 Features

 Applications

Universal AC input / Full range

Industrial control system

Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15

Semiconductor fabrication equipment Factory automation Electro-mechanical apparatus

UL 508 (industrial control equipment) approved

BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level

100% full load burn-in test

2 years warranty

 Description
EDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. EDR-120 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20 and 60 under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-120 a very competitive power supply solution for industrial applications.

 Model Encoding EDR - 120- 12

Output voltage Output wattage Series name

File Name:EDR-120-SPEC 2021-09-15

Downloaded from Arrow.com.

120W Single Output Industrial DIN RAIL

EDR-120 series

SPECIFICATION

MODEL

EDR-120-12

EDR-120-24

EDR-120-48

DC VOLTAGE

12V

24V

48V

RATED CURRENT CURRENT RANGE RATED POWER

10A 0 ~ 10A 120W

5A 0 ~ 5A 120W

2.5A 0 ~ 2.5A 120W

OUTPUT

RIPPLE & NOISE (max.) Note.2 100mVp-p

VOLTAGE ADJ. RANGE

12 ~ 14V

VOLTAGE TOLERANCE Note.3 ±2.0%

LINE REGULATION

±0.5%

LOAD REGULATION

±1.0%

120mVp-p
24 ~ 28V ±1.0% ±0.5% ±1.0%

150mVp-p
48 ~ 55V ±1.0% ±0.5% ±1.0%

SETUP, RISE TIME

1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load

HOLD UP TIME (Typ.)

16ms/230VAC 10ms/115VAC at full load

VOLTAGE RANGE Note.6 90 ~ 264VAC

FREQUENCY RANGE

47 ~ 63Hz

127 ~ 370VDC

[DC input operation possible by connecting AC/L(+), AC/N(-)]

INPUT

EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

85% 2.25A/115VAC 20A/115VAC

1.3A/230VAC 35A/230VAC

87.5%

88.5%

LEAKAGE CURRENT

<1mA / 240VAC

OVERLOAD

105 ~ 130% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed

PROTECTION OVER VOLTAGE

14 ~ 17V

29 ~ 33V

Protection type : Shut down o/p voltage, re-power on to recover

56 ~ 65V

OVER TEMPERATURE

WORKING TEMP.

WORKING HUMIDITY

ENVIRONMENT STORAGE TEMP., HUMIDITY

TEMP. COEFFICIENT

VIBRATION

SAFETY STANDARDS

SAFETY & WITHSTAND VOLTAGE

EMC

ISOLATION RESISTANCE

(Note 4) EMC EMISSION

Shut down o/p voltage, re-power on to recover -20 ~ +60 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing -40 ~ +85, 10 ~ 95% RH ±0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508,TUV BS EN/EN62368-1,EAC TP TC 004,BSMI CNS14336-1,IS13252(Part1)/IEC60950-1 approved;(meet BS EN/EN60204-1) I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A

EMC IMMUNITY

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55024, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, criteria A, EAC TP TC 020

OTHERS NOTE

MTBF

474.6K hrs min. MIL-HDBK-217F (25)

DIMENSION

40*125.2*113.5mm (W*H*D)

PACKING

0.6Kg; 20pcs/13Kg/1.16CUFT

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets

EMC directives.

5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.

In case the adjacent device is a heat source, 15mm clearance is recommended.

6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).

 Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Downloaded from Arrow.com.

File Name:EDR-120-SPEC 2021-09-15

120W Single Output Industrial DIN RAIL

EDR-120 series

Block Diagram

EMI FILTER

I/P

&

RECTIFIERS

FG

O.L.P. O.T.P.

POWER SWITCHING
PWM CONTROL

RECTIFIERS &
FILTER

O.C.P.
DETECTION CIRCUIT
O.V.P.

fosc : 70KHz
+V -V

Derating Curve

Static Characteristics

230VAC 100
80 115VAC
60 50 40
20

12V(230VAC) 24V,48V(230VAC)
12V,24V,48V(115VAC)

-20 -10 0

10

20

30

40 45 50

AMBIENT TEMPERATURE ()

60 70 (VERTICAL)

100 90 80 70 60 50 40
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz

LOAD (%) LOAD (%)

Downloaded from Arrow.com.

File Name:EDR-120-SPEC 2021-09-15

120W Single Output Industrial DIN RAIL
Mechanical Specification

EDR-120 series
Case No.992D Unit:mm

35 125.2

113.5 Side View
Installation Instruction

Top View 40
1234
TB2 +V ADJ. +
DC OK
TB1 123 Front View
Bottom View

Side View
Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 AC/N or DC 3 AC/L or DC +
Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 DC OUTPUT -V 3,4 DC OUTPUT+V

35

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)

Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Downloaded from Arrow.com.

File Name:EDR-120-SPEC 2021-09-15



References

iText 5.5.6 ©2000-2015 iText Group NV (AGPL-version)