Installation Guide for ASPEN models including: NTS03, NTS05, NTS08, NTS10, NTM03, NTM05, NTM08, NTM10, NTM15, NTL03, NTL05, NTL08, NTL10, NTL15, NTX03, NTX05, NTX08, NTX10, NTX15, NTX20, NCS03, NCS05, NCS08, NCS10, NCM03, NCM05, NCM08, NCM10, NCM15, NCL03, NCL05, NCL08, NCL10, NCL15, NCX03, NCX05, NCX08, NCX10, NCX15, N Series Electric Heat Kits, N Series, Electric Heat Kits, Heat Kits, Kits

INSTALLATION INSTRUCTIONS “N” Series Electric Heat Kits for Aspen Multi ...

1 II-002 | REV3 caused due to modification of the unit to operate with alternative power sources. NTS08 NTX03 NTX20 WARNING INSTALLATION INSTRUCTIONS


File Info : application/pdf, 4 Pages, 4.77MB

PDF preview unavailable. Download the PDF instead.

II-002-Heat-Kit-Multi-Position
INSTALLATION INSTRUCTIONS

"N" Series Electric Heat Kits for Aspen Multi-Position Air Handlers
WARNING Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
The unit is designed for operation with 208/240 V, single phase, 60 Hz power supply. Aspen will not be responsible for damages caused due to modification of the unit to operate with alternative power sources.

This product designed and manufactured to permit installation in accordance with local and national building codes. It is the installer's responsibility to ensure that product is installed in strict compliance with national and local codes. Manufacturer takes no responsibility for damage (personal, product or property) caused due to installations violating regulations. Installation of this unit shall be made in accordance with the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements.
Do not bypass safety devices.

Kit #

Description

NTS03 3KW Heat Strip w/ Terminal Block

NTS05 5KW Heat Strip w/ Terminal Block

NTS08 8KW Heat Strip w/ Terminal Block

NTS10 10KW Heat Strip w/ Terminal Block

NTM03 3KW Heat Strip w/ Terminal Block

NTM05 5KW Heat Strip w/ Terminal Block

NTM08 8KW Heat Strip w/ Terminal Block

NTM10 10KW Heat Strip w/ Terminal Block

NTM15 5KW Heat Strip w/ Terminal Block

NTL03 3KW Heat Strip w/ Terminal Block

NTL05 5KW Heat Strip w/ Terminal Block

NTL08 8KW Heat Strip w/ Terminal Block

NTL10 10KW Heat Strip w/ Terminal Block

NTL15 15KW Heat Strip w/ Terminal Block

NTX03 3KW Heat Strip w/ Terminal Block

NTX05 5KW Heat Strip w/ Terminal Block

NTX08 8KW Heat Strip w/ Terminal Block

NTX10 10KW Heat Strip w/ Terminal Block

NTX15 15KW Heat Strip w/ Terminal Block

NTX20 20KW Heat Strip w/ Terminal Block

Electric Heat Kits

Kit #

Description

NCS03 3KW Heat Strip w/ Circuit Breaker

NCS05 5KW Heat Strip w/ Circuit Breaker

NCS08 8KW Heat Strip w/ Circuit Breaker

NCS10 10KW Heat Strip w/ Circuit Breaker

NCM03 3KW Heat Strip w/ Circuit Breaker

NCM05 5KW Heat Strip w/ Circuit Breaker

NCM08 8KW Heat Strip w/ Circuit Breaker

NCM10 10KW Heat Strip w/ Circuit Breaker

NCM15 15KW Heat Strip w/ Circuit Breaker

NCL03 3KW Heat Strip w/ Circuit Breaker

NCL05 5KW Heat Strip w/ Circuit Breaker

NCL08 8KW Heat Strip w/ Circuit Breaker

NCL10 10KW Heat Strip w/ Circuit Breaker

NCL15 15KW Heat Strip w/ Circuit Breaker

NCX03 3KW Heat Strip w/ Circuit Breaker

NCX05 5KW Heat Strip w/ Circuit Breaker

NCX08 8KW Heat Strip w/ Circuit Breaker

NCX10 10KW Heat Strip w/ Circuit Breaker

NCX15 15KW Heat Strip w/ Circuit Breaker
INSTRUCTIONS:
NCX20 20KW Heat Strip w/ Circuit Breaker

Model used
LEM24A-E
LEM24F-J LEM36A-E
LEM36F-J LEM48A-E LEM60A-E
LEM48F-J LEM60F-J

W/ Terminal Block W/ Circuit Breaker

1

II-002 | REV3

1) Refer to Table 1 for appropriate kit
2) Check kit for physical damage, do not installed damaged kit
3) Remove the upper access panel from air handler
4) Unplug the Mate-n-Lock connector (FIG. 3) and Remove block-off plate or existing heater kit from air handler by removing 6 screws (See FIG. 2)
5) Slide the heater kit into the slot and secure element plate and to divider deck with the six previously removed screws
6) Insert power leads into the circuit breaker lugs or terminal block and tighten (FIG. 3)
7) Connect ground wire to ground lug (FIG. 3)
8) Plug in the Mate-N-Lock connector
9) Break out appropriate number of circuit breaker openings (if applicable) on the access panel of the air handler

FIG. 1
FIG. 2
(a) FIG. 3 (a) (b)

2

II-002 | REV3

10) Find the nameplate of the air handler unit and cross out the existing configuration and check the new heat kit model configuration that was installed. Nameplate shown below is a sample only.
11) Find the wiring diagram label that is included in the heat kit and stick it near the nameplate. Wiring Diagram shown below is a sample only.

3

II-002 | REV3

HOW TO REPLACE A DEFECTIVE THERMAL CUT OFF (TCO) OF A HEATER KIT:

Fig. 1 ­ TCO Image

Screw

TCO

TCO

Heater Kit

Black Wire

Fig. 2 ­ Heater Kit w/ TCO

1. Disconnect power, unscrew and open upper access panels to access the heater kit from the unit.
2. Locate the TCO(s) and disconnect the 2 black wires per TCO. Using a multimeter, measure continuity/ resistance of the fuse element by placing the test probes across the two terminals to verify if the fuse has failed. The quantity of TCO's depends on the heater kit model. The heater kit model shown in Figure 2 has two TCOs.
3. Unscrew the defective TCO from the base plate and using the same screw(s) mount the new one back in the same spot.
4. Re-connect all the wirings in the same terminals that you disconnect it from.
5. Mount the access panel back in the unit.

373 Atascocita Rd., Humble, TX 77396 · Phone: 281.441.6500 · Toll Free: 800.423.9007 ·Fax: 282.441.6510
www.aspenmfg.com
Subject to change without notice and without incurring obligation. © Copyright 2024 Aspen Manufacturing. All Rights Reserved