Thermal Fire Detectors

Exp lo sio n Pro o f Mo d els
ENG INEER AND ARC HITEC T SPEC IFIC ATIO NS

DETECT-A-FIRE MODELS

l Explosion Proof

l Self-Restoring Detector Element

l Models Available in both Normally Open and Normally Closed Contacts in a Wide Range of Temperature Settings

l Factory Set and Hermetically Sealed in Stainless Steel Shell

l

Listed and FM Approved as Fenwal

Model Series 27120 and 27121

Manufactured for Cerberus Pyrotronics

by Fenwal

Introd uc tion
Detect-A-Fire explosion proof detectors are of the rate compensated type and are designed for use with either standard Cerberus Pyrotronics systems or other commercially available fire alarm systems. The detector element in all models is self-restoring after operation. The DetectA-Fire explosion proof models can be supplied with normally closed contacts at 140, 160, 190, 210, 225, 275, 325, 360 or 450°F settings or with normally open contacts at 140, 160, 190, 210, 275, 325, 360, 450, 500, 600, or 725°F settings. These detectors are only explosion proof when mounted in an approved explosion proof junction box.
Princ ip le of Op era tion
Detect-A-Fire units have met with wide acceptance because they are designed with rate compensation. This provides a unique advantage over both standard fixed temperature and rate-of-rise types of detectors because only the Detect-A-Fire unit accurately senses the surrounding air temperature regardless of the fire growth rate. At precisely the predetermined danger point the system is activated.
The secret of the unit's sensitivity is in the design. The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner struts are made of a lower expanding alloy.

Designed to resist thermal energy absorption and sealed inside the shell, the struts follow temperature changes more slowly.
A slow rate fire will heat the shell and struts together. At the "set point" the unit will trigger, actuating the alarm or releasing the extinguishant.
A transient rush of warm air up to 40°F/min. may expand the shell, but not enough to trigger the unit. In ignoring transient warm air excursions, the Detect-A-Fire unit virtually eliminates false alarms prevalent with rate-of-rise devices.
If a fast rate fire starts, then the shell will expand rapidly. The struts will close, actuating the alarm or releasing the agent. The faster the fire rate of growth, the sooner the alarm.
Eng ineer a nd Arc hitec t Sp ec ific a tions
The explosion proof thermal fire detector shall be a DetectA-Fire explosion proof model, Fenwal (__M_o_d_e_l _#__), also for purchasing purposes referred to as Cerberus Pyrotronics (___M_o_d_el_#__), and shall be of the rate compensated type. The explosion proof detector shall have a self-restoring element and shall be factory set and hermetically sealed in stainless steel. These detectors shall be mounted in an approved explosion proof junction box.
The explosion proof detectors must be UL listed and FM approved.

6128 CATALOG NUMBER
firealarmresources.com

Model Cross-Reference Chart

Normally Open Contact Normally Closed Contact

°F

°F

Color

Setting Tolerance Coding

140

(+7,-8)

Yellow

160

(+7,-8)

Yellow

190

(+7,-8)

White

210

(+7,-8)

White

225

(+7,-8)

White

275

(+/-10)

Blue

325

(+/-10)

Red

360

(+/-10)

Red

450

(+/-15)

Green

500

(+/-15)

Orange

600

(+/-20)

Orange

725

(+/-25)

Orange

Fenwal Model
27121-140 27121-160 27121-190 27121-210 27121-225 27121-275 27121-325 27121-360 27121-450 27121-500 27121-600 27121-725

Cerberus Pyrotronics
Model DT-140EP DT-160EP DT-190EP DT-210EP DT-225EP DT-275EP DT-325EP DT-360EP DT-450EP DT-500EP DT-600EP DT-725EP

Fenwal Model
27120-140 27120-160 27120-190 27120-210 27120-225 27120-275 27120-325 27120-360 27120-450

Cerberus Pyrotronics
Model * * * * * * * * *

* Normally Closed Contact Detectors do not operate with any Cerberus Pyrotronics Control Panels. These Normally Closed Contact Detectors are offered for special applications only.

Ord ering Inform a tion
Refer to the chart above. When placing a purchase order refer to the Cerberus Pyrotronics model number. The format of the model number is: DT- (the temperature setting desired) EP. For example, if you wish to order a normally open 140°F detector, you would order model numbers DT-140EP. The Cerberus Pyrotronics model numbers DT-140EP and DT-190EP (both normally open) are stocked items. All other models are special orders. Contact Cerberus Pyrotronics Customer Service Department for assistance. Shipping weight for these items is approximately one pound.
Dim e nsio ns

Mounting a nd Insta lla tion Inform a tion
The explosion proof (EP) models attach to the threaded hub cover of listed explosion proof junction boxes such as Killark Series, UL or equal. The EP models should not be installed in outdoor or other wet locations.

°F Setting and
Tolerance
140+7°/-8°
160+7°/-8°
190+7°/-8°
Fenwal 210+7°/-8°
27120
Series 225 7°/-8°
275 10°
325 10°
360 10°
450 15°
500 15°
600 20°
725 25°

Color Coding
Yellow Yellow White White White Blue Red Red Green Orange Orange Orange

Spacings (in Feet) See Note B
UL FM ULC

50 25 50 25 25 25 50 25 50 25 25 50 25 25 50 25 25 50 50 25 50 25 25 50 25 25 50 50 25 50 N/A 25 50 N/A 25 50

Fenwal 27121 Series

Hazardous Locations Applications
Class I, Groups B, C and D;
Class II, Groups E, F and G;

CONSTRUCTION: Units have a stainless steel sensing shell and a brass mounting head.

Detector Model Series 27120
27121

Fitting Required for UL & ULC Listings and FM
Approval
Mount detector to a suitably listed fitting in accordance withthe National Electric Code and/or local authority having jurisdiction

Fenwal Model No.

Contacts

27120 Series

Normally Closed

27121 Series

Normally Open

**Electrical Rating (Resistive Only)
5 Amps., 125 VAC 0.5 Amps., 125 VDC
5 Amps., 125 VAC 0.5 Amps., 125 VDC 2.0 Amps., 24 VDC 1.0 Amps., 48 VDC

Cerberus Pyrotronics

Cerberus Pyrotronics

8 Ridgedale Avenue

50 East Pearce Street

Cedar Knolls, NJ 07927

4/97

Richmond Hill, Ontario

Tel: (201) 267-1300

5M

L4B, 1B7 CN

FAX: (201) 397-7008

CPY-IG

Tel: (905) 764-8384

Website: www.cerbpyro.com

Printed in U.S.A.

FAX: (905) 731-9182

firealarmresources.com

April 1997 Supersedes sheet dated 1/95



References

Acrobat PDFWriter 3.0 for Windows