MECH-iB-G07 PI Sheet AUG 24
MECH-iB-G07
Air Sourced Chiller

Mitsubishi Electric's MECH-iB-G07 chiller provides compact and convenient solution to your small-scale cooling needs.
Designed to meet the highest of quality standards, the range uses variable speed scroll compressors optimised for using the low GWP refrigerant R32.
The MECH-iB-G07 can provide efficient cooling, with inverter driven compressors and EC fans as standard, enhancing energy saving at part load conditions.
With an EC hydronic pump, hydronic flow switch, expansion vessel and advance controls all integrated, the MECH-iB-G07 is a `plug-&-play' solution, made simpler with options available such as BMS interface cards, anti-vibration mounts and buffer tanks that fit within the unit's footprint.

Key Features & Benefits:
Extended cooling envelope Compact design Providing fluid leaving temperatures as low as -12°C Operates down to -20°C ambient temperatures Low GWP R32 Refrigerant High seasonal efficiency (EER, SEER, SEPR) Plug & Play with Integrated hydronic pump, flow switch and expansion vessel

les.mitsubishielectric.co.uk

MECH-iB-G07 Air Sourced Chiller

MECH-iB-G07

Performance - Cooling Only

Gross Value*1

Total Cooling Capacity

Total Power Input

EER

EN14511 Values*1 *2

Total Cooling Capacity

EER

Seasonal Performance*3

Prated, c

SEER

Performance s

Electrical Data

Power Supply

Total

F.L.A.*4

Exchangers

Minimum Water Flow Heat Exchanger

Minimum Water Content System

Heat Exchanger User Side in Cooling*1 *2

Water Flow

Pressure Drop

Refrigerant Circuit

Compressors

Circuits

Regulation

Minumum Capacity Step

Refrigerant

Refrigerant Charge*5

Oil Charge

RC (ASHRAE)*6

Fans

Quantity

Airflow

Power Input

Noise Levels

Total Sound Pressure*7

Total Sound Power Level in Cooling*8 *9

Size and Weight*10

Width (A)

Depth (B)

Height (H)

Operation Weight

kW kW kW/kW
kW kW/kW
kW
%
V/ph/Hz A
l/s l
l/s kPa
l/s kPa
%
kg
kg/kW
No. m3/s kW
dB(A) dB(A)
mm mm mm kg

15Y
14.93 4.83 3.09
15.00 3.10
15.0 5.23 206.0
400/3+N/50 11
0.389 75
0.714 15.2
1 1 Stepless 32 R32 2.10 1.00 0.14
2 1.84 0.22
39 70
900 420 1390 144

18Y
17.79 5.23 3.40
17.90 3.40
17.9 5.4 213.0
400/3+N/50 12
0.464 90
0.851 21.6
1 1 Stepless 34 R32 2.83 1.00 0.16
2 1.95 0.22
40 71
900 420 1390 155

23Y
21.03 6.50 3.23
21.10 3.25
21.1 5.66 223.0
400/3+N/50 15
0.581 115
1.005 15.1
1 1 Stepless 29 R32 3.60 1.00 0.17
1 2.34 0.39
45 76
1450 550 1200 207

27Y
27.73 8.42 3.29
27.80 3.31
27.8 5.39 212.0
400/3+N/50 20
0.728 140
1.326 20.5
1 1 Stepless 30 R32 4.74 2.30 0.17
2 4.52 0.78
46 78
1450 550 1700 256

35Y
32.51 9.90 3.28
32.70 3.30
32.7 5.46 215.0
400/3+N/50 24
0.856 165
1.554 25.1
1 1 Stepless 26 R32 5.67 2.30 0.18
2 4.35 0.78
47 79
1450 550 1700 272

40Y
38.19 11.88 3.21
38.40 3.23
38.4 5.24 207.0
400/3+N/50 28
0.986 193
1.827 23.8
1 1 Stepless 26 R32 6.00 2.30 0.16
2 4.75 0.78
48 80
1700 650 1700 306

Eurovent Certified Data
Notes: 1. Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C 2. Values in compliance with EN14511 3. Parameter calculated according to [Regulation (EU) N. 2016/2281] 4. Values calculated referring to the version with the maximum number of fans working at the max absorbed current. Safety values to be considered when cabling the unit for power supply and line-protection. Data valid for standard units without any additional options and only indicative. Refer to databook. 5. Theoretical - refer to serial plate for actual charge volumes 6. Rate in accordance with AHRI standard 550/590 7. Average sound pressure level at 1m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level. 8. Sound power on the basis of measurement taken in compliance with ISO 9614. 9. Sound power level in cooling, outdoors. 10. Unit in standard configuration, without option accessories.

MECH-iB-G07 DIMENSIONS AND CLEARANCES
B

MECH-iB-G07 Air Sourced Chiller
All dimensions are in millimetres.

H

A
FRONT VIEW

TOP VIEW

400

400

900

400

400

MECH-iB-G07 OPERATING ENVELOPES

MECH-iB-G07 Air Sourced Chiller

Outdoor air temperature (ºC)

ºC 50 45 40 36 30
20
10
0
-10 -12
-20 -12 -10

-5

0

3 5 6.5 10

15 18 20

Evaporator leaving water temperature (ºC)

24 25 ºC

Antifreeze option(s) required

Glycol required for low evaporator leaving water temperature

Note: For specific limits of each model, please contact your local sales representative.

Telephone: 01707 282880 email: chillers@meuk.mee.com les.mitsubishielectric.co.uk

@meuk_les @green_gateway

Mitsubishi Electric Living Environmental Systems UK

Mitsubishi Electric Cooling and Heating UK

mitsubishielectricuk_les

Mitsubishi Electric Living Environmental Systems UK

thehub.mitsubishielectric.co.uk

UNITED KINGDOM Mitsubishi Electric Europe Living Environment Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. Telephone: 01707 282880 Fax: 01707 278881 IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: (01) 419 8800 Fax: (01) 419 8890 International code: (003531)
Country of origin: United Kingdom - Italy - Turkey - Japan - Thailand - Malaysia. ©Mitsubishi Electric Europe 2024. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company's General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Note: The fuse rating is for guidance only and please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions. Mitsubishi Electric's air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R290 (GWP:3), R32 (GWP:675), R407C (GWP:1774), R134a (GWP:1430), R513A (GWP:631), R454B (GWP:466), R454C (GWP:148), R1234ze (GWP:7) or R1234yf (GWP:4). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IP CC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP:550), R407C (GWP:1650) or R134a (GWP:1300).

Effective as of August 2024