Installation Guide for Danfoss models including: AK-CC55, 84B3240, 84B3241, 84B3247, 84B3248, 84B3249, 84B3250, 84B3251, 84B3252, 84B3253, AK-CC55 Case Room Controller EEV Single Coil, AK-CC55, Case Room Controller EEV Single Coil, Room Controller EEV Single Coil, Controller EEV Single Coil, EEV Single Coil, Single Coil

Case/room controller (EEV), type AK-CC55 Single Coil

AK-CC 55 Single Coil Installation Guide

Technical support for supermarket refrigeration system technicians | Danfoss


File Info : application/pdf, 10 Pages, 834.07KB

PDF preview unavailable. Download the PDF instead.

AN294432763974en-000501
Installation Guide
Case/room controller (EEV) Type AK-CC55 Single Coil
Identification

Dimensions

084B4082

Principle

084B4083

113

084R8053 AN294432763974en-000501

Danfoss 84B3240

180

60

Danfoss 84B3241

© Danfoss | Climate Solutions | 2021.12

AN294432763974en-000501 | 1

Danfoss 84B8271

The controller is provided with labels from the factory indicating a generic application. When selecting the required application, specific labels are provided so that you can mount the relevant one.

Danfoss 84B3247

0 ­ 10 V/ PWM

1.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

S2

S3

S4

S5 S6 DI1/ DI2 AO1

AI7

1
83 84 85 B- A+ MODBUS

115 ­ 230 V AC
LN 123

AKV 789

Alarm 10 11 12

Comp. 13 14

Defrost 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

0 ­ 10 V/ PWM

2.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

S2

S3

S4

S5 S6 DI1/ DI2 AO1

AI7

2
83 84 85 B- A+ MODBUS

115 ­ 230 V AC
LN 123

AKV 789

Railheat 10 11 12

Comp. 13 14

Defrost 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

0 ­ 10 V/ PWM

3.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

S2

S3

S4

S5 S6 DI1/ DI2 AO1

AI7

3
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

Alarm 10 11 12

Comp. 13 14

Defrost 15 16 17

Railheat 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

Danfoss 84B3248

Danfoss 84B3249

2 | AN294432763974en-000501

© Danfoss | Climate Solutions | 2021.12

Danfoss 84B3250

0 ­ 10 V/ PWM

4.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71
S2 S3 S4 S5 S6 DI1/ DI2 AO1 AI7

4
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

Alarm 10 11 12

Railheat Defrost 13 14 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

0 ­ 10 V/ PWM

5.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71
S2 S3 S4 S5 S6 DI1/ DI2 AO1 AI7

5
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

Suction 10 11 12

Drain 13 14

HG 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

0 ­ 10 V/ PWM

6.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71
S2 S3 S4 S5 S3B DI1/ DI2 AO1 AI7

6
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

Alarm 10 11 12

Railheat Defrost 13 14 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

Danfoss 84B3251

Danfoss 84B3252

© Danfoss | Climate Solutions | 2021.12

AN294432763974en-000501 | 3

Danfoss 84B3253

0 ­ 10 V/ PWM

.

P

13 2

40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

5V s Pe

S2

S3

S4

S5 S3B S5B DI2 AO1

7
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

Alarm 10 11 12

Defrost B Defrost A 13 14 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

B

A

0 ­ 10 V/ PWM

8.

P

13 2

U
RH 0 10

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

S2

S3

S4

S5 S6 DI1/ DI2 AO1

AI7

8
83 84 85 B- A+ MODBUS

115 ­ 230 V AC
LN 123

AKV 789

Alarm 10 11 12

Humidity Defrost 13 14 15 16 17

Light 18 19 20

Fan 21 22

DI3 115 ­ 230 V AC
30 31

0 ­ 10 V/ PWM

9.

P

13 2

40 41 42 5V s
Pe

43 44 45 46 47 48 49 50 51 52 53 54 60 61 70 71

S2

S3

S4

S5 S6 DI1/ DI2 AO1

AI7

9
83 84 85 B- A+ MODBUS

115 ­ 230 V AC LN 123

AKV 789

DO2 10 11 12

DO3

DO4

DO5

DO6

13 14 15 16 17 18 19 20 21 22

Custom set-up

DI3 115 ­ 230 V AC
30 31

Danfoss 84B3254

Danfoss 84B3266

4 | AN294432763974en-000501

© Danfoss | Climate Solutions | 2021.12

Data communication

Important

AKV info AKS 32R info

230 V AC (115 AC)
AKS 32R out

Black Brown Blue

Coordinated defrost via cable connections
External display AK-UI55
© Danfoss | Climate Solutions | 2021.12

Danfoss 84B8239

It is important that the installation of the data communication cable is performed correctly with sufficient distance to high voltage cables.
230 V or 115 V AC coil Max. 0.5 A
The signal from one pressure transmitter can be received by up to 10 controllers. There must not be a significant pressure drop from the pressure transmitter's position in the suction line to the individual evaporators.
Max. 10 The following controllers can be connected in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550 and AK-CC55. Refrigeration is resumed at the same time when all controllers have terminated defrost.
Display 084B4075 / 084B4076 / 084B4077 Cable 3 m: 084B4078 Cable 6 m: 084B4079 (L: Max. 100 m)
AN294432763974en-000501 | 5

Technical data

Electrical specifications

Electrical data Supply voltage AC [V] Power consumption [VA] Power ON indicator Electrical cable dimensioning [mm]

Value 115 V / 230 V, 50/60 Hz 5 VA Green LED Max. 1.5 mm multi-core cable

Sensor and measuring data Sensor and measuring data Sensor S2, S6 Sensor S3, S4, S5
Temperature measuring accuracy
Pt1000 sensor specification Pe measuring RH measuring

Value
Pt 1000 AKS11
Pt 1000 AKS11 PTC 1000 EKS111 NTC5K EKS211 NTC10K EKS221 sensor
(All 3 must be of the same type)
Pt1000: -60 ­ 120 °C. ±0.5 K PTC1000: -60 ­ 80 °C. ±0.5 K NTC5K: -40 ­ 80 °C. ±1.0 K NTC10K: -40 ­ 120 °C. ±1.0 K
±0.3 K at 0 °C ±0.005 K per degree
AKS 32R Ratiometric pressure transmitter: 10 ­ 90%
0 ­ 10 V Ri > 10K ohm Accuracy +/- 0,3% FS

Function data
Function data Display External display, AK-CC55 Single Coil UI External display, AK-CC55 Single Coil External display connection Max. display cable length [m] Data communication built-in Data communication option
Clock battery backup power reserve Mounting

Value LED 3 digit 1 external display 2 external displays RJ12 100 m MODBUS AK-OB55 Lon RS485 module (Not AK-CC55 Compact) 4 days DIN rail

Environmental conditions

Environmental conditions

Value

Ambient temperature range, operating [°C] 0 ­ 55 °C

Ambient temperature range, transport [°C] -40 ­ 70 °C

Enclosure rating IP

IP20

Relative humidity range [%]

20 ­ 80%, non-condensing

Shocks/Vibrations

No shocks and vibrations allowed

Input and output relay specifications

Input and Input/ output relay output specifications
Digital input DI1 DI2

Digital input
Solid state output

DI3
DO1 (for AKV coil)

Relays

DO2

DO3

DO4

DO5

DO6

Analogue

AO1

output/ PWM

Description
Signal from dry contact functions Requirements to contacts: Gold plating Cable length must be max. 15 m Use auxiliary relays when the cable is longer Open loop: 12 V (SELV) Contact 3.5 mA
115 V / 230 V AC
115V / 230 V AC Max. 0.5 A Max. 1 x 20 W AKV for 115 V AC 2 x 20 W AKV for 230 V AC Note: 2 EC coils are not supported.
115 V / 230 V AC Load max.: CE. 8 (6)A UL. 8A res. 3FLA 18LRA Load min.: 1VA Inrush: DO5 DO6 TV-5 80A
0 / 10 V Pulse Width Modulated (PWM) max. 15 mA. 0 ­ 10 V variable, max. 2 mA

NOTE: · DO2 to DO6 are 16 A relays. · Max. load must be observed. · DO5 / DO6 is recommended for load with high inrush current e.g. EC Fan
and LED light. · All relays are sealed for use with flammable refrigerant like Propane
R290. · Compliance with EN 60 335-2-89: 2010 Annex BB.

6 | AN294432763974en-000501

© Danfoss | Climate Solutions | 2021.12

Electric noise Cables for sensors, low voltage DI inputs and data communication must be kept separate from other electric cables: - Use separate cable trays - Keep a distance between cables of at least 10 cm - Long cables at the low voltage DI input should be avoided
Installation considerations Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown.

Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer's responsibility to check the installation thoroughly, and to fit the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.

Replacing AK-CC 550A with AK-CC55 Be aware when exchanging an AK-CC 550A controller with a new AK-CC55 controller - new wiring principles!

AK-CC 550A

AK-CC55

· Pressure sensor has new connection ­ signal and ground are switched

· SPDT relays have a new wiring scheme ­ NO and NC terminals are switched (e.g. defrost heater on when it should be off )

C NC NO

· Modbus has new connection scheme (A,B and screen)

C NO NC

· New AK-UI55 displays and cables with 6 wires vs. 4 wires for EKA 16x
AK-CC55 does not support two EEC coils connected to one AKV output. Pressure transmitter can be shared between AK-CC 550 and AK-CC55. DI2 defrost coordination can be wired between AK-CC 550 and AK-CC55.
© Danfoss | Climate Solutions | 2021.12

AN294432763974en-000501 | 7

Operation with setting display
Display AK-UI55 Set The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.

Lights up in event of: Energy optimization Cooling Defrosting Fan operation

Lights in event of alarm -- press on alarm button -- alarm relay is reset -- alarm code displayed -- e.g. "A1"
Alarm codes are shown on page 18.
Long press (3 seconds) gives access to the information menu "InF". Up arrow / Down arrow / Arrow to left: Navigation in the menu and setting of values.
Long press (3 seconds) will start a defrost, "-d-" is shown in the display. Ongoing defrosting can be stopped by a long press. SET: Long press (3 seconds) gives access to the "SEt" menu. If the operation is locked with a password, "PS" is shown. Enter the code.
Shows the setting for a chosen parameter / saves a changed setting. Short press gives access to entering of the thermostat's cut-out limit.

The display can give the following messages:

-d- Defrost is in progress

Err The temperature cannot be displayed due to a sensor error

Err1 The display cannot load data from the controller. Disconnect and then reconnect the display

Err2 Lost display communication

ALA The alarm button is activated. The first alarm code is then shown

- - - At top position of the menu or when max. value has been reached, the three dashes are shown in the top of the display

- - - At bottom position of menu or when min. value has been reached, the three dashes are shown in the bottom of the display

Loc The configuration is locked. Unlock by pressing (for 3 seconds) on the `up arrow' and `down arrow' simultaneously

UnL The configuration is unlocked

- - - The parameter has reached min. or max. limit

PS

A password is required for access to the menu

Fan Appliance cleaning has been initiated. The fans are running

OFF Appliance cleaning is activated and the appliance can now be cleaned

OFF The main switch is set to Off

SEr The main switch is set to service / manual operation

CO Flashes: Will display in event of a refrigerant leakage alarm, but only if the refrigerant is set up for CO

Factory setting If you need to return to the factory-set values, do the following: - Cut off the supply voltage to the controller - Keep up "" and down "" arrow buttons depressed at the same time as you reconnect the supply voltage - When FAc is shown in the display, select "yes".

8 | AN294432763974en-000501

© Danfoss | Climate Solutions | 2021.12

84B8279

Read input status

Parameter grouping at display operation

<

<

SET Set (PS) cFg SET
r-A-c-d-n-F-t-h-o-p-q-u-< (Return)

Menu groups See also the following pages.

SET button, 3 s: Configuration settings
PS: Password (if any)
r12 Main switch o61 Application o03 MODBUS address r89 Food type r00 Cut-out temperature r15 Ther. sensor S4 % r61 Ther. sensor S4% night A36 Alarm sensor S4% o17 Display air S4% o30 Refrigerant type o20 Min. transmitter range o21 Max. transmitter range d01 Defrost method d03 Defrost interval d10 Defrost sensor d04 Max. defrost time d02 Defrost stop temperature < (Return)

Danfoss 84B8272

<

Info button, 3 s: Information for service use Inf
StA SET See control state message
App SET See selected application
in SET

out SET buS SET SoF SET < (Return)

MODBUS quality See SW version

Output status When you want info on a relay output, the dot will show whether the relay is activated (energized) for, e.g.: do4 = not activated do.4 = activated

do1 Akv do2 do3 do4 do5 do6 Ao1 (Return)

****** Read output status

di1/ AI7

**

di2 **

di3 **

AI1 PE

AI2 S2

AI3 S3

AI4 S4

AI5 S5

AI6 ** <

(Return)

*) The output's function. (Determined at configuration). The DOs and AOs can also be forced controlled from this menu, when r12 Main switch has been set in position "service". Forced control of a function can also be performed in codes q11 to q27.

**) The input's function. (Determined at configuration).

Danfoss

Get a good start With the following procedure you can start regulation very quickly: 1. Open parameter r12 and stop the regulation (in a new and
not previously set unit, r12 will already be set to 0 which means stopped regulation) 2. Select application based on the wiring diagrams on pages 2-4 3. Open parameter o61 and set the application number 4. For network. Set the address in o03 5. Then select a set of presets from the "Food type" help table 6. Open parameter r89 and set the number for the array of presettings. The few selected settings will now be transferred to the menu 7. Set the desired cut-out temperature r00 8. Set the weighted thermostat air temperature between S4 and S3 sensor r15 9. Set the weighted thermostat air temperature between S4 and S3 during night operation r61 10. Set the weighted alarm air temperature between S4 and S3 A36 11. Set the weighted display readout between S4 and S3 o17 12. Select refrigerant via parameter o30 13. Set the pressure transmitter min. and max. range via parameter o20 and o21 14. Set the desired defrost method in d01 15. Set the interval time between defrost starts in d03 16. Set the desired defrost sensor in d10

17. Set the maximum defrost time in d04 18. Set the defrost stop temperature in d02 19. Open parameter r12 and start the regulation 20. Go through the parameter list and change the factory values
where needed. 21. Get the controller up and running on network:
· MODBUS: Activate scan function in system unit · If another data communication card is used in the controller:
- Lon RS485: Activate the function o04 - Ethernet: Use the MAC address

Food type

Setting of presettings (r89). After

1

2

3

4

5

setting 1-5,

setting is returned to 0.

Vege-

Meat/ Frozen Ice

Food type =

tables Milk fish food cream

Temperature (r00)

8 °C 0 °C -2 °C -20 °C -24 °C

Max. temp. setting (r02)

10 °C 4 °C 2 °C -16 °C -20 °C

Min. temp. setting (r03)

4 °C -4 °C -6 °C -24 °C -28 °C

Upper alarm limit (A13)

14 °C 8 °C 8 °C -15 °C -15 °C

Lower alarm limit (A14)

0 °C -5 °C -5 °C -30 °C -30 °C

Upper alarm limit for S6 (A22)

14 °C 8 °C 8 °C -15 °C -15 °C

Lower alarm limit for S6 (A23)

0 °C -5 °C -5 °C -30 °C -30 °C

© Danfoss | Climate Solutions | 2021.12

AN294432763974en-000501 | 9

Fault message

In an error situation the alarm LED on the front will be on and the alarm relay will be activated (depending on priority). If you push the alarm button for 3 seconds you can see the alarm report in the display. (Alarm priorities can be changed. See the User Guide.) Here are the messages that may appear:

Code Alarm text

Description

E01 Hardware failure

The controller has a hardware failure

E06 Clock lost time

Clock has lost valid time

E20 Pe Evap. pressure A - Sensor error Sensor signal is out of range. Please check the sensor for correct operation

E24 S2 Gas outlet A - Sensor error

Sensor signal is out of range. Please check the sensor for correct operation

E25 S3 Air ON evap. A - Sensor error Sensor signal is out of range. Please check the sensor for correct operation

E26 S4 Air OFF evap. A - Sensor error Sensor signal is out of range. Please check the sensor for correct operation

E27 S5 Evaporator A - Sensor error

Sensor signal is out of range. Please check the sensor for correct operation

E28 S6 product temp. A - Sensor error Sensor signal is out of range. Please check the sensor for correct operation

E34 S3 Air ON evap. B - Sensor error Sensor signal is out of range. Please check the sensor for correct operation

E37 S5 Evaporator B - Sensor error

Sensor signal is out of range. Please check the sensor for correct operation

E59 Humidity sensor - Sensor error

Sensor signal is out of range. Please check the sensor for correct operation

A01 High temperature alarm A

The alarm temperature has been above the max alarm limit for a longer time period than the set alarm delay.

A02 Low temperature alarm A

The alarm temperature has been below the min alarm limit for a longer time period than the set alarm delay.

A04 Door open alarm

The door has been open for a too long time

A05 Max defrost hold time exceeded The controller has been waiting longer time than permitted after a co-ordinated defrost.

A11 Refrigerant not selected

The refrigerant has not been selected hence control can not be initiated

A13 S6 high product temperature A The S6 Product temperature has been above the max alarm limit for a longer time period than the set alarm delay.

A14 S6 low product temperature A

The S6 Product temperature has been below the min alarm limit for a longer time period than the set alarm delay.

A15 DI alarm 1

Alarm signal from digital input signal

A16 DI alarm 2

Alarm signal from digital input signal

A45 Main switch set OFF

The controller manin switch has been set to either Stop or Manaual control. Alternatively a digital input set up for "main switch" function, has stopped control

A59 Case in cleaning mode

A case cleaning operation has been started on a case

A70 High temperature alarm B

The alarm temperature has been above the max alarm limit for a longer time period than the set alarm delay.

A71 Low temperature alarm B

The alarm temperature has been below the min alarm limit for a longer time period than the set alarm delay.

AA2 CO2 leak detected

CO2 is leaking from the refrigerantion system

AA3 Refrigerant leak detected

Refrigerant is leaking from the refrigeration system

a02 High humidity alarm

The humidity level is too high

a03 Low humidity alarm

The humidity level is too low

a04 Wrong IO configuration

Inputs and outputs have not been configured correctly

X02 Evaporator is icing up

The adaptive defrost function has detected heavy ice formation on evaporator.

X03 Flash gas detected

The adaptive defrost function has detected heavy flash gas in front of injection valve

Z01 Max defrost time exceeded A

The last defrost cycle has stopped on time instead of set temperature

A34 Fan alarm

Alarm from digital input monitoring function

A43 Valve driver alarm

Alarm from digital input monitoring function

Data communication: The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"

Additional information not relevant for safe installation and use can be found on Danfoss Store:

For more detailed information, please see the respective User Guide.

10 | AN294432763974en-000501

© Danfoss | Climate Solutions | 2021.12


Danfoss A/S GPL Ghostscript 9.55.0