RTD Operator Manual

Self Tune PID Temperature Controller | PID Control with Self-Tuning


File Info : application/pdf, 2 Pages, 627.16KB

PDF preview unavailable. Download the PDF instead.

Product-036-OM-1
Jan 2022

Composite `Temperature + Humidity' Controller Version : RTD Pt100, 3-wire for Temperature
DC Linear (Voltage) for Humidity

Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net

UTILITY PARAMETERS : PAGE-33

Parameters

Settings (Default Value)

Compressor Control Strategy

Dry Bulb SP Dry Bulb PV
(Default : Dry Bulb SP)

Zero Offset for Temperature Value

-25.0 to +25.0°C (Default : 0.0)

Zero Offset for RH Value

-25.0 to +25.0% (Default : 0.0)

Range Low Range High

-199.9 to 999.9 (Refer Table 1) (Default : 0.0)
-199.9 to 999.9 (Refer Table 1) (Default : 151.5)

TEMPERATURE PARAMETERS : PAGE-10

Parameters

Settings (Default Value)

Alarm-1 Band

0.3 to 25.0°C (Default : 0.5)

Alarm-1 Hysteresis

0.2 to 10.0°C (Default : 0.2)

Proportional Band

0.1 to 999.9°C (Default : 5.0)

Integral Time

0 to 1000 Seconds (Default : 100)

Derivative Time

0 to 250 Seconds (Default : 25)

Cycle Time

0.5 to 25.0 Seconds (in steps of 0.5 secs.)
(Default : 1.0)

RELATIVE HUMIDITY (% RH) PARAMETERS : PAGE-11

Parameters

Settings (Default Value)

Alarm-2 Band

0.3 to 25.0% (Default : 2.0)

Alarm-2 Hysteresis

0.2 to 10.0% (Default : 2.0)

Parameters Proportional Band Integral Time Derivative Time Cycle Time

Settings (Default Value)
0.1 to 999.9% (Default : 10.0)
0 to 1000 Seconds (Default : 100)
0 to 250 Seconds (Default : 25)
0.5 to 25.0 Seconds (in steps of 0.5 secs.)
(Default : 1.0)

OP3 FUNCTION PARAMETERS : PAGE-13

Parameters

Settings (Default Value)

Output-3 Function Selection

Alarm Compressor

(Default : Alarm)

Compressor Setpoint

0.0 to 50.0°C or 0.0 to 25.0°C
(Default : 45.0 or 0.2)

Compressor Hysteresis

0.1 to 25.0°C (Default : 0.2)

Compressor Time Delay

0.00 to 10.00 Min. Sec (in steps of 5 Seconds)
(Default : 00.00)

SUPERVISORY PARAMETERS : PAGE-12

Parameters

Settings (Default Value)

SP Adjustment on PAGE-0

Enable Disable

(Default : Enable)

Self-Tune Command

No

Yes

(Default : No)

Baud Rate

(Default : 4800)

Parameters ID for Temperature Loop
ID for %RH Loop

Settings (Default Value)
1 to 8 (Default : 1)
1 to 8 (Default : 2)

COMPRESSOR OPERATION & POWER INDICATION : PAGE-1

Parameters

Settings (Default Value)

Compressor Operation Mode

Automatic Off

Output Power for Temperature Loop

On (Default : Auto)
0 to 100.0% (View Only - Non editable)

Output Power for %RH Loop

0 to 100.0% (View Only - Non editable)

TABLE-1 RH INPUT CONFIGURATION
The controller is calibrated for 0 to 5 VDC input for % RH. The transmitter output signal, however, may be any voltage between 0 to 5 VDC (For e.g. 0 to 1 VDC,1 to 3.6 VDC, 0 to 3.3 VDC etc.). The value for `Range Low' and `Range High' parameters must be corresponding to 0 and 5 VDC only. For this, use the following formulae for computing the `Range Low' and `Range High' values.

100 Range Low = Span X (0 - Signal Low)

100.0 Range High = Span X (5 - Signal Low)

(where; Span = Signal High - Signal Low)

Example 1 Signal Low = 0 VDC, signal High = 1.0 Vdc

Range Low =

100.0 1.0

X (0 - 0) = 0.0

Range High = 100.0 X (5 - 0) = 500.0 1.0

Example 2 Signal Low = 0 VDC, signal High = 3.3 VDC Here, Span = 3.3 -0 = 3.3 VDC

Example 3 Signal Low = 1.0 VDC, signal High = 3.6 VDC Here, Span = 3.6 - 1.0 = 2.6 VDC

Range Low =

100.0 2.6

X (0 - 1.0) = -38.5

Range

High

=

100.0 2.6

X (5 - 1.0) = 153.8

Range Low =

100.0 3.3

X (0 - 0) = 0.0

Range High =

100.0 3.3

X (5 - 0) = 151.5

FRONT PANEL LAYOUT

Front Panel

PPI

HumiTherm-c
°C

Upper Readout

Lower Readout Tune Indicator
Alarm -1 Indicator PAGE Key

%RH 1

2

AL1

TUN

AL2

Output-1 Indicator Output-2 Indicator Alarm-2 Indicator
ENTER Key

DOWN Key

UP Key

Symbol Key PAGE

Keys Operation Function
Press to enter or exit set-up mode.

DOWN UP
ENTER

Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications For Dry Bulb Temperature (Upper Readout)

Message

PV Error Type

Over-range (Dry-Bulb Temp. above Max. Range)
Under-range (Dry-Bulb Temp. below Min. Range)
Open (Sensor open / broken)

PV Error Indications For Relative Humidity (RH) (Lower Readout)

Message

PV Error Type
Over-range (Wet-Bulb Temp. above Max. Range)
Under-range (Wet-Bulb Temp. below Min. Range)

Open (Sensor open / broken)

Either Dry Bulb Temp. is below 20.0°C or above 162.0°C. The error may also occur if Wet Bulb depression is more then 60.0°C.

INPUT 1 OUTPUT 1 & 2 Pt100
+ SERIAL COMMS. SUPPLY

+
+

ELECTRICAL CONNECTIONS

OUTPUT 3

N/C C N/O RELAY

_

SSR

+5V 6 7 8 9 10 GND

OC2 5

11

OC1 4 PPI 12 L AC
3 HumiTherm-c 13 N DC

2

14

1 18 17 16 15

Ex -

RH SENSOR

INPUT 2

JUMPER SETTINGS
OUTPUT-3
Output Type Jumper Setting - A Jumper Setting - B Relay
SSR Voltage Pulses
Jumper Setting-B
Jumper Setting-A

ENCLOSURE ASSEMBLY

MOUNTING DETAILS
OUTPUT-3 MODULE

INPUT 1 OUTPUT 1 & 2 Pt100 + COSMERMISA.L SUPPLY

`UP' inscribed on topside

Plug & Socket Connector

UP UP

+5V OOCC21

6 5 4 3 2 1

H1ON7u_IE8PN/UxmCTPi1PC-PTU87UhTNTeI/2O1r396mRRS111111EHS140352LRSAEYNNL

SOR

AC DC

Removal

Bezel

Placing Back

PPI

HumiTherm-c °C %RH1 2

AL2 TUN AL1

Front Label Pullout Grip

Power Supply Board
PPI

HumiTherm-c

Front Label Upright

Output Module Projections
Slots

MOUNTING DETAILS
SERIAL COMM. MODULE

Power Supply Board

Serial Communication Module
Plug & Socket Connectors

PPI

-c iTherm Hum

Front Label Upside-down

WIRING CONNECTION
RH SENSORS

R=Red G= Green B=Black

Ex
-
+

18 17 16

R B G

(Humirel RH sensor) ( R LO- 38.4 R HI-153.6)

Ex
-

18 17

R B

+ 16 G

(IST RH sensor) ( R LO- 0 R HI-100)

Ex
-

18 17

R B

+ 16 G

(Capacitance RH sensor) ( R LO- 0 R HI-151.5)



References