Polar ESS ALPS Series Installation Manual

Part of the GiveEnergy ${ }^{\circ}$

Models: ALPS HY3.6-CL | ALPS HY6.0-CL

Version: V2.1 | Date: 12/06/24

1 Product Description

The Polar ESS ALPS series models are designed for energy storage, utilizing energy from solar PV or the grid. They can also be used to feed energy back into the grid for profit or serve as a backup power source during grid outages.

This manual provides essential product information and installation instructions for ALPS users. For further details, please visit polar-ess.co.uk or contact customer service. The latest release version supersedes any previous versions.

The Polar ESS ALPS inverter package includes:

1.2 Safety Declarations

CAUTION

The ALPS inverter is designed and tested according to international safety regulations. Always refer to and strictly follow the safety instructions in this manual before and during operation, installation, and use. Installation must be performed by qualified personnel in compliance with local regulations. Non-compliance may result in injury, death, or damage to the inverter and other property.

1.3 Safety Instructions

DANGER: High Voltages and Large Currents

WARNING: Avoid Misoperation and Inappropriate Usage

NOTE

2 Installation

2.1 Packaging List

The packaging includes:

2.2 Installation Instructions

2.2.1 Installation Position

Observe minimum clearances for heat dissipation:

2.2.2 Step-by-Step Installation

  1. Mark the positions for the wall mounting bracket holes on the wall. The minimum wall thickness required is 80 mm.
  2. Drill 3 holes at the marked positions, at least 55 mm deep. Secure the mounting bracket to the wall using 3 wall plugs and suitable fixings (e.g., M8 coach screws/bolts).
  3. Install the bracket using 2 fixings.
  4. Mount the inverter onto the bracket and secure it with one screw in the bottom bracket.

2.3 Connection

2.3.1 System Wiring Diagram

An external AC breaker is required for grid connection. The inverter must be connected to its own bidirectional TYPE A 30mA RCD device with over-current protection.

Inverter ModelAC Breaker Specification
ALPS HY3.6-GLC20
ALPS HY6.0-GLC32

If the EPS port load is 6kW-9kW, the switch should be 230VAC/63A.

Inverter overview of terminals:

2.3.2 PE Connection

The main earth connection should be connected to the grid-tied terminal block. The earth bond point at the bottom of the inverter is for connection to the battery and additional earth bonding.

2.3.3 Grid and EPS Connection

2.3.3.1 On/Off-Grid Load Connection

Distribute loads rationally between the AC grid side and EPS side according to the inverter's rated power. Maximum pass-through current is 39A.

2.3.3.2 AC Connection

Suggested cable requirement for AC wires:

  1. Strip 6-8mm of insulation from the AC/EPS wire.
  2. Open the lower cover to access the wiring bay and remove the dust plug from the AC input/output port.
  3. Cut a hole in the wire entry and pass the AC/EPS wire through the AC input/output holes. Insert the wire into the connecting port of the AC terminal block.
  4. Tighten the screws on the AC connection terminal block to ensure a stable connection.
2.3.3.3 CT/Meter Connection

Install a CT at the total output port, close to the supplier's meter, for accurate power measurement. The unit ships with a standard CT.

Port1234
CT/MeterCT+CT-METER485+METER485-

CT Installation Diagram: The arrow on the CT must point towards the inverter.

Meter Outlet Pin Definition: If using meters, connect the communication cable to the METER port. Recommended: shielded cable for meter communication. Refer to wiring examples for correct installation.

2.3.4 Battery Comms Connection

Connect the battery communication cable to the inverter's RJ45 socket for normal system operation. The port supports CAN and 485 communication. Pin definitions are provided for creating custom cables.

The connection uses the TS568B standard.

2.3.5 PV Connection

WARNING: Verify the minimum ambient temperature. Solar panel Voc increases as temperature decreases. Ensure the maximum solar panel string voltage at the lowest temperature does not exceed the maximum inverter input voltage.

Recommended PV cable.

The inverter has two independent MPPTs, each with one string input. If only one string is used with high current, it can be connected to both MPPT interfaces. Connecting two PV channels limits the total solar input power to 9KW, with a maximum of 4.5KW per MPPT. Connecting a single PV channel limits the maximum MPPT input power to 6KW.

Follow the wiring annotations under the connector block.

2.3.6 Battery Connection

  1. Open the lower cover to access the wiring bay and remove the dust plug on the battery input port.
  2. Strip 6-8mm of insulation from the battery positive and negative wires and crimp OT terminals (QT25-8) onto the wires.
  3. Pass the battery wires through the input hole and fix the OT terminals to the corresponding terminal blocks.
  4. Tighten the screws on the battery connection terminal block.

2.3.7 Connecting Communication Cables between Polar Inverter and Associated Battery Packs

Connect the communication cables between the Polar Inverter (CAN/RS485 port) and the Polar Battery using the RS485 (in/out) ports. All power connections between batteries must be wired according to the diagram.

2.3.8 DRMS Function

For use in Australia, the DRMS device may need to be connected to the inverter's DRMS terminal. The RJ45 terminal pin definitions for DRMS are provided.

PinPin1 orange whitePin2 orangePin3 green whitePin4 bluePin5 blue whitePin6 greenPin7 brown whitePin8 brown
DRMSDRM1/5DRM2/6DRM3/7DRM4/8Ref/GenGND//

Inverter Demand Response Modes:

MODERJ45 pins to be connectedDemand
DRM0Connect Pin5 and Pin6Stop
DRM1Connect Pin1 and Pin5Disallow charge
DRM2Connect Pin2 and Pin5Charge power should be less than 50% of the rated power
DRM3Connect Pin3 and Pin5Charge power should be less than 75% of the rated power
DRM4Connect Pin4 and Pin5Charge power should be less than 100% of the rated power
DRM5Connect Pin1 and Pin5Disallow discharge
DRM6Connect Pin2 and Pin5Discharge power should be less than 50% of the rated power
DRM7Connect Pin3 and Pin5Discharge power should be less than 75% of the rated power
DRM8Connect Pin4 and Pin5Discharge power should be less than 100% of the rated power

DRM1-4 limit charging, DRM5-8 limit discharging. These modes do not limit charge power.

2.3.9 Data Collector Connection

2.3.9.1 WiFi/4G Dongle Connection

Use the WiFi/4G dongle for remote monitoring via the Polar ESS mobile app. Download the app and register an account. For 4G dongles, ensure a SIM card is inserted.

3 Description of LCD Display

The inverter features an LED screen, an LED indicator, and four function buttons for information display and system settings.

DESCRIPTIONSCLARIFICATION
ButtonsFor operating the display and setting up the system
Status indicator (Green light always on)Normal operation
Status indicator (Red light always on)Fault condition
Status indicator (Green light flashing)System is starting up or shutting down
Status indicator (Red light flashing)Warning or error
Status indicator (Red and green lights flash alternatively)Communication error

The display shows grid, PV, battery, and load power, energy flow, current operating mode, and basic inverter status.

3.1 Basic Information View

Press any button to wake the screen. The main interface displays real-time system information. Press the OK button to enter the system menu. Use the down button to navigate through system information, operating states, and power generation history.

3.2 Parameterisation

From the system menu, navigate to the parameter setting screen. Key settings include:

Control Setting

Basic Setting

HMI Setting

Remote Control Setting

Protection Setting

DC-DC Setting

DC-DC Setting2

Allows setting up to three time periods for charging priority mode and the corresponding cut-off SOC values.

4 Mode Setting

The ALPS inverter can be configured for different operating modes to suit various application scenarios. Settings are typically made via the WiFi interface.

4.1 Self-generation and Self-Use Mode (Default)

In this mode, the priority for load response is Photovoltaic > Battery > Grid. Photovoltaic energy flow priority is Load > Battery > Grid. This is the factory default mode and is active when no other mode is selected.

4.2 Charge Priority Mode

Photovoltaic energy preferentially charges the battery until the set SOC is reached. Excess energy is then supplied to the load or fed to the grid. The battery does not discharge actively in this mode. This mode is beneficial for areas with frequent power outages, high peak electricity prices, or significant night-time energy demand.

4.3 Discharge Priority Mode

To activate this mode, enable Battery Discharge, set the desired working period, and the SOC at which to stop discharging.

4.4 AC Charge Function

When enabled, the inverter uses grid energy to charge the battery, allowing for energy arbitrage or emergency backup.

4.5 Export Limit Function

This function limits the maximum power fed back to the grid to a user-defined value, suitable for regions with grid connection power restrictions.

5 Troubleshooting and Maintenance

5.1 Troubleshooting based on LCD Displays

Refer to the following table for fault codes and troubleshooting steps. Contact Polar ESS support if issues persist.

FAULT CODEDESCRIPTIONTROUBLESHOOTING
DC highHigh DC component of output currentRestart the inverter; contact Polar ESS for technical support.
PV isolation lowLow insulation resistance of photovoltaic panelsCheck PV panel to inverter connection. Ensure inverter earth wire is properly connected.
NTC openNTC open circuit faultSwitch off the inverter and contact Polar ESS support.
Bus voltage highHigh bus voltageCheck PV panel input voltage against inverter's rated input voltage range. Restart the inverter.
PV voltage highHigh PV voltageCheck PV panel input voltage against inverter's rated input voltage range.
Boost over temperatureBoost overtemperatureEnsure ambient temperature is within the inverter's operating specifications.
BuckBoost over temperatureBuckboost overtemperatureEnsure ambient temperature is within the inverter's operating specifications.
INV over temperatureInverter overheatingEnsure ambient temperature is within the inverter's operating specifications.
EPS output short faultOff-grid output short circuitCheck EPS port loads for damage or shorts. Inspect EPS port for damage or foreign objects.
Init model faultInitialisation mode exceptionCheck the inverter model number.
Bus Voltage UnbalancePositive and negative bus voltage imbalanceRestart the inverter; contact Polar ESS for technical support.
FW UnmatchM3 and DSP version mismatchCheck PV panel to inverter connection. Ensure inverter earth wire is properly connected.
PV1 Short FaultPV1 short circuit faultSwitch off the inverter and contact Polar ESS customer support.
PV2 Short FaultPV2 short circuit faultCheck PV panel input voltage against inverter's rated input voltage range. Restart the inverter.
NE Detect FaultZero ground fault detectionCheck PV panel input voltage against inverter's rated input voltage range.
Exter Device FaultyFailure of external equipmentEnsure ambient temperature is within the inverter's operating specifications.
Internal Com Fault1Internal communication failure 1Ensure ambient temperature is within the inverter's operating specifications.
Internal Com Fault2Internal communication failure 2Ensure ambient temperature is within the inverter's operating specifications.
GFCI HighHigh leakage currentCheck EPS port loads for damage or shorts. Inspect EPS port for damage or foreign objects.
Internal Com Fault3Internal communication failure 3Check the inverter model number.
Internal Over TempInner ring temperature too highEnsure ambient temperature is within the inverter's operating specifications.
Fan FaultFan failureCheck for clogged fans; restart the inverter; replace the fan if necessary.
Hardware UnmatchHardware version mismatchRestart the inverter.
Meter Comm LossLoss of meter communicationVerify meter functionality and check meter communication cable connection.

5.2 Fan Maintenance

Regular fan maintenance (cleaning) is recommended every 6 months, or more frequently depending on the environment. Follow these steps:

  1. Turn off the system and wait at least 5 minutes. Isolate the system.
  2. Remove the fixing screws securing the fan assembly.
  3. Carefully remove the fan assembly, noting the internal power cable connection.
  4. Clean dust and debris from the fan and check the cable for damage.
  5. If the fan is damaged, replace it with a new one and reinstall following the above steps.

6 Datasheet

ModelALPS HY3.6-GLALPS HY6.0-GL
Max. DC Input Power (W)5400 W9000 W
Start-up Voltage98 V
Max. PV Voltage550 V
MPPT Range90V-500V
Nominal Voltage360 V
Max. Short Current23A/23A
Max. Input Current16A/16A
MPPT Tracker/No. of Strings per MMP Tracker2 / 1
Battery
Battery TypeLi-ion
Battery Voltage Range42-60 V
Nominal Voltage48 V
Charge/Discharge Current80A/80A125A/125A
Max. Battery Charge/Discharge Power (W)3600W/3600W6000W/6000W
Communication InterfaceCAN
Output Data
Nominal AC Output Power3600 W6000 W
Max. Apparent Power Output to Utility Grid (VA)3600VA6000VA
Max. Output Current16VAC26VAC
Nominal Voltage/Range230VAC; 184 - 260VAC
Frequency Range50 ± 5 Hz
Power Factor (Full Load)+0.99
Power Factor Range0.85 lagging - 0.85 leading
THDI (Nominal Power)<3 %
Backup
Nominal EPS Output Power3600 W6000 W
EPS Peak Power (10s)5400VA9000VA
Nominal Voltage238VAC
Max. Output Current23A (peak)39A (peak)
Nominal Frequency50 Hz
Automatic Switch Time<10 ms
THDv (Linear Load)<3 %
General
Battery Charge/Discharge Efficiency94%/94%
PV Max. Efficiency97.60%
Dimensions (W x D x H)420 x 195 x 475 (mm), 460W (mm) inc. PV Isolator
IP GradeIP20
Warranty5 years
Models: ALPS HY3.6-GL, ALPS HY6.0-GL, ALPS Series Hybrid Inverter 6KW, ALPS Series, Hybrid Inverter 6KW, Inverter 6KW, 6KW

File Info : application/pdf, 18 Pages, 2.18MB

PDF preview unavailable. Download the PDF instead.

polar-ess-hybrid-inverter---installation-manual

References

Adobe PDF Library 17.0 Adobe InDesign 19.5 (Windows)