iO-MZR Installation Instructons (Rev 1)

phil

iO-MZR Installation Instructons (Rev 1)

When the iO-MZR™ is used with a zone control system, the register actuator is wired to the proper damper terminals on the zone control panel.


File Info : application/pdf, 2 Pages, 529.80KB

PDF preview unavailable. Download the PDF instead.

iO-MZR Installation Instructons (Rev 1.2)
iO-MZRTM Motorized Zone Register When used as a stand-alone register Installation Instructions
The iO-MZRTM Motorized Zone Register can be used as a stand-alone register. It is recommended that no more than 30% of the existing registers be replaced with iO-MZRTM registers. iO-MZRTM registers should not be installed in the same room as the HVAC unit thermostat.
When the iO-MZRTM is used as a stand-alone register, it can be wired to a hardwired or battery powered thermostat using standard 18-gauge wire. However, if the thermostat wire is run through the supply duct work, use plenum rated wire to comply with local code. The thermostat should be configured for manual heating or cooling mode of operation since it does not control the HVAC equipment. Time delays should also be disabled to provide an immediate reaction on a call for heating or cooling. When the thermostat calls for heating or cooling, the MZRTM register is powered open. When the space temperature reaches setpoint, the MZRTM register spring returns close.

WIRING DIAGRAM FOR BATTERY POWERED THERMOSTAT OPERATION
JUMPER `W' AND `Y'
WYG R

WIRING DIAGRAM FOR HARDWIRED THERMOSTAT OPERATION
JUMPER `W' AND `Y'
WYG RC

iO-MZR AUTOMATIC ZONE REGISTER

iO-MZR AUTOMATIC ZONE REGISTER

ACTUATOR PO/SC

24V

120V

24 VAC TRANSFORMER

ACTUATOR PO/SC

24V

120V

24 VAC TRANSFORMER

iO-MZRTM Motorized Zone Register When used with a zone control panel Installation Instructions
When the iO-MZRTM is used with a zone control system, the register actuator is wired to the proper damper terminals on the zone control panel. The iO-MZRTM wires the same as a standard powered closed / spring return open zone damper.

ZONE PANEL

ZONE 1 STAT
72°

ZONE 1 REGISTER

ZONE 1 REGISTER

TRANS. 24VAC

ZONE 2 STAT
70°

ZONE 2 REGISTER

ZONE 2 REGISTER

Up to six registers may be connected to a single zone

WIRING SUGGESTIONS
The most common methods used to run wire inside the duct work is as follows:
1. Drill a hole in the register boot and run the wire in a conventional manner.
2. Use a fish tape to pull the wire through the duct.
3. Use a duct cleaning vacuum machine to draw a plastic bag with an attached line to pull wire through the duct.
If wiring from actuator is run inside the duct work, plenum rated wire must be used.

AVAILABLE SIZES
4" X 10" 4" X 12" 4" X 14" 6" X 12"

COLORS
Tan and White

APPLICATION NOTES
MZR zone registers are not designed to work in a 3-1/2" stud wall.

SPECIFICATIONS

Operating Voltage:

24VAC

Amperage:

0.26A

VA Rating:

6.5VA

Configuration:

Spring Open/Power Close

Indianapolis, IN 46237

www.iohvaccontrols.com For Technical Support Call Toll Free: 866-225-5032
iO-06-1181-022124

