Panasonic FP7 Series TCP
HMI Factory Setting:
Controller IP Address: 192.168.0.1
Controller COM Port: 9094
Controller Station Number: 238
Control Area / Status Area: DT0/DT10
Connection
Standard Jumper Cable / Network Cable without jumper (Auto-detected by HMI)
Definition of PLC Read/Write Address
a. Registers
Type | Format Word No. (n) |
Read/Write Range | Data Length | Note |
Internal Relay | WRn | WR0 - WR2047 | Word | |
Link Relay | WLn | WL0 - WL1023 | Word | |
External Input Relay | WXn | WX0 - WX511 | Word | |
External Output Relay | WYn | WY0 - WY511 | Word | |
Data Register | DTn | DT0 - DT999423 | Word | |
Special Data Register | SDn | SD0 -SD39 | Word | |
SD50 -SD85 | Word | |||
SD100-SD115 | Word | |||
SD120 -SD125 | Word | |||
Link Data Register | LDn | LD0 - LD16383 | Word | |
Timer Setting Value | TSn | TS0 - TS4095 | Double Word | |
Timer Elapsed Value | TEn | TE0 - TE4095 | Double Word | |
Counter Setting Value | CSn | CS0 - CS4095 | Double Word | |
Counter Elapsed Value | CEn | CE0 - CE4095 | Double Word |
b. Contacts
Type | Format Slot No. (s) Word No. (n) Bit No. (b) |
Read/Write Range | Note |
Internal Relay | Rnb | R00 - R2047F | |
Special Internal Relay | SRnb | SR00 - SR3F | |
SR100 - SR259 | |||
SR1000 - SR1499 | |||
Link Relay | Lnb | Ln00 - Ln1023F | |
External Input Relay | Xnb | Xn00 - Xn511F | |
External Output Relay | Ynb | Yn00 - Yn511F | |
Direct Input | INs.nb | IN1.00 - IN64.62F | |
Direct Output | OTs.nb | OT1.00 - OT64.62F | |
Pulse Relay | Pnb | P00 - P255F | |
Error Notification Relay | Eb | E0 - E4095 | |
Timer Flag Contact | Tb | T0 - T3071 | |
Counter Flag Contact | Cb | C0 - C3071 |
NOTE
- PLC default setting is 238. It supports the external device connections of all station numbers. To change the setting, PLC supports station number range from 0 to 99. For more detail on PLC station number, please refer to PLC user manual.