EAE KNX Rosa Switch Series STx Installation Manual
Rosa Switch IM R3.0
Operation and Display
Diagram of the EAE KNX Rosa Switch front, showing four touch-sensitive button areas in a 2x2 grid.[Diagram: Four touch button areas]
Diagram of the EAE KNX Rosa Switch rear, indicating connection points:
- KNX Port Terminal
- Programming Button
- Programming LED
Description of the Device
- Serial switches with plastic push-button.
- Can be configured with ETS5 or higher.
- Independent button configuration for each fold.
- Integrated Temperature Sensor (°C/°F) (Optional).
- Integrated Humidity Sensor (Optional).
- Different color options.
- Cleaning mode function.
- Logical function.
- Dependent or independent programmable buttons.
- 60x60 mm easy mounting to standard junction boxes.
- 4 rockers can be programmed to perform different functions:
- Switching
- Dimming
- Shutter/Blind
- Value
- Scene control
- Status
Technical Data
| Parameter | Value | Specification |
|---|---|---|
| Type of protection | IP 20 | EN 60 529 |
| Safety class | II | EN 61 140 |
| KNX Supply (1) | Voltage | 21 V... 30 V DC SELV |
| Current Consumption | ≤ 10 mA | |
| Connections | KNX | Bus connection terminal |
| Installation | 60x60 mm standard box | |
| Temperature range | Ambient | -5° C + 45° C |
| Storage | -25°C + 55° C | |
| Humidity | Max. air humidity condensation | 95 % no moisture |
| Dimensions | Front face (2, 3, 4 fold) | 85x85 mm |
| Side- Surface of plaster | 11 mm | |
| Side- Under plaster | 19,4 mm | |
| Weight | 93 g | |
| Box | Metal, Aluminum | |
| CE | In accordance with the EMC guideline and low voltage | |
| Application Program | Communication Object | 50 |
| Number of Addresses(max) | 254 | |
| Number of assignments(max) | 255 | |
Installation
Installation of the product is done with the help of the flange which is inside the box. The flange is fixed to the junction box by using screws while the arrows on flange are headed to up. The switch is placed into the junction box by positioning the EAE logo upwards and then reclining it to the flange. The switch is slowly turned clockwise to give the right position to it on the flange. After the clicks are on the right position, switch is turned counter-clockwise to lock it on the flange.[Diagram: Mounting flange and locking direction (CCW)]
Diagrams showing dimensions: Front face 85.00 mm x 85.00 mm; Side depth 11.00 mm (surface of plaster) and 19.40 mm (under plaster).[Diagram: Dimensions of the switch]
Commissioning
Device default physical address is 15.15.255. Determination of the physical address and setting of parameters are actualized with Engineering Tool Software (ETS5 or higher). ".knxprod" file must be imported to the ETS. www.eaetechnology.com
ℹ️ A detailed information about parameter configuration can be found in Product Manual of device.
⚠️ Installation and commissioning of device may only be implemented by trained electricians. The relevant standards, directives, regulations and instructions must be observed when planning and implementing the electrical installation.
- When connecting the device make sure that the device can be isolated!
- Protect the device against moisture, dirt and damage during transport, storage and operation!
- Do not operate the device out of the specified technical data which is stated.
- The device may only be operated in closed enclosures (Distribution boards).
Cleaning
If device becomes dirty, only a dry cloth can be used for cleaning. It is not suitable to use wet cloths, caustics and solvents.