Owner's Manual for Honeywell models including: SLC-IM, SLC-IM Signaling Line Circuit Integration Module, Signaling Line Circuit Integration Module, Line Circuit Integration Module, Integration Module, Module

DN 60755-C

e451217

Click here to download

Notifier SLC-IM Signaling Line Circuit Inte- gration Module - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 2 Pages, 884.87KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676769353
SLC-IM

DN-60755:C

Signaling Line Circuit Integration Module

General

Network Systems

The Signaling Line Circuit-Integration Module (SLC-IM) provides a communication link between a VESDAnet network and a Fire Alarm Control Panel (FACP) SLC loop via the High Level Interface (HLI) VHX-1420-HFS. It allows mapping of alarms and faults from VESDA detectors onto FACP monitor module addresses. The SLC-IM translates VESDAnet protocol to SLC protocol, enabling VESDA detector events on the VESDAnet to be annunciated by an FACP.

Features
The SLC-IM:
· Communicates with the VESDAnet via an RS-232 connection.
· Supervises the connection to the VHX-1420-HFS HLI. · Provides 159 FlashScan® monitor module addresses that
can be mapped to events from VESDA detectors using the SLC-IM configuration tool. · Provides individual alarm annunciation from VESDA-E VEA detector addressable sampling points. · Uses seven user-defined FlashScan monitor module addresses for each programmed VESDA detector plus one additional monitor module address for VESDAnet wiring fault. · Supports up to 22 VESDA detectors on one SLC loop. · Supports Style 4 and Style 6 configurations on the VESDAnet network. NOTE: The SLC-IM cannot monitor VESDA devices with addresses higher than 247.
Compatibility
The SLC-IM interface is listed with ONYX® Ninth edition panels:
· NFS2-3030. · NFS2-640. · NFS-320. The SLC-IM is compatible with the following VESDA detectors:
· VESDA VLC. · VESDA VLF. · VESDA VLI. · VESDA VLP. · VESDA VLS. · VESDA-E VEA. · VESDA-E VEP. · VESDA-E VEU.

SLC-IM
Alarm Control Unit; or a ULC-listed, regulated, 24 VDC power supply for fire application. · Temperature: 0°C to 49°C (32°F - 120°F). · Relative Humidity: 93 ±2% non-condensing at 32 ±2°C (90 ±3°F). NOTE: It is recommended that this product be installed in an environment with a normal room temperature of 15-27º C (60-80º F).
Standards and Codes
The SLC-IM complies with the following standards and requirements: · NFPA 72 National Fire Alarm Code. · UL 864, 9th Edition: Control Units for Fire Alarm Systems. · UL 2017, 1st Edition: General Purpose Signaling Devices
and Systems. · CAN: ICES-003, CSA C22.1. · CAN/ULC S527-11, 3rd Edition: Standard for Control
Units for Fire Alarm Systems. · ULC: S524-06, S561-03.
Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. · UL / ULC: S635.

SLC-IM-cov.jpg

Specifications
· Power input: 24 VDC. Input current: 100 mA @ 24 VDC.
­ The SLC-IM must be powered by a UL1481 and/or UL 864 listed, regulated, power-limited, battery-backed, 24 VDC power supply.
­ For Canadian installation, the SLC-IM must be powered by a ULC-listed, regulated, 24 VDC power output, Fire

firealarmresources.com

DN-60755:C · 6/9/17 -- Page 1 of 2

Ordering Information
EQUIPMENT ORDERED FROM NOTIFIER
SLC-IM: Signaling Line Circuit-Integration Module. Includes circuit board and RS-232 cable (PN 75583) for connection to PC. Download the SLC-IM Configuration Tool from www.magni-fire.com.
VHX-1420-HFS: VESDAnet Network Interface Card. (See DN-60753.) Includes DB-9 cable for connection to SLC-IM.
UBS-1B, UBS-1R: Cabinet required for SLC-IM. Order UBS-1B for black; UBS-1R for red. Dimensions: 12.22" L X 9.23" W X 2.75" H (31.04 cm L X 23.44 cm W X 6.99 cm H).
For detailed information about required components, see the SLC-IM Programming and Operation Manual and the SLC-IM Listing Document.
EQUIPMENT SUPPLIED BY CUSTOMER
Computer with available COM port on which to run the SLC-IM configuration tool.

FACP

SLC-IM

VHX-1420-HFS

VESDA Detector

VESDAnet Network

VESDA Detector

VESDA Detector
SLC-IM System Architecture

NOTIFIER®, ONYX®, and ONYXWorks® are registered trademarks and NOTI·FIRE·NETTM is a trademark of Honeywell International Inc. Windows® is a registered trademark of Microsoft Corporation. VESDA® is a registered trademark and XtralisTM is a trademark of Xtralis Pty Ltd. ©2017 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com
Page 2 of 2 -- DN-60755:C · 6/9/17
firealarmresources.com



References