN 54-7 Fires emerging from smoldering coals

ADICOS GSME-X22

400-2410-002 EN22

13

technicAl DAtA

Information regarding explosion protection

Explosion protection class:

Max. surface temperature:

°C

Device group:

Other

Bending radius connection cable:

mm

9.1 ID Plate

II 3D Ex tc IIIC T 80 °C Dc 80
II, Kategorie 3D
> 91,5

Model: Device model
ART-Nr: Article number (variable)
COM-Nr: Communication number (variabel)
CE marking

SERIAL: Serial number (variable)

YR: Year of production (variable)

TEMP: VDC/VA:

Ambient

IP:

temperature

Voltage range / maximum pow-

I
0 :

er consumption

(heating incl.)

Degree of protection
Internal fusing (Short-circuit current)

Information on explosion protection

14

400-2410-002 EN22

ADICOS GSME-X22

10 Appendix
10.1 ADICOS mounting plate 150 130

AppenDix

A

A

150 130

6,4 A-A

ADICOS GSME-X22

400-2410-002 EN22

15


Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)