TX3-TOUCH-F15-C/D QUICK START

1

1 Mount the Enclosure

AC or DC Door Strik1es: see 2 and 3

Auxiliary Door Strike: see 4

2 3 AC Door Strike or Maglock 18 AWG

DC Door Strike
(Output 1)

The enclosure mounts on the wall. Mount the

AC Door Strike or

18 AWG

enclosure right-side up (the Mircom logo on the

Mounting hole

door is in the lower right corner).

You need:

NO NC

Jumper JW8

NO NC

TS8

Magnetic Lock AC Power Supply for Door Strike

AC or DC Power Supply for Door Strike

DC Output Door Strike or Magnetic Lock

4 fasteners appropriate for the wall that you are mounting the enclosure on.

Jumper JW8

For a door strike: connect the jumper wire to the top pin of

Unused pin

Mounting hole

1. Find a suitable location for the enclosure. You can mount the enclosure using the keyholes on the back, or the knockouts on the side, or both.
2. Trace an opening in the wall for the enclosure

SW1

jumper JW8 (normally open).

TS8

TS9

DIP Switches:
see 5

For a maglock: connect the jumper wire to the bottom

pin of jumper JW8 (normally

with one side aligned with a wall stud. 3. Cut an opening in the wall 3/32" (3 mm) larger
than the tracing, ensuring that one side is aligned with the wall stud or supporting structure. 4. Insert the enclosure into the wall cutout, and using the side of the enclosure as a template

closed).
4 Auxiliary Door (Output 2)

The maximum supply for the AC or DC Power Supply for Door Strike must not exceed: 28 VAC / 1 A max 30 VDC / 1 A max

1

mark the hole mounting locations (either

18 AWG

Alternative Wiring

keyholes or knockouts or both). 5. If you are using the keyholes, remove the
enclosure and place 2 fasteners halfway into the wall into the two top keyhole locations. 6. Place the enclosure onto the top fasteners, then lower it so that the fasteners fit in the narrow part of the keyholes. 7. Screw the other fasteners into the remaining holes.

Power switch

- Door Strike

TS9

Note: Most door

for Dry Contact

strikes are non-
+ polarity.

Jumper JW8

Trigger for door operator

NO NC

TS8

Jumper JW8 controls whether the contact

+

-

is normally open or normally closed.

11

Keyhole

8. Tighten all fasteners into place.

Warning: Turn the power

Power Supply Note: If AC power

Installation Prerequisites

off before wiring.

supply is used,

· Verify that the building telephone

Install all power supplies outside the enclosure.

infrastructure is operational. When wiring an

polarity does not apply.

Mounting hole

9 1

NSL installation it may be necessary to check Wiring Requirements

each resident's line.

Unless specified otherwise, all wiring is a maximum length

· Ensure there is a provision for a ground

of 1000 ft (304.8 m).

circuit. The Telephone Access System

assembly must be grounded by a qualified

RS-485: Maximum total length: 4000 ft (1219.2 m)

electrician. An improperly grounded unit

Use twisted shielded pair.

can result in equipment malfunction and

Outputs 2-4
Output 2

Output 4 Output 3

5 DIP Switch Settings for RS-485 Address

Mircom http://www.mircom.com CANADA - Main Office 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) 660-4655 (905) 660-4655

1
U.S.A 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: (888) 660-4655 TECHNICAL SUPPORT Tel: 1-888-647-2665

void the warranty. · Use the latest Telephone Access System
controller firmware. Mircom periodically updates panel firmware and Configurator Software to add features and correct any minor inconsistencies. For information about the latest firmware or software visit the `Manuals and Downloads' section of the Mircom website at www.mircom.com

For more details, see LT-996 and LT-969 on the Mircom website and the USB flash. Mircom technical support: 1-888-647-2665

Door Strike: The door strike power supply depends on the door strike power requirements.
Maximum Power Supply Wire Distances

Gauge 16 14 12 10

Distance 125 ft (38.1 m) 200 ft (60.96 m) 320 ft (97.536 m) 500 ft (152.4 m)

Contact ratings for outputs 2-4: 125 VAC / 2 A 30 VDC / 1 A

Address 1

Address 2

Address 3

Address 4 ON

OFF

1

81

81

81

8

Each Touch Screen must have a unique RS-485 address. Use DIP switches 1-6 to set the RS-485 network address. See LT-969 for details. Leave DIP switch 7 on.

© Mircom 2021 Printed in Canada Subject to change without prior notice

LT-6201 rev 4

TX3-TOUCH-F15-C/D QUICK START

Warning: Turn the power off before wiring.
Phone Lines:
see 7
P7 Guard Phone board connector
P4 TX3-MDM Modem board connector

7 Phone Lines
Line 1
TR T Line 2 R (optional)
Non-configurable PBX systems are not supported. For more information, contact Mircom technical support at 1- 888-647-2665.

9 RS-485

Maximum total length: 4000 ft (1219.2 m) for 22 AWG Use twisted shielded pair. See LT-996 for complete details.

Panel 1
First panel on network

Panel 2

Panel 3
Last panel on network

120 

120 

Optional common reference connection if available

Connect shield to chassis ground on one panel only

Connect shield to chassis ground on one panel only

11 Mount the TX3-PS24-5A 24 VDC, 156 W Power Supply

9

9

1 2

1 2

2 1

{ {

12 Connect the Power
1. Set the voltage selectable switch on the power supply to the appropriate voltage. The voltage selectable switch can be set to either 115 V or 230 V.
2. Connect the load power supply wires to the Touch Screen terminal screws as shown in step 10.
3. Connect the other end of the load power supply wires the Load terminals.
4. Connect the building power supply wires to the Line terminals as shown below.
5. Turn the power on by pressing the power button.
To building power To Touch Screen

USB connector: Connect to computer for firmware upgrade and configuration (maximum length of USB cable: 8 feet/2.4 m)

Postal Lock:
see 6

RS-485: see 9

6 Postal Lock (Input 1) Fire Alarm Override (Input 2) Door Contact (Input 3) 22 AWG

8 Camera Supply Note: Do not use for any other purpose TS3
Camera Power Supply (12 VDC)

TS5
Postal Lock Warning: Do not attach the wiring until after the postal lock is installed.

Activation of this Door input relocks the main Contact door (Output 1).
Fire Activation of this input Panel unlocks the main
and auxiliary doors (Outputs 1 and 2).

For more details, see LT-996 and LT-969 on the Mircom website and the USB flash. Mircom technical support: 1-888-647-2665

10 Ground and Power

USB port for keyboard

Power button

+ To TX3-PS24-5A - 24 VDC power supply
Ground (16 AWG)

1 2

9
To surface mount the power supply enclosure: You need 4 fasteners appropriate for the wall that you are mounting the enclosure on. 1. Find a suitable location for the power supply
enclosure, such as over a wall stud. 2. Using the enclosure as a template, mark the
two top mounting hole locations. Ensure that at least one side is over a wall stud. 3. Remove the enclosure and place two wall fasteners halfway into the marked hole locations. 4. Place the enclosure onto the fasteners and lower it so that the fasteners fit in the narrow part of the keyholes. 5. Screw the other two fasteners into the two remaining holes. 6. Tighten all four fasteners into place.
Note: The enclosure can also be mounted directly onto the drywall using anchors.

13 Connect the UPS
Follow the manufacturer's instructions included with TX3-TOUCH-UPS-KIT. See the Mircom document LT-6714, included with TX3-TOUCH-UPS-KIT, for instructions on: · Connecting the USB cable to the TX3
Touch. · Installing the APC PowerChute Personal
Edition Software (only on existing TX3 Touch installations). · Connecting the power cable from the TX3-PS24-5A power supply to the uninterruptible power supply.
WARNING
To ensure the security of occupants, change the level 3 passcode from its default setting. See LT-995 on mircom.com for details.