Operation
Residential/Commercial Generator Sets
Models:
14RCA 14RCAL
20RCA 20RCAL
Controller:
RDC2
TP-7092 2/21a

WARNING: This product can expose you to chemicals, including carbon monoxide and benzene, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov
Kohler strongly recommends that only factory-authorized distributors or dealers install and service the generator.

Product Identification Information

Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation Specification Number Serial Number
Accessory Number Accessory Description

Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice. Controller Description
Engine Identification
Record the product identification information from the engine nameplate. Manufacturer Model Designation Serial Number

Table of Contents

Product Identification Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Section 1 Descriptions and Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.2 Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.3 Alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.4 Generator Set Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.5 Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.6 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.7 OnCue Plus Generator Management System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1.8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.8.1 Cold Weather Package Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1.8.2 Programmable Interface Module (PIM) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1.8.3 Load Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1.8.4 Battery Heater Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 1.8.5 Fuel Regulator Heater (20kW models only) . . . . . . . . . . . . . . . . . . . . . . . 18 1.8.6 Carburetor Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 1.8.7 Emergency Stop Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 1.8.8 Breather Tube Heater and Oil Heater Kit . . . . . . . . . . . . . . . . . . . . . . . . . 20 1.8.9 Oil Pressure Sensor Boot Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 1.9 Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Section 2 Generator Set Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.1 Prestart Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.2 Exercising the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.3 Generator Set Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.3.1 Local Starting and Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.3.2 Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.3.3 Remote Starting and Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.3.4 Remote emergency Stop Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.3.5 Engine Start Crank Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 2.3.6 Engine Cooldown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 2.3.7 Automatic Operation with Model RXT Transfer Switch . . . . . . . . . . . . . . 25 2.3.8 Automatic Operation with Other Transfer Switches . . . . . . . . . . . . . . . . . 26 2.4 Exercise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 2.4.1 Setting the Exerciser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 2.4.2 Unloaded Cycle Exercise with Complete System Diagnostics . . . . . . . 26 2.4.3 Unloaded Full-Speed Exercise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 2.4.4 Loaded Full-Speed Exercise (with RXT only) . . . . . . . . . . . . . . . . . . . . . . 27 2.4.5 Shutdown During Exercise (Advanced Diagnostic) . . . . . . . . . . . . . . . . . 27 2.4.6 Power Failure During Exercise Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.5 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.5.1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.5.2 Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.5.3 Shutdown During Exercise (Advanced Diagnostic) . . . . . . . . . . . . . . . . . 28 2.5.4 ATS Communication Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.5.5 Resetting the Controller after a Fault Shutdown . . . . . . . . . . . . . . . . . . . 28 2.5.6 Faults Related to Paralleling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Section 3 RDC2 Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1 RDC2 Generator Set/ Transfer Switch Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 3.2 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.2.1 Controller Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

TP-7092 2/21

Table of Contents

Table of Contents, continued

3.2.2 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3.2.3 LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 3.3 Controller Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3.4 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3.5 Changing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3.6 Setting the Exerciser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 3.6.1 Setting the Exerciser at Controller Power-up . . . . . . . . . . . . . . . . . . . . . . 40 3.6.2 Changing the Exercise Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 3.7 RDC2 Controller Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 3.8 Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 3.9 Overview Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3.10 Engine Metering Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 3.11 Generator Metering Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 3.12 Generator Set Information Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3.13 Genset Run Time Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3.14 Genset System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 3.15 ATS Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 3.16 ATS Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 3.17 Date and Time Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 3.18 Networking Information Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 3.18.1 Networking Status Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 3.18.2 Networking Configuration Submenu (OnCue Password) . . . . . . . . . . . . 52 3.18.3 RBUS Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 3.18.4 Remote Devices Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 3.19 Programmable Interface Module (PIM) Status Menu . . . . . . . . . . . . . . . . . . . . . . . 56 3.20 Load Control Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 3.21 Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Section 4 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
4.1 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 4.1.1 Service Schedule, 14 kW Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 4.1.2 Service Schedule, 20 kW Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.2 Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 4.2.1 Low Oil Pressure Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 4.2.2 Oil Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 4.2.3 Engine Oil Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 4.2.4 Oil Change Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 4.2.5 Resetting the Maintenance Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 4.2.6 Oil Cooler (20RCA/RCAL only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4.3 Spark Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 4.4 Air Cleaner Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4.4.1 Air Cleaner, 14 kW Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 4.4.2 Air Cleaner, 20 kW Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 4.5 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 4.6 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 4.7 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 4.7.1 Cleaning the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 4.7.2 Checking Electrolyte Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 4.7.3 Checking Specific Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 4.8 Storage Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 4.8.1 Lubricating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 4.8.2 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 4.8.3 Cylinder Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 4.8.4 Exterior Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 4.8.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Table of Contents

TP-7092 2/21

Table of Contents, continued
Section 5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.2 Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.3 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.3.1 Controller Internal Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.3.2 Line Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.4 USB Port and Auxiliary Winding Mini-Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.5 Stop Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 5.6 Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 5.7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

TP-7092 2/21

Table of Contents

Notes

6

TP-7092 2/21

Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS.

Electromechanical

equipment,

including generator sets, transfer

switches, switchgear, and accessories,

can cause bodily harm and pose

life-threatening danger when

improperly installed, operated, or

maintained. To prevent accidents be

aware of potential dangers and act

safely. Read and follow all safety

precautions and instructions. SAVE

THESE INSTRUCTIONS.

This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE NOTICE is used to address practices not related to physical injury.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.

Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.

WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.

TP-7092 2/21

Safety Precautions and Instructions 7

Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.

Battery short circuits. Explosion

can cause severe injury or death.

Short circuits can cause bodily injury

and/or

equipment

damage.

Disconnect the battery before

generator set installation or

maintenance. Remove all jewelry

before servicing the equipment. Use

tools with insulated handles. Remove

the negative (- ) lead first when

disconnecting the battery. Reconnect

the negative (- ) lead last when

reconnecting the battery. Never

connect the negative (- ) battery cable

to the positive (+) connection terminal

of the starter solenoid. Do not test the

battery condition by shorting the

terminals together.

Engine Backfire/Flash Fire
WARNING

Risk of fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.

Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death. Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING

Carbon monoxide. Can cause severe fainting, or death.

nausea,

The exhaust system must be leakproof and routinely inspected.

Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building's occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer's instructions.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
Light-headedness, dizziness Physical fatigue, weakness in joints and muscles Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.

8 Safety Precautions and Instructions

TP-7092 2/21

Fuel System
WARNING

Hazardous Noise
CAUTION

WARNING

Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6- 8 ounces per square inch (10- 14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.

Hazardous noise. Can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death. This equipment must be installed and serviced by qualified electrical personnel.
DANGER
Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.

Hazardous voltage. Backfeed to the utility system. Can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Welding on generator set will cause serious damage to engine electronic controls components. Disconnect all engine electronic control connections before welding.
Grounding electrical equipment. Hazardous voltage will cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the generator set perform the following steps: (1) Remove the battery cables, negative (- ) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine batterycharging alternator connections. (5) Attach the weld ground connection close to the weld location.

TP-7092 2/21

Safety Precautions and Instructions 9

Connecting the battery and the battery charger. Hazardous voltage will cause severe injury or death. Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).

Short circuits.

Hazardous

voltage/current will cause severe

injury or death. Short circuits can

cause bodily injury and/or equipment

damage. Do not contact electrical

connections with tools or jewelry while

making adjustments or repairs.

Remove all jewelry before servicing the

equipment.

Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.

Heavy Equipment
WARNING

Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.

Notice
NOTICE Canadian installations only. For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.

Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage. Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools.
10 Safety Precautions and Instructions

TP-7092 2/21

Introduction

This manual provides operation and maintenance instructions for residential/commercial model 14/20RCA/RCAL generator sets equipped with the RDC2 generator set/transfer switch controller. See Figure 1.
Kohler strongly recommends that only factoryauthorized distributors or dealers install and service the generator.
Have the generator set installed by an authorized distributor/dealer or service technician. Refer to the Installation Manual for installation instructions.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.

Figure 1 Generator Set

aac11780

List of Related Literature
Figure 2 identifies literature available for the generator sets covered in this manual and related accessories. Only trained and qualified personnel should install or service the generator set.

Generator Set Literature

Specification Sheet, 14RCA/L

Specification Sheet, 20RCA/L

Installation Manual, Generator Set

Service Manual, Generator Set

Transfer Switch Literature

Operation/Installation Manual, Model RXT Automatic Transfer Switch

Operation/Installation Manual, Model RDT Automatic Transfer Switch

Accessory Literature

User Guide, OnCue Plus

Technical Manual, OnCue Plus

Operation Manual, SiteTech Software

Installation Instructions, Load Shed Kit

Installation Instructions, Programmable Interface Module (PIM)

Installation Instructions, PowerSync Automatic Paralleling Module (APM)

Installation Instructions, Carburettor Heater Kit

Installation Instructions, Fuel Regulator Heater Kit

Installation Instructions, Battery Heater Kit

Installation Instructions, Breather Tube Heater and Oil Heater

Installation Instructions, Oil Pressure Sensor Boot Kit

Installation Instructions, Remote Emergency Stop (Lockable)

Switch

Figure 2 Related Literature

Part Number G4-270 G4-272 TP-7091 TP-7093
TP-6807 TP-6345
TP-7006 TP-7007 TP-6701 TT-1609 TT-1584 TT-1596 TT- 1297 TT- 1482
TT- 1569 TT- 1634 TT- 1709 TT- 1717
TT- 1795

TP-7092 2/21

Introduction 11

Nameplate
The following illustration shows a typical generator set nameplate. Copy the model, serial, and specification numbers from the nameplate into the spaces provided in the product information section on the inside front cover of this manual. See the service views in Section 1.9 for the nameplate location.

Genset Model Spec Number Serial Number Material Number

Service Duty

Amps

kW

Voltage

Phase

kVA

Alt Model

RPM

PF

Insulation

Battery

Hz

MFG Date

Fuel

GM12070
Emission Information
The Kohler Model CH740 engine used on the 14RCA/RCAL generator set is certified to operate using natural gas or propane fuel.
The Kohler Model CH1000 engine used on the 20RCA/RCAL generator sets is certified to operate using natural gas or propane fuel for emergency standby use only. This generator set is certified by the U.S. EPA for emergency standby operation backing up a reliable utility source. Operation outside these guidelines is a violation of national EPA regulations.
The Emission Compliance Period referred to on the Emission Control or Air Index label indicates the number of operating hours for which the engine has been shown to meet CARB or EPA emission requirements. Figure 3 provides the engine compliance period (in hours) associated with the category descriptor, which may be found on the certification label.

Emission Compliance Period

EPA

Category C 250 hours

Category B 500 hours

Category A 1000 hours

CARB

Moderate 125 hours

Intermediate 250 hours

Extended 500 hours

Figure 3 Emission Compliance Period

Refer to the certification label for engine displacement.

The exhaust emission control system for the CH740 engines (14RCA/L) is EM for U.S. EPA, California, and Europe.

The exhaust emission control system for the CH1000 engine (20RCA/L) is EM for U.S. EPA, California, and Europe.

Generator Set Application
Kohler Co. ensures that all Kohler generator sets are certified to applicable standards for their intended application. It is the owner/operator's responsibility to operate Kohler generator sets exclusively according to the directions provided in the accompanying operation manuals.
Kohler generator sets designated as Stationary Standby, Emergency or Emergency Standby may only be operated for emergency power generation and for maintenance/testing. Emergency power generation is limited to power production when electric power from a local utility (or the normal power source, if the facility runs on its own power production) is interrupted. Stationary non-emergency application of a Standby, Emergency, or Emergency Standby rated generator set is not allowed.
The U.S. Clean Air Act explicitly prohibits using Emergency Standby generator sets as a primary electric power source regardless of whether a site is connected to the electrical grid. Emergency Standby generators may NOT be used to power sites which are not connected to an electric utility.
Owners/operators must ensure that the generator is operated, exercised, and maintained according to this operation manual. Owners/operators must retain maintenance records.

12 Introduction

TP-7092 2/21

For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
Visit the Kohler Co. website at KOHLERPower.com.
Look at the labels and decals on your Kohler product or review the appropriate literature or documents included with the product.
Call toll free in the US and Canada 1-800-544-2444.
Outside the US and Canada, call the nearest regional office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler EMEA Headquarters Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific Kohler Asia Pacific Headquarters Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455

Service Assistance
China North China Regional Office, Beijing Phone: (86) 10 6518 7950 (86) 10 6518 7951 (86) 10 6518 7952 Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka India Regional Office Bangalore, India Phone: (91) 80 3366208 (91) 80 3366231 Fax: (91) 80 3315972
Japan, Korea North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727

TP-7092 2/21

Service Assistance 13

Notes

14 Service Assistance

TP-7092 2/21

Section 1 Descriptions and Service Views

1.1 Introduction
The generator set specification sheets provide specific generator and engine information. Refer to the spec sheet for data not supplied in this manual. Consult the generator set service manual, engine operation manual, and engine service manual for additional specifications. Obtain copies of the latest spec sheets, manuals, diagrams, and drawings from your local distributor/ dealer.

1.2 Engine
The generator set has a four-cycle, twin cylinder, aircooled Kohler engine. The engine operates on cleanburning natural gas or LPG. Engine features include:
Efficient overhead valve design and full pressure lubrication for maximum power, torque, and reliability under all operating conditions.
Dependable, maintenance-free electronic ignition.
Precision-formulated cast iron construction of parts subjected to the most wear and tear.
Field-convertible multi-fuel systems that allow fuel changeover from natural gas to LPG (and vice- versa) while maintaining emissions certification.
Digital spark advance optimizes ignition timing for the selected fuel.

1.3 Alternator

The generator uses Kohler's unique PowerBoost voltage regulation system, which provides instant response to load changes.

PowerBoost

ensures reliable motor starting and

consistent voltage levels. PowerBoost utilizes a

voltage excitation system that employs a winding

independent of the main output windings to provide

excitation voltage.

To open the roof, insert the key provided with the enclosure and turn counterclockwise 1/4 turn. Then just raise the roof. The roof stays open until you are ready to close it.
Be sure to close and lock the enclosure, and keep the key in a secure location.
1.5 Transfer Switch
The RDC2 controller is designed to interface with and control the Kohler Model RXT Automatic Transfer Switch (ATS).
If the power system uses a different model transfer switch, the RDC2 controller will not control the transfer switch. An ATS other than the Model RXT must be equipped with a transfer switch controller and engine start contacts that connect to the remote engine start terminals on the generator set.
1.6 Controller
RCA and RCAL models are equipped with the RDC2 controller. See Figure 1-1.
The controller provides integrated control for the generator set, Kohler Model RXT transfer switch, programmable interface module (PIM) and load management devices.
The controller's 2-line LCD screen displays status messages and system settings that are clear and easy to read, even in direct sunlight or low light.

1.4 Generator Set Enclosure
The generator set is housed in an aluminum enclosure with our fade-, scratch-, and corrosion-resistant Kohler Power Armor automotive-grade textured cashmere finish. The enclosure has a hinged, locking roof that allows easy access to the generator set controller when required, but locks securely to prevent unauthorized access.
TP-7092 2/21

Figure 1-1 RDC2 Generator Set Controller
Section 1 Descriptions and Service Views 15

RDC2 Controller Features
Six-button keypad
OFF, AUTO, and RUN pushbuttons Select and arrow buttons for access to system configuration and adjustment menus LED indicators for OFF, AUTO, and RUN modes
LED indicators for utility power and generator set source availability and ATS position (Model RXT transfer switch required)
LCD display
Two lines x 16 characters per line Backlit display with adjustable contrast for excellent visibility in all lighting conditions
Scrolling system status display
Generator set status Voltage and frequency Engine lube oil temperature Oil pressure Battery voltage Engine runtime hours
Date and time displays
Smart engine cooldown senses engine temperature
Digital isochronous governor to maintain steady-state speed at all loads
Digital voltage regulation: ±0.5% RMS no-load to full-load
Automatic start with programmed cranking cycle
Programmable exerciser can be set to start automatically on any future day and time, and run every week or every two weeks
Exercise modes
Unloaded cycle exercise with complete system diagnostics Unloaded full-speed exercise Loaded full-speed exercise (Model RXT ATS required) Front-access mini USB connector for Kohler SiteTech connection
Integral Ethernet connector for the Kohler OnCue Plus Generator Management System
16 Section 1 Descriptions and Service Views

Built-in battery charger Remote two-wire start/stop capability for connection of Model RDT or other transfer switches Diagnostic messages
Displays diagnostic messages for the engine, generator, Model RXT transfer switch, programmable interface module (PIM), and load management device Over 70 diagnostic messages can be displayed Maintenance reminders System settings System voltage, frequency, and phase Voltage adjustment Measurement system, English or metric ATS status (Model RXT ATS required) Source availability ATS position (normal/utility or emergency/generator) Source voltage and frequency ATS control (Model RXT ATS required) Source voltage and frequency settings Engine start time delay Transfer time delays Voltage calibration Fixed pickup and dropout settings Programmable Interface Module (PIM) status displays Input status (active/inactive) Output status (active/inactive) Load control menus Load status Test function
TP-7092 2/21

1.7 OnCue Plus Generator Management System
The Kohler OnCue Plus Generator Management System is now included with the generator set. The OnCue Plus System allows monitoring and control of your generator set from your home or other location with Internet access using a computer or mobile device. OnCue Plus can be configured to send email or text message notifications in the event of a generator set fault.
You can also use Google Assistant or Amazon Alexa and your smart device to control your generator. Use voice commands to check your generator's status, check for active alerts, and start or stop an exercise. See the OnCue Plus User Guide, TP- 7006, for simple setup instructions and voice commands
OnCue Plus Wireless is also available. OnCue Plus Wireless works with the customer's wireless ethernet router and does not require the installation of a network cable between the generator set and the customer's router/modem.
1.8 Accessories
The following optional accessories are offered for the generator sets.
1.8.1 Cold Weather Package Kit
Heater kits are recommended for improved cold starting in locations where the ambient temperature drops below 0 C (32 F).
The cold weather package kit includes:
Alternator brush cover Battery heater Breather tube heater Fuel regulator heater Oil heater Oil pressure sensor cover 3-way extension cord for power connection
The heaters require a continuous source of AC power. See the generator set Installation Manual and the installation instructions provided with the kits for more information.

1.8.2 Programmable Interface Module (PIM)
The optional Programmable Interface Module (PIM) provides two programmable inputs and six programmable dry contact outputs for connection to customer-supplied equipment. The outputs are controlled by the RDC2 controller, and can also be controlled remotely using OnCue Plus.
The PIM is mounted in a NEMA 3R aluminum enclosure, which can be mounted indoors or outdoors. See the installation instructions provided with the PIM.
1.8.3 Load Management
Two optional load management devices are available for use with single-phase generator sets and a model RXT or RDT transfer switch.
The optional Load Shed Kit mounts inside a model RDT or RXT transfer switch.
The combined interface/ load management board is available for the Model RXT transfer switch.
The load management devices provide an automatic load management system to comply with Section 702.5 of NEC 2008. The installer is responsible for ensuring that the power system installation complies with all applicable state and local codes.
Note: The load management devices are only compatible with single-phase generator sets.
The load management device automatically manages up to six residential loads. Two relays are provided to control two independent air conditioner loads. Up to four power relay modules can be connected for management of non-essential secondary loads.
The load management device is controlled by the RDC2 controller. The load on the generator set is monitored, and loads are added or shed in the order of their priority. See the installation instructions provided with the load shed kit or the Model RXT Operation and Installation Manual for more information.

TP-7092 2/21

Section 1 Descriptions and Service Views 17

1.8.4 Battery Heater Kit
The battery heater kit contains a heating wrap to help warm the battery in cold climates. See Figure 4. The battery heater is equipped with a thermostat that turns the heater on at 16- 18 C (60- 65 F) and off at 27 C (80 F). Battery heaters are recommended for regions where the temperature regularly falls below 0 C (32 F).
Note: Battery heaters are compatible with all Kohler-supplied lead-acid batteries.* For other battery types, check the battery manufacturer's instructions for any restrictions regarding the use of battery heaters.
The battery heater requires a source of AC power. Verify that AC power is connected to the generator set as described in the generator set Installation Manual. The circuit must be backed up by the generator set to provide power at all times.
1
2
3

1.8.5 Fuel Regulator Heater (20kW models only)
An optional fuel regulator heater for the 20RCA/L is recommended for improved cold starting in locations where the ambient temperature drops below - 18 C (0 F). The heater requires a continuous source of AC power.

Heater rating 120 VAC, 60 W

240 VAC, 100 W

Thermostat Pad diameter Cord length

4 C/13 C (40 F/55 F) Snap action 127 mm (5 in.) 914 mm (36 in.)

Figure 5 Regulator Heater Kit Specifications

Figure 6 120 VAC Fuel Regulator Heater

1. Battery heater wrap 2. Retaining strap or cable ties (included) 3. Power cord
Figure 4 Battery Heater (typical)

1 2
2

4
3
1. Bushing 2. Cable ties 3. Heater, fuel regulator pad
Figure 7 Fuel Regulator Heater Installation, 20RCA/L
18 Section 1 Descriptions and Service Views

GM79141H
4. Screw, spacer, and existing nut Note: Place spacer between regulator and mounting bracket.
TP-7092 2/21

1.8.6 Carburetor Heater
An optional carburetor heater is recommended for improved cold starting in locations where the ambient temperature drops below 0 C (32 F). The carburetor heater prevents condensation and carburetor icing. The heater requires a continuous source of AC power.
See the generator set Installation manual for more information.

Voltage

120 VAC

240 VAC

Thermostat ON

4 ± 3 C (40 ± 5 F)

Thermostat OFF

16 ± 3 C (60 ± 5 F)

Figure 8 Heater Specifications, 14kW Models

Voltage

120 VAC

240 VAC

Thermostat ON

4 ± 4 C (40 ± 7 F)

Thermostat OFF

16 ± 3 C (60 ± 5 F)

Figure 9 Heater Specifications, 20kW Models

1

2

3

1. 120 VAC plug 2. Thermostat 3. 240 VAC 3-pin Mate-N-Lock connector.
Figure 10 Carburetor Heater with Thermostat and Power Connectors, 14kW Models

GM19463

1

2

3

GM57968

4

5

6

1. Heating element 2. 1/8 NPT threaded fitting 3. Power cord disconnect plug

4. Thermostat 5. 120 VAC plug 6. 240 volt 3-pin plug

GM88228

Figure 11 Carburetor Heater, 20kW Models

1.8.7 Emergency Stop Kit
An emergency stop button is available as a loose kit. Pressing the emergency stop button causes the generator set to shut down immediately. The generator controller displays an emergency stop shutdown message after the button is pressed.
E-stop assembly harness contains the E-stop, contact block, and two leads connected to the contact block. The harness is factory-assembled. The kit also includes the emergency stop switch decal.

The generator set enclosure is designed with an opening for the emergency stop button. Install the emergency stop button as described in the TT- 1613 and TT- 1795 instructions.
RDC2 firmware to version 5.5 or higher is required for E-stop operation. Use a personal computer (laptop) and Kohler SiteTech software or the USB Utility to update the controller firmware, if necessary. See TP-6701, SiteTech Operation Manual, or TT-1636, Firmware Update Using the USB Utility, for instructions if necessary.

TP-7092 2/21

Section 1 Descriptions and Service Views 19

1.8.8 Breather Tube Heater and Oil Heater Kit
The breather tube heater and oil heater kit is recommended for improved cold starting in locations where the ambient temperature drops below 0 C (32 F).
Note: The heaters require a continuous source of AC power. See Figure 12 and Figure 13 for the power supply voltage required.
Note: The breather tube heater and oil heater must be used together.
Verify that AC power is connected to the generator set as described in the generator set Installation Manual. The circuit must be backed up by the generator set to provide power at all times. Refer to TT- 1709 for
3
2 1

instructions to install the heaters and connect 120VAC power.
See Figure 14 and Figure 15 for illustrations of the 120VAC breather tube heater and oil heater.

Heater Part Number GM110893, GM110894

Voltage

120VAC

Thermostat ON

4 C (40 F)

Thermostat OFF

13 C (55 F)

Figure 12 Breather Tube Heater Specifications

Heater Part Number GM110895, GM110896

Voltage

120VAC

Thermostat ON

4 C (40 F)

Thermostat OFF

13 C (55 F)

Figure 13 Oil Heater Specifications

4 5

1. Heating element 2. Thermostat 3. 120VAC female connector (connect to oil heater)
Figure 14 Breather Tube Heater

4. Label 5. 120VAC plug

1

2

4 3
5

1. Heating element 2. Heating probe 3. Thermostat
Figure 15 Oil Heater

GM101483
4. Label 5. 120VAC male connector (connect to breather tube heater)

20 Section 1 Descriptions and Service Views

TP-7092 2/21

1.8.9 Oil Pressure Sensor Boot Kit
The oil pressure sensor boot protects the oil pressure sensor and its connection from moisture and frost buildup that can cause false low oil level faults. Install the oil pressure sensor boot in locations where the ambient temperature drops below 0 C (32 F). See Figure 16 for illustrations of the installed kit. Follow the instructions provided with the kit to install the boot.
1

14RESA(L) 1

20 kW Models
1. Oil pressure sensor boot

GM102176

Figure 16 Oil Pressure Sensor Boot Location

TP-7092 2/21

Section 1 Descriptions and Service Views 21

1.9 Service Views

1

2

56
3 10 9

4

8

13 14

15 16

12 11

20

17

7

3

21 22 23 24 25 26

27

7 31

19 18
1. Hinged roof 2. Lock 3. Air intake 4. Enclosure key, provided with generator set 5. High voltage electrical in 6. Optional emergency stop button location 7. Lifting holes 8. Fuel inlet 9. Air intake 10. Low voltage electrical in 11. Oil check (dipstick) 12. Air cleaner 13. Nameplate location 14. Oil filter (20 kW models) 15. Auxiliary winding circuit breaker 16. Oil fill

30
ENCLOSURE PANELS
REMOVED TO SHOW DETAIL

28 29

ADV9746

17. AC receptacles for accessories (not shown)

18. Oil drain valve

19. Exhaust outlet

20. Silencer

21. USB connector (for firmware updates)

22. RDC2 controller

23. Line circuit breaker

24. Field-connection terminal block (behind panel)

25. Digital spark advance ignition (DSAI) lead location (14RCA/L

only)

26. Thermostat location

27. Fuel system

28. Battery cables (provided)

29. Engine starting battery location (battery purchased separately)

30. Oil drain hose (shown in storage position)

31. Oil filter (14 kW models)

Figure 1-2 Service Views (20 kW model shown)
22 Section 1 Descriptions and Service Views

TP-7092 2/21

Section 2 Generator Set Operation

2.1 Prestart Checklist
To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult the battery manufacturer's instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
Inspect the exhaust system components for cracks, leaks, and corrosion. Check for tight exhaust system connections.
Check for corroded or broken metal parts and replace them as needed.
Check that the exhaust outlet is unobstructed.
Oil Level. Check the oil level before starting the generator set and at the intervals given in Section 4, Scheduled Maintenance. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
2.2 Exercising the Generator Set
Operate the generator set once each week for 20 minutes. See Section 2.4 for information about loaded and unloaded exercise modes. For instructions to set the exerciser, see Section 3.6, Setting the Exerciser.

2.3 Generator Set Operation
DANGER

Hazardous voltage. Moving parts. Will cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
WARNING

Carbon monoxide. Can cause severe fainting, or death.

nausea,

The exhaust system must be leakproof and routinely inspected.

Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
Light-headedness, dizziness Physical fatigue, weakness in joints and muscles Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.

TP-7092 2/21

Section 2 Generator Set Operation 23

Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building's occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer's instructions.
CAUTION
Hot surfaces.
Remind family members, children, and visitors to use caution near the generator set. Generator sets connected to automatic transfer switches will start automatically during exercise periods and power outages. Some generator components become hot when the generator is running and remain hot for a time after the generator set shuts down.
2.3.1 Local Starting and Stopping
Start: Press the RUN button to immediately start the generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2.3.2 Automatic Operation
An automatic transfer switch monitors the utility power and signals the generator set to start when utility power is lost. The ATS then transfers the load to the generator set.
When utility power is restored, the transfer switch transfers the load back to utility, runs the generator set with no load to cool down the engine, and then stops the generator set.
See Sections 2.3.7 and 2.3.8 for more information about automatic operation.
2.3.3 Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be used to start and stop the generator set. Close the switch to start and run the generator set. Open the switch to stop the generator set.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
24 Section 2 Generator Set Operation

2.3.4 Remote emergency Stop Switch
The generator set may be connected to an optional remote emergency stop switch. See Figure 2-1. The remote emergency stop switch may be mounted near the generator set or in a remote location. If the emergency stop button is activated, the controller display will show Emerg Stop Shutdwn. Emergency Stop Switch Operation Press the red STOP button to shut down the generator set in an emergency. Using the emergency stop button bypasses the engine cooldown cycle, stopping the engine immediately. The controller emergency stop lamp lights (if equipped) and the unit shuts down. The generator set cannot be restarted until the emergency stop switch(es) is/are reset. Lockout/Tagout The emergency stop button can be locked in the STOP position. Insert a lock through two openings in the yellow shroud to prevent the stop button from being pulled out. See Figure 2-1. Remove the lock for normal operation. A lock is not required in order to keep the switch activated. The switch button will stay depressed until it is pulled out by the operator. Resetting the Emergency Stop Switch To reset the E-stop switch, remove the locking device and pull the button out. Reset the controller by pressing the OFF/RESET button.
1
2
GM103743
1
1. Two openings in the shroud for customer-provided lockout/ tagout device
2. Stop button
Figure 2-1 Emergency Stop Switch (optional)
TP-7092 2/21

Shutdown Switch
The generator set may be equipped with a Shutdown switch. See Figure 2-2. This switch, also referred to as the Engine Shutdown switch, commands an immediate shutdown and prevents an engine start if the switch is turned to the off (open, O) position. When the shutdown switch is activated, the controller display shows Emerg Stop Shutdwn.
The switch is a mechanical, rocker-style switch. Press O to prevent engine start during generator set service. Press I to allow the engine to start and run.
See Figure 2-2 for switch connections.

I = On. The engine is allowed to start.
O = OFF. Engine shuts down, will not start.

Figure 2-2 Shutdown Switch

dwg GM111084

2.3.5 Engine Start Crank Cycle
The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.5.
Cranking 1, 2, and 3 are displayed during the crank cycle. Pressing the OFF button during the crank cycle stops the cranking. No other buttons are acknowledged during the crank cycle.
20 kW Models (RDC2.4 v1.4.4)
For RDC2.4 controllers with firmware version 1.4.4 or later, the 20 kW models will perform two crank cycles with 3 starting attempts during each cycle. The controller attempts to start the generator set three times (three starting attempts, 15 seconds crank and

15 seconds off). If the generator set does not start in three attempts, the controller pauses for 45 seconds, and then performs another set of 3 starting attempts. If the generator set does not start during these crank cycles, the system shuts down on an overcrank fault. See Section 2.5.
2.3.6 Engine Cooldown
The engine cooldown time delay allows the engine to run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature drops below the cooled-down temperature level, or if the temperature rises above the high limit during the cooldown cycle.
If a transfer switch other than the Model RXT is used, an additional engine cooldown time delay may be programmed on the transfer switch. To allow the smart engine cooldown on the RDC2 controller to operate most efficiently, set the cooldown time on the transfer switch controller to zero or the minimum time allowed. Refer to the instructions provided with the transfer switch for more information.
2.3.7 Automatic Operation with Model RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2 controller through the ATS interface board on the transfer switch. Also see the Model RXT Transfer Switch Operation/Installation Manual for more information about transfer switch operation.
The controller must be in AUTO mode for automatic transfer switch operation.
Automatic Start
The RDC2 controller receives utility source voltage sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an acceptable level, the controller starts the engine start time delay.
2. If the utility source is not restored before the time delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the ATS is signaled to transfer the load to the emergency source.

TP-7092 2/21

Section 2 Generator Set Operation 25

Automatic Stop with Engine Cooldown
1. When the utility source is restored, the Emergency-to-Normal time delay starts.
2. When the Emergency-to-Normal time delay expires, the load is transferred to the utility.
3. The generator set runs through the engine cooldown cycle and then stops.
2.3.8 Automatic Operation with Other Transfer Switches
If a transfer switch other than the Model RXT (such as a Kohler Model RDT) is used, the engine start contacts from the ATS must be connected to engine start leads 3 and 4 on the generator set.
The controller must be in AUTO mode to respond to remote start/stop signals from an ATS or remote switch. Press the AUTO button to put the controller into automatic mode.
Automatic Start
The engine start contacts on the ATS close to signal the generator set to start, and remain closed while the generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the generator set to stop.
2.4 Exercise
The RDC2 controller can be set to automatically run the generator set at the same time and day each week. Exercising the generator set weekly or every two weeks is required to keep the engine and alternator in good operating condition.
Three exercise modes are available: unloaded cycle, unloaded full speed, and loaded full speed. See Sections 2.4.2 through 2.4.4 for information about the exercise modes. A loaded exercise can be set at the RDC2 controller only if a Model RXT transfer switch is connected.
Note: With transfer switches other than the Model RXT, it is possible to have two exercise settings (one unloaded exercise set at the generator set controller, and another exercise set at the ATS controller). If the exercise times overlap, the ATS exercise setting takes priority.

If a transfer switch other than the Model RXT is used, refer to the instructions provided with the transfer switch to set a loaded exercise at the ATS, if desired.
2.4.1 Setting the Exerciser
When power is applied to the RDC2 controller (that is, when the battery is connected), you will be prompted to set the date and time, select a language, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section 3.5 for more detailed instructions to change settings on the RDC2. See Section 3.6 for more detailed instructions to set the exerciser or change the exercise settings.
2.4.2 Unloaded Cycle Exercise with Complete System Diagnostics
An unloaded exercise runs the generator set without signalling the transfer switch to transfer the electrical load from the utility source to the generator set. The Unloaded Cycle exercise with diagnostics is the recommended exercise mode and is the default exercise setting.
The Unloaded Cycle exercise runs the engine for 20 minutes in the cycle shown in Figure 2-3 and described below.
Runs at reduced speed for 10 minutes to warm up and exercise the engine.
Ramps up and runs at full speed for 3 minutes. Engine diagnostics are performed during this full-speed portion of the cycle, which provides the best test of engine and alternator power backup capability. Diagnostic tests at full speed can identify potential problems with the power output and alert the operator before an emergency event.
Ramps down and runs at reduced speed for 5 minutes to cool down the engine before shutting down automatically.

26 Section 2 Generator Set Operation

TP-7092 2/21

Engine Speed, RPM

3 min.

1 min.

1 min.

10 min.
Engine Exercise

Full-Speed Diagnostics

5 min. Cooldown

Figure 2-3 Unloaded Exercise Cycle

System Diagnostics
During the unloaded exercise, the controller monitors the following data. The controller display indicates that the generator set is running, unless a fault is detected as described below.
ATS connection. The controller verifies that the Model RXT ATS interface board is connected.
Battery voltage. Battery voltage is checked before exercise to verify engine starting capability. Battery voltage provides a measurement of battery health. If the controller detects low battery voltage, the condition is indicated on the display.
Communication integrity tests. J1939, RBUS, Ethernet, and USB are monitored for messages indicating that the controller and wiring are reliable.
Engine speed. Engine speed is measured at reduced speed and full speed. An overspeed or underspeed condition will result in a fault condition and shutdown.
Generator output frequency and voltage. Operating the generator at full speed allows the RDC2 controller to check the output power for correct voltage, frequency, and stability. When the engine is running at full speed, the controller verifies that the voltage and frequency are within acceptable limits. A fault message is displayed if the voltage or frequency is out of range.
Oil pressure. Oil pressure is verified to ensure proper lubrication of critical engine components. Pressure is monitored at both reduced and full speeds. If the oil pressure is low, the Low Oil Pressure message is displayed and the generator set shuts down.

2.4.3 Unloaded Full-Speed Exercise
The unloaded full-speed exercise runs the generator set at full speed for 20 minutes without transferring the load.
To set an unloaded full-speed exercise, follow the procedure in Figure 3-8 and select Exercise Mode: Unloaded Full.
2.4.4 Loaded Full-Speed Exercise (with RXT only)
A loaded exercise starts the generator set, ramps up to full speed, and then transfers the electrical load from the utility source to the generator set. After 20 minutes, the load is transferred back to the utility source. The engine runs without load for 5 minutes or until cool, and then shuts down automatically.
Note: With a loaded exercise, power to the building is lost for up to 10 seconds during load transfer.
For a loaded exercise controlled by the RDC2 controller, a Model RXT transfer switch must be connected to the generator set. To set a loaded exercise, follow the procedure in Figure 3-8 and select Exercise Type: Loaded.
For a loaded exercise with a transfer switch other than a Kohler Model RXT, program the exercise at the transfer switch controller. Refer to the transfer switch operation manual for instructions.
2.4.5 Shutdown During Exercise (Advanced Diagnostic)
The following advanced diagnostic operation applies to RDC2 controllers with firmware versions 5.04 and higher.
If the generator set shuts down on a fault during an exercise, the controller will try to restart the engine. If the engine starts, the generator set will run at full speed for two minutes and then stop. The event history will show Advanced Diagnostic Active. The exercise schedule is maintained.
If the engine does not start, the shutdown message will be displayed. Correct the fault condition and reset the fault as described in Section 2.5.

TP-7092 2/21

Section 2 Generator Set Operation 27

2.4.6 Power Failure During Exercise Cycle
If the utility power is lost during an unloaded exercise, the ATS transfers to the emergency source, the exercise is ended and the control remains in the AUTO mode.
If the utility power is lost during a loaded exercise, the exercise is ended. The ATS remains in the emergency position and the control goes into the AUTO mode.
The generator set continues to run and supply power to the load for the duration of the utility power outage. When Utility power is restored, the ATS will re-transfer to the utility source through normal timing sequences.
2.5 Faults
The RDC2 controller displays fault messages for generator set warnings and shutdowns. Selected fault messages are shown in Figure 2-5. Contact an authorized distributor/dealer for service, if necessary.
2.5.1 Warnings
The controller displays a fault message but the generator set does not shut down on a warning. The controller resets automatically after a warning condition is corrected.
2.5.2 Shutdowns
Under a fault shutdown condition, the generator set shuts down automatically and the controller displays a fault message. The OFF LED flashes. In some cases, the engine cooldown cycle runs before the engine shuts down. See Figure 2-5.
Shutdown switches (such as the low oil pressure switch or high engine temperature switch) on the generator set will automatically reset when the problem is corrected. However, the fault condition at the controller does not clear until the controller is reset.
The generator set cannot be restarted until the fault condition is corrected and the controller is reset. See Section 2.5.5 for instructions to reset the controller after a fault shutdown.
2.5.3 Shutdown During Exercise (Advanced Diagnostic)
If the generator set shuts down on a fault during an exercise, the controller will try to restart the engine. If the

engine starts, the generator set will run at full speed for two minutes and then stop. The event history will show Advanced Diagnostic Active. The exercise schedule is maintained.
If the engine does not start, the shutdown message will be displayed. Correct the fault condition and reset the fault as described in Section 2.5.

2.5.4 ATS Communication Errors
When a Model RXT transfer switch is used, an ATS fault indicates that the connection to the interface board on the transfer switch has been lost. Check the connection to the ATS interface board.

2.5.5 Resetting the Controller after a Fault Shutdown

Always identify and correct the cause of a fault

shutdown before resetting the controller. Check the

fault message displayed on the controller and refer to

Figure 2-5 to identify and correct the fault condition

before proceeding.

Contact an authorized

distributor/dealer for service, if necessary.

RDC2 Controller Reset Procedure
Press the OFF button to reset the controller, or follow the procedure below. See Figure 2-4.
1. While the fault message is displayed, press the Select button to go to the Overview menu.
2. Press Select again. The active fault message is displayed.
3. Press Select. Confirm Clear Fault: NO is displayed.
4. Press the Up arrow button. Confirm Clear Fault: YES is displayed.
5. Press the Select button to enter YES and clear the fault.
6. Press the Select button to return to the overview menu. The controller changes to OFF mode.
7. Press AUTO to put the generator set into automatic mode.

28 Section 2 Generator Set Operation

TP-7092 2/21

Fault Message

Overview - - > 1.2 h

Figure 2-4 Clearing a Fault on the RDC2 Controller

Fault Message

Confirm Clear Fault: NO

Press Up arrow button.
Confirm Clear Fault: YES

tp6809

TP-7092 2/21

Section 2 Generator Set Operation 29

Warning (W) or Fault Message Shutdown (SD) Condition

Check

AC Sens Loss

W (1 sec.) SD (3 sec.) *

AC sensing lost. In Auto mode, generator output Contact an authorized AC sensing is lost. Detection begins10 seconds distributor/dealer for service. after crank disconnect.
Warning: after 1 second if no output detected after crank disconnect.

Shutdown: after 3 seconds if voltage was present and then lost.

Accy PwrOver Warning

W

Accessory Power Overload. An over current

Contact an authorized

fault (short circuit) on the accessory controller distributor/dealer for service.

power output.

Advanced Diagnostic

SD

Shutdown during the reduced speed portion of If the generator set does not restart

an exercise. The event history will show

and return to AUTO, check for other

Advanced Diagnostic Active. The engine then faults that prevent generator set

restarts, runs at full speed for 2 minutes, and

operation.

stops. The controller returns to AUTO mode.

The exercise schedule does not change.

ATS ComError

W

ATS communication error. Warning is displayed Check communication wiring between

if ATS interface connection is lost.

transfer switch interface board and

See Section 2.5.4.

generator set.

ATS PhaseRot

W

ATS phase rotation mismatch. Transfer switch Correct the ATS connection. Refer to

phase rotation does not match, ATS will not

the ATS Installation manual, wiring

transfer.

diagrams, and labels on the transfer

switch.

Aux Input

SD *

Auxiliary input. An optional customer-connected Check customer-supplied equipment. input is closed. (Digital input from optional PIM.)

Batt Chg Flt

W

Battery charger fault. Input to PIM from an

Check external battery charger.

external battery charger (not the built-in battery

charger).

Battery CrLo Warning

W

Engine starting battery voltage falls below

Check the battery rating and

11 VDC for more than 10 seconds. Inhibited

condition.

during the engine crank cycle.

Check the battery charger operation.

Clears when the battery voltage returns to an acceptable level.

Charge or replace the battery.

Battery High

W

Engine starting battery voltage rises above 16 Check the battery rating and

VDC for more than 10 seconds. Inhibited during condition.

the engine crank cycle.

Check the battery charger operation.

Clears when the battery voltage returns to an

acceptable level.

Battery Voltage Low

W

Engine starting battery voltage falls below 12.5 Check the battery rating and

VDC for more than 90 seconds when the engine condition.

is not running. Not operative during the engine crank cycle.

Check the battery charger operation.

Clears when the battery voltage returns to an

Charge or replace the battery.

acceptable level.

Eng Speed High

SD *

Engine speed exceeds 115% of the normal running speed for more than 0.3 seconds.

Contact an authorized distributor/dealer for service.

Eng Speed Low

SD *

Engine speed drops below 85% of the normal running speed for more than 3 seconds.

Reduce the load.
Model 20RCA/20RCAL only: Check enclosure thermostat and reset if tripped. See Section 5.6.
Contact an authorized distributor/dealer for service.

Exer Not Sch

W

Exercise not scheduled. No exercise is

scheduled on the controller.

See Section 3.6 for instructions to set the exerciser.

* Engine cooldown runs before shutting down. 30 Section 2 Generator Set Operation

TP-7092 2/21

Warning (W) or Fault Message Shutdown (SD) Condition

Check

Frequency High

SD *

Governed frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start (10 second inhibit).

Contact an authorized distributor/dealer for service.

Frequency Low

SD *

Governed frequency falls below 90% of the

Reduce the load and restart the

system frequency setting for more than

generator set.

10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds.

Model 20RCA/20RCAL only: Check enclosure thermostat and reset if

Function becomes active 10 seconds after

tripped. See Section 5.6.

engine start (10 second inhibit).

Contact an authorized

distributor/dealer for service.

Lo Crank Vlt

W

Low cranking voltage. Battery voltage dropped Charge or replace the battery.

below 3.5 VDC during engine cranking.

Locked Rotor

SD

No engine rotation is sensed during cranking. Check the battery.

Shuts down 3 seconds after the fault is detected. Check for loose connections.

Contact an authorized distributor/dealer for service.

MainPwrOverL

SD

Main power overload. An over current fault on Contact an authorized

the 70 controller power output (short circuit).

distributor/dealer for service.

Not in Auto

W

The generator set is not in Automatic (standby) Press AUTO to place the generator

mode. Remote start and stop commands from a set in Automatic mode, when

transfer switch or remote switch will be ignored. appropriate.

Oil Press Low

SD *

The LOP switch indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit).
Note: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level regularly as recommended in Section 4.

Check for leaks in the lubrication system.
Check the oil level and add oil if the level is low.
Check the oil pressure switch and wiring.

Over Crank

SD

Three unsuccessful starting attempts.

Check the fuel supply, spark plug, and battery.

Check for loose connections.

Contact an authorized distributor/dealer for service.

Spd Sens Flt

SD

Engine speed sensor has failed or engine

stalled.

Contact an authorized distributor/dealer for service.

Volts L1-L2 High

SD *

Generator voltage high. Output voltage exceeds Contact an authorized 120% of the system nominal voltage for more distributor/dealer for service. than 2 seconds.

Volts L1-L2 Low

SD *

Generator voltage low. Output voltage falls below 80% of the nominal system voltage for more than 10 seconds.

Reduce the load and restart the generator set.
Model 20RCA/20RCAL only: Check enclosure thermostat and reset if tripped. See Section 5.6.

Contact an authorized distributor/dealer for service.

* Engine cooldown runs before shutting down.

Figure 2-5 Controller Fault Messages

TP-7092 2/21

Section 2 Generator Set Operation 31

2.5.6 Faults Related to Paralleling
If the PowerSync Automatic Paralleling Module (APM) is used with two 14 kw or two 20 kW generator sets, additional faults and events related to the paralleling system may be displayed on the controller and/or in OnCue Plus. This section lists those faults and events.

See the installation instructions provided with the APM for additional paralleling information.
Note: Contact an authorized distributor or dealer for paralleling system installation, startup, troubleshooting, or service.

Fault Text

Description

When Active

Current A High Warning

Over Current

Paralleled

Frequency High Warning

Over Frequency

Paralleled

Frequency Low Warning

Under Frequency

Paralleled

Reactive Power Low Warning Loss of Field

Paralleled

Real Power High Warning

Over Power

Paralleled

Real Power Low Warning

Reverse Power

Paralleled

Voltage L1-L2 High Warning

Over Voltage

Paralleled

Voltage L1-L2 Low Warning

Under Voltage

Paralleled

* Pressing OFF will stop the generator set.

Figure 2-6 Warning Messages (protective relay disconnect)

Warning Delay, sec.
10 10 10 10 10 10 10 10

Display Cleared On
Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF * Press AUTO or OFF *

Fault Text BusDeadLive BusLiveDead CfgModelNum
CfgSysVolt
ChkngMeter ConCheckFail ConChecking ConNotDeterm
ContactorOk

Description The bus is measured to be dead when one of the generators is supposed to be supplying voltage to the bus (closed contactor) The bus is measured to be live when no generators are connected to it (both contactors open).
The two generators that are intended to be paralleled have incompatible model numbers.
The system voltage of the two generators intended to be paralleled is not the same. Because the system does not know which voltage is correct, the generators will not be allowed to start.
This generator has paralleled to the other generator and is verifying that the metering is connected and establishing the connection direction. Failure to Auto-Discover APM connections.
Performing APM connection auto-discovery.
APM connection auto-discovery is not complete. This means that the generator does not know which contactor is connected to it.
Successful auto-discovery of APM connections.

Possible Causes *
Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.
Bus metering V9A and V9B connections to V9 of paralleling protection harness connected incorrectly.
Incorrect configuration of one of the generators. Different generator types.
The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kW models.)
One of the two generators is incorrectly configured.
Intermittent connections on RBUS network wiring.
Status message appears the first time the two generators are paralleled.
Wires 9A and 9B crossed between the generators.
Wires 9A or 9B not connected
This generator has started in RUN, the other generator is in OFF.
Generators not yet started in RUN with other generator in OFF. See the APM instruction sheet for instructions to perform the auto-discovery procedure.
Auto-discovery was activated by placing other generator in OFF and this generator in RUN.

32 Section 2 Generator Set Operation

TP-7092 2/21

Fault Text

Description

Possible Causes *

ErraticSig

The power metering on this controller gives a signal that is not consistent with the system configuration. Reversing the power direction does not resolve the problem.

Bad wiring to the CT.
Too much tension on wires from the CT to the controller.

LossOfComAPM

The Automatic Paralleling Module has stopped communicating on RBUS. (An APM was detected on the RBUS network but is no longer communicating.)

APM is unplugged.
Primary controller is powered down. Check the battery connections. See previous page for more information.
Intermittent connections on RBUS network wiring. Check RBUS communication connections.

LossOfComm2

The primary controller has lost communication with the secondary controller. (A secondary controller was detected, then communication was lost.)

RBUS disconnected, secondary controller battery disconnected, updating firmware in secondary controller, or intermittent RBUS connections.

LossOfField

This generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds

Generator voltage on this generator is not calibrated correctly.
Generator voltage on other generator is not calibrated correctly.
Bus voltage on this generator is not calibrated correctly.
Bus voltage on the other generator is not calibrated correctly.

MeteringOk

The generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction.

Status message indicates that the CT is connected to the generator correctly.

MeterUnknown

This generator does not know if the metering is connected or the orientation of the connection. This means that the generators can't share load accurately until this information is known.

System commissioning and startup not yet complete. See the APM instructions.

NoCurrent

The generator has applied load (using the other generator) and has observed no current on the power sensing inputs.

The CT is not connected to the controller.
The output leads from the generator do not go through the CT in the correct direction. See the APM instructions.

SyncFailure

The generator has been attempting to synchronize for over 2 minutes without success.

Generator is hunting.
Advanced speed control settings need adjustment.
Load is changing frequently to disturb the online generator.

* For paralleling system troubleshooting and service, contact an authorized distributor or dealer.

Figure 2-7 Events Related to Paralleling

Generator Set State

Description

Generator Management Off

This generator has been stopped by generator management because it is not presently needed to supply the load. The generator is available and will start if it is needed again.

ProtectiveRelayTrippedContactor

The contactor has been forced to open to protect one of the generators or the customer's load.

Synchronizing

The generator is actively trying to match frequency, voltage and phase with that of the paralleling bus.

Unloading

The generator is actively trying to transfer load from itself to the other generator.

Figure 2-8 Generator Set States Related to Paralleling

TP-7092 2/21

Section 2 Generator Set Operation 33

Notes

34 Section 2 Generator Set Operation

TP-7092 2/21

Section 3 RDC2 Controller Operation

3.1 RDC2 Generator Set/Transfer Switch Controller
Model RCA and RCAL generator sets are equipped with the RDC2 generator set/transfer switch controller. See Figure 3-1 for controller illustrations.
The RDC2 controls the following power system components:
Model RCA or RCAL generator set
Model RXT Automatic Transfer Switch (ATS)
Load management device
Programmable Interface Module (PIM)
The RDC2 controller features include:
Two-line x 16 character backlit digital display with adjustable contrast
OFF, AUTO, and RUN generator set master control buttons
Generator set status indicating LEDs (OFF, AUTO, RUN)
Up, Down, and Select buttons for navigation through menus and adjustments
Power system indicator LEDs to show utility and generator source status, and to show which source (utility or generator) is supplying power to the load (Model RXT automatic transfer switch is required for operation of these LEDs.)
3.2 Controls and Indicators
Figure 3-1 illustrates the RDC2 controller. See Figure 3-2 for details of the controller's user interface.

1

1. User Interface; see Figure 3-2

GM90304

Figure 3-1 RDC2 Controls and Indicators

1

11

2

3
10 4

5

9 87
1. 2-line LCD display 2. Up button 3. Select button 4. Down button 5. RUN button and LED 6. Generator power available LED* 7. Building on generator power LED* 8. Building on utility power LED* 9. Utility power available LED* 10. OFF button and LED 11. AUTO button and LED

6
GM77569

* These LEDs operate only if a Model RXT automatic transfer switch is connected.

Figure 3-2 RDC2 User Interface

TP-7092 2/21

Section 3 RDC2 Controller Operation 35

3.2.1 Controller Keypad

3.2.2 LED Indicators

The RUN, OFF, and AUTO buttons control the generator set as described in Figure 3-3.

LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 3-4.

Use the Select, Up arrow, and Down arrow buttons to navigate through the menus and change settings, if necessary. See Section 2.3 for operation instructions.

Power System LEDs indicate the status of the utility power and the generator set, and indicate which source is supplying power to the building (based on the position of the RXT transfer switch). See Figure 3-2 and Figure 3-4.

Note: The power system LEDs operate only if a Model RXT transfer switch is connected.

Button

Button Function

RUN

Starts the generator set. The engine start time delay is ignored.

OFF

Stops the generator set. The cooldown time delay is ignored.

During the engine crank cycle, pressing OFF will stop the crank cycle.

Press OFF to clear faults and reset the controller.

AUTO

Places the generator set in Automatic (standby) mode.

Down arrow Select Up arrow

Use to navigate through menus and change settings. This manual contains instructions to navigate the controller menus and adjust settings on the RDC2 controller.

Figure 3-3 RDC2 Controller Pushbutton Operation

LED

LED Operation

RUN

Lights when the generator set has been started locally by pressing the RUN button. Remote start and stop commands are ignored.

OFF

Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller are off. Remote start/stop commands have no effect. The exercise cycle will not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required. Identify and correct the fault condition before resetting the controller.

AUTO
Utility Power Available * Building on Utility Power *

Lights when the generator is in automatic (standby) mode. Generator set will respond to engine start and stop commands from the controller (for example, exercise start and stop commands) or an ATS. Time delays operate as described in Section 2.3.
Lights when utility power is available.
Lights when the building load is connected to utility power through the RXT transfer switch.

Generator Power Available * Building on Generator Power *

Lights when generator power is available.
Lights when the building load is connected to generator power through the RXT transfer switch.

* These LEDs operate only if a Model RXT transfer switch is connected.

Figure 3-4 RDC2 Controller LED Operation

36 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.2.3 LCD Display
The controller is equipped with a two-line x 16 character backlit digital display with adjustable contrast. When the generator is running, the controller automatically scrolls through the displays shown in Figure 3-5. When the system is in AUTO, the screens shown in Figure 3-6 are displayed.
When a fault or warning condition exists, the controller will show the corresponding message. See Section 2.5 for more information about faults.
Controller menus display power system information, including status information for the engine, generator, and optional RBUS accessories, exercise settings, and event history. Some menus allow changes to the controller settings. See Sections 3.7 through 3.21 for menu diagrams.

The display contrast is adjustable. Navigate to the Genset System menu and step down to the Contrast screen. Press the Select button, and then use the up and down arrow buttons to adjust the contrast. See Section 3.5, Changing Settings, and Section 3.14, Genset System Menu. The display backlight turns off after about a minute of no activity. The backlight turns on when a button is pressed or when the generator set starts.
Active Alert
Genset Status Standby

Active Alert
Genset Status Running
Voltage: 240V Freq: 60.0Hz

Battery 12.3V
Engine Runtime: 24.5 h
Date: 02DEC2011 Time: HR:MNpm

Engine: 72.0 F Oil Pressure: OK
Battery 12.3V
Engine Runtime: 24.5 h

Next Exercise: 09:00p 09Dec2011
Next Maintenance: 150 h or Mar2012
Sample data shown.
tp6804
Figure 3-6 Autopaging Displays, Automatic Mode

Date: 02DEC2011 Time: HR:MNpm
Sample data shown.
tp6804
Figure 3-5 Autopaging Displays, Generator Running

TP-7092 2/21

Section 3 RDC2 Controller Operation 37

3.3 Controller Power
The RDC2 controller is powered by the generator set engine starting battery and the built-in battery charger.
Note: To disconnect controller power, disconnect the utility power to the generator set and disconnect the battery.
If controller power is disconnected and reconnected, you will be prompted to set the language, time, date, and exerciser. The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. Repeat until all settings are saved and the controller returns to the main menu. See Section 3.5 for more detailed instructions to change settings on the RDC2. See Section 3.6 for more detailed instructions to set the exerciser or change the exercise settings.
3.4 Battery Charging
The controller includes a built-in battery charger to maintain the engine starting battery. The RDC2 controller monitors the battery voltage and provides a constant 13.4 ±2% VDC voltage and maximum 2.5 amps to charge the battery.
The installer must connect utility power provided from the building on a breaker-protected circuit for the built-in battery charger as described in the generator Installation Manual.
3.5 Changing Settings
Some settings can be changed from the controller keypad. The controller settings and generator set output are factory-set and should not require field adjustment under normal circumstances. Check and adjust the settings and/or output when:
The controller has been replaced.
The voltage requires adjustment for a particular application.
Troubleshooting generator set problems.
Have controller setup and adjustment performed only by an authorized distributor/dealer or authorized representative.

The following procedure explains how to change settings. See Figure 3-7 for an example using the Date and Time settings.
Note: Use caution when navigating the controller menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.
Procedure to Change Settings
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired menu is displayed. The Genset System menu is used for this example. See Figure 3-9.
3. Press the Select button to enter the genset system displays. See Figure 3-7.
4. Press the down arrow button to step through the generator set system settings.
5. To change any of the genset system settings, press the Select button. The selected setting flashes.
6. Press the up or down arrow buttons to increase or decrease the setting.
7. When the desired setting is shown, press Select. The value stops flashing. If there are additional adjustable settings on the screen, the next setting flashes. For example, in the date menu, the day, month, and year can be adjusted.
8. Repeat steps 6 and 7 for each setting on the screen.
9. Press the down arrow to step to the next screen.
10. To exit, press the down arrow button until Return is displayed. Press the Select button to exit the menu.
11. Press the AUTO or OFF button to exit the main menu.
Note: If no buttons are pushed, the controller exits the menus and returns to the generator set status display after 5 minutes.

38 Section 3 RDC2 Controller Operation

TP-7092 2/21

Changing Settings on the RDC2 Controller

1. Press the Select button to enter the main menu.

Press:

Display:

Overview - - > 1.2 h

8. When the correct date is shown, press the Select button. The saved date is shown.

Press:

Display:

Date: 03Jan2012

2. Press the down arrow button until the desired menu is displayed. See Figure 3-9. Date and Time are used for this example.

Press:

Display:

Date - - > and Time

9. Press the down arrow button to step to the next menu.

Press:

Display:

Time: 01:49pm

3. Press the Select button to enter the Date and Time menu.

Press:

Display:

Date: 05Dec2011

4. To change the date and time settings, press the Select button again. The year will flash.

Press:

Display:

Date: 05Dec2011

5. Press the up or down arrow buttons to change the year.

Press:

OR

Display:

Date: 05Dec2012

10. Repeat steps 5 and 6, using the arrow and select buttons to set and save the time.

Note: To change from am to pm, press the up arrow key to increase the hour until the correct hour and pm is displayed.

11. In the time format menu, press Select and then press the up or down arrow button to change the format, 12 hr. or 24 hr. Press Select to save the displayed format.

12. Press the down arrow button. Return is displayed.

Press:

Display:

<- - Return

13. Press Select to return to the Date and Time menu.

Press:

Display:

Date - - > and Time

6. When the correct year is shown, press the Select button. The year is saved and the next setting (month) flashes.

Press:

Display:

Date: 05Dec2012

7. Repeat steps 5 and 6, using the arrow and select buttons to set the month and the date.
Figure 3-7 Changing Settings

14. Press the Up or Down arrow buttons to step to a different menu.
15. Press Auto to signal the controller to exit the menus and return to the generator set status display.

Press:

AUTO

Display:

Genset State Standby

Note: If no buttons are pressed, the controller returns to the status display after 5 minutes.

TP-7092 2/21

Section 3 RDC2 Controller Operation 39

3.6 Setting the Exerciser
Set the exerciser to automatically run the generator set for 20 minutes every week or every two weeks.
3.6.1 Setting the Exerciser at Controller Power-up
When battery power is connected to the controller, you will be prompted to set the language, date and time, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section 3.5 for more detailed instructions to change settings on the RDC2.
If the battery is disconnected and reconnected during generator set maintenance or service, the time, date, and exercise settings will need to be re-entered.
3.6.2 Changing the Exercise Settings
This section explains how to change the exercise settings after the initial setup.
Follow the procedure below and see the flowchart in Figure 3-8 to set the exercise time and date, mode, and frequency.
Procedure to Set the Exerciser
1. Press the AUTO button on the controller.
2. Press the Select button to go to the main menu. See Figure 3-9.
3. Press the down arrow button to step to the Genset System menu.
4. Press the Select button to enter the Genset system menu. See Figure 3-8.
5. Use the down arrow button to step to the Next Exercise menu. If the exerciser is not set, No Exercise Scheduled will be displayed.
6. Press and HOLD the Select button to enable editing.

7. Press the Select button. The setting flashes to show that it can be changed. For example, HR flashes to show that the hour can be changed.
8. Press the Up or Down arrow buttons to change the setting.
9. Press the Select button to save the setting and move to the next. For example, save HR setting and move to MN.
10. Repeat steps 5 through 9 to change the next item on the line until the desired settings are displayed.
11. Press Select to save after all settings have been selected. Settings will stop flashing.
12. If the generator set is connected to a Kohler Model RXT transfer switch, the exercise can be changed to a loaded exercise. Set the Exercise Mode to Unloaded Cycle, Unloaded Full, or Loaded Full (RXT ATS required) as shown in Figure 3-8. Unloaded Cycle is recommended. See Sections 2.4.2 through 2.4.4 for information about the exercise modes.
13. Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended.
14. Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu.
After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency setting.
Other transfer switches: For a loaded exercise with a transfer switch other than a Kohler Model RXT ATS, refer to the transfer switch operation manual for instructions.
Exerciser Reset
To reset the exerciser to run at a different day and/or time or to change the exercise mode, follow the procedure in Section 3.6.2 to change the exerciser settings.

40 Section 3 RDC2 Controller Operation

TP-7092 2/21

Genset - - > System

System Freq: XX.X Hz
System Phase

System Volt

System Battery

Fuel Type

Next Exercise * HR:MN PM MM/DD/YY

HOLD:

Next Exercise HR:MN PM MM/DD/YY

Exercise Mode: Loaded

HOLD:

Exercise Mode:
Unloaded Cycle/Unloaded Full/ Loaded Full

Exercise Freq: Weekly

HOLD:

Exercise Freq: Weekly/Bi-Weekly

Language:

Contrast: 50

<- - Return

* If the exerciser has not been set, No Exercise Sch will be displayed. Figure 3-8 Procedure to Set the Exerciser on the RDC2 Controller
TP-7092 2/21

tp6804
Section 3 RDC2 Controller Operation 41

3.7 RDC2 Controller Menus
Controller menus display power system information, including status information for the engine, generator, and optional RBUS accessories, exercise settings, and event history. Some menus allow changes to the controller settings. Status information, including the engine runtime, cannot be changed by the operator.
Diagrams in the following sections show how to navigate through the menus. The diagrams show sample settings. Settings for your application may vary.
Note: Use caution when navigating the controller menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.

If a setting on the controller display is flashing, edit mode has been enabled. Press the OFF or AUTO button to exit the edit mode.
3.8 Main Menu
Press the Select button once to bring up the main menu. Overview is displayed. See Figure 3-9. Press the down arrow button to step to the next menu, Engine Metering. Use the UP and DOWN arrow buttons to step up and down through the menus shown in Figure 3-9.
The controller will exit the main menu after 5 minutes if no buttons are pressed. To exit the main menu immediately, press the controller's OFF or AUTO button.

42 Section 3 RDC2 Controller Operation

TP-7092 2/21

Status Displays

Overview - - > 1.2 h

Press the Up and Down arrow buttons to move between menus. Press OFF or AUTO to exit the menus.

Engine - - > Metering
Generator- - > Metering

Genset - - > Information

Genset - - > Run Time

Genset - - > System

ATS

-->

Status

* ATS Configuration appears only if a Model RXT transfer switch is connected. PIM Status appears only if a programmable interface module is connected. Load Control appears only if a load management device is connected.
Figure 3-9 RDC2 Main Menu

ATS

-->

Configuration *

Date - - > and Time

Network - - > Information

PIM

-->

Status

Load - - > Control

Event Log- - >

tp6804

TP-7092 2/21

Section 3 RDC2 Controller Operation 43

3.9 Overview Menu

Overview - - > 1.2 h

Active Alert (if any)

Genset Status Standby
Voltage: 240V Freq: 60.0Hz
Engine: 72F Oil Pressure: OK
Battery 12.0V
Engine Runtime: 24.5 h
Date: 02DEC2011 Time: HR:MNpm
Next Exercise: 09:00p 09Dec2011
Next Maintenance: 150 h or Mar2012
SW Version: 4.07

3.10 Engine Metering Menu
The engine metering menu displays engine status information as shown in Figure 3-11. This menu displays status information only. No settings can be changed from this menu.

Engine - - > Metering

Eng Speed: 3600 RPM

Oil Pressure: Switch: OK

Oil Temp: 72.0 F

Battery: 12.0 V

<- - Return

Note: Actual settings may vary.

tp6810

Figure 3-11 Engine Metering Menu

<- - Return

Note: Actual settings may vary.

tp6804

Figure 3-10 Overview Menu

44 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.11 Generator Metering Menu
The generator metering menu displays the generator voltage and frequency. See Figure 3-12.

Voltage Calibration
DANGER

Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
The voltage calibration mode can be entered from the Generator Metering menu. Contact a Kohler-authorized distributor/dealerdealer for service.
The Reset Calibration menu allows you to set the voltage reading back to the original value after calibration, if necessary. See Figure 3-12.

Generator - - > Metering
Three-phase
Volts L1- L2: 240 V
Volts L2- L3: 240 V
Volts L3- L1: 240 V
Frequency: 60.0 Hz

Single-phase

Volts:

240 V

Note: Actual settings may vary.

Frequency: 60.0 Hz

Reset Calibration
<- - Return
Figure 3-12 Generator Metering Menu
TP-7092 2/21

Reset Calib? No
Reset Calib? Yes

tp6810

Section 3 RDC2 Controller Operation 45

3.12 Generator Set Information Menu
The generator set model number and serial numbers are displayed. No changes are allowed from this menu.
Model and serial numbers are factory set and should not require changes in the field, except in the event that the controller is being replaced. A personal computer running Kohler SiteTech software is required to enter the generator set model number and serial numbers on a replacement controller. Contact an authorized Kohler distributor/dealer for service.

Genset - - > Information

Genset M/N: 20RCA
Genset S/N: ########
Controller S/N: ########
<- - Return

3.13 Genset Run Time Menu
The data shown in Figure 3-14 are displayed. No changes are allowed from this menu.
Eng Runtime displays the total number of hours that the generator set engine has run. The runtime is not resettable.
The Next Maintenance menu shows the number of hours of generator set operation until maintenance is required. The estimated date for the next scheduled maintenance is also displayed. The maintenance reminder intervals are based on the engine manufacturer's recommendation for changing the oil. Refer to Section 4, Scheduled Maintenance, for maintenance instructions.
After changing the oil and performing other recommended maintenance, go to the Overview menu to reset the maintenance timer. See Section 4.2.5 for instructions to reset the maintenance timer.

Genset - - > Run Time

Eng Runtime: 24.5 h
Eng Starts: 18

tp6804
Figure 3-13 Generator Set Information Menu

Next Maintenance: 150 h or Mar2014

<- - Return

Note: Sample data shown.

tp6810

Figure 3-14 Generator Set Run Time Menu

46 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.14 Genset System Menu
The genset system menu displays the system information shown in Figure 3-15. Generator sets are factory set and should not require changes to the system settings in the field.
A Kohler authorized distributor or dealer can adjust these settings, if necessary. If the generator set is reconnected to a different voltage or the system settings require adjustment for some other reason, see Section 3.5 for instructions to enable editing and change the system settings.
Note: Use caution when navigating the controller menus. In some menus, pressing the Select button can enable editing of the controller settings. Changing the settings to incorrect values can adversely affect generator set operation or render the unit inoperable.
Voltage Regulator (VR) Voltage Adj
The generator set voltage is factory set and typically does not require adjustment in the field. If voltage adjustment is required, contact a Kohler authorized distributor or dealer for service. Refer to the generator set Installation Manual for instructions to adjust the voltage.
Fuel Type
The fuel type, LP or natural gas, is shown. Do not change the fuel type in this menu unless the generator's fuel system has been converted by an authorized distributor or dealer.
Setting the Exerciser
Use the Genset System menus to set the generator set exerciser. Refer to Section 2.4 for instructions to set the exerciser and for more information about exercising the generator set.
After a scheduled exercise run, the Next Exercise time and date will be updated automatically based on the Exercise Frequency setting.
Language
Controllers can be set for the following languages: English, French, Spanish, Dutch, or German.
Adjusting the Display Contrast
To adjust the display contrast, use the down arrow button to step to the Contrast menu. Press the Select button, and then use the up and down arrow buttons to

adjust the contrast. Press the Select button to save the contrast setting.

Genset - - > System

System Voltage: 240 V

System Freq: 60 Hz
VR Voltage Adj: 240.0V
System Phase: Single
System Battery: 12 V
Fuel Type LP
Next Exercise 06:30p 15Dec2011
Exercise Mode: Unloaded Variable
Exercise Freq: Weekly
Language: English
Meas System: English
Contrast: 50
<- - Return
Note: Actual settings may vary. Figure 3-15 Genset System Menu

tp6804

TP-7092 2/21

Section 3 RDC2 Controller Operation 47

3.15 ATS Status Menu
ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen.

The ATS Status menu displays Model RXT transfer switch and source information.
The voltage shown in these menus can be calibrated. Follow the safety precautions at the beginning of this manuals. Use a voltmeter to measure the line-to-line voltage and follow the instructions in Figure 3-16 to calibrate the voltage readings.

ATS - - > Status

ATS Position: Normal

Note: If there is no Model RXT transfer switch connected to the generator set, Remote ATS is displayed and the other screens on this page do not appear.

Normal Status: Not/Acceptable
Emerg. Status: Standby Single-phase Normal Volts:
240.0 V
Normal Freq.: 60.0 Hz
Emerg Volts: 240.0 V
Emerg. Freq.: 60.0 Hz
Reset Calibration

Note: Sample data shown. Three-phase
Normal Voltage: L1- L2 240 V
Normal Voltage: L2- L3 240 V
Normal Voltage: L3- L1: 240 V
Normal Freq.: 60.0 Hz
Normal Rotation:
Similar screens appear for the emergency source.
Reset Calib? No

<- - Return Figure 3-16 ATS Status Menu, with Calibration
48 Section 3 RDC2 Controller Operation

Reset Calib? Yes

tp6810
TP-7092 2/21

3.16 ATS Configuration Menu
Note: The ATS Configuration menu appears only if a Model RXT transfer switch is connected.
Use the ATS Configuration submenu to check the Model RXT transfer switch system settings and time delays, and change the settings, if necessary.
Changing ATS Configuration Settings
To enable editing, press the select button. The value flashes to indicate that it can be changed. Press the up and down arrow buttons to change the value. Press the Select button to save the value shown.
Use the up and down arrow buttons to move to the next value to be changed. Repeat the adjustment process until all values are correct.
Press the down arrow until Return is displayed. Press the select button to return to the main menu.

ATS - - > Configuration

Normal Freq: 60 Hz
Normal Voltage: 240 V
Emerg. Freq: 60 Hz
Emerg. Voltage: 240 V
Emergency Start: 3 sec

Xfer frm Normal 3 sec

Xfer from Emerg: 120 sec

<- - Return

Note: Actual settings may vary.

tp6810

Figure 3-17 ATS Configuration Menu

TP-7092 2/21

Section 3 RDC2 Controller Operation 49

3.17 Date and Time Menu
The date and time will typically be set at controller power- up. To change the date, time, or time format (12 hour or 24 hour), use the Date and Time menu. See Figure 3-18.
3.18 Networking Information Menus
Use the networking menus to view and adjust communication settings for systems with remote RBUS devices such as a PIM or load shed kit, and for systems that use the Kohler OnCue Plus Generator Management System.
RBUS is a proprietary RS-485 communications protocol.
The Networking Information menu leads to submenus for network and RBUS communication settings.

Date and Time

Date: 02Dec2011
Time: 12:34pm
Time Format: 12hr|24hr

<- - Return

To change the date and time, press the Select button See Figure 3-7 for instructions.
Figure 3-18 Date and Time Menu

tp6804

Networking- - > Information

Networking- - > Status

Networking- - > Configuration
RBUS - - > Information

<- - Return

Figure 3-19 Networking Information Menu

NS See Figure 3-20. NC See Figure 3-21. RB See Figure 3-22.

tp6810

50 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.18.1 Networking Status Submenu
The Networking Status submenu contains settings for OnCue . Changes to these settings are not typically required.
If DHCP is enabled, IP parameters are not displayed. If DHCP is disabled (i.e., if a static IP address is used), the IP parameters are displayed.

To enable or disable DHCP and change the IP settings, go to the Networking Configuration menu. See Section 3.18.2.

Networking- - > Information

Networking- - > Status

Figure 3-20 Network Status Submenu

OnCue Status: Connected
DHCP: Enabled
IP Address: 123.456.789.123
Subnet Mask: 123.456.789.123
Gateway: 123.456.789.123
DNS 1: 123.456.789.123
DNS 2: 123.456.789.123
Ethernet Status: Disconnected
OnCue Server: 123.456.789.123
<- - Return

tp6804

TP-7092 2/21

Section 3 RDC2 Controller Operation 51

3.18.2 Networking Configuration Submenu (OnCue Password)
The Networking Configuration menu includes settings used for communication with the Kohler OnCue Plus Generator Management System.
Password
Note: Use the OnCue password shown on the controller display for OnCue or OnCue Plus applications.
For the initial OnCue Plus setup, you will be required to reset the OnCue password on the RDC2 controller, and then enter it into the OnCue Plus application. To reset the password, follow the instructions in Figure 3-21.
Note: The password is displayed for only 10 seconds. Be sure to write down the password and serial number.
A new password is generated each time the reset password procedure is performed. If the password is

reset after the OnCue Plus system has been set up, the connection will be lost. Disconnect the battery power to the controller, wait a minute, then reconnect power.
DHCP Submenu
For most applications, the Dynamic Host Configuration Protocol (DHCP) is enabled and the IP settings cannot be changed from the controller keypad. If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is required), then the IP parameters can be modified. For applications that require a static IP address, press and hold the select button to enable editing, press the down arrow to disable DHCP, and then step to the next parameters and enter the information. See Figure 3-21.
If an error occurs while setting a parameter, an error message is displayed and then the controller exits the edit mode. Previous settings are preserved.

52 Section 3 RDC2 Controller Operation

TP-7092 2/21

Networking- - > Information

Networking- - > Status
Networking Configuration
RBUS - - > Information

Reset OnCue Password

HOLD
Reset OnCue Password? No
UP arrow for YES, Down arrow for NO.
Reset OnCue Password? Yes
Press Select to enter YES or NO as displayed. New password is displayed for approximately 10 seconds.
S/N: 1234567 New PW: 12345

DHCP: Enabled
<- - Return Figure 3-21 Networking Configuration Submenu

HOLD
DHCP: Disabled
UP arrow to enable, Down arrow to disable.
IP Address: 123.456.789.123
Subnet Mask: 123.456.789.123
Gateway: 123.456.789.123
DNS 1: 123.456.789.123
DNS 2: 123.456.789.123
tp6804

TP-7092 2/21

Section 3 RDC2 Controller Operation 53

3.18.3 RBUS Information
The RBUS Information menu contains settings for remote modules that communicate with the RDC2 controller using RBUS protocol. This includes the following optional modules:

Model RXT transfer switch Combined interface/ load managment board on the RXT transfer switch Programmable Interface Module (PIM) Load shed kit PowerSync Automatic Paralleling Module (APM)

Networking- - > Information

Networking- - > Status

Networking- - > Configuration RBUS - - > Information <- - Return
Figure 3-22 RBUS Information Submenu

Modules Connected: 2

Remote - - > Devices
Net Cycle Time: 123ms

RD See Figure 3-23.

Module Timeouts: 1234

Module Errors: 1234

< - - Return

tp6804

54 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.18.4 Remote Devices Submenu
Check the status of remote devices communicating through RBUS. Device types can include:
Model RXT ATS
Programmable Interface Module (PIM)
Load shed kit or combined interface/load management board on a Model RXT transfer switch
PowerSync Automatic Paralleling Module (APM)

The serial number for the RBUS module is shown on the circuit board inside the module enclosure.

From Figure 3-22:
Remote - - > Devices

S/N: XXXXXXXXX <<*DeviceType*>>

S/N: XXXXXXXXX <<*DeviceType*>>

<- - Return

Module Status: Connected
Comm. Errors: 12345
Comm. Timeouts: 12345
Module ID: 12
Firmware Ver.: 4.07
(Dis)Connected: MM/DD/YY 12:12
Return - - >
Figure 3-23 Remote Devices Submenu

Connected: Displays the date and time that the device was connected. Disconnected: Displays the last date and time of successful communication.
tp6804

TP-7092 2/21

Section 3 RDC2 Controller Operation 55

3.19 Programmable Interface Module (PIM) Status Menu
The PIM status menu displays the status of inputs and outputs connected to the programmable interface module (PIM). this menu appears only if a PIM is connected. This is a status display menu only. Input and output settings cannot be changed from the RDC2 controller's user interface.

A personal computer running Kohler SiteTech software is required to change the input and output settings. Contact an authorized distributor or dealer for service.
The Kohler OnCue Plus Generator Management System can be used to turn outputs on and off. See the OnCue Plus Operation Manual for instructions.

PIM Status:

PIM 1 - - >

Input 1 In/Active

<- - Return

Input 2 In/Active
Output 1: In/Active
Output 2: In/Active
Output 3: In/Active
Output 4: In/Active
Output 5: In/Active
Output 6: In/Active

<- - Return

Figure 3-24 Programmable Interface Module (PIM) Status Menu

tp6810

56 Section 3 RDC2 Controller Operation

TP-7092 2/21

3.20 Load Control Menus
The Load Control menu displays the status of the load management device inputs and outputs, and allows a test of the load control output relays. This menu appears only if a load management device (load shed kit or Model RXT transfer switch with the combined interface/load management board) is connected.

Generator current is displayed as a percent of the maximum generator capacity. The load control module adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their priority. For detailed information, refer to the instructions provided with the load shed kit. For the RXT combined interface/ load management board, refer to the RXT automatic transfer switch Operation and Installation Manual.

Load - - > Control

Generator Current: 123 %
Load - - > Control 1
<- - Return

Figure 3-25 Load Control Status Menu

Test Outputs Push Select (blinking)
Input 1: In/Active
Input 2: In/Active
Output 1: Add/Shed
Output 2: Add/Shed
Output 3: Add/Shed
Output 4: Add/Shed
Output 5: Add/Shed
Output 6: Add/Shed
<- - Return

tp6810

TP-7092 2/21

Section 3 RDC2 Controller Operation 57

3.21 Event Log
The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are numbered 1- 1000, with 1 being the most recent. Each event is displayed with the date and time of the event, the number of the event, a code to indicate whether the event was a warning ( W ), shutdown (S), or informational notice ( I ), the engine hours at the time of the event, and the event description.
The time and date for notices (I) are not stored in the controller.
Procedure to View Event History
1. Press Select to enter the main menu.
2. Press the down arrow to step down to the event log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Use the up and down arrow buttons to view events.
6. Press the Select button to exit the event log.
To stop viewing the event history before the last event, press the select button to return to the main menu.

Event Log - - >

Date MO/DA/YEAR time HR:MN event number, W/S/I, engine hours event name

Press UP and Down arrow buttons to scroll through events

Date MO/DA/YEAR time HR:MN event number, W/S/I, engine hours event name

Press Select button at any time to return to the main menu.
Figure 3-26 Event Log

tp6810

58 Section 3 RDC2 Controller Operation

TP-7092 2/21

WARNING

Section 4 Scheduled Maintenance
WARNING

Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
DANGER

Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
4.1 Scheduled Maintenance
Refer to the following service schedules and the runtime hours displayed on the controller to schedule routine maintenance. Intervals are shown in hours of operation and/or time intervals (i.e. weekly, monthly, quarterly, etc.) Have an authorized distributor/dealer service the generator set at the designated intervals in the service schedule for the life of the generator set. Service units subject to extreme weather, long operating hours, or dusty or dirty conditions more frequently.
Contact an authorized distributor/dealer for parts.

Hazardous voltage. Moving parts. Will cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.

TP-7092 2/21

Section 4 Scheduled Maintenance 59

4.1.1 Service Schedule, 14 kW Models

System Component or Procedure Fuel
Flexible lines and connections Main tank supply level Fuel piping
Lubrication
Oil level

See Section
4.2

Crankcase breather hose

Change oil

Replace filter

Cooling

4.5

Air ducts, louvers

Exhaust Line

4.6

Leakage

Insulation, fire hazards

Obstructions or combustible materials near exhaust outlet

DC Electrical System

4.7

Check battery charger operation, charge rate

Remove corrosion, clean and dry battery and rack

Clean and tighten battery terminals and inspect boots

Battery electrolyte level and specific gravity *

AC Electrical System

Tighten control and power wiring connections Remote control system, if equipped

Visible wear or damage

Wire abrasions where subject to motion

Wire-cable insulation condition

Engine and Mounting

Visible wear or damage

Air cleaner service

4.4

Spark plugs

4.3

Replace stepper motor coupling and bushing

Generator

Visible wear or damage

Exercise generator set

Brushes and collector ring

Measure and record resistance readings of windings with insulation tester (Megger , with SCR assembly or rectifier and load leads disconnected) *

General Condition of Equipment

Evidence of vibration, leakage, excessive noise, temperature, or deterioration

Interior of sound enclosure

* Not necessary for maintenance-free batteries. Service more frequently under extremely dusty/dirty conditions.
Megger is a registered trademark of Biddle Instruments.

Procedure
Visually Inspect Check Change Clean

X

R

X

X

X

X

X X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

150

300

300

D

X

D

D

X

X

X

X

X

X Action D Authorized distributor/dealer only R Replace as necessary

Test Frequency
Quarterly Weekly Yearly
Every 8 hours of engine operation Yearly or 500 hours Yearly or 100 hours Yearly or 200 hours
Yearly
Weekly Yearly Weekly

Monthly Yearly Yearly Yearly

Yearly

X

Monthly

Quarterly

Six Months

3 Years or 500 hours

Weekly
Yearly or hours shown
500 hours

Quarterly

X

Weekly

Yearly or 300 hours

D

3 Years

Weekly Quarterly

60 Section 4 Scheduled Maintenance

TP-7092 2/21

4.1.2 Service Schedule, 20 kW Models

System Component or Procedure Fuel
Flexible lines and connections Main tank supply level Fuel piping
Lubrication
Oil level

See Section
4.2

Change oil

Replace filter

Crankcase breather hose

Oil cooler

Cooling

4.5

Air ducts, louvers

Exhaust System

4.6

Leakage

Insulation, fire hazards

Obstructions or combustible materials near exhaust outlet

DC Electrical System

4.7

Check battery charger operation, charge rate

Remove corrosion, clean and dry battery and rack

Clean and tighten battery terminals and inspect boots

Battery electrolyte level and specific gravity *

AC Electrical System

Tighten control and power wiring connections

Remote control system, if equipped

Visible wear or damage

Wire abrasions where subject to motion

Wire-cable insulation condition

Engine and Mounting

Visible wear or damage

Air cleaner service

4.4

Spark plugs

4.3

Replace stepper motor coupling and bushing

Generator

Visible wear or damage

Exercise generator set

Brushes and collector ring

Measure and record resistance readings of windings with insulation tester (Megger , with SCR assembly or rectifier and load leads disconnected)

General Condition of Equipment

Evidence of vibration, leakage, deterioration, unusual or excessive noise or temperature

Interior of sound enclosure

* Not necessary for maintenance-free batteries. Service more frequently under extremely dusty/dirty conditions.
Megger is a registered trademark of Biddle Instruments.

Procedure
Visually Inspect Check Change

Clean

Test

Frequency

X

R

X

X

Quarterly Weekly Yearly

X

X

X

X

X

X

Every 8 hours of engine operation
Yearly or 150 hours Yearly or 150 hours Yearly or 500 hours Yearly or 150 hours

X

X

Yearly

X

X

X

X

Weekly Yearly
Weekly

X

X

X

X

X

Monthly

X

Yearly

Yearly

Yearly

X

X

X

X

X

Yearly

X

Monthly

Quarterly

Six Months

3 Years or 500 hours

X

150

300

150

300

D

Weekly
Yearly or hours shown
500 hours

X

Quarterly

W

Weekly

D

D

Yearly or 300 hours

D

3 Years

X

X

X

X

X

X Action D Authorized distributor/dealer only R Replace as necessary

Weekly Quarterly

TP-7092 2/21

Section 4 Scheduled Maintenance 61

4.2 Lubrication System
See the service schedules in Section 4.1 for oil change and oil filter replacement intervals. See the service views in Section 1.9 for the oil drain, oil check, oil fill, and oil filter locations.
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools.

4.2.2 Oil Check
The generator set is shipped with oil. Before operating the generator set, check the engine oil in the crankcase. To check the oil level, shut down the generator set and wait several minutes. Remove the dipstick and wipe the end clean, reinsert, and remove. See Figure 4-1. Maintain the oil level between the Add and Full marks on the dipstick. Add 5W-30 or 10W-30 synthetic oil when the oil level is low. Check the oil level before each use. For extended operation, check the oil level every 8 hours. Do not check the oil level when the generator set is running.
6515
Figure 4-1 Oil Check (typical)
4.2.3 Engine Oil Recommendation
Use 5W-30 or 10W-30 API (American Petroleum Institute) Service Class SG, SH, or SJ synthetic oil. Synthetic oil oxidizes and thickens less than other oils and leaves the engine intake valves and pistons cleaner.

4.2.1 Low Oil Pressure Shutdown
The low oil pressure (LOP) shutdown feature protects the engine against internal damage if the oil pressure drops below a minimum pressure because of oil pump failure or other malfunction.
Note: The LOP shutdown feature does not protect against damage caused by operating when the oil level is low; it is not a low oil level shutdown. Check the oil level regularly, and add oil as needed.

62 Section 4 Scheduled Maintenance

TP-7092 2/21

4.2.4 Oil Change Procedure
Note: Dispose of all waste materials (engine oil, fuel, filter, etc.) in an environmentally safe manner.
Drain the oil while it is still warm.
1. Drain the oil.
a. Press the OFF button on the generator set controller.
b. Disconnect the utility power to the generator set.
c. Disconnect the generator set engine starting battery, negative (- ) lead first.
d. Remove the end panels from the enclosure by lifting the panels up and out. Then lift off the service-side panel to access the oil drain valve and hose.
e. Clean the area around the dipstick and oil fill cap.
f. Remove the oil drain hose from its retaining clip. Remove the cap from the oil drain hose and lower the hose into an oil collection container.
g. Open the oil drain valve on the engine.
h. Remove the dipstick and oil fill cap. Allow time for the engine oil to drain completely.
i. Close the oil drain valve. Replace the cap on the oil drain hose. Replace the oil drain hose in its retaining clip.
j. Replace the dipstick.
2. Replace the oil filter.
a. Clean the area around the oil filter.
b. Loosen the oil filter by rotating it counterclockwise with an oil filter wrench. On 20 kW models, allow the oil to drain from the filter. Then remove the oil filter.
c. Clean the gasket sealing surface of the oil filter adapter.
d. Apply a light coat of clean oil to the rubber seal of the new oil filter.
e. Install the new oil filter following the instructions provided with the filter.

3. Fill with oil.
Note: When the oil is drained, some oil remains in the engine. The amount of oil needed to refill the engine may be less than the capacity shown in Figure 4-2. Use the dipstick shown in Figure 4-1 to check the oil level during the fill. Do not fill past the full mark on the dipstick.
Note: See Section 4.2.3 for the recommended oil type.

Generator Set Model

Oil Capacity, L (qt.)

14 kW 20 kW

1.8 (1.9) 1.9 (2.0)

Figure 4-2 Engine Oil Capacity

a. Add oil through the oil fill port; see Figure 4-3.

b. Use the dipstick to check the oil level before starting to add the final quart of oil. Fill the engine to the F mark on the dipstick.

c. Reinstall the dipstick and the oil fill cap.

1

img1062

3

2

Note: 20 kW model shown; 14 kW model is similar
1. Dipstick 2. Oil cooler located under shroud (20 kW only) 3. Oil fill location

Figure 4-3 Oil Fill Components

TP-7092 2/21

Section 4 Scheduled Maintenance 63

d. Reconnect the generator set engine starting battery, negative (- ) lead last.
e. Reconnect the utility power to the generator set.
f. Press the RUN button on the generator set controller. The generator set will start.
g. Run the generator set for a minute to allow the oil pressure to reach operating range.
h. Stop the generator set, wait 1 minute, and then recheck the oil level. Add oil to bring the level up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
5. Reset the maintenance timer on the controller.
4.2.5 Resetting the Maintenance Timer
1. From the Overview menu, step down to the Genset Run Time menu.
2. Press the Select button and then step down to the Next Maintenance screen.
3. Press the Select button.
4. Press the Up arrow button so that "Reset Maint Timer? Yes" is displayed.
5. Press the Select button. After about two minutes, the new maintenance interval and date are displayed.

4.2.6 Oil Cooler (20RCA/RCAL only)
Inspect and clean the oil cooler at the intervals indicated in the service schedule. The oil cooler must be kept free of debris.
See Figure 4-3 and Figure 4-4 for the oil cooler location. The oil cooler is located under the No. 2 cylinder shroud. Remove the top mounting screw and loosen the two side screws, then lift off the cylinder shroud.
Clean the outside of the oil cooler fins with a brush or with compressed air.

1 Note: See Figure 4-3 for location.
1. Oil cooler
Figure 4-4 Oil Cooler

62 590 01

64 Section 4 Scheduled Maintenance

TP-7092 2/21

4.3 Spark Plugs
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING

3. Check the spark plug gap using a wire feeler gauge. See Figure 4-5 for the recommended spark plug gap. Adjust the gap by carefully bending the ground electrode. See Figure 4-6 and Figure 4-7.
4. Reinstall the spark plug into the cylinder head. Torque the spark plug to 24.4- 29.8 Nm (18- 22 ft. lb.)

Generator Set Model 14 and 20 kW models

Spark Plug Gap 0.76 mm (0.030 in.)

Figure 4-5 Spark Plug Gap

1- 514
Figure 4-6 Checking the Spark Plug Gap

Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.

1- 511
Figure 4-7 Adjusting the Spark Plug Gap

Reset the spark plug gap or replace the plugs with new plugs as necessary.
1. Clean the area around the base of the spark plug to keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition. Replace the spark plug if it is worn or if its reuse is questionable.

TP-7092 2/21

Section 4 Scheduled Maintenance 65

4.4 Air Cleaner Service
WARNING
Risk of fire. Can cause severe injury or death. Do not smoke or permit flames or sparks near fuels or the fuel system. Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
4.4.1 Air Cleaner, 14 kW Models
The engine has a replaceable high-density paper air cleaner element. See Figure 4-8.
1
2 3
4
5
6
586536
1. Cover knob 2. Air cleaner cover 3. Element cover nut 4. Element cover 5. Air cleaner element 6. Air cleaner base
Figure 4-8 Air Cleaner Components Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components. Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air into the engine causing premature wear and failure.

Air Cleaner Service
Use the following procedure to replace the paper element at the intervals specified in the service schedule. Replace the paper element more often under extremely dusty or dirty conditions.
1. Press the OFF button on the generator set controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting battery, negative (- ) lead first.
4. Loosen the cover retaining knob and remove the cover.
5. Remove the element cover nut, element cover, and the paper element.
Note: Do not wash the paper element or clean it with pressurized air, as this will damage the element.
6. Replace the element if it is dirty, bent, or damaged.
7. Check the air cleaner base. Make sure it is secure and not bent or damaged. Also check the element cover for damage and fit. Replace all damaged air cleaner components. Remove any loose dirt or debris from the air cleaner base. Wipe the base carefully so that no dirt drops into the intake throat. Check the condition of the rubber seal on the air cleaner stud and replace the seal if necessary.
8. Reinstall the paper element, element cover, element cover nut, and the air cleaner cover. Secure the cover with the cover retaining knob.
9. Reconnect the utility power to the generator set.
10. Reconnect the generator set engine starting battery, negative (- ) lead last.

66 Section 4 Scheduled Maintenance

TP-7092 2/21

4.4.2 Air Cleaner, 20 kW Models
The engine is equipped with a replaceable, high density paper air cleaner element. See Figure 4-9.
1 2
3

4

tp6515

1. Knobs (qty.2) 2. Cover

3. Paper element 4. Base

Figure 4-9 Air Cleaner Components

Check the air cleaner daily or before starting the engine. Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components.

Note: Operating the engine with loose or damaged air cleaner components could allow unfiltered air into the engine causing premature wear and failure.

Air Cleaner Service
Replace the paper element at the intervals indicated in the service schedule. See Section 4.1.2 for the service schedule. See Figure 4-9 for the air cleaner components.
1. Loosen the two cover retaining knobs and remove the cover.
2. Remove the paper element.
3. Do not wash the paper element or use pressurized air, as this will damage the element. Replace a dirty, bent, or damaged element. Handle new elements carefully; do not use if the sealing surfaces are bent or damaged.
4. When servicing the air cleaner, check the air cleaner base. Make sure it is secured and not bent or damaged. Also, check the element cover for damage or improper fit. Replace all damaged air cleaner components.
Note: If any loose dirt or debris fell on the air cleaner base when the element was removed, carefully remove it and wipe the base clean. Be careful that none of it drops into the intake throat.
5. Reinstall the paper element onto the air cleaner base. Make sure the element is flat and properly seated.
6. Install the air cleaner cover and secure with the two retaining knobs.
7. When element replacement is necessary, order genuine Kohler parts.

TP-7092 2/21

Section 4 Scheduled Maintenance 67

4.5 Cooling System
The engine fan draws cooling air through the openings in the sides and end near the battery. The alternator fan draws cooling air through openings on the side walls of the enclosure. The cooling air mixes with the engine exhaust and is discharged at the exhaust outlet. See the service view in Section 1.9 for air intake and exhaust locations. To prevent generator set damage caused by overheating, keep the housing cooling inlets and outlets clean and unobstructed at all times.
Note: Do not block the generator set cooling air inlets or mount other equipment above them. Overheating and severe generator damage may occur.
4.6 Exhaust System
WARNING

Carbon monoxide. Can cause severe fainting, or death.

nausea,

The exhaust system must be leakproof and routinely inspected.

Remove all combustible materials from the exhaust location. Combustible materials include building materials as well as natural surroundings. Keep dry field grass, foliage, and combustible landscaping material a minimum of 1.2 m (4 ft.) from the exhaust outlet.
Periodically inspect the exhaust system components for cracks, leaks, and corrosion.
Check for corroded or broken metal parts and replace them as needed.
Check that the exhaust outlet is clear.

4.7 Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery. Never connect the negative (- ) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.

68 Section 4 Scheduled Maintenance

TP-7092 2/21

Refer to this section for general battery information and maintenance. Also consult the battery manufacturer's instructions for battery maintenance.
All generator set models use a negative ground with a 12-volt engine electrical system. Consult the generator set nameplate for the engine electrical system voltage. Consult the generator spec sheet for battery size and capacity recommendations for replacement purposes. Wiring diagrams provide battery connection information. See Figure 4-10 for typical battery connections.

1

2

1. To positive (+) terminal on starter solenoid. 2. To ground (- ) terminal on or near starter motor.

EZ-273000-J

Figure 4-10 12-Volt Engine Electrical System Single Starter Motor, Typical Battery Connection

4.7.1 Cleaning the Battery
Clean the battery and cables and tighten battery terminals using the service schedule recommendations. To prevent corrosion, maintain tight, dry electrical connections at the battery terminals. To remove corrosion from battery terminals, disconnect the cables from the battery and scrub the terminals with a wire brush. Clean the battery and cables with a solution of baking soda and water. After cleaning, flush the battery and cables with clean water and wipe them with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery terminals with petroleum jelly, silicone grease, or other nonconductive grease.
4.7.2 Checking Electrolyte Level
Check the electrolyte level of batteries with filler caps monthly. Remove filler caps and verify that electrolyte level reaches bottom of filler holes. Refill as necessary with distilled water. DO NOT add fresh electrolyte. Tighten all filler caps. If water is added during freezing temperatures, run the generator set for 20- 30 minutes to mix the electrolyte and water to prevent battery damage from freezing.

4.7.3 Checking Specific Gravity
Use a battery hydrometer to check the specific gravity of the electrolyte in each battery cell. While holding the hydrometer vertically, read the number on the glass bulb at the top of the electrolyte level or the number adjacent to the pointer. If the hydrometer used does not have a correction table, use the correction factors in Figure 4-13. Determine specific gravity and electrolyte temperature of battery cells. Locate temperature in Figure 4-13 and adjust the specific gravity by the amount shown.

The battery is fully charged if the specific gravity is 1.260 at an electrolyte temperature of 80°F (26.7°C). The difference between specific gravities of each cell should not exceed 0.01. Charge the battery if the specific gravity is below 1.215 at an electrolyte temperature of 80°F (26.7°C). See Figure 4-11.

Specific Gravity, Corrected to 80°F (26.7°C)

Battery Condition

Below 1.215 1.260

Needs charging Fully charged

Figure 4-11 Specific Gravity Interpretation

Some battery testers have four or five beads in the test tube. Draw electrolyte into the tube as performed with the battery hydrometer described previously. Use the manufacturer's instructions. Figure 4-12 interprets typical test results.

Number of Floating Beads

Battery Condition

5

Overcharged

4

Fully charged

3

Good charge

1 or 2

Low charge

0

Dead battery

Figure 4-12 Bead-Type Test Interpretation

TP-7092 2/21

Section 4 Scheduled Maintenance 69

Tempera-
°C t°uFre
71.1 160 65.6 150 60.0 140 54.4 130 48.9 120 43.3 110 37.8 100 32.2 90 26.7 80 21.1 70 15.6 60
10 50 4.4 40 - 1.1 30 - 6.7 20 - 12.2 10

Correction

+ .032

+ .030

+ .028 + .026 + .024

EXAMPLE NO. 1--
Temperature below 80°F (26.7°C)

+ .022 + .020 + .018 + .016 + .014

Hydrometer Reading 1.250
Acid Temperature 20°F (- 6.7°C)
Subtract .024 Specific Gravity Corrected Specific Gravity is 1.226

+ .012 1.250 - .024 = 1.226
+ .010

+ .008

+ .006 + .004 + .002 0

EXAMPLE NO. 2--
Temperature above 80°F (26.7°C)
Hydrometer Reading 1.235

- .002 - .004 - . 006 - .008 - .010 - .012

Acid Temperature 100°F (37.8°C)
Add .008 Specific Gravity Corrected Specific Gravity is 1.243
1.235 + .008 = 1.243

- .014

- .016

- .018

- .020

- .022

- .024

- .026

- .028

The temperature correction amounts to about .004 (4 points) of specific gravity for each 10°F (5.5°C) change in temperature.
1-787
Figure 4-13 Specific Gravity Temperature Correction

70 Section 4 Scheduled Maintenance

TP-7092 2/21

4.8 Storage Procedure
Perform the following storage procedure before removing the generator set from service for three months or longer. Follow the engine manufacturer's recommendations for storage, if available.
Note: Run the generator set monthly whenever possible.
4.8.1 Lubricating System
1. Operate the generator set until it reaches operating temperature, or about 15 minutes.
2. Stop the generator set.
3. While the engine is still warm, drain the engine lubrication oil from the engine crankcase.
4. Refill engine crankcase with oil. See Section 4.2.3 for oil recommendations.
5. Run the generator set for a few minutes to distribute the clean oil.
6. Stop the generator set.
4.8.2 Fuel System
1. Start the generator set.
2. With the generator set running, shut off the gas supply.
3. Run the generator set until the engine stops.
4. Press the OFF button on the generator set controller.

4.8.3 Cylinder Lubrication
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark plug hole. Install the spark plugs and ground the spark plug leads. Do not connect the leads to the plugs.
3. Crank the engine two or three revolutions to lubricate the cylinders.
4.8.4 Exterior Preparation
1. Clean the exterior surface of the generator set.
2. Seal all openings in the engine with nonabsorbent adhesive tape.
3. Mask all areas to be used for electrical contact.
4. Spread a light film of oil over unpainted metallic surfaces to prevent rust and corrosion.
4.8.5 Battery
Perform battery storage last.
1. Press the OFF button on the generator set controller.
2. Disconnect the battery, negative (- ) lead first.
3. Clean the battery.
4. Place the battery in a warm, dry location.
5. Connect the battery to a float/equalize battery charger, or charge the battery monthly using a trickle charger. Follow the battery charger manufacturer's recommendations.

TP-7092 2/21

Section 4 Scheduled Maintenance 71

Notes

72 Section 4 Scheduled Maintenance

TP-7092 2/21

5.1 Introduction
Use the troubleshooting charts in this section to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery, loose connections, or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, and recommended corrective actions.
If the procedures in this manual do not explain how to correct the problem, contact an authorized distributor/dealer. Maintain a record of repairs and adjustments performed on the equipment. Use the record to help describe the problem and repairs or adjustments made to equipment.
5.2 Fault Messages
The controller displays fault messages to aid in troubleshooting. Selected fault messages and recommended checks are listed in Figure 2-5.
Identify and correct the cause of the fault condition. Then reset the controller after a fault shutdown. See Section 2.5.5.

Section 5 Troubleshooting
5.4 USB Port and Auxiliary Winding Mini-Breaker
The USB port is located under a small rubber cover as shown in Figure 5-1. The alternator winding circuit breaker is located on the engine side of the bulkhead as shown in Figure 5-1.
A personal computer (laptop) with Kohler SiteTech software can be used to view the event history and adjust controller settings. Use a USB cable with a mini-B connector to connect the controller's USB port to your PC.
See TP-6701, SiteTech Software Operation Manual, for software operation instructions.
1
2

5.3 Circuit Protection
If the generator set circuit breaker trips repeatedly, contact an authorized distributor/ dealer for service.
5.3.1 Controller Internal Circuit Protection
The controller is equipped with internal circuit protection. A fault message, Accy PwrOver Warning or MainPwrOverL Shutdown, is displayed if this internal protection is activated. Press OFF to reset. Contact an authorized Kohler distributor/dealer for service.
5.3.2 Line Circuit Breaker
The line circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. If the circuit breaker trips, reduce the load and switch the breaker back to the ON position.

ADV-8928
1. Mini-breaker location (access through engine compartment) 2. USB port on RDC2 controller
Figure 5-1 USB Port and Mini-Breaker Locations
5.5 Stop Switches
The generator set may be equipped with an optional emergency stop switch or an engine shutdown switch. Verify that it is safe to start the generator set and apply power to the load before deactivating these switches. See Section 2.3.4.

TP-7092 2/21

Section 5 Troubleshooting 73

5.6 Thermostat
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING

Procedure to Reset the Thermostat 1. Disconnect the utility power to the generator by opening (turning OFF) the corresponding circuit breaker at the building's distribution panel.
2. Open the enclosure roof and secure it with the roof stay on the left side of the enclosure.
3. Remove the air intake panel. See Figure 5-2.
4. Press the button on the thermostat to reset it.
5. Replace the air intake panel.
6. Reconnect utility power to the generator set by closing the circuit breaker in the distribution panel.
7. Reset the fault on the controller. Refer to Section 2.5 for instructions, if necessary.
1

Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
2 The generator sets include a resettable thermostat. See Figure 5-2 for the thermostat location in the air intake area, near the fuel system. The thermostat detects excess heat inside the enclosure. If the thermostat trips, the generator will shut down and the controller will display a fault (underspeed, underfrequency, or undervoltage). Check for blocked air inlets and exhaust outlets. Then follow these steps to reset the thermostat.
1. Thermostat location 2. Thermostat reset button
Figure 5-2 Thermostat
74 Section 5 Troubleshooting

TP-7092 2/21

5.7 Troubleshooting

Figure 5-3 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections before replacing parts.

Troubleshooting Table

Problem

Possible Cause

Controller

Backlight turns off after about 1 minute with no

display

activity.

backlight is off.

Controller display is off.

Low or no battery voltage.

The generator set does not crank.

Battery weak or dead. Battery connections reversed or poor.

Emergency stop switch switch activated.

Fault shutdown.

Generator set in the OFF mode.

Generator thermostat tripped.

The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
No AC output.

Air cleaner clogged. Battery weak or dead. Battery connection poor. Spark plug wire connection loose. Low oil pressure shutdown.
Fuel pressure insufficient. Engine malfunction. Line circuit breaker in the OFF position. Line circuit breaker tripping because of overload. Line circuit breaker tripping because of short circuit. Auxiliary winding circuit breaker tripped.

Low output or Generator set overloaded. excessive drop in voltage.

Corrective Action
Backlight will turn on when a button is pressed or the generator set starts.
Check connections. Check generator set battery. See Figure 5-3. Recharge or replace the battery. Make sure that the AC power to the generator set controller is backed up by the generator set. Check the connections.
Verify that it is safe to start the engine and apply load. Then reset the stop switch or engine shutdown switch. Check the controller display for fault messages. See Section 2.5. Correct the fault condition and reset the controller. Press the RUN button to start the engine or press AUTO to allow remote starting.
Check for obstructed air inlets and outlets. Reset the thermostat. See Section 5.6.
Clean and/or replace the air cleaner. Recharge or replace the battery. Clean and tighten the battery connections. Check the spark plug wires. Check for oil leaks. Check the oil level and add oil if necessary.
Check the fuel supply and valves. Contact an authorized distributor/dealer. Place the circuit breaker in the ON position. Reduce the load on the generator set by unplugging non-essential appliances.
Contact an authorized distributor/dealer for service.
Reset the circuit breaker (located in controller's service access area). Contact an authorized distributor/dealer for service if breaker trips repeatedly. Reduce the load by unplugging non-essential appliances.

TP-7092 2/21

Section 5 Troubleshooting 75

Troubleshooting Table

Problem
Generator set stops suddenly.

Possible Cause Low oil pressure shutdown.
No fuel.

Corrective Action Check for oil leaks. Check the oil level and add oil if necessary.
Check fuel valves and fuel supply.

Overcrank shutdown. Auxiliary winding circuit breaker tripped.

Model 20RCA/20RCAL only: Check enclosure thermostat and reset if tripped. See Section 5.6. Check and clear air inlets and exhaust outlets.
Reset the controller. If the overcrank fault occurs again, contact an authorized distributor/dealer.
Reset the auxiliary winding circuit breaker. Contact an authorized distributor/dealer for service if breaker trips repeatedly.

Emergency stop switch switch activated. Fault shutdown.
Generator set in the OFF mode. Remote stop command received from a remote switch, ATS, or OnCue Plus. Generator thermostat tripped. Engine malfunction.

Verify that it is safe to start the engine and apply load. Then reset the stop switch or engine shutdown switch. Check the controller display for fault messages. See Section 2.5. Correct the fault condition and reset the controller. Press the RUN button to start the engine or press AUTO to allow remote starting.
Check the remote switch position. Check OnCue Plus.
Check for obstructed air inlets and outlets. Reset the thermostat. See Section 5.6.
Contact an authorized distributor/dealer.

Figure 5-3 General Troubleshooting

76 Section 5 Troubleshooting

TP-7092 2/21

Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.

A, amp ABDC AC A/D ADC
adj. ADV
Ah AHWT
AISI
ALOP alt. Al ANSI
AO APDC API approx. APU AQMD AR AS
ASE ASME
assy. ASTM
ATDC ATS auto. aux. avg. AVR AWG AWM bat. BBDC BC
BCA BCI BDC BHP blk.
blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CAN CARB CAT5 CB CC cc CCA ccw. CEC cert. cfh

ampere after bottom dead center alternating current analog to digital advanced digital control; analog to digital converter adjust, adjustment advertising dimensional drawing amp-hour anticipatory high water temperature American Iron and Steel Institute anticipatory low oil pressure alternator aluminum American National Standards Institute (formerly American Standards Association, ASA) anticipatory only Air Pollution Control District American Petroleum Institute approximate, approximately Auxiliary Power Unit Air Quality Management District as required, as requested as supplied, as stated, as suggested American Society of Engineers American Society of Mechanical Engineers assembly American Society for Testing Materials after top dead center automatic transfer switch automatic auxiliary average automatic voltage regulator American Wire Gauge appliance wiring material battery before bottom dead center battery charger, battery charging battery charging alternator Battery Council International before dead center brake horsepower black (paint color), block (engine) block heater brake mean effective pressure bits per second brass before top dead center British thermal unit British thermal units per minute Celsius, centigrade calorie controller area network California Air Resources Board Category 5 (network cable) circuit breaker crank cycle cubic centimeter cold cranking amps counterclockwise Canadian Electrical Code certificate, certification, certified cubic feet per hour

cfm

cubic feet per minute

CG

center of gravity

CID

cubic inch displacement

CL

centerline

cm

centimeter

CMOS complementary metal oxide

substrate (semiconductor)

com

communications (port)

coml

commercial

Coml/Rec Commercial/Recreational

conn. connection

cont.

continued

CPVC chlorinated polyvinyl chloride

crit.

critical

CSA

Canadian Standards Association

CT

current transformer

Cu

copper

cUL

Canadian Underwriter's

Laboratories

CUL

Canadian Underwriter's

Laboratories

cu. in. cubic inch

cw.

clockwise

CWC city water-cooled

cyl.

cylinder

D/A

digital to analog

DAC

digital to analog converter

dB

decibel

dB(A) decibel (A weighted)

DC

direct current

DCR

direct current resistance

deg., ° degree

dept.

department

dia.

diameter

DI/EO dual inlet/end outlet

DIN

Deutsches Institut fur Normung

e. V. (also Deutsche Industrie

Normenausschuss)

DIP

dual inline package

DPDT double-pole, double-throw

DPST double-pole, single-throw

DS

disconnect switch

DVR

digital voltage regulator

E2PROM, EEPROM

electrically-erasable

programmable read-only

memory

E, emer. emergency (power source)

ECM

electronic control module,

engine control module

EDI

electronic data interchange

EFR

emergency frequency relay

e.g.

for example (exempli gratia)

EG

electronic governor

EGSA Electrical Generating Systems

Association

EIA

Electronic Industries

Association

EI/EO end inlet/end outlet

EMI

electromagnetic interference

emiss. emission

eng.

engine

EPA

Environmental Protection

Agency

EPS

emergency power system

ER

emergency relay

ES

engineering special,

engineered special

ESD

electrostatic discharge

est.

estimated

E-Stop emergency stop

etc.

et cetera (and so forth)

TP-7092 2/21

exh. ext. F FHM fl. oz. flex. freq. FS ft. ft. lb. ft./min. ftp g ga. gal. gen. genset GFI

exhaust external Fahrenheit, female flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute file transfer protocol gram gauge (meters, wire size) gallon generator generator set ground fault interrupter

GND, ground

gov.

governor

gph

gallons per hour

gpm

gallons per minute

gr.

grade, gross

GRD

equipment ground

gr. wt. gross weight

H x W x D height by width by depth

HC

hex cap

HCHT high cylinder head temperature

HD

heavy duty

HET

high exhaust temp., high

engine temp.

hex

hexagon

Hg

mercury (element)

HH

hex head

HHC

hex head cap

HP

horsepower

hr.

hour

HS

heat shrink

hsg.

housing

HVAC heating, ventilation, and air

conditioning

HWT

high water temperature

Hz

hertz (cycles per second)

IBC

International Building Code

IC

integrated circuit

ID

inside diameter, identification

IEC

International Electrotechnical

Commission

IEEE

Institute of Electrical and

Electronics Engineers

IMS

improved motor starting

in.

inch

in. H2O inches of water in. Hg inches of mercury

in. lb. inch pounds

Inc.

incorporated

ind.

industrial

int.

internal

int./ext. internal/external

I/O

input/output

IP

internet protocol

ISO

International Organization for

Standardization

J

joule

JIS

Japanese Industry Standard

k

kilo (1000)

K

kelvin

kA

kiloampere

KB

kilobyte (210 bytes)

kg

kilogram

Appendix 77

kg/cm2 kilograms per square

centimeter

kgm kg/m3

kilogram-meter kilograms per cubic meter

kHz

kilohertz

kJ

kilojoule

km

kilometer

kOhm, k kilo-ohm

kPa

kilopascal

kph

kilometers per hour

kV

kilovolt

kVA

kilovolt ampere

kVAR kilovolt ampere reactive

kW

kilowatt

kWh

kilowatt-hour

kWm

kilowatt mechanical

kWth

kilowatt-thermal

L

liter

LAN

local area network

L x W x H length by width by height

lb. lbm/ft3

pound, pounds pounds mass per cubic feet

LCB

line circuit breaker

LCD

liquid crystal display

LED

light emitting diode

Lph

liters per hour

Lpm

liters per minute

LOP

low oil pressure

LP

liquefied petroleum

LPG

liquefied petroleum gas

LS

left side

Lwa LWL

sound power level, A weighted low water level

LWT

low water temperature

m

meter, milli (1/1000)

M

mega (106 when used with SI

units), male

m3

cubic meter

m3/hr. cubic meters per hour m3/min. cubic meters per minute

mA

milliampere

man.

manual

max. MB

maximum megabyte (220 bytes)

MCCB molded-case circuit breaker

MCM

one thousand circular mils

meggar megohmmeter

MHz

megahertz

mi.

mile

mil

one one-thousandth of an inch

min.

minimum, minute

misc.

miscellaneous

MJ

megajoule

mJ

millijoule

mm

millimeter

mOhm, mmilliohm

MOhm, Mmegohm

MOV

metal oxide varistor

MPa

megapascal

mpg

miles per gallon

mph

miles per hour

MS

military standard

ms

millisecond

m/sec. meters per second

mtg.

mounting

MTU

Motoren-und Turbinen-Union

MW

megawatt

mW

milliwatt

µF

microfarad

N, norm. normal (power source)

NA

not available, not applicable

nat. gas natural gas

NBS

National Bureau of Standards

NC

normally closed

NEC

National Electrical Code

NEMA National Electrical

Manufacturers Association

NFPA National Fire Protection

Association

Nm

newton meter

NO

normally open

no., nos. number, numbers

NPS

National Pipe, Straight

NPSC National Pipe, Straight-coupling

NPT

National Standard taper pipe

thread per general use

NPTF National Pipe, Taper-Fine

NR

not required, normal relay

ns

nanosecond

OC

overcrank

OD

outside diameter

OEM

original equipment

manufacturer

OF

overfrequency

opt.

option, optional

OS

oversize, overspeed

OSHA Occupational Safety and Health

Administration

OV

overvoltage

oz.

ounce

p., pp. page, pages

PC

personal computer

PCB

printed circuit board

pF

picofarad

PF

power factor

ph.,  phase

PHC

Phillips head Crimptite

(screw)

PHH

Phillips hex head (screw)

PHM

pan head machine (screw)

PLC

programmable logic control

PMG

permanent magnet generator

pot

potentiometer, potential

ppm

parts per million

PROM programmable read-only

memory

psi

pounds per square inch

psig

pounds per square inch gauge

pt.

pint

PTC

positive temperature coefficient

PTO

power takeoff

PVC

polyvinyl chloride

qt.

quart, quarts

qty.

quantity

R

replacement (emergency)

power source

rad.

radiator, radius

RAM

random access memory

RBUS RS-485 proprietary

communications

RDO

relay driver output

ref.

reference

rem.

remote

Res/Coml Residential/Commercial

RFI

radio frequency interference

RH

round head

RHM

round head machine (screw)

rly.

relay

rms

root mean square

rnd.

round

RO

read only

ROM

read only memory

rot.

rotate, rotating

rpm

revolutions per minute

RS

right side

RTDs Resistance Temperature

Detectors

RTU RTV RW SAE
scfm SCR s, sec. SI
SI/EO sil. SMTP SN SNMP
SPDT SPST spec specs sq. sq. cm sq. in. SMS SS std. stl. tach. TB TCP TD TDC TDEC TDEN
TDES TDNE
TDOE TDON temp. term. THD TIF tol. turbo. typ.
UF UHF UIF UL UNC UNF univ. URL
US UV V VAC VAR VDC VFD VGA VHF W WCR w/ WO w/o wt. xfmr

remote terminal unit room temperature vulcanization read/write Society of Automotive Engineers standard cubic feet per minute silicon controlled rectifier second Systeme international d'unites, International System of Units side in/end out silencer simple mail transfer protocol serial number simple network management protocol single-pole, double-throw single-pole, single-throw specification specification(s) square square centimeter square inch short message service stainless steel standard steel tachometer terminal block transmission control protocol time delay top dead center time delay engine cooldown time delay emergency to normal time delay engine start time delay normal to emergency time delay off to emergency time delay off to normal temperature terminal total harmonic distortion telephone influence factor tolerance turbocharger typical (same in multiple locations) underfrequency ultrahigh frequency user interface Underwriter's Laboratories, Inc. unified coarse thread (was NC) unified fine thread (was NF) universal uniform resource locator (web address) undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt withstand and closing rating with write only without weight transformer

78 Appendix