Installation Guide for LENNOX models including: ML18XC2 Outdoor Air Conditioner, ML18XC2, Outdoor Air Conditioner, Air Conditioner, Conditioner

Lennox Technical Publications

INSTALLATION INSTRUCTIONS

Dec 11, 2023 — Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line. Remove service ...

(opens in new window)

Merit Series Small Split Systems ML18XC2 | Lennox Commercial


File Info : application/pdf, 17 Pages, 1.87MB

PDF preview unavailable. Download the PDF instead.

508277-01a
©2023 Lennox Industries Inc. Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE General This ML18XC2 outdoor air conditioner with all-aluminum coil is designed for use with HFC-410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. For AHRI Certified system match-ups and expanded ratings, visit www.LennoxPros.com. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
NOTICE!
Charging information is given on the charging procedure sticker on the unit access panel. For more indepth information, consult the Installation and Service Procedures manual on LennoxPros.com or through the Technical Support department at 800-453-6669.
STEP 1 ­ SETTING THE UNIT ­ Clearances

INSTALLATION INSTRUCTIONS
Merit® Series ML18XC2 Units
AIR CONDITIONER 508277-01 9/2023
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, or service agency.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
IMPORTANT: Special procedures are required for cleaning the all-aluminum coil in this unit. See page 16 in this instruction for information.

See NOTES

See NOTES

See NOTES

CONTROL See NOTES BOX

NOTES Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm).
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.

NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
FIGURE 1

Page 1

UNIT DIMENSIONS - INCHES (MM) A
B

SIDE VIEW
FIGURE 2

TABLE 1 UNIT DIMENSIONS

Model Numbers

A

ML18XC2-024-230A

28.25 (718)

ML18XC2-036-230A

28.25 (718)

ML18XC2-048-230A

32.25 (817)

ML18XC2-060-230A

32.25 (817)

B 29.25 (743) 33.25 (845) 33.25 (845) 43.25 (1099)

STEP 1 ­ SETTING THE UNIT (Continued) ­ Unit Placement

CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.

WARNING
To prevent personal injury, as well as damage to panels, unit or structure, observe the following:
While installing or servicing this unit, carefully stow all removed panels so that the panels will not cause injury to personnel, objects or nearby structures. Also, take care to store panels where they will not be subject to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions (especially wind) that may cause panels to be blown around and damaged.
NOTICE!
Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil, causing the rubber to degrade. Failure to follow this notice could result in damage to roof surface.

IMPORTANT
This unit must be matched with an indoor coil as specified with AHRI. For AHRI Certified system matchups and expanded ratings, visit www.LennoxPros.com Coils previously charged with HCFC-22 must be flushed.

IMPORTANT
Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit performance and longevity.
PLACEMENT
INSTALL UNIT AWAY FROM WINDOWS

TWO 90º ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION
FIGURE 3

SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.

BUILDING STRUCTURE

DISCHARGE AIR

MOUNTING SLAB

FIGURE 4

GROUND LEVEL

STEP 2 ­ REFRIGERANT PIPING ­ Flushing Existing Line Set & Indoor Coil

WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.

Page 2

IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyvinyl ether (PVE) oils are used in Lennox variable-capacity units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device and reduce system performance and capacity. Failure to properly flush the system per this instruction and the detailed Installation and Service Procedures manual will void the warranty.
Flush the existing line set per the following instructions. For more information, refer to the Installation and Service Procedures manual available on LennoxPros.com. CAUTION - DO NOT attempt to flush and re-use existing line sets or indoor coil when the system contains contaminants (i.e., compressor burn out).
If a new line set is being installed, size the piping per table 2.
WARNING
When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.

WARNING
Fire, Explosion and Personal Safety hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/ or an explosion, that could result in property damage, personal injury or death.
LIQUID LINE FILTER DRIER INSTALLATION The provided filter drier must be field installed in the liquid line between the outdoor unit's liquid line service valve and the indoor coil's metering device (fixed orifice or TXV) as illustrated in figure 5. This filter drier must be installed to ensure a clean, moisture-free system. Failure to install the filter drier will void the warranty. A replacement filter drier is available from Lennox. See Brazing Connections page 6 for special procedures on brazing filter drier connections to the liquid line.
Typical Liquid Line Filter Drier Installation
BRAZE CONNECTION POINTS

LIQUID LINE SERVICE VALVE
OUTDOOR UNIT

LINE

LIQUID LINE FILTER DRIER

FIGURE 5

LIQUID LINE

Model Number
ML18XC2-024-230
ML18XC2-036-230 ML18XC2-048-230 ML18XC2-060-230

TABLE 2 REFRIGERANT LINE SET ­ INCHES (MM)

Valve Size Connections

Liquid Line

Suction Line

3/8" (10 mm)

3/4" (19 mm)

L15 Line Set Model
L15-41-20 L15-41-30 L15-41-40 L15-41-50

Recommended Line Sets

Line Set Length

Catalog Number

20 feet (6.1 m) 30 feet (9.1 m) 40 feet (12.2 m) 50 feet (15.2 m)

89J56 89J57 89J58 89J59

L15-65-30

30 feet (9.1 m)

89J60

3/8" (10 mm)

7/8" (22 mm)

L15-65-40

40 feet (12.2 m)

89J61

L15-65-50

50 feet (15.2 m)

89J62

3/8" (10 mm)

1-1/8" (29 mm) *

Field-fabricated

N/A

N/A

* Some applications may require a field-provided 1-1/8" to 7/8" adapter.

NOTE - When installing refrigerant lines longer than 50 feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual available on LennoxPros.com (Corp. 9351-L9), or contact the Technical Support Department Product Application group for assistance.
NOTE - For new or replacement line set installation, refer to Service and Application Note - Corp. 9112-L4 (C-91-4).

Page 3

LINE SET

IMPORTANT -- Refrigerant lines must not contact structure.

INSTALLATION
Line Set Isolation - The following illustrations are examples of proper refrigerant line set isolation:

REFRIGERANT LINE SET -- TRANSITION FROM VERTICAL TO HORIZONTAL

ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER

AUTOMOTIVE MUFFLER-TYPE HANGER

REFRIGERANT LINE SET -- INSTALLING VERTICAL RUNS (NEW CONSTRUCTION SHOWN)

NOTE - Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.

IMPORTANT - Refrigerant lines must not contact wall

OUTSIDE WALL

SUCTION LINE

LIQUID LINE

WALL STUD

STRAP LIQUID LINE TO SUCTION LINE

NON-CORROSIVE METAL SLEEVE

LIQUID LINE
SUCTION LINE WRAPPED IN ARMAFLEX

WOOD BLOCK BETWEEN STUDS

WIRE TIE INSIDE WALL STRAP NON-CORROSIVE METAL SLEEVE WIRE TIE
WOOD BLOCK WIRE TIE STRAP

REFRIGERANT LINE SET -- INSTALLING HORIZONTAL RUNS

To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.

8 FEET (2.43 METERS)

WIRE TIE (AROUND SUCTION LINE ONLY)

STRAPPING MATERIAL (AROUND
SUCTION LINE ONLY)

FLOOR JOIST OR ROOF RAFTER

TAPE OR WIRE TIE

8 FEET (2.43 METERS)

NON-CORROSIVE METAL SLEEVE

TAPE OR WIRE TIE
FLOOR JOIST OR ROOF RAFTER

STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.

SLEEVE

SUCTION LINE WRAPPED WITH ARMAFLEX

OUTSIDE WALL

LIQUID LINE

PVC PIPE

CAULK
FIBERGLASS INSULATION

NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.

FIGURE 6

Page 4

STEP 2 ­ REFRIGERANT PIPING ­ Removing Existing Indoor Metering Device

1A TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
DISTRIBUTOR TUBES LIQUID LINE ORIFICE HOUSING
TEFLON® RING FIXED ORIFICE

OR

1B TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE (UNCASED COIL ONLY)
DISTRIBUTOR TUBES

STUB END
LIQUID LINE ORIFICE HOUSING

CHECK EXPANSION
VALVE
TEFLON® RING

BRASS NUT

TEFLON® RING

SENSING LINE

DISTRIBUTOR ASSEMBLY

REMOVE AND DISCARD WHITE TEFLON® SEAL
(IF PRESENT)

LIQUID LINE ASSEMBLY (INCLUDES STRAINER)

A - On fully cased coils, remove the coil access and plumbing panels.

DISTRIBUTOR ASSEMBLY

EQUALIZER LINE

LIQUID LINE ASSEMBLY WITH
BRASS NUT

B sembly.
C - Using two wrenches, disconnect liquid line from liquid line ing. T cess.
D - Remove and discard fixed orifice, valve stem assembly (if present) and Teflon® washer as illustrated above.
E - Use a field-provided fitting to temporarily reconnect the liquid line to the indoor unit's liquid line orifice housing.

MALE EQUALIZER LINE FITTING
SENSING BULB

VAPOR LINE

LIQUID LINE

A - On fully cased coils, remove the coil access and plumbing panels.
B - Remove any shipping clamps from the liquid line and distributor assembly.
C - Disconnect the equalizer line from the check expansion valve equalizer line fitting on the vapor line.

2 CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE

D - Remove the vapor line sensing bulb.
E - Disconnect the liquid line from the check expansion valve at the liquid line assembly.

CYLINDER CONTAINING CLEAN HCFC-22 TO BE USED FOR FLUSHING (Positioned to deliver liquid
A refrigerant)

GAUGE MANIFOLD

F - Disconnect the check expansion valve from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
G - Remove and discard check expansion valve and the two Teflon®

1

LOW

HIGH

rings.

VAPOR LINE SERVICE VALVE

NEW OUTDOOR

H - Use a field-provided fitting to temporarily reconnect the liquid line to the indoor unit's liquid line orifice housing.

EXISTING INDOOR
UNIT

UNIT
B

OPENED

CLOSED

3FLUSHING LINE SET The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.

VAPOR LIQUID

LIQUID LINE SERVICE VALVE
RECOVERY CYLINDER
D

TANK RETURN

C

INLET

DISCHARGE

RECOVERY MACHINE

A - Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor
unit coBil.
B - Position the cylinder of clean HCFC-22 for delivery of liquid refrigerant and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.

C - After all of the liquid refrigerant has been recovered, switch the

A - HCFC-22 cylinder with clean refrigerant (positioned to deliver liquid refrigerant) to the vapor service valve.

recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull the system

B - HCFC-22 gauge set (low side) to the liquid line valve.

down to 0.

C - HCFC-22 gauge set center port to inlet on the recovery machine with an D - Close the valve on the inverted HCFC-22 drum and the gauge set

empty recovery tank connected to the gauge set.

valves. Pump the remaining refrigerant out of the recovery

D - Connect recovery tank to recovery machine per machine instructions.

machine and turn the machine off.

FIGURE 7

Page 5

STEP 2 ­ REFRIGERANT PIPING ­ Brazing Procedures

1CUT AND DEBUR Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.

2 CAP AND CORE REMOVAL Remove service cap and core from both the vapor and liquid line service ports.

CUT AND DEBUR

LINE SET SIZE MATCHES SERVICE VALVE CONNECTION

COPPER TUBE STUB

SERVICE VALVE CONNECTION

REDUCER

SERVICE PORT CAP

SERVICE PORT CORE

SERVICE PORT CORE
LIQUID LINE SERVICE VALVE

SERVICE PORT CAP
VAPOR LINE SERVICE VALVE

LINE SET SIZE IS SMALLER THAN CONNECTION
REFRIGERANT LINE

DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION

3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND VAPOR LINE SERVICE VALVES

Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the vapor line service port valve.

A - Connect gauge set low pressure side to liquid line service valve (service port).
B - Connect gauge set center port to bottle of nitrogen with regulator.

LOW

HIGH

USE REGULATOR TO FLOW NITROGEN AT 1 TO 2 PSIG.

C - Remove core from valve in vapor line service port to allow nitrogen to escape.

ATTACH GAUGES

VAPOR SERVICE PORT MUST BE OPEN
C TO ALLOW EXIT POINT FOR NITROGEN

INDOOR UNIT

VAPOR LINE

VAPOR LINE SERVICE VALVE

B
OUTDOOR UNIT

LIQUID LINE

LIQUID LINE SERVICE VALVE

NITROGEN
A WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY FROM SERVICE VALVE.

FIGURE 8

CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.

WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.

Page 6

4 WRAP SERVICE VALVES To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use additional water-saturated cloths underneath the valve body to protect the base paint.
5 FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
6 BRAZE LINE SET Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths must remain water-saturated throughout the brazing and cool-down process.
LIQUID LINE SERVICE VALVE

WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT -- Allow braze joint to cool. Apply additional water-saturated cloths to help cool brazed joint. Do not remove water-saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water-saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing the line set! The braze, when complete, must be quenched with water to absorb any residual heat. Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated. Refer to Installation and Service Procedures manual found on LennoxPros.com.

WATER-SATURATED CLOTH
LIQUID LINE
VAPOR LINE SERVICE VALVE
WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.

VAPOR LINE

WATER-SATURATED CLOTH

7 PREPARATION FOR NEXT STEP After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both services valves to cool piping. Once piping is cool, remove all water-saturated cloths.

FIGURE 8 (CONTINUED)

Page 7

STEP 2 ­ REFRIGERANT PIPING ­ Install Indoor Expansion Valve
This outdoor unit is designed for use in systems that use an expansion valve metering device (purchased separately) at the indoor coil. See the ML18XC2 Product Specifications bulletin (EHB) for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit.

INDOOR EXPANSION VALVE INSTALLATION

TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
DISTRIBUTOR TUBES

(Uncased Coil Shown)

LIQUID LINE ORIFICE HOUSING

STUB END

CHECK EXPANSION
VALVE
TEFLON® RING

DISTRIBUTOR ASSEMBLY

TEFLON® RING
EQUALIZER LINE

SENSING LINE

1/2 Turn 3 - Install one of the provided Teflon® rings around the

stubbed end of the check expansion valve and lightly
lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.

11 12 10
9

1 2 3

4 - Attach the stubbed end of the check expansion valve to the liquid line orifice housing. Finger tighten and use an

8 76

4 5

appropriately sized wrench to turn an additional 1/2 turn

clockwise as illustrated in the figure above, or tighten to

20 ft-lb.

5 - Place the remaining Teflon® washer around the other

end of the check expansion valve. Lightly lubricate connector threads and expose surface of the Teflon®

ring with refrigerant oil.

6 - Attach the liquid line assembly to the check expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft-lb.

LIQUID LINE ASSEMBLY WITH
BRASS NUT

SENSING BULB INSTALLATION
1 - Attach the vapor line sensing bulb in the proper orientation as illustrated belowusing the clamp and screws provided.

MALE EQUALIZER LINE FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)

VAPOR LINE

LIQUID LINE

ON LINES SMALLER THAN 3/4", MOUNT SENSING BULB AT EITHER THE 1 OR 11 O'CLOCK POSITION.

Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
1 - Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.
2 - Remove the field-provided

ON 3/4" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 3 OR 9 O'CLOCK POSITION.

sembly.

NOTE - NEVER MOUNT THE SENSING BULB ON BOTTOM OF LINE.

FLARE SEAL CAP

FLARE NUT

NOTE - Though it is preferred to have the sensing bulb

installed on a horizontal run of the vapor line, installation

OR

COPPER FLARE SEAL BONNET

on a vertical run of piping is acceptable if necessary. See figure to right for proper bulb orientation on vert-

ical run of piping.

MALE BRASS EQUALIZER LINE FITTING

NOTE - Confirm proper thermal contact between vapor line and check/expansion bulb before insulating the sensing bulb once installed.

1/8 Turn

VAPOR LINE

2 - Connect the equalizer line from the check expansion valve tothe equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated to the right.

11 12 1

10

2

9

3

8

4

76 5

FIGURE 9

Page 8

STEP 3 ­ LEAK TEST AND EVACUATION
LEAK TEST

LOW

HIGH MANIFOLD GAUGE SET

OUTDOOR UNIT

B

A

NITROGEN

TO VAPOR SERVICE VALVE
NOTE - Position canister to deliver liquid refrigerant.
HFC-410A

1CONNECT GAUGE SET A - Connect the high pressure hose of an HFC-410A manifold gauge set to the vapor valve service port.
NOTE - Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B - With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set.
NOTE - Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
2TEST FOR LEAKS After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
A - With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
B - Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C - Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D - Adjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
E - After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
F - After leak testing, disconnect gauges from service ports.
FIGURE 10

Page 9

STEP 3 ­ LEAK TEST AND EVACUATION (Continued)

3 EVACUATION CONNECT GAUGE SET NOTE - Remove cores from service valves (if not already done).

A - Connect low side of manifold gauge set with 1/4 SAE in-line tee to vapor line service valve
B - Connect high side of manifold gauge set to liquid line service valve
C - Connect available micron gauge connector on the 1/4 SAE in-line tee.
D - Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC-410A and nitrogen containers. NOTE ister to deliver liquid NITROGEN refrigerant.

OUTDOOR UNIT
A

1/4 SAE TEE WITH SWIVEL COUPLER

500

C

MICRON GAUGE

LOW
MANIFOLD GAUGE SET
TO VAPOR SERVICE VALVE

HFC-410A

B

VACUUM PUMP

TO LIQUID LINE SERVICE VALVE

HIGH

D

4 EVACUATE THE SYSTEM A - Open both manifold valves and start the vacuum pump.

RECOMMEND MINIMUM 3/8" HOSE

B - Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).

NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.

NOTE - The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C - When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:

WARNING !

Close manifold gauge valves. Close valve on vacuum pump.

Possible equipment damage.

Turn off vacuum pump.

Avoid deep vacuum operation. Do not use

Disconnect manifold gauge center port hose from vacuum pump.

compressors to evacuate a system.

Attach manifold center port hose to a nitrogen cylinder with pressure Extremely low vacuum can cause internal

regulator set to 150 psig (1034 kPa) and purge the hose.

arcing and compressor failure. Damage

Open manifold gauge valves to break the vacuum in the line set and indoor caused by deep vacuum operation will

unit.

void warranty.

Close manifold gauge valves.

D - Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the

nitrogen from the line set and indoor unit.

E - Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the

absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump

and closing the manifold gauge valves.

F - When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a

cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the

line set and indoor unit.

G - Perform the following: Close manifold gauge valves.

1/6 TURN

Shut off HFC-410A cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure.

11 12 1

10

2

Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6) of a turn as illustrated.

9
8 76

3 4
5

FIGURE 11

Page 10

STEP 4 ­ ELECTRICAL ­ Circuit Sizing and Wire Routing

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC - 40 VA minimum).

WARNING
Fire Hazard. Use of aluminum wire with this product may result in a fire, causing property damage, severe injury or death. Use copper wire only with this product.
WARNING
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specifications bulletin (EHB) and unit rating plate.

WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures

WARNING
Electrostatic discharge can affect electronic components. Take care during unit installation and service to protect the unit's electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge.

SIZE CIRCUIT AND INSTALL SERVICE DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
MAIN FUSE BOX/ BREAKER PANEL
SERVICE DISCONNECT
SWITCH

INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT

5 FEET (1.5M)

NOTE - Units are approved for use only with copper conductors. Ground unit at disconnect switch or connect to an earth ground.

NOTE - 24VAC, Class II circuit connections are made in the control panel.

FIGURE 12

Page 11

UNIT LOW VOLTAGE CONNECTIONS
C WIRE NUTS
ACUTOUT WITH
GROMMET
B 24V CONTROL WIRES

BLUE BLACK
YELLOW

HIGH VOLTAGE FIELD WIRING FACTORY WIRING LOW VOLTAGE (24V) FIELD WIRING

WIRE RUN LENGTH LESS THAN 100' (30 METERS) MORE THAN 100' (30 METERS)

AWG# INSULATION TYPE 18 TEMPERATURE RATING 16 35ºC MINIMUM.

D TIGHTEN WIRE TIE

A. Run 24VAC control wires through cutout with grommet. B. Run 24VAC control wires through wire tie. C. Make 24VAC control wire connections using field-provided wire
nuts. D. Tighten wire tie to security 24V control wiring.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES) GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS SEPARATION OF FIELD-INSTALLED LOW-AND HIGH-VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.

FIGURE 13

24VAC Control Wiring Diagrams (Field Installed)

EL280, EL295, EL296 THERMOSTAT

SLP98, SL28UH, SL280DF THERMOSTAT

ML18XC2 5
BLUE

ML18XC2 5
BLUE

CBA27

CBA38MV

THERMOSTAT

2

ML18XC2

1

ML18XC2

RED
BROWN 3

4 BLUE

5

Y2 BLUE

THERMOSTAT

Air handler shipped with jumpers installed between W1 and W2 1 and W2 and W3.
R connection required for air conditioner with LSOM. Resistor kit 2 (CAT #47W97) required when connection ComfortSense 7000
with LSOM 2. 3 L connection wired on units with LSOM. 4 Remove jumper for 2-stage cooling. 5 Clip onboard Y1 to Y2 for 2-stage cooling.
NOTE - Refer to furnace, blower coil and accessory instructions for additional wiring configurations with other optional controls.
FIGURE 14. Typical Control Wiring
Page 12

ML18XC2-024 ML18XC2-036 ML18XC2-048

START CAPACITOR

GROUND LUG

B4 OUTDOOR FAN (LEADED)

2

ORANGE-RUN BLACK-COMMON

31

PURPLECAPACITOR

F

C

S87 LOW PRESSURE SWITCH
S4 HIGH PRESSURE SWITCH

B1 COMPRESSOR 2
C SR

10

L34

K1

COMPRESSOR

4

K31 POTENTIAL

CONTACTOR

RELAY

5 (OPTIONAL)

C12 H DUAL
CAPACITOR

CRANKCASE THERMOSTAT

K1-1 COMPRESSOR CONTACTOR
L1

11 S11

D4 10

BLACK

BLACK

S40
5 K31
2

B4

FAN MOTOR

R

C

B1

(LEADED)

COMPRESSOR

2

S

YELLOW

RED

13

1

PURPLE OR BROWN ORANGE

RED

12
C7 HR1

H RED
C

F C12 DUAL CAPACITOR

L34

S4
K1 BLUE

230/60/1 CRANKCASE HEATER

RED

L2
EQUIPMENT GROUND

3 EL196E ML180E ML193E EL180E EL195E ML196E

INDOOR UNIT TB1
R

THERMOSTAT A2
R

W

W1

W2

G

G

YELLOW

Y

Y1

BLUE

Y2

BLACK

C

C

YELLOW BLUE
BLACK

SLP99V SL297V SL280V ML296V

ML180V EL280E EL 296E SLP99

INDOOR UNIT A92 TB1 5

THERMOSTAT A2

W914 DS

D

R

R

W951 O

H

6 W1

W1

W2

W2

G

G

Y1

Y1

4

Y2

Y2

C

C

K1-1

COMPRESSOR

CONTACTOR

RED

L1

RED L2
EC MOTOR CONNECTION (ML18XC2-060)

YELLOW

Y1

BLUE

S87

Y2

BLACK C

YELLOW BLUE BLACK

CBA25UH, CBA27UHE

& CBA38MV

INDOOR

UNIT

THERMOSTAT

TB1

A2

R

R

9

W3

W2

W2

W1

W1

7

G

G

DS
O
Y1 4
Y2
C

H D 8
Y1 Y2 C

EQUIPMENT GROUND

1 NOTEFOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE
2 REFER TO COMPRESSOR IN UNIT FOR ACTUAL TERMINAL ARRANGEMENT
3 WARNINGELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH.UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
4 REMOVE JUMPER FOR TWO STAGE COOL
5 ON A92 CUT ONBOARD W914 JUMPER FROM D5 TO R, WHEN HUMIDITY CONTROL IS USED
6 ON A92 DO NOT CUT ONBOARD W951 JUMPER FROM R TO O. IT IS USED FOR APPLICATIONS FOR CONDENSING UNITS
7 FOR CONDENSING UNIT APPLICATIONS USE R TO O JUMPER. REMOVE IN HEAT PUMP APPLICATIONS
8 REMOVE DS TO Y1 JUMPER WHEN HUMIDITY CONTROL IS USED
9 WHEN TWO STAGE THERMOSTAT IS USED, CONNECT SECOND STAGE HEAT BULB TO TERMINAL "W2", AND REMOVE JUMPER BETWEEN "R" AND "W2"
10 L34 SOLENOID IS LOCATED IN COMPRESSOR. COIL IS 24VDC. DO NOT CONNECT 24VAC TO COIL TERMINALS
11 S11 IS OPTIONAL LOW AMBIENT SWITCH
12 OPTIONAL HARD START KIT MAY BE REQUIRED ON APPLICATIONS WHERE VOLTAGES ARE LESS THAN 230 VOLT KIT ICLUDES K31 AND C7 WITH ALL NECESSARY WIRING.
13 S40 AND HRI ARE USED ON 048 AND 060 UNITS ONLY
NOTEIF ANY WIRE IN THIS APPLIANCE IS REPLACED,IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING, INSULATION THICKNESS, AND TERMINATION.
NOTE-MINIMUM TRANSFORMER REQUIRED IN INDOOR UNIT-40 VA
LINE VOLTAGE FIELD INSTALLED CLASS II VOLTAGE FIELD WIRING DENOTES OPTIONAL COMPONENTS

LENNOX
ML18XC2-024 ML18XC2-036

COOLING CONDENSING
ML18XC2-048 ML18XC2-060
Supersedes

C 2011
FIGURE 15. Typical Field Wiring

Litho U.S.A.

Page 13

STEP 5 ­ UNIT START-UP

IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

1 - Rotate fan to check for binding.
2 - Inspect all factory- and field-installed wiring for loose connections.
3 - After evacuation is complete, open the liquid line and vapor line service valve stems to release the refrigerant charge (contained in outdoor unit) into the system.
4 - Replace the stem caps and tighten to the value listed in table 2.
5 - Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6 - Connect manifold gauge set for testing and charging.
7 - Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
8 - Recheck voltage while the unit is running. Power must be within range shown on the unit nameplate.
9 - Check system for sufficient refrigerant using the procedures outlined under Checking Refrigerant Charge.
OPERATING MANIFOLD GAUGE SET AND SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory-installed valve stem. Figures 14 and 15 provide information on how to access and operate both angle- and ball-type service valves.
Torque Requirements
When servicing or repairing heating, ventilating and air conditioning components, ensure the fasteners are appropriately tightened. Table 3 lists torque values for fasteners.

TABLE 3 ­ TORQUE REQUIREMENTS

Parts

Recommended Torque

Service valve cap

8 ft.-lb.

11 NM

Sheet-metal screws 16 in.-lb. Machine screws #10 28 in.-lb.

2 NM 3 NM

Compressor bolts

90 in.-lb.

Gauge port seal cap 8 ft.-lb.

10 NM 11 NM

IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted snugly over the cap before tightening.

Using Manifold Gauge Set
When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings. Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING BALL-TYPE SERVICE VALVE
1 - Remove stem cap with an appropriately sized wrench.
2 - Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.

TO OPEN, ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE, ROTATE STEM CLOCKWISE 90°.
SERVICE PORT SERVICE PORT
CORE SERVICE PORT
CAP

BALL (SHOWN CLOSED)
VALVE STEM
STEM CAP

FIGURE 16
OPERATING ANGLE-TYPE SERVICE VALVE
1 - Remove stem cap with an appropriately sized wrench. 2 - Use a service wrench with a hex-head extension (3/16" for liquid
line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT CAP SERVICE PORT CORE
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE

STEM CAP ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED) When service valve is OPEN, the service port is
open to line set, indoor and outdoor unit.
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
ANGLE-TYPE SERVICE VALVE (FRONT-SEATED CLOSED)
When service valve is CLOSED, the service port is open to the line set and indoor unit.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
FIGURE 17

Page 14

ACCESS SERVICE PORT
A service port cap protects the service port core from contamination and serves as the primary leak seal.

1 - Remove service port cap with an appropriately sized wrench.

2 - Connect gauge set to service port.

3 - When testing is completed, replace service port cap and tighten as follows:

With torque wrench, finger tighten and torque

cap per table 2.

1/6 TURN

Without torque wrench, finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

11 12 10

1 2

Reinstall Stem Cap

9

3

87 6

4 5

Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:

With torque wrench, finger tighten and then torque cap per table 2.
Without torque wrench, fi en and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.

1/12 TURN

11 12 10

1 2

9

3

8 7

6

4 5

FIGURE 18

Checking and Adding System Charge

The ML18XC2 unit is factory-charged with enough HFC410A refrigerant to accommodate a 15-foot length of refrigerant piping. For refrigerant piping greater than 15 feet, calculate the additional charge using the table below. Then add the additional charge specified for the specific indoor coil match-up listed on the unit charging sticker.
Charge should be checked and adjusted using the tables provided on the charging procedure sticker on the unit access panel. Detailed information is given in the ML18XC2 Installation and Service Procedures manual, which is available on LennoxPros.com.

Refrigerant Charge per Line Set Length

LIQUID LINE DIA.

OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M) LINE SET*

3/8" (9.5 MM)

3 OUNCES PER 5' (85 G PER 1.5 M)

*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
NOTE ­ Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.

High Pressure Switch (S4)
This unit is equipped with a high pressure switch which is located on the liquid line. The SPST, normally closed pressure switch opens when liquid line pressure rises above the factory setting of 590 ± 15 psig and automatically resets at 418 ± 15 psig.

Low Pressure Switch
This unit is equipped with a low pressure switch which is located on the compressor suction line. The SPST, normally closed pressure switch opens when suction line pressure drops below the factory setting of 40 ± 5 psig and automatically resets at 95 ± 5 psig.
Homeowners Information
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. The system should be inspected and serviced before each cooling and heating season by a licensed professional HVAC service technician (or equivalent).
Homeowner Maintenance
The following maintenance may be performed by the homeowner.
· Contact a licensed professional HVAC technician to schedule inspection and maintenance appointments for your equipment before each heating and cooling season.
· Check the indoor unit filter each month and replace the filter, if necessary.
· Have your Lennox dealer show you where your indoor unit filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. Disposable filters should be replaced with a filter of the same type and size.
· Check the indoor unit drain line for obstructions monthly. The indoor coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
· Check the area around the outdoor unit monthly and remove any obstructions that may restrict airflow to the outdoor unit. This would include grass clippings, leaves, or papers that may have settled around the unit.
· Trim shrubbery away from the unit and periodically check for debris which collects around the unit.
· During the winter months, keep the snow level below the louvered panels.
NOTE - The filter and all access panels must be in place any time the unit is in operation. If you are unsure about the filter required for your system, call your Lennox dealer for assistance.

Page 15

IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of the steel and aluminum parts, diminish performance and affect longevity of the unit.
Thermostat Operation See the thermostat homeowner manual for instructions on how to operate your thermostat.
Pre-Service Check If your system fails to operate, check the following before calling for service:
· Verify room thermostat settings are correct.
· Verify that all electrical disconnect switches are ON.
· Check for any blown fuses or tripped circuit breakers.
· Verify unit access panels are in place.
· Verify air filter is clean.
If service is needed, locate and write down the unit model number and have it handy before calling.
Professional Maintenance
NOTICE !
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum coils may be damaged by exposure to solutions with a pH below 5 or above 9. The aluminum coil should be cleaned using potable water at a moderate pressure (less than 50psi). If the coil cannot be cleaned using water alone, Lennox recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt).
Your heating and air conditioning system should be inspected and maintained twice each year (before the start of the cooling and heating seasons) by a licensed professional HVAC technician. You can expect the technician to check the following items. These checks may only be conducted by a licensed professional HVAC technician.
Outdoor Unit 1 - Inspect component wiring for loose, worn or damaged connections. Also check for any rubbing or pinching of wires. Confirm proper voltage plus amperage of outdoor unit.
2 - Check the cleanliness of outdoor fan and blade condition (cracks) and clean or replace them, if necessary.

3 - Inspect base pan drains for debris and clean as necessary.
4 - Inspect the condition of refrigerant piping and confirm that pipes are not rubbing copper-tocopper. Also, check the condition of the insulation on the refrigerant lines. Repair, correct, or replace as necessary.
5 - Test capacitor. Replace as necessary.
6 - Inspect contactor contacts for pitting or burn marks. Replace as necessary.
7 - Check outdoor fan motor for worn bearings/ bushings. Replace as necessary.
8 - Inspect and clean outdoor coils, if necessary and note any damage to coils or signs of leakage.
Indoor Unit (Air Handler or Furnace)
1 - Inspect component wiring for loose, worn or damaged connections. Confirm proper voltage plus amperage of indoor unit.
2 - Inspect and clean or replace air filters in indoor unit.
3 - Check the cleanliness of indoor blower and clean blower, if necessary.
4 - Inspect the indoor coil drain pans and condensate drains for rust, debris, obstructions, leaks or cracks. Pour water in pans to confirm proper drainage from the pan through to the outlet of the pipe. Clean or replace as necessary.
5 - Inspect and clean indoor coil, if necessary.
6 - Inspect the condition of the refrigerant lines and confirm that pipes are not rubbing copper-tocopper. Also, ensure that refrigerant pipes are not being affected by indoor air contamination. Check condition of insulation on the refrigerant lines. Repair, correct, or replace as necessary.
7 - Inspect the duct system for leaks or other problems. Repair or replace as necessary.
8 - Check for bearing/bushing wear on indoor blower motor. Replace as necessary.
9 - Indoor unit service will also include inspection and cleaning of the burners, and a full inspection of the gas valve, heat exchanger and flue (exhaust) system.
General System Test with System Operating
1 - Your technician should perform a general system test. They will turn on the air conditioner to check operating functions such as the startup and shutoff operation. They will also check for unusual noises or odors, and measure indoor/outdoor temperatures and system pressures as needed. They will check the refrigerant charge per the charging sticker information on the outdoor unit.
2 - Verify that system total static pressure and airflow settings are within specific operating parameters.
3 - Verify correct temperature drop across indoor coil.

Page 16

ML18XC2 Start-Up and Performance Checklist
Customer Indoor Unit Model Outdoor Unit Model Notes:

Address Serial Serial

START UP CHECKS Refrigerant Type:

Rated Load Amps: Condenser Fan Full Load Amps

Actual Amps Rated Volts Actual Amps:

Actual Volts

COOLING MODE Suction Pressure:

Liquid Pressure:

Supply Air Temperature:

Ambient Temperature: Return Air: Temperature:

System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required subcooling and approach temperatures.)

Subcooling:

A -- B = SUBCOOLING

Saturated Condensing Temperature (A) minus Liquid Line Temperature (B)

Approach:

A -- B = APPROACH

Liquid Line Temperature (A) minus Outdoor Air Temperature (B)

Indoor Coil Temperature Drop (18 to 22°F)

A -- B = COIL TEMP DROP

Return Air Temperature (A) minus Supply Air Temperature (B)

Page 17



References

Adobe PDF Library 17.0