Motion sensor, Detector 120 - 277,120 VAC Version

Model: UM01/FU, UM01

Product Features

On/off function

The motion detector activates lighting based on detected movement. When the detector is active, lights turn on automatically when needed and off when no motion is detected.

Scenario 1: The light remains off during daytime, even if movement is detected, provided the ambient lux level is above the preset daylight threshold.

Scenario 2: With detected movement and insufficient ambient lux level, the light is triggered on by the detector.

Scenario 3: If no movement is detected, the light automatically turns off after the configured hold-time.

Wiring

The wiring diagram illustrates the connection of Live (L), Neutral (N) input power, and the switched Live (L') and Neutral (N) output to the control gear, connected to the UM01/FU unit.

Detection Pattern

Ceiling Mounting

Illustrates the detection coverage area for ceiling mounting. The pattern shows distinct zones for high sensitivity and low sensitivity coverage, mapped against height (1-6m) and distance (1-6m).

Wall Mounting

Illustrates the detection coverage area for wall mounting. The pattern shows distinct zones for high sensitivity and low sensitivity coverage, mapped against height (1-9m) and distance (1-9m).

Assembly Notes

Settings

1. Sensitivity

Sensitivity is adjustable via DIP switch combinations to suit various applications.

DIP Switch SettingSensitivity Level
I100%
II75%
III50%
IV10%

2. Hold-time

Hold-time determines the duration the light remains on at 100% after the last detected movement.

DIP Switch SettingHold-time Duration
I5s
II90s
III5min
IV15min

3. Daylight Threshold

Daylight thresholds are preset using DIP switches. If the daylight sensor is disabled, the light will always turn on upon detecting movement.

DIP Switch SettingDaylight Threshold
IDisable
II50Lux
III10Lux
IV2Lux

Specifications

Operating voltage120-277 VAC 50/60Hz
Rated load400W @120VAC, 900W@277 VAC (capacitive load)
Stand-by power<0.5W
Sensitivity Options10%/50%/75%/100%
Hold-time Options5s/90s/5min/15min
Daylight Sensor Options2lux/10lux/50lux, disable
Microwave frequency5.8 GHz +/- 75MHz
Transmitting power<0.2mW
Detection RangeMax. installation height: 6m; Max. detection range: Ø 12m @ 3m installation height
Detection angle30° ~ 150°
Working temperature-20°C ~ +60°C
IP ratingIP20
CertificatesETL, FCC

Compliance Information

This device complies with Part 15 of the FCC rules. Operation is subject to two conditions: (1) it must not cause harmful interference, and (2) it must accept any received interference, including that which may cause undesired operation. Modifications not expressly approved by the party responsible for compliance may void the user's authority to operate the equipment. This equipment complies with FCC radiation exposure limits for an uncontrolled environment. Maintain a minimum distance of 20cm between the user and the product.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy. If not installed and used according to instructions, it may cause harmful interference to radio communications. There is no guarantee that interference will not occur in a specific installation. If interference occurs, users are encouraged to correct it by: reorienting or relocating the receiving antenna, increasing separation between equipment and receiver, or connecting the equipment to a different outlet circuit. Consult the dealer or an experienced radio/TV technician for assistance.

This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development (ISED) Canada's licence-exempt RSS(s). Operation is subject to two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation. The device has been evaluated to meet general RF exposure requirements. The distance between the user and products should be no less than 20cm.

French Compliance Statement: Cet appareil contient des émetteurs/récepteurs exemptés de licence qui sont conformes aux flux RSS exempts de licence du Canada pour l'innovation, la Science et le développement économique (ISDE). Le fonctionnement est soumis aux deux conditions suivantes: (1) ce dispositif ne peut pas causer d'interférence, et (2) ce dispositif doit accepter toute interférence, y compris les interférences pouvant causer un fonctionnement indésirable du dispositif. L'appareil a été évalué pour répondre aux exigences générales d'exposition aux RF. La distance entre l'utilisateur et les produits devrait être au moins 20 cm.

Models: UM01, UM01-FU, UM01 Motion Sensor Detector, UM01, Motion Sensor Detector, Sensor Detector

File Info : application/pdf, 3 Pages, 1.40MB

PDF preview unavailable. Download the PDF instead.

GetApplicationAttachment.html?id=7483746

References

Adobe PDF library 15.00 Adobe Illustrator CC 2017 (Windows)