Installation Instructions

For use by heating contractor

Vitocell 100-V, CVA/CVAA Series

Enameled indirect-fired domestic hot water storage tank with capacities ranging from 42 USG to 119 USG (160 L to 450 L).

CAUTION: The heat transfer medium must be water or other non-toxic fluid having a toxicity rating or class of 1, as listed in clinical toxicology of commercial products, 5th edition. This tank version is not suitable for steam heating applications. The pressure of the heat transfer medium must be limited to a max. of 30 psig by an approved safety or relief valve.

Document Number: 5697 615 03. Revision: 05/2025

IMPORTANT: Read and save these instructions for future reference. Please file in Service Binder.

Introduction

Safety, Installation and Warranty Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).

CAUTION (In solar applications): The heat transfer medium must be either potable water or contain only substances which are recognized as safe by the U.S. Food and Drug Administration. The Pressure of the heat transfer medium must be maintained less than the normal minimum operating pressure of the potable water system.

General Information

About These Instructions

Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include "WARNING", "CAUTION", and "IMPORTANT".

Product Information

42 USG to 119 USG (160 L to 450 L) capacity

Enameled indirect-fired domestic hot water storage tank with one heat exchanger coil for use with hot water heating boilers, residential/commercial heating plants, and low-temperature heating systems. These tank versions are not suitable for steam heating applications.

Set-up and Connections

Tank Connections

The tank features various connection points for domestic hot water (DHW), recirculation tapping (RT), sensors (TS/AQ), boiler water supply (BWS), boiler water return (BWR), domestic cold water supply (DCW), and grounding (GND).

42 to 79 USG (160 to 300 L) Tanks

Supplied adaptor sizes:

Part Size CVA 42/53 USG (160/200 L) CVAA 79 USG (300 L)
A Brass cap 3/4 in. 1 --
A Brass cap 1 in. -- 1
B Brass tee 3/4 in. 1 --
B Brass tee 1 in. -- 1
C Reducer hex bushing 1 in. x 3/4 in. 1 1
D Temperature and pressure relief valve 3/4 in. 1 1

Legend: DHW: Domestic hot water supply; RT: Recirculation tapping; TS/AQ: DHW temperature sensor or aquastat of boiler control (upper indirect coil); BWS: Boiler water supply; BWR: Boiler water return; DCW: Domestic cold water supply; GND: Grounding connection (casing) for 42 to 79 USG (160 to 300 L) only. The upper indirect coil is provided for connection to a boiler or a heat pump.

119 USG (450 L) Tank

Supplied adaptor sizes:

Part Size CVA 119 USG (450 L)
A Brass cap 1 in. 1
B Brass tee 1 1/4 in. 1
C Reducer hex bushing 1 1/4 in. x 3/4 in. 1
D Temperature and pressure relief valve 3/4 in. 1
IMPORTANT: Apply approved thread sealant to each tank nipple (field supplied).

Tank Set-up

When transporting the tank through narrow passageways, remove upper and lower portions of the crating and use crating boards mounted on the tank. Position the tank carefully and remove wood crating. Locate the tank(s) on a floor or foundation capable of supporting the weight of the tank(s) when filled with water. The tank does not require a special foundation and can be placed directly on the floor. If desired for cleanliness, a foundation can be used to elevate the tank(s) off the floor.

CAUTION: Install the DHW tank in a frost-protected and draft-free room. Otherwise, it must be drained when not in use to reduce the risk of damage from freezing.
IMPORTANT: Provide sufficient clearances towards the wall to allow the aquastat to be operated (if installed).

Recommended installation clearances for service access

Location Clearance (in./mm)
Rear 18 (460)
Sides 12 (300) (May be reduced if rear pipe connections can be reached with less clearance)
Top 36 (900)
Front 24 (600)

Minimum clearances to combustibles

Location Clearance (in./mm)
All sides 0 (0)
Floor Combustible
IMPORTANT: Apply approved thread sealant to each tank nipple (field supplied).
CAUTION: Do not overtighten the adaptors as this may damage the Ceraprotect enamel of the tank.

42 to 79 USG (160 to 300 Liter) Tank Installation

Thermal insulation and thermometer installation

All required components are included in the insulation jacket carton. Note: The 42 to 79 USG (160 and 300 L) tank comes with the insulation jacket installed.

  1. Position and level the DHW tank with its leveling bolts.
    IMPORTANT: Do not extend the leveling bolts beyond an overall length of 1½ in. (35 mm).
  2. Mount the sensor on the outside of the sensor spring-clip (not in the center groove) so that it is flush with the front of the sensor spring-clip.
  3. Snap the sensor cabling into the plastic clip of the sensor mounting equipment.
    IMPORTANT: Never wrap insulating tape around the sensor.
  4. Completely insert sensor mounting hardware along with the sensor into the sensor well.
  5. Remove the top cover and insulation blanket.
  6. Remove the cap from the thermometer opening.
  7. Slide the thermometer sensor cable through the thermometer opening in the panel and insert the thermometer.
  8. Completely insert the sensor into the metal clip on the flange (check anode connection on page 9). Install the insulation blanket and top cover.

Temperature sensor installation for solar operation using 42 to 79 USG (160 to 300 L) tanks

The temperature sensor for solar operation is included in the solar control unit package. The brass elbow with sensor well is available as an option and must be used when solar connection is required.

  1. For solar operation, install the sensor well into the brass elbow and connect the assembly to the solar return line.
  2. Insert the temperature sensor until it bottoms out inside the sensor well.
    IMPORTANT: Never wrap insulating tape around the sensor. Do not install solar tank sensor anywhere other than the brass elbow with sensor well.

Checking anode connections

Ensure the grounding wire is properly secured to the magnesium anode.

IMPORTANT: When connecting an externally powered anode to the top flange lid, separate the magnesium anode in the bottom flange lid from the grounding cable. The magnesium anode may remain installed.

119 USG (450 Liter) Tank Installation

Temperature sensor installation (when using a Vitotronic 200 / 300 or Vitodens 200)

  1. Mount the sensor on the outside of the sensor spring-clip (not in the center groove) so that it is flush with the front of the sensor spring-clip.
  2. Snap the sensor cabling into the plastic clip of the sensor mounting equipment.
    IMPORTANT: Never wrap sensor with any type of tape or insulation.
  3. Completely insert sensor mounting equipment along with the sensor into the sensor well. Note: When using a Vitotronic 100 boiler control, refer to page 14 for aquastat installation.
    IMPORTANT: Always use spring clip to ensure proper contact of capillary bulb against the stainless steel well for proper sensing/heat transfer!

Temperature sensor installation for solar operation using 119 USG (450 L) tank

The temperature sensor for solar operation is included in the solar control unit package. The brass elbow with sensor well is available as an option and must be used when solar connection is required.

  1. For solar operation, install the sensor well/brass elbow and connect the assembly to the solar return line.
  2. Insert the temperature sensor until it bottoms out inside the sensor well.
    IMPORTANT: Never wrap insulating tape around the sensor. Do not install solar tank sensor anywhere other than the brass elbow with sensor well.
  3. Tighten screws to secure sensor (do not over tighten).

Levelling and bottom thermal insulation

All necessary parts for enclosure assembly are packaged in a separate carton.

CAUTION: The thermal insulation must not come in contact with open flames. Exercise extreme caution when welding and soldering.
  1. Fit the thermal insulation blanket below the tank prior to the installation of the tank itself.
  2. Position and level the DHW tank with its leveling bolts.
    IMPORTANT: Do not extend the leveling bolts beyond an overall length of 1½ in. (35 mm).

Fitting the thermal insulation jacket

Note: Insulation remnants must not enter the tank through the tank connections. 2 people are recommended to complete this work.

  1. Fit both halves of the insulation jacket close to the tank. Orient the jacket so the profile cutouts match the tank fittings.
  2. At the rear of the tank, install all 6 clip closures evenly to both halves of the insulation jacket.
  3. At the front of the tank, install all 6 clip closures evenly to both halves of the insulation jacket.
  4. At the rear of the tank, tighten all 6 clip closures until both halves of the insulation jacket meet.
  5. At the front of the tank, tighten all 6 clip closures until both halves of the insulation jacket meet.

Fitting the thermometer and thermometer sensor and covers

  1. Smooth out the insulation jacket by tapping the jacket evenly against the tank.
  2. Route the thermometer capillary tube through the front cover hole and insulation jacket, then snap the thermometer in place.
  3. Insert the thermometer probe under the clip.
  4. Install the front cleanout cover and the front lower seam cover.
  5. Install the upper front seam cover.
  6. Install the back seam cover.
  7. Install the top insulation and press down the edges as shown.
  8. Install the top lid and press the logo A into the lid. Note: Seal the hole in the seam cover below the thermometer with a cover.

Aquastat Installation (when using a Vitotronic 100)

Where a Vitotronic 100 and a Viessmann Power/Pump Control Module (accessory) are utilized to control DHW production, follow these aquastat mounting instructions:

Probe style aquastat:

  1. Insert the extended capillary of the aquastat (supplied with Viessmann Power/Pump Control Module, not illustrated) fully and completely into the sensor well. Mount the aquastat inconspicuously on the tank paneling. Follow instructions below with regard to sensor and spring clip installation.
  2. If the aquastat is to be mounted remote from the tank well, align the sensor bulb with the spring clip.
  3. Slide the assembly into the well.
  4. The retention spring clip must press the bulb properly to ensure surface contact with the well.
  5. If the aquastat is to be mounted directly on the tank well, mount the aquastat with the holding clip supplied directly onto the well. Bend the capillary tube into the groove opening to allow for mounting of the aquastat.
IMPORTANT: Always use the spring clip to ensure proper contact of the capillary bulb against the stainless steel well for proper sensing/heat transfer!

Grounding connection: Connect the grounding in accordance with the requirements stipulated by your local electricity supply company and current local regulations.

WARNING: The operating aquastat and any secondary high limit aquastat of the tank must be set such that the DHW temperature inside the tank never exceeds 203°F (95°C).
WARNING: Domestic hot water temperatures over 125°F (52°C) can cause severe burns instantly or death from scalds. Children, disabled, and the elderly are at the highest risk of being scalded. Feel water before bathing or showering. Temperature limiting valves are available and must be used where domestic hot water storage tank temperatures exceed 140°F (60°C).

Boiler Water Connections (heat exchanger connection)

Recommended piping for solar application with an additional tank

Diagram Description: The diagram illustrates a solar heating system connected to a Vitocell 100-V tank. Components include a solar collector (A), high limit safety cut-out (B), filling valve (C), Solar-Divicon (D), Vitocell 100-V (E), individual DHW tank heating system (F), and an anti-scald tempering valve (G).

WARNING: Due to the potentially high DHW temperatures generated by the solar heating system, the domestic hot water temperature must be limited to a maximum of 140°F (60°C) by installing an anti-scald tempering valve. The tempering valve does not completely eliminate the risk of scalding at the tap. The installation of a mixing tap is recommended.
  1. For boiler water supply temperatures over 203°F (95°C): Remove plastic supply and return grommets (grommets are left-threaded).
  2. Pipe the supply line with an incline and install an air vent valve at the highest point.
  3. For boiler water supply temperatures over 230°F (110°C): Install a type-tested high limit safety cut-out, if no other has previously been installed in this system. For this purpose, install a dual thermostat (high limit thermostat and high limit safety cut-out).
  4. Close off test nipples which are not used for the installation of a probe or sensor.

Domestic Water Connections

Notes: Connect all pipe work with detachable fittings. Seal connections that are not required with red brass caps. Equip the DHW circulation pipe with a circulation pump, check valve, and time switch. Gravity operation is only feasible to a limited degree. Always install DHW group of tanks with connected DHW circulation.

  1. Pipe together the boiler and tank as illustrated. Connections must be accessible for service (use factory supplied adaptors).
  2. Insulate domestic hot water supply piping.
IMPORTANT: This is a simplified conceptual drawing only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field are the responsibility of the heating contractor.

Legend: A: Spring-loaded flow check valve, B: Discharge pipe, C: Anti-scald tempering valve (field supplied), SV: Shut-off valve, FV: Flow check valve, PR: Pressure reducing valve, D: Drain, DCW: Cold water supply lines, PGC: Pressure gage connection, E: Precharged expansion tank (required where backflow preventer is installed; check local plumbing codes and requirements), BP1: Backflow preventer, BP2: Backflow preventer, T&P: Temperature and pressure relief valve, DW: Water filter, DHW: Domestic hot water supply, RP: Recirculation pipe, RPU: Recirculation pump.

Domestic Water Connections (continued)

Always ensure the use of type approved devices. Safety devices include:

IMPORTANT: In situations where a booster pump is used to maintain DHW pressure, Viessmann strongly recommends the installation of an oversized large expansion tank to ensure longer, less frequent pump cycles with less severe pressure gradients. If possible, use flexible piping before and after the booster pump to isolate system piping from vibration and shocks.

Temperature and pressure relief valve (T&P valve): A T&P valve is supplied with the tank. The heating contractor must install the valve on each tank in a method meeting code requirements. If local codes require a different relief valve, consult Viessmann Manufacturing for a substitute valve. The tank is approved for 150 psig. Maximum operating pressure is 150 psig. The T&P valve supplied with the tank is tested under ANSI Z21.22 Code for Relief Valves and Automatic Gas Shut-off Devices for Hot Water Supply Systems.

Proper installation of the T&P valve shall include all of the following:

WARNING: The discharge line for the T&P valve must be oriented to prevent scalding of attendants. Do not route discharge line directly to the outdoors. Do not install any type of valve or restriction of any kind between the tank and the T&P valve, or between the T&P valve and the discharge line outlet.
WARNING: The valve test lever must be operated at least once per year by the owner to ensure that waterways are clear. A licensed professional heating contractor shall reinspect the T&P valve at least once every three years. Failure to inspect can result in unsafe temperature or pressure build-up, which can result in death, serious injury or substantial product/property damage.

T&P Valve Specifications:

Recirculation Connections

Pipe domestic hot water supply piping with the tank as illustrated. Connections must be accessible for service (use factory supplied adaptors). Install recirculation pump, flow check valve, and recirculation timer (for shut-down during off-hours where feasible) on the recirculation piping side. Gravity circulation of the recirculation system is restricted due to the upward-curved domestic hot water discharge piping inside the tank.

Connect tanks to existing recirculation piping. Cap off unused recirculation connections of individual tanks.

Saving Energy

A timer on the recirculation pump reduces heat loss significantly in commercial applications during times when no or reduced demand for domestic hot water occurs.

Connection of a recirculation system in a multiple tank installation for systems utilizing boilers or remote heating plants without low temperature boiler return water:

Diagram Description: Illustrates recirculation connections for multiple tanks, showing drawpoints, recirculation piping, circulation pump, flow check valve, domestic cold water supply, domestic hot water supply, secondary high limit aquastat location, and air vent.

Legend: A: Drawpoints, B: Recirculation piping, C: Circulation pump, D: Spring-loaded flow check valve, E: Domestic cold water supply, F: Domestic hot water supply, G: Secondary high limit aquastat location, H: Air vent.

Connection of a recirculation system in a multiple tank installation for remote heating plants with low temperature boiler return water limit and/or for multiple recirculation lines:

Diagram Description: Similar to the above, illustrating recirculation connections for multiple tanks in a remote heating plant setup.

Legend: A: Drawpoints, B: Recirculation piping, C: Circulation pump, D: Spring-loaded flow check valve, E: Domestic cold water supply, F: Domestic hot water supply, G: Secondary high limit aquastat location, H: Air vent.

Multiple Tank Set-up [only for 79 and 119 USG (300 and 450 L) capacities]

Two tanks, each with 79 USG (300 L) content, or up to four tanks, each with 119 USG (450 L) content, may be installed side-by-side. The tanks are controlled via one DHW tank aquastat; individual control of tanks within the group is not possible. If individual tank control is necessary, a 4-tank group can be separated into smaller groups (e.g., two batteries of two tanks each), or all tanks can be installed individually.

  1. Install aquastat in the boiler water supply of the last tank receiving the boiler water in a group of tanks (see illustration).
  2. Install domestic cold and hot water header lines (see illustration).
  3. Install boiler water supply and return header lines (see illustration).
  4. Make final cold and hot water connections.
  5. Insulate header piping lines.
IMPORTANT: Both the boiler supply/return header and the domestic hot/cold water header must be installed in a reverse return method. This ensures uniform heating of all tanks in the group. Header sizes for batteries up to four 79 to 119 USG (300 to 450 L) tanks are listed below.
CAUTION: In commercial installations, we recommend the installation of an additional high limit aquastat in the main discharge pipe of domestic hot water from a group of tanks into the system, and to wire this additional high limit aquastat in series with the operating aquastat.

Storage capacity / tank:

79 (300 L) 119 (450 L)
Number of tanks 2 2, 3
Connections (individual tank)
Heating water supply/return (common header size) 1 1/4" 1 1/4"
Domestic cold/hot water (common header size) 1" 1 1/4"
Recirculation tapping 1" 1"

Recommended piping of multiple tanks

All piping should be reverse return or use balancing valves. Connections must be accessible for service (use factory supplied adaptors).

  1. Pipe together boiler and tanks as illustrated.
  2. For boiler water supply temperatures over 203°F (95°C): Remove plastic supply and return grommets (grommets are left-threaded).
  3. Pipe the supply line with an incline and install an automatic air vent at the highest point.
  4. Install boiler sensor in sensor well (see pages 8 and 10).
  5. Insulate piping.
IMPORTANT: The circulation pump is activated by the operating aquastat or by the control system installed. The operating aquastat should be mounted on the tank which receives the boiler water supply last. Viessmann recommends the installation of an additional high limit aquastat in the main discharge pipe of the DHW system. This aquastat should be wired in series with the operating aquastat and should be set approximately 9°F (5°C) higher than the operating aquastat.

Additional Information

Pressure Drop Information

Pressure drop on heating water side (primary circuit): Graphs show pressure drop in w.c./mbar versus flow rate in L/min and GPM for different storage capacities (A: 42/53 USG, B: 79 USG, C: 119 USG).

Pressure drop on domestic hot water side (secondary circuit): Graphs show pressure drop in w.c./mbar versus flow rate in L/min and GPM for different storage capacities (A: 42/53 USG, B: 79 USG, C: 119 USG).

Inspection Opening

Inspection opening for 79 USG (300 L) tank

  1. Install front insulation blanket.
  2. Install inspection cover and front cover.
  3. Tighten screws.

Inspection opening for 119 USG (450 L) tank

  1. Install front insulation blanket.
  2. Install inspection cover.

Post Installation

Service binder

  1. File all Parts Lists, Operating and Service Instructions in the Service Binder.
  2. Install a protective hanging case near the boiler and store the Service Binder in this location. For a listing of applicable Viessmann literature, please see Important Regulatory and Installation Requirements on page 4.

Start-up information

Refer to DHW Tank Start-up/Service Instructions.

Installation Set

Parts:

*1 Not on models: CVA 42 USG (160 L), CVA 53 USG (200 L)

Models: CVA, CVAA, CVA-CVAA Series Floor Standing DHW Cylinder, CVA-CVAA Series, Floor Standing DHW Cylinder, Standing DHW Cylinder, DHW Cylinder

File Info : application/pdf, 24 Pages, 2.00MB

PDF preview unavailable. Download the PDF instead.

vitocell-v 100 ii

References

Adobe PDF Library 17.0 Adobe InDesign 20.2 (Windows)

Related Documents

Preview Viessmann Vitocell 100-V CVWC Indirect DHW Storage Tank Technical Data
Detailed technical specifications, benefits, dimensions, and performance data for the Viessmann Vitocell 100-V CVWC indirect domestic hot water (DHW) storage tanks, available in 53, 66, and 79 US gallon capacities.
Preview Viessmann Vitodens 100-W Installation and Start-up Guide
A guide for licensed professional heating contractors on the installation and start-up of Viessmann Vitodens 100-W, B1HA/B1KA wall-mounted, gas-fired condensing boilers. Covers unpacking, dimensions, piping, venting, electrical connections, and basic operation.
Preview Viessmann Vitorond 200 VD2/VD2A Series Operating Instructions and User's Information Manual
Comprehensive operating instructions and user information for the Viessmann Vitorond 200 VD2/VD2A Series oil/gas-fired boiler. This manual covers essential safety guidelines, installation considerations, operational procedures, and maintenance schedules, specifically tailored for heating contractors.
Preview Vitodens 200-W B2HE Service Instructions
Comprehensive service instructions for the Viessmann Vitodens 200-W B2HE gas-fired condensing boiler, covering installation, safety, commissioning, and maintenance for heating contractors.
Preview Viessmann Vitodens 200 WB2 Series: Start-up and Service Instructions
This document provides essential start-up and service instructions for the Viessmann Vitodens 200 WB2 Series gas-fired condensing boiler. It is designed for heating contractors and covers installation, operation, maintenance, and troubleshooting procedures to ensure optimal performance and safety.
Preview Viessmann Vitodens 100-W B1HA/B1KA Installation and Service Instructions
This manual provides detailed installation and service instructions for Viessmann Vitodens 100-W B1HA and B1KA gas-fired condensing boilers (Models 26 to 125). It covers safety, regulatory requirements, technical data, installation procedures, troubleshooting, and parts lists, intended for professional heating contractors.
Preview Vitodens 200-W B2HA Installation Instructions
Comprehensive installation instructions for the Viessmann Vitodens 200-W B2HA series gas-fired condensing boiler, covering safety, general information, setup, and connections.
Preview Viessmann Vitodens Gas Boiler Guide: Efficient Heating Solutions
Explore the Viessmann Vitodens range of high-efficiency gas condensing boilers, including models 050-W, 100-W, 111-W, 200-W, 222-F, and 242-F. Learn about their features, benefits, technical specifications, installation accessories, and control systems for optimal home comfort and energy savings.