Multi-channel Circuit Metering System BJ-MCM400 User Manual

MCM400 User manual -V1.31

MCM400 Multi Channel Energy Meter - High quality Sub Meter - Blue Jay

Multi-channel Circuit Metering System - cqbluejay.com

Read me When you use BJ-MCM400 series Multi-Channel Circuit Metering system, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use this AC Energy Meter, and help to solve the various problems at the scene.


File Info : application/pdf, 19 Pages, 743.22KB

PDF preview unavailable. Download the PDF instead.

MCM400-User-manual-V1.31
User Manual
Multi-channel Circuit Metering System BJ-MCM400 User Manual

Version1.31

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Revision 2023-5 Email:tech@cqbluejay.com

Read me

User Manual

When you use BJ-MCM400 series Multi-Channel Circuit Metering system, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use this AC Energy Meter, and help to solve the various problems at the scene.
1. Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
2. When installation, the current input terminal must non-open, voltage input terminals must Nonshort circuit;
3. Be sure the instrument wiring consistent with the internal system settings;
4. When communicating with the PC, instrument communication parameters must be consistent with the PC

 Please read this user manual carefully  Please save this document

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

Directory

User Manual

CONTENTS

Page

1. - SUMMARIZE .............................................................................................................................. - 4 2. - SPECIFICATIONS ...................................................................................................................... - 5 3.- INSTALLATION AND START-UP ............................................................................................... - 7 -
3.1.- INSTALLATION ........................................................................................................................... - 7 3.2. - CONNECTION TERMINAL OF MCM400........................................................................................- 8 -
4. - SETUP PROCEDURE ................................................................................................................ - 9 4.1. - KEY OPERATION ....................................................................................................................... - 9 4.2. - SHOW ELECTRIC PARAMETERS .................................................................................................. - 9 4.3.- PARAMETERS SETTING............................................................................................................ - 11 4.4. - MENU STRUCTURE.................................................................................................................- 12 -
5. - COMMUNICATION PROTOCOL.............................................................................................. - 13 5.1. - CONNECTION FOR THE RS485 BUS........................................................................................- 13 5.2. - MODBUS © PROTOCOL ......................................................................................................... - 14 5.3. - REGISTER ADDRESS TABLE .................................................................................................... - 15 -
6. - SAFETY CONSIDERATIONS................................................................................................... - 18 7. - MAINTENANCE........................................................................................................................ - 18 8. - TECHNICAL SERVICE............................................................................................................. - 18 -

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

User Manual
1. - SUMMARIZE
The MCM400 Series provides a compact and robust metering solution, enable reliable monitoring of building electrical loads with a low installation cost-per-point by combining sub-metering. The unit performs real-time metering, measures energy consumption of 4 channels circuits for three phase circuits.
Advanced communications options including Modbus via RS485, I/O communications provide for extensive reliable data exchange. Multiple units can be connected together to meter unlimited number of circuits. The versatility of MCM400 meters are ideal for multi-tenant or departmental metering applications within office towers, condominiums, apartment buildings, shopping centers and other multi-user environments.
Measurement Function
Voltage: Line Voltage; Phase Voltage Current: Total Current; Current per channel Power and Power Factor: Total power Reactive Power, Apparent Power, Power Factor and for per channel Frequency: System Frequency
Energy Function
Energy (kWh) measurement meeting international standards, accuracy is Class 1.0. It optional Time of Use feature: 12 Seasons, 4 Tariffs record, max three-month data for each channel.
Over/Under Limit Alarming
Users can select parameters and set their set points. An alarm will be triggered when the setpoint is reached, user can get the info from MODBUS reading.
Power Quality Analysis
Optional power quality parameters such as voltage and current THD, Odd harmonic distortion (Total Odd HD), even harmonic distortion (Total Even HD), 2 ~ 21 times the harmonic content, Current Kfactor (KF), crest factor (CF), telephone interference factor (THFF), voltage and current unbalance etc.
Communication and Network
Supports RS485 communication open protocol: Modbus RTU;

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

2. - SPECIFICATIONS

User Manual

Reference standard: Basic electricity: IEC 61557-12:2007 Active energy: IEC 62053-21:2003 Reactive energy: IEC 62053-23:2003

Accuracy standards

Parameter

Accuracy A phase B phase C phase

All

Voltage

0.2

Current

0.2

Active Power

0.5

Reactive Power

0.5

Apparent power

0.5

Power Factor

0.5

Active Energy

1

Reactive Energy

2

Frequency

0.1

V1

V2

V3

A1

A2

A3

W1

W2

W3

W

var1

var2

var3

var

VA1

VA2

VA3

VA

PF1

PF2

PF3

PF

Wh

varh

Hz

Notes: final metering accuracy depends one sampling CT and PT accuracy

Input Voltage: Rated 100~220V (need confirm before order) Current: Rated ../100mA (optional ../0.333V, need confirm before order) Frequency: 45-65Hz

Overload Current: 1.2 times rated continuous; 5 seconds for 10 times the rated Voltage: 1 seconds for 2 times the rated

Dielectric strength IEC/EN 61010-1:2010 2kV AC RMS 1 minute, between input / output / case / power supply

EMC Test
Electrostatic discharge immunity test: Electrical fast transient burst immunity test
Surge (Shock) immunity test

standard
IEC-61000-4-2 level 4 IEC61000-4-4 level 3
IEC61000-4-5 level 4

Test voltage 8Kv
Input 1kV; Power supply 2kV
common mode test voltage 4kV

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

Work environment Temperature: -15C~ +55C Humidity: RH 20%~95% (No condensation)
Storage Conditions Temperature: -30C~+70C Humidity: RH 20%~95%
Working Power AC/DC 85-265V, 45-65Hz DC 20-60V (Optional) Maximum power consumption 3W
Dimensions L × H × D =87.3X132X46.5mm (with wiring terminal)

User Manual

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

3.- INSTALLATION AND START-UP

User Manual

The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly is on the cabinet's door.
Whether the instrument is not used as manufacturer's specifications, the protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages),the instrument must be immediately powered off. In this case contact a qualified service representative.

3.1.- Installation
Mounting
Instrument is to be mounted on 35mm Din-rail. Keep all connections inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touch and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.

Notes:

Auxiliary power:

MCM400 meter with AUX power input, if not for a special statement, we provide the 85265VAC/DC power interface for standard products. Please ensure that the auxiliary power match meter access to prevent damage to the product.

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

3.2. - Connection terminal of MCM400

3635 34 3332 31 30 29 28 2726 25 24 2322 21 2019
IC IC* IB IB* IA IA* IC IC* IB IB* IA IA* IC IC* IB IB* IA IA*

CH4-AM P

CH3-AM P

CH2-AM P

M CM 4 0 0

User Manual

CH1-AM P

VOLTAGE RS 485 AUX

IC IC* IB IB* IA IA* NC UN UC UB UA NC SHLD B A NC N L 18 1716 1514 13 12 11 10 9 8 7 6 5 4 3 2 1

Notes:
The current input pin need to access the CT, and output signal of CT is 0-100mA or 0~0.333V, please confirm your ordering meter types and prepare related CT.
Wiring diagram may be changed due to the special requirements of customers order, please refer the label on the rear part.
If you are or sure or signs unclear please contact:
Blue Jay Technical Support: tech@cqbluejay.com

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

4. - SETUP PROCEDURE

User Manual

4.1. - Key operation

"" or "" for screen switch or value increase/decrease

"SET"

for menu enters or exit

""

for enter next menu or confirm the change

4.2. - Show electric parameters
When the MCM400 in monitor screen, user can use keypad switch shows the electrical parameters, press "" to switch another screen in this channel, press "" to switch another channel parameter press " " to switch more details parameter in screen screen roller logic as following:

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

User Manual

Note:
Energy data is displayed in 8-digit decimal format by default. As counter increased, the decimal point position will move right, data increased by 10 times, the unit display changing from KWh to MWh.

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

4.3.- Parameters Setting

User Manual

The SETUP procedure of the MCM400 is performed by means of several SETUP options. When into the SETUP, use the keyboard to select different options and enter required variables:

Press the key SET can enter the parameter setting. the screen ask access password (Default is

0001), then press

can enter the menu.

The operation menu logic as following:

Notes:
1. Clear energy: Customers can write commands through RS485 or through the screen to clear the energy data to 0. Once the secondary side value of the internal memory reaches to 232(4294,967,296), counter automatically reset to 0.
2. Clear energy: write command 0x0A0A to register address 3000

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

4.4. - Menu Structure

User Manual

level 1
Input Setting
Comm Setting
Alarm Setting
System Settings

Level 2 Wiring mode Rated volt Rated amp PT ratio CT ratio of CH1 CT ratio of CH2 CT ratio of CH3 CT ratio of CH4 Address Baud Rate Check format
Alarm_1~5
Password Display
Backlight Clear
Contrast

Level 3 3P4L/3P3L2CT/3P3
L3CT 220V 0.100A(100mA) Last time set value Last time set value Last time set value Last time set value Last time set value 1~247 2400 / 4800 / 9600 n.8.1 / o.8.1 / e.8.1
Mode
Delay Parameter
Value
hysteresis Related channel
0~9999 MAN
Number 1~9 1~5
Energy 1~9

Level 4
1~9999 1~9999 1~9999 1~9999 1~9999
/ / / OFF / Upper Limit / Lower Limit / Ua/Ub/Uc/Uab/Ubc...
0~9999
0~9999 CH1-4
/ / / / /

Description
input signal network measurement
Default setting, cannot be modified
Default setting, cannot be modified
Default 0001
Default 0050
Default 0050
Default 0050
Default 0050
Default 0001 Default is 9600
Factory default (n.8.1)
Total three mode
Alarm triggered time delay, Default 001.0s
Alarm triggered parameters Default is 5500,value
related to secondary side parameters, unit: Volte - 0.1V; Amp - 0.001A;
Active power - 0.1W; Reactive power - 0.1VAR;
Power factor - 0.001; Frequency - 0.01HZ;
Default is 0050
Default CH1
Reset user password Manual switching, or automatic switching in
1~9sec LCD backlight duration, unit
is min, default is 5 Clear the record in meter
LCD display contrast, default is 5

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

User Manual
5. - COMMUNICATION PROTOCOL
5.1. - Connection for the RS485 BUS
The composition of the RS-485 cabling must be carried out with a meshed screen cable (minimum 3 wire), diameter of not less than 0.5mm2, with a maximum distance of 1,200 m between the BJ194... and the master unit. This Bus may connect a maximum of 32 BJ194...

Note: 1. For communication with the master unit, customers can choose the RS-232 to RS-485 converter to use
2. Full range of BJ-... meter RS485 PIN number is 58,59,60
3. Due to product modifications or custom requirements, the interface pin place may be changed. For details, please refer to product label on the rear board

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

5.2. - MODBUS © protocol
Modbus RTU Frame Format:

Address code

1 BYTE

Function code

1 BYTE

Data code

4 BYTE

Error Check code


2 BYTE

MODBUS FUNCTIONS

Code:

Meaning:

FUNCTION 03/04

Reading of n Words

User Manual
Slave device address 1-247 Indicates the function codes like read coils / inputs Starting address, high byte Starting address, low byte Number of registers, high byte Number of registers, low byte Cyclical Redundancy Check ( CRC )
Description: This function permits to read all the electrical parameters of the BJ...series.

FUNCTION 06

Write register

Write value in to the relevant register

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

5.3. - Register Address Table

User Manual

5.3.1- Basic Power Data--Primary Side

Address

Data

Byte mode

0

CH1_Ua

float

2

2

CH1_Ub

float

2

4

CH1_Uc

float

2

6

CH1_Uab

float

2

8

CH1_Ubc

float

2

10

CH1_Uca

float

2

12

CH1_Ia

float

2

14

CH1_Ib

float

2

16

CH1_Ic

float

2

18

CH1_Pa

float

2

20

CH1_Pb

float

2

22

CH1_Pc

float

2

24

CH1_P

float

2

26

CH1_Qa

28

CH1_Qb

30

CH1_Qc

float

2

float

2

float

2

32

CH1_Q

float

2

34

CH1_Sa

36

CH1_Sb

38

CH1_Sc

float

2

float

2

float

2

40

CH1_S

float

2

42

CH1_PFa

44

CH1_PFb

46

CH1_PFc

float

2

float

2

float

2

48

CH1_PF

float

2

50

CH1_FR

float

2

52

CH1_EpZ+

float

2

54

CH1_EpZ-

float

2

56

CH1_EqZ+

float

2

58

CH1_EqZ-

float

2

60

CH1_EpA+

float

2

62

CH1_EpA-

64

CH1_EqA+

float

2

float

2

Instruction
Channel_1 Phase to Line Voltage, Unit: V
Channel_1 Phase to Phase Voltage, Unit: V
Channel_1 Three phase Current, Unit: A
Channel_1 Individual phase active power, Unit: kW
Channel_1 Total active power, Unit: kW
Channel_1 Individual phase reactive power, Unit: kVar
Channel_1 Total reactive power, Unit: kVar
Channel_1 Individual apparent power, Unit: kVA
Channel_1 Total apparent power, Unit: kVA
Channel_1 Individual power factor, 0~1.000
Channel_1 Total power factor, 0~1.000 Channel_1 Frequency, Unit:0.01Hz Channel_1 Total positive active energy, Unit: kWh Channel_1 Total negative active energy, Unit: kVarh Channel_1 Total positive reactive energy, Unit: kVarh Channel_1 Total negative reactive energy, Unit: kWh Channel_1 A phase positive active energy, Unit: kWh Channel_1 A phase negative active energy, Unit: kVarh Channel_1 A phase positive reactive energy,

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

66

CH1_EqA-

float

68

CH1_EpB+

float

70

CH1_EpB-

float

72

CH1_EqB+

float

74

CH1_EqB-

float

76

CH1_EpC+

float

78

CH1_EpC-

float

80

CH1_EqC+

float

82

CH1_EqC-

float

100-182 CH2_

float

200-282 CH3_parameter float

300-382 CH4_parameter float

User Manual

Unit: kVarh

2

Channel_1 A phase negative reactive energy, Unit: kWh

2

Channel_1 B phase positive active energy, Unit: kWh

2

Channel_1 B phase negative active energy, Unit: kVarh

2

Channel_1 B phase positive reactive energy, Unit: kVarh

2

Channel_1 B phase negative reactive energy, Unit: kWh

2

Channel_1 C phase positive active energy, Unit: kWh

2

Channel_1 C phase negative active energy, Unit: kVarh

2

Channel_1 C phase positive reactive energy, Unit: kVarh

2

Channel_1 C phase negative reactive energy, Unit: kWh

2

Channel_2 parameter, structure refer to Channel_1

2

Channel_3 parameter, structure refer to Channel_1

2

Channel_4 parameter, structure refer to Channel_1

5.3.2- Meter status data

Address

Data

1202

Alarm

1240
1241 1242 1243 1244 1245 1246 1247

Wiring mode
Voltage range Current range PT ratio CT of CH1 CT of CH2 CT of CH3 CT of CH4

Byte mode

int

1

Int

1

Int

1

Int

1

Int

1

Int

1

Int

1

Int

1

Int

1

Instruction
0: without alarm 1: Alarm trigged Bit 0~4 show Alarm_1~5 status 0: 3P4W 1: 3P3W-2CT 2: 3P3W-3CT Unit: V Unit: mA Range: 1-9999 Range: 1-9999 Range: 1-9999 Range: 1-9999 Range: 1-9999

5.3.3 - Voltage harmonic (max 21th)

Address

Data

Byte mode

Instruction

1300 1301 1302 1303
1304

THDUa THDUb THDUc
TOHDUa
TOHDUb

int

1 A-phase Voltage THD, unit 0.1%

int

1 B-phase Voltage THD

int

1 C-phase Voltage THD

int

1

A-phase Voltage odd harmonic total distortion, unit 0.1%

int

1 B-phase Voltage odd harmonic total distortion

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

1305 1306
1307 1308 1320-1339
1340-1359 1360-1379

TOHDUc TEHDUa TEHDUb TEHDUc HUa HUb HUc

User Manual

int

1 C-phase Voltage odd harmonic total distortion

int

1

A-phase Voltage even harmonic total distortion, unit 0.1%

int

1 B-phase Voltage even harmonic total distortion

int

1 C-phase Voltage even harmonic total distortion

int

20

A phase voltage harmonic ratio for 2 to 21th, unit 0.1%

int

20 B phase voltage harmonic ratio for 2 to 21th

int

20 C phase voltage harmonic ratio for 2 to 21th

5.3.4 - Current harmonic (max 21th)

Address

Data

Byte mode

1400 1401 1402 1403

THDIa1 THDIb1 THDIc1
TOHDIa1

int

1

int

1

int

1

int

1

1404

TOHDIb1

int

1

1405

TOHDIc1

int

1

1406

TEHDIa1

int

1

1407

TEHDIb1

int

1

1408

TEHDIc1

int

1

1420-1439 HIa1

int

20

1440-1459 HIb1

int

20

1460-1479 Hlc1

int

20

1500-1579 CH2 Harmonic int

20

1600-1679 CH3 Harmonic

int

20

1700-1779 CH4 Harmonic int

20

Instruction
Channel_1 A-phase Current THD, unit 0.1%
Channel_1 B-phase Current THD
Channel_1 C-phase Current THD
Channel_1 A-phase Current odd harmonic total distortion, unit 0.1% Channel_1 B-phase Current odd harmonic total distortion Channel_1 C-phase Current odd harmonic total distortion Channel_1 A-phase Current even harmonic total distortion, unit 0.1% Channel_1 B-phase Current even harmonic total distortion Channel_1 C-phase Current even harmonic total distortion Channel_1 A phase Current harmonic ratio for 2 to 21th, unit 0.1% Channel_1 B phase Current harmonic ratio for 2 to 21th Channel_1 C phase Current harmonic ratio for 2 to 21th Channel_2 harmonic value, structure refer to Channel_1 Channel_3 harmonic value, structure refer to Channel_1 Channel_4 harmonic value, structure refer to Channel_1

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:tech@cqbluejay.com

6. - SAFETY CONSIDERATIONS

User Manual

All installation specification described at the previous chapters named: INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

7. - MAINTENANCE

The MCM400 does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument open and powered on, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out; the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument's design allows a quick replacement in case of any failure.

8. - TECHNICAL SERVICE
For any inquiry about the instrument performance or any failure Contact to Blue Jay's technical service. Blue Jay - After-sales service E-mail : tech@cqbluejay.com