SICCOM mini FLOWATCH® 2

Innovative Vision

Product Overview

The SICCOM mini FLOWATCH® 2 is a compact and efficient condensate pump designed for air conditioning units. It is suitable for lifting condensate up to 10 meters vertically with a flow rate of 15 liters per hour.

Technical Specifications

Feature Specification
Model mini FLOWATCH® 2 (DE05LC4400)
Capacity 15 l/h
Max Head 10 m
Electrical Features 220-240V 50-60Hz / 19W
Class Class I
Operation 100% Continuous
Alarm NO/NC 3A
Thermal Protection Yes
IP Protection IP64
Noise Level 2 m (max)
Suction Tube Diameter 5 mm
Vent Tube Diameter 4 mm
Vent Tube Length 150 mm
Discharge Tube Diameter 6 x 9 mm

Safety Precautions

This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children must not play with the appliance. Cleaning and maintenance by the user must not be performed by children.

The connection of the power supply cable must be carried out by a qualified professional, in accordance with the standards in force, providing a means of disconnection in the fixed pipes.

If the power cable is damaged, it must be replaced with a special cable or assembly available from the manufacturer or its service department.

Installation Instructions

A. Electric / Alarm Connection

1. Pump Power Supply: Disconnect all AC power during installation.

2. Alarm Connection: The pump has a normally closed (NC) safety contact to stop the indoor air conditioning unit if there is a risk of condensate overflow. Follow Figure 4 for the alarm connection.

B. Detection Unit Installation

The detection unit (B) is supplied with very low voltage by the pump unit. It is imperative to use the supplied cable. A flexible elbow sleeve (F) is used to connect the detection unit to the air conditioner tank. Suction is made through the 1.8m flexible tube (G) with an internal diameter of 5 mm. Use 2 clamps (E) to ensure water/air tightness of this flexible tube to the detection unit and the pump. Connect the vent tube (D), internal diameter 4 mm, length 150 mm.

The detection unit must be placed and fixed in a horizontal position (see Figure 5) by means of the plastic stand and the double-sided adhesive (I). Choose the most suitable discharge direction for the application and seal the unused discharge outlet with the black plug (see Figure 5).

C. Pump Unit Installation

The pump (A) can be mounted in the air conditioner, in a trunking, or in a false ceiling. A double-sided adhesive (H) is provided for this purpose. A free space must be left around the pump (A) to allow it to cool down in case of prolonged operation. The pump (A) must not be covered (no insulation, foam, etc.).

The discharge tube (not supplied) must have a diameter of 6x9mm to be fixed on the outlet connection. Use a hose clamp (E) to ensure water/air tightness. Observe the direction of flow indicated by the arrow on the pump unit.

If the end of the discharge tube is at a lower level than the pump unit, and in order to avoid a siphoning effect (negative discharge - see Figure 7), it is imperative to:

Operation and Maintenance

D. Operation and Maintenance

1. Operating Test (recommended): Caution: Never run the pump dry for more than the few seconds required for commissioning (risk of damage to the pump). Pour water into the air conditioner tray without excess (NB the vent tube must remain dry). Check that the pump is switched on and that the water is drained from the pump and then switched off. Test the alarm by pouring water continuously, even after the pump is switched on, so that the float activates the alarm (high level float).

2. Maintenance: Any work on the condensate pump must be carried out with the power off. When maintenance is required: Remove the cover of the detection unit, the filter, and the float. Clean the inside of the reservoir and the float with an anti-bacterial solution. Rinse thoroughly after using any cleaning product. Make sure that the cover gasket is in its housing. Make sure that the float is correctly positioned (magnet upwards) (see Diagram 6).

Warranty Information

For warranty conditions, please visit: www.siccom.com/garantie

Models: DE05LC4400 Mini FLOWATCH 2, DE05LC4400, Mini FLOWATCH 2, FLOWATCH 2