Instruction Manual for HYTRONIK models including: HIM35 High Bay Dual Sense Independent Dali Sensor, HIM35, High Bay Dual Sense Independent Dali Sensor, Independent Dali Sensor, Dali Sensor, Sensor

Instruction manual for HIM35

User manual for installation HIM35

HIM35 Independent DALI Sensor Hytronik

Instruction manual for HIM35

Detection range. 10% / 50% / 75% / 100%. Hold time. 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Stand-by time.

Instruction manual for HIM35 - Hytronik.com

2 giorni fa — scene selection / fast programming. Total ... Installation and Instruction Manual ... Installation of the sensor involves connecting it to the mains supply.


File Info : application/pdf, 2 Pages, 1.16MB

PDF preview unavailable. Download the PDF instead.

Instruction-manual-for-HIM35-1
HIGH BAY DUAL SENSE INDEPENDENT DALI SENSOR HIM35
Installation and Instruction Manual

1. Technical Specifications

Product type Operating voltage Switched power Power consumption Detection angle Detection area (Max.)*
Detection range Hold time Stand-by time Stand-by dimming level Daylight threshold Warming up time Operating temperature IP rating Sensor mode

High bay independent DALI sensor (tri-level control) 220-240VAC 50/60Hz Maximum 20pcs DALI devices, Maximum 40mA < 1W 360o Installation Height : 15m Detection Range (Ø) :18m
10% / 50% / 75% / 100% 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min 0s / 10s / 1min / 5min / 10min / 30min / 1h / +  10% / 20% / 30% / 50% 2 ~ 500Lux, Disable 30s -35oC ~ +50oC IP65 HF, PIR, HF+PIR, HF / PIR

2. Installation
Warnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be
carried out by a specialist in accordance with electrotechnical regulations. 2. Disconnect power supply before installing.
A. Ceiling mount

91.5 80.7
75 4.1

LED indicator Daylight sensor
PIR

Infrared receiver Rotary switch for programing

Sensor module

Cable entry

4.1 66.6 81.5

47.5

57.3

59.3

73.5

Installation rack

64 24.5

3. Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:

B. Screw to the Luminaire by conduit

Rotary switch preset (Please see the location in 2. Installation)

LED indicator Daylight sensor
PIR

Infrared receiver Rotary switch for programing

75

59.6 43

0.825"

43.8

66.6 89.9

Channel
0 1 2 3 4 5 6 7 8 9 A B C D E F

Detection range
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 100% 100%

Hold time
5s 1min 5min 5min 5min 5min 5min 10min 10min 10min 10min 10min 10min 30min 30min 5s

Stand-by time
10s 5min 10min 30min 0s + + 10min 30min + + + + + + 10s

Stand-by dimming level
10% 10% 10% 10% Disable 10% 30% 10% 10% 10% 30% 10% 10% 10% 30% 10%

Daylight threshold
Disable 2Lux 10Lux 30Lux 10Lux 30Lux Disable 2Lux 10Lux 30Lux Disable 30Lux 10Lux 50Lux Disable 2Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

73.5 59.3 57.3 47.5 33.7 35.2

Sensor module

Cable entry

C. Attach to the shade by clamp

LED indicator Daylight sensor
PIR

Rotary switch for programing Infrared receiver Angle adjustment Luminaire clamp

Sensor module

66.6 96.8 163.2

4.5
15
4.5 28.5

29

93.8 84.5 59.3

Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

4. Functions
4.1 Tri-level Control (Corridor Function) Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off. It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
4.2 Lux Off Function The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is not required (natural light lux level exceeds daylight threshold). Note: if the stand-by time is preset at "+", the fixture never switches off even when natural light
is sufficient.
4.3 Load Indication The light will flash ONCE rapidly after receiving the command from the remote controller. Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.

5. Wiring Diagram
L N
Brown Blue Red Black
HIM35

L LED N Driver
DALI +
DALI -

HIM35-20190104-A1

6. Three Options for PIR Lens and Detection Patterns (End user can choose the suitable lens in real application for various requirements)
* For single person walking across, the detection range is reduced by 1/3.

1

2

PIR

15m

HF

HFPIwR atalknignegnatiacrlomssov1e4mment 18m
PIR detection: H x D:15 x 18m (max.) HF detection: H x D:15 x 14m (max.)

PIR

15m

HF

5m

14m 18m
PIR detection: L x W x H:18 x 5 x 15m (max.) HF detection: H x D:15 x 14m (max. )

PIR

15m

HF

18m

5m 14m
PIR detection: L x W x H:5 x 18 x 15m (max.) HF detection: H x D:15 x 14m (max. )

7. Descriptions of the Button Functions (remote control HRC-11)

4

1

2

5

3

6 7

8

9

10

11

12

& A

4h

h

4h

13

14 15

HRC-11

Permanent ON/OFF [button 1 ] Press button 1 ,to select permanent ON or permanent OFF mode. * Press button 2 / 4 to resume automatic operation. The mode will change to AUTO Mode after power failure.
RESET[ button 2 ] Press button 2 , all settings go back to the rotary switch settings.
Shift [ button 3 ] Press button 3 , the LED on the top left corner is on for indication. All values / settings in RED are valid for 20 seconds.
Auto Mode [ button 4 ]
Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF. Note: the function of Semi-auto is disabled.
Power output [ button 5 ] Press button 5 , the light output shifts between 80% and 100%. Note: the function of "Sensor off" and "Twilight" are disabled.
Brightness +/- [ button 6 ] Press button 6 to adjust the light brightness between 10%~100% .
Scene prog. [ zone 7 ] (One-key-commissioning)
1. Press button "start" to program. 2. Select the buttons in 8 "Detection range", 9 / 10 "Daylight threshold",
11 "Hold time", 12 "Stand-by time", 13 "Stand-by dimming level" to set all parameters. 3. Press button "Memory" to save all the settings programmed in the remote control. 4. Press button "Apply" to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, the steps should be as follows: Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min, 3 Shift, 12 +, 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ] Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.

Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press
button 3 Shift at first.
Ambient daylight threshold [ button 10 ] 1. Press button 3 Shift, the red LED is on for indication. 2. Press button 10, the ambient lux level is sampled and set as
the new daylight threshold.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
3 Shift at first. 2. 2s is for testing purpose only, stand-by period and daylight
sensor settings are disabled in this mode. *To exit from Test mode, press button 2 or any button in zone 11 .
Stand-by time [ zone 12 ]
Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +. Note: "0s" means on/off control; "+" means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence is detected after hold-time.
Stand-by dimming level [ zone 13 ] Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%. Note.the function of 24h / 12h / 4h / 30s are disabled.
Dual tech [ zone 14 ] Press buttons in zone 14 to select sensor technology. HF+PIR: Light is on when both HF and PIR sensors are activated. HF/PIR: Light is on when HF or PIR sensors are activated.
RF mode [ zone 15 ] All buttons in zone 15 are disabled.

8. Troubleshooting

MALFUNCTION CAUSE REMEDY

CAUSE Incorrect daylight threshold setting

The fixture does not light up
The fixture is always on The fixture is on when it should not

Faulty fixture No power supply Detection zone not targeted Continous movement in the detection zone Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows

Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877

REMEDY Adjust daylight threshold setting Replace fixture Check power to sensor Check detection area setting Check detection area setting Adjust zone, change installation site
HIM35-20190104-A1

