Enerlites MPW-L Occupancy Sensor Installation Guide

Model: MPW-L

Brand: Enerlites

Product Overview

The Enerlites MPW-L is a 150° Passive Infrared (PIR) Low Voltage Occupancy Sensor designed to automate lighting control based on occupancy and ambient light levels. Its features include automatic light activation upon detecting motion and deactivation after a set period of inactivity. The integrated light level sensor prevents lights from turning on when sufficient ambient light is present.

This sensor operates on 24V DC, typically supplied by the Enerlites MPP-24 Power Pack (sold separately).

Coverage

The MPW-L offers a wide 150° coverage pattern, providing approximately 900 square feet of detection area when mounted at a height of 10 feet. Coverage may be reduced in environments with obstacles or lower activity levels.

Specifications

SpecificationValue
Voltage22-26 VDC
Current Consumption40mA
Power SupplyMPP-24 Power Pack (Not Included)
Operating Temperature32° to 131°F (0° to 55°C)
Adjustable Time Delay30 Seconds to 30 Minutes
Adjustable Light Level100 Lux - daylight
PIR Adjustment25% to 100%
PIR Coverage900 sq ft

Installation Instructions

⚠️ WARNING: Ensure power is completely ⚡ OFF at the circuit breaker before beginning installation. Read and understand all instructions. Installation should comply with the National Electric Code and local regulations. It is recommended that a qualified electrician performs this installation. Use copper wire only.

Wiring and Mounting Steps:

  1. Turn OFF power at the circuit breaker.
  2. Wire the device according to the diagram: Connect the Black lead to 'Common', the Red lead to '+24V', and the Blue lead to 'Control Out'.
    Wiring Diagram Description: A diagram shows the connections for the MPW-L sensor to the MPP-24 Power Pack. The Black wire connects to 'Common', the Red wire to '+24V', and the Blue wire to 'Control Out'.
  3. Mount the device to walls or ceilings.
  4. Gently position wires into the wall or octagon box.
  5. Attach the sensor switch to the box and secure it to the wall/ceiling with two screws.
  6. Attach the sensor switch to the mounting yoke, passing wires through the central hole, and fix the yoke to the wall/ceiling.
  7. Restore power at the circuit breaker. Wait approximately one minute for the device to initialize.
  8. Remove the small cover plate on the sensor.
  9. Locate the adjustment knobs on the control panel to perform test and adjustment procedures. (Refer to Settings Adjustment section).
  10. Replace the small cover plate after completing testing and adjustments.
?️ Figure 1: PIR Coverage Diagram
Diagram showing the 150° Passive Infrared (PIR) coverage pattern of the MPW-L sensor. The coverage extends outwards, with a note indicating PIR coverage up to 50ft. A scale shows distances from 0 to 50 ft.
?️ Figure 2: Wiring Diagram
Wiring diagram for the MPW-L sensor. It illustrates connections to the MPP-24 Power Pack. The Black wire connects to 'Common', the Red wire to '+24V', and the Blue wire to 'Control Out'.
?️ Figure 3: Control Panel and Adjustments
Illustration of the MPW-L sensor's control panel. It shows the PIR Lens, Control Panel Cover, Mounting Yoke, Detection LEDs (labeled Red=PIR), and three adjustment knobs: TIME, RANGE, and LIGHT.

Settings Adjustment

The sensor features adjustable settings accessible via control knobs on the panel.

Adjustment Dials Description: The TIME adjustment dial allows setting the delay from 5 seconds to 30 minutes. The RANGE dial likely adjusts sensitivity or coverage area. The LIGHT dial adjusts the ambient light threshold for activation.

Operation

The sensor operates exclusively in Occupancy Mode.

Automatic Load Control:

Troubleshooting

⚠️ WARNING: Always turn OFF power at the circuit breaker before performing any troubleshooting or installation steps.

Issue: Lights do not turn on with occupancy.

Condition: PIR Activity LED does not flash.

Condition: PIR Activity LED flashes.

Issue: Lights do not turn off automatically.

Warranty Information

This device is warranted by Enerlites, Inc. to be free of material and workmanship defects for a period of 2 years from the original date of purchase. A valid original receipt or proof of purchase from an authorized retailer is required for all warranty claims.

This warranty is non-transferable and does not cover damages resulting from normal wear and tear, misuse, abuse, neglect, alteration, modification, or improper installation. Enerlites, Inc. shall not be liable for any indirect, incidental, or consequential damages. The sole and exclusive remedy for breach of warranty is limited to repair, replacement, or refund of the product.

Certification: ✅ UL LISTED

© 2019 Enerlites Inc. CA, U.S.A.

Website: www.enerlites.com

Document Revision: REV 20230802

Models: MPW-L, MPW-L 150 Degree Low Volt PIR Wall Mount Sensor, 150 Degree Low Volt PIR Wall Mount Sensor, Low Volt PIR Wall Mount Sensor, Volt PIR Wall Mount Sensor, PIR Wall Mount Sensor, Wall Mount Sensor, Mount Sensor, Sensor

File Info : application/pdf, 2 Pages, 1.36MB

PDF preview unavailable. Download the PDF instead.

IM 20230802 MPW-L

References

Acrobat Distiller 4.0 for Macintosh

Related Documents

Preview Enerlites MPC-50VD 360° Occupancy Sensor Installation Instructions
Comprehensive installation guide for the Enerlites MPC-50VD 360° Passive Infrared Line Voltage Occupancy Sensor with 0-10V Dimming. Covers wiring, sensor adjustments, mounting options, testing procedures, troubleshooting, and warranty information.
Preview Enerlites LVD-102 Low Voltage Dual Dimmer Switch Installation Instructions
Installation instructions for the Enerlites LVD-102 Low Voltage Dual Dimmer Switch, including specifications, LED indicators, wiring diagrams, troubleshooting, and warranty information.
Preview Enerlites LVD-101 Low Voltage Dimmer Switch Installation Instructions
Installation guide for the Enerlites LVD-101 Low Voltage Dimmer Switch, including wiring diagrams, specifications, and troubleshooting tips for various configurations with MPP-24, MPC-50L, and MPL-010 sensors.
Preview Enerlites LVS Series Low Voltage Switch Installation Guide
Comprehensive installation instructions and wiring diagrams for Enerlites LVS-101, LVS-102, LVS-103, and LVS-104 low voltage switches, including specifications, troubleshooting, and warranty information.
Preview Enerlites HMOS-J Occupancy/Vacancy Sensor Switch Installation Instructions
Detailed installation instructions for the Enerlites HMOS-J 2-in-1 Occupancy and Vacancy Sensor Switch. Learn about coverage, wiring, operation modes, troubleshooting, and specifications.
Preview Enerlites DWOS-3R Occupancy/Vacancy Sensor Switch Installation Instructions
Comprehensive installation guide for the Enerlites DWOS-3R 2-in-1 Occupancy/Vacancy Sensor Switch. Learn about wiring, adjustments, operation modes, and troubleshooting for single pole and 3-way installations.
Preview Enerlites Model 67300 & 66500 NEMA Receptacle Installation Guide
Installation instructions and warranty details for Enerlites NEMA 10-30R (Model 67300) and NEMA 14-50R (Model 66500) power receptacles. Includes wiring directions and safety warnings.
Preview Enerlites 61501-TRSS/62001-TRSS Installation Instructions: Surge Protector Receptacle
Detailed installation guide for Enerlites 61501-TRSS and 62001-TRSS 15A/20A Decorator Tamper-Resistant Receptacles with Surge Protection and Grounding Indicator. Learn about features, specifications, wiring, indicator lights, and warranty.