Installation Guide for VIVE models including: TP-N-751, VM-751-IM-242, VM-751-IM-2422, TP-N-751 Programmable Thermostat, TP-N-751, Programmable Thermostat, Thermostat
Dec 2, 2024 — The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show ...
File Info : application/pdf, 4 Pages, 768.92KB
DocumentDocumentInstallation Manual Installation Tips TP-N-751 Wall Locations The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation. Vive Comfort P.O. Box 3377 Springfield, MO 65808-3377 Toll Free : 888-776-1427 Web: www.vivecomfort.com Hours of Operation: M-F 9AM - 6PM Eastern *VM-751-IM-242 * VM-751-IM-2422 Thermostat Application Guide Power Type Description Gas or Oil Heat Yes Electric Furnace Yes Heat Pump (No Aux. or Emergency Heat) Yes Heat Pump (With Aux. or Emergency Heat) Yes Multi-Stage Systems Yes Heat Only Systems Yes Cool Only Systems Yes Millivolt Yes Table of Contents Page Installation Tips 2-3 Thermostat Quick Reference 4-5 Wiring 6 Wiring Diagrams 7-9 Technician Setup 10-15 Specifications 16 Battery Power Hardwire (Common Wire) Hardwire (Common Wire) with Battery Backup A trained, experienced technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions. Una version en español de este manual se puede descargar en la pagina web de la compañia. Installation Tip Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building. Do not install thermostat in locations: · Close to hot or cold air ducts · That are in direct sunlight · With an outside wall behind the thermostat · In areas that do not require conditioning · Where there are dead spots or drafts (in corners or behind doors) · Where there might be concealed chimneys or pipes Subbase Installation Horizontal Mount Vertical Mount Installation Tip: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage. 1 U.S. Registered Trademark. Patents pending Copyright 2024 All Rights Reserved. Installation Tips Mount Thermostat Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place. Rev. 2422 For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right. Mercury Notice All of our products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal. 2 Thermostat Quick Reference Getting to know your thermostat Set At Set At Battery Installation Battery installation is optional if thermostat is hardwired (R and C terminal connected to 24V power). Important: High quality alkaline batteries are recommended. Rechargeable batteries or low quality batteries do not guarantee a 1-year life span. Insert 2 AA Alkaline batteries (included). High quality alkaline batteries are recommended. Located on the back of the thermostat. About The Private Label Badge All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program. Use the bevel on lower ridge 3 Magnet in door Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE. LCD Display Glow in the dark light button Fan Button System Button Temperature Setpoint Buttons Private Label Badge 4 Thermostat Quick Reference Getting to know your thermostat 2Set At COOL ON 1 3 HEAT ON FAN ON Wiring Wiring 1. If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color coded. For example, the green wire may not be connected to the G terminal. 2. Loosen the terminal block screws. Insert wires then retighten terminal block screws. 3. Place nonflammable insulation into wall opening to prevent drafts. Caution: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage. Warning: All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code. On LHM Auto STAGES 1+2+3 Em.Heat AutoCool 7 1 Indicates the current room temperature 2 Setpoint: Displays the selected setpoint temperature. 3 System Operation Indicators: The COOL ON, HEAT ON or FAN ON will display when the COOL, HEAT, or FAN is on. The compressor delay feature is active if these are flashing. Low Battery Indicator: Replace batteries when this indicator is shown. Globe: Globe is displayed if an energy efficient temperature has been selected. Fan: Indicates the current fan setting. 7 Stages: +1 will appear in the display when the first stage of heat or cool is on. +2 will appear for the second stage of heat. System: Indicates current system mode setting. Important The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since first "low battery" display) the setpoints will change to 55°F (Heating) and 85°F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours then return to either 55°F or 85°F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because 5 the thermostat will shut the unit off until the batteries are changed. Terminal RC RH C B O G W/E W2 Y Y2 2 Heat 2 Cool Conventional System Transformer power (cooling) Transformer power (heating) Transformer common Reverse Valve / Configurable Terminal Reverse Valve / Configurable Terminal Fan relay First stage of heat Second stage of heat First stage of cool Second stage of cool 2 Heat 1 Cool Heat Pump System Transformer power (cooling) Transformer power (heating) Transformer common 3 Heat 2 Cool Heat Pump System Transformer power (cooling) Transformer power (heating) Transformer common Reverse Valve / Configurable Terminal Reverse Valve / Configurable Terminal Reverse Valve / Configurable Terminal Reverse Valve / Configurable Terminal Fan relay Fan relay First stage of emergency heat Auxiliary heat relay, second stage of heat First stage of emergency heat Auxiliary heat relay, third/fourth stage of heat First stage of heat & cool First stage of heat & cool N/A Second stage of cool & second stage of heat 6 Wiring Diagrams Wiring Tips C Terminal The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries. Wire Specifications Use shielded or non-shielded 18-22 gauge thermostat wire. Wiring Diagrams Note: This thermostat is hardwire powered when the 24V transformer is connected to the Common and RC terminals of the thermostat. Note: In many systems with no emergency heat relay a jumper can be used between E and W2. Installation Tip: Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues. Max Torque = 6in-lbs. Power supply Factory - installed jumper. Remove only when installing on a 2 transformer systems. Use either O or B terminals for changeover valve. Optional 24 VAC common connection when thermostat is used in battery power mode. Typical Cool-Only System With Fan R L1(HOT) RC L2 RH C Y COMPRESSOR RELAY C W/E G FAN RELAY Typical Heat Only System With Fan R RC L1(HOT) RH L2 Y C C W/E HEAT RELAY G FAN RELAY 7 Typical 2H/2C System: 1 Transformer R RC RH C Y COMPRESSOR RELAY C W/E HEAT RELAY G W2 FAN RELAY Y2 HEAT RELAY 2 COMPRESSOR RELAY 2 L1(HOT) L2 Typical 2H/2C System: 2 Transformer REMOVE JUMPER RC RH Y C W/E G W2 Y2 COMPRESSOR RELAY FAN RELAY COMPRESSOR RELAY 2 R L1(HOT) L2 C R C HEAT RELAY HEAT RELAY 2 L1(HOT) L2 8 Wiring Diagrams Typical 3H/2C or 2H/1C Heat Pump System R L1(HOT) RC L2 RH Y COMPRESSOR C RELAY C W/E EMERGENCY HEAT RELAY COOL CHANGE OVER VALVE O G HEAT CHANGE B W2 FAN RELAY OVER VALVE Y2 AUXILIARY HEAT RELAY COMPRESSOR RELAY 2 Note: In many systems with no emergency heat relay a jumper can be installed between W/E and W2. Tech Settings Technician Setup Menu This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application: 1. Hold down the + and - buttons together for 3 seconds. 2. Use the + and - buttons to modify a setting. Use the Fan button to go back a step and use the system button to go forward a step. 3. To exit Tech Settings, press and hold the + and - button together for 3 seconds or wait 60 seconds. Tech Setup Steps LCDWillShow Adjustment Options Room Temperature Calibration This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70° and you would like it to read 72° then select +2. 0 CALIBRATE You can adjust the room temperature display to read up to 4°above or below the factory calibrated reading. Cooling Swing The swing setting often called "cycle rate","differential"or "anticipation" is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.5 COOL SWING The cooling swing setting is adjustable from 0.2° to 2°. For example: A swing setting of 0.5° will turn the cooling on at approximately 0.5° above the setpoint and turn the cooling off at approximately 0.5° below the setpoint. Heating Swing The swing setting often called "cycle rate", "differential", or "anticipation" is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.4 HEAT SWING The heating swing setting is adjustable from 0.2° to 2°. For example: A swing setting of 0.5° will turn the heating on at approximately 0.5° below the setpoint and turn the heating off at 0.5° above the setpoint. Default 0°F 0.5° 0.4° Swing Setting Tip Temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing setting that is as long as possible without making the occupants uncomfortable. 9 10 Tech Settings Tech Settings Tech Settings LCD Will Show Adjustment Options Default PTAC Mode This setting allows the thermostat to operate a PTAC. This will allow for multiple fan speeds selectable in the next two tech settings. OF PTAC MODE Use the and to select ON/OFF. buttons OFF This setting allows you to choose Use the and buttons PTAC Fan Speeds (Only displayed if PTAC mode is ON) the number of fan speeds the thermostat will control. G = Low Speed Fan B/O = Medieum Speed Fan Y2 = High Speed Fan 2 FAN SPEEDS to select , 2 or 3. 1. Speeds: ON, Auto 2. Speeds: Low, High, Auto 3. Speeds: Low, Med, High, Auto 2 PTAC Medium This setting will select the terminal for medium fan speed Fan Speed operations. The selected terminal Use the and buttons to select O/B terminals. Terminal cannot be used for reversing valve operations when heat pump is (Only displayed enabled. 0 0 if PTAC mode is ON and PTAC fan speeds is set to 3) MED FAN TERM Heat Pump When turned on the thermostat will operate a heat pump. EM. Heat will show as an option in the system switch tech setting. Use the and button to adjust. OF HEAT PUMP OFF configures the thermostat for conventional systems. ON configures the thermostat for heat pump systems. OFF Swing Setting Tip The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is .5 degrees for heating and the thermostat is set at 70°F, the first stage will turn on at approximately 69.5°F. The second stage will turn on at 69°F. The second stage will turn off at 69.5°F and the first will turn off at 70.5°F. If the third stage is used, it will turn on at 68.5°F and turn off at approximately 69°F. Tech Settings This setting allows you to select the number of heat and cool stages. System Stages LCD Will Show Adjustment Options Default 2H2C Use the and buttons to select 1H/1C, 1H/2C, 2H/1C, 2H/2C, 3H/1C, 3H/2C, SET 4H/2C. 2H STAGES Note: Heat and cool choices are limited based on conventional, heat pump, or PTAC system configuration. System Set You can configure the system switch for the particular application. Heat - Off - Cool, Heat - Off, Cool - Off, Heat - Off Cool Auto. Note: Emergency Heat is available in heat pump mode only. Use the or buttons until the desired application is flashing. AUTO = (Auto SYSTEM SET Changeover) Off Em.Heat AutoCool Heat Off Cool Dual Fuel Auxiliary For Heat Pump (Only displayed if heat pump is set to ON) This setting allows the system to run Gas, Oil, Propane or any other types of auxiliary heat. The thermostat will default to electric auxiliary heat in heat pump applications. Electric or Gas Fan Operation Select GAS to have the system control the fan during a call for heat, select Electric to have the thermostat control the fan during a call for heat. OF Use the and buttons to select ON/OFF. DUAL FUEL GAS Use and buttons to change the setting. (Only displayed if Note: If heat pump is set to "ON" this heat pump is set step will not show, and will default to OFF) to ELECTRIC. FAN SET OFF GAS Satisfy Setpoint Staging (Only displayed if there are more than one stage of heat or cool) This feature allows the thermostat to keep multiple stages of heat or cool energized until the setpoint is satisfied. OF SS STAGING Use the or to turn on of off. buttons OFF 11 12 Tech Settings Tech Settings Tech Settings LCD Will Show Adjustment Options Staging Delay (Only displayed if there are more than one stage of heat or cool) This feature allows a delay to occur if an additional stage is needed. This allows the previous stage extra time to satisfy the setpoint. Note: Will not show if using outdoor sensor with balance point temperature. OF STAGING DELAY Use the or key to select OFF, 5, 10, 15, 30, 45, 60, or 90 minutes. Default OFF Minimum Compressor On Time This feature allows the installer to select the minimum run time for the compressor. For example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature. You can set the minimum compressor run time to OF "OFF", "3", "4", or "5" minutes. If 3, 4 or 5 is selected, the compressor will run for at least the selected time before turning off. Use the and buttons to MIN COMP ON change the setting. OFF The compressor short cycle delay Selecting "ON" will not allow protects the compressor from the compressor to be turned Compressor Short Cycle Delay "short cycling". This feature will not altlow the compressor to be turned on for 5 minutes after it was last turned off. on for 5 minutes after the ON last time the compressor was on. Select "OFF" to remove this delay. Use the and buttons to change the COMP DELAY setting. Cooling Fan Delay The cooling fan delay setting will delay the fan from coming on in cool mode and keep it running after the compressor shuts off for a short time to save energy in some systems. You can set the cooling fan delay to OFF, 10, 30, 60 or 90 OF seconds. If 10, 30, 60, or 90 is selected the fan will not turn on for that many seconds when there is a call for cool and will run for that many seconds after satisfying a call COOL FAN DL for cool. OFF Tech Settings LCD Will Show Adjustment Options Default Heat Setpoint Limit Cool Setpoint Limit °F or °C This feature allows you to set a maximum heating setpoint limit. The setpoint temperature cannot be raised above this value. HE HEAT LIMIT This feature allows you to set a minimum cooling setpoint limit. The setpoint temperature cannot be lowered below this value. CO This feature allows you to display temperatures in either Fahrenheit or Celsius. COOL LIMIT oF Use the or key to select the maximum heat setpoint and the minimum cooling setpoint. Use the or key to select the minimum cooling setpoint. °F for Fahrenheit °C for Celsius 90°F 44°F °F F OR C SET Display Light The display light can be configured to stay on all the time or turn on when any key dL Use the and buttons to select OFF, LOW, or HIGH. OFF is pressed. There are LOW and HIGH selections for continuous ON selection. ALWAYS ON LIT OFF configures the display light to come on when the light key or any button is If Battery Powered NOTE: The thermostat will need to pressed. dL LOW be hardwired in order for the LOW and HIGH display light functions to work properly. "ALWAYS ON LIT" will alternate in the text field with "HARDWIRE ONLY"when HIGH is selected. These prompts will alternate every three seconds. LOW configures the display light to stay on at a low intensity constantly. When a button is pressed, the display light will transition to high intensity. HIGH configures the display If the thermostat is hardwired this feature will default to LOW. HARDWIRE ONLY light to remain on at high intensity all the time. If Hardwired 13 14 Tech Settings Specifications Specifications The display range of temperature ... 41°F to 95°F (5°C to 35°C) The control range of temperature.... 44°F to 90°F (7°C to 32°C) Load Rating............................................... 1 amp per terminal, 1.5 amp maximum all terminals combined Swing (cycle rate or differential) ...... Heating is adjustable from 0.2° to 2.0° Cooling is adjustable from 0.2° to 2.0° Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire Battery power from 2 AA Alkaline batteries Operating ambient ............................... 32°F to +105°F (0°C to +41°C) Operating humidity .............................. 90% non-condensing maximum Dimensions of thermostat ................. 4.7" W x 4.3" H x 0.9" D Warranty Information Warranty Registration Please Register Your Thermostat Here Your new thermostat has a 5 year limited warranty. You must register your thermostat within 60 days of installation. Without this registration the warranty period will begin on date of manufacture. For warranty issues please contact the HVAC professional that installed this product. Please register your new thermostat online. www.vivecomfort.com/warranty 15 16