Split System Air Conditioners Odyssey™ with Symbio™ Controls

Split System Air Conditioners Odyssey™ with Symbio™ Controls

PDF preview unavailable. Download the PDF instead.

SS-PRC029Y-EN 09102021
Product Catalog
Split System Air Conditioners OdysseyTM with SymbioTM Controls
Cooling Condenser, 5 to 20.9 Tons, 50 Hz Air Handler, 4.6 to 20.9 Tons, 50 Hz

September 2021

SS-PRC029Y-EN

Introduction

OdysseyTM Split Systems offer a wide range of options, allowing you to easily match unit tonnage with the right load requirements.
When a project calls for the convenience and cost efficiency of a unitary product, where a rooftop unit isn't right, Odyssey may be the answer. It provides heating and cooling in a split configuration that's unique in its versatility while staying true to our standards for efficiency and reliability. And with the Symbio® digital controller on board, Odyssey introduces smart building capabilities that take service, comfort and sustainability beyond the expected.
With wide network availability, flexible applications, installation ease, built-in reliability and easy servicing, Odyssey will meet any number of customer applications. Add to that Trane's outstanding customer service and you have the formula to make Odyssey the clear choice for continued customer satisfaction.
Wide network availability
A broad distribution network provides owners, maintenance personnel, contractors, etc., the means to get their hands on equipment when they need it. Whether it's an emergency replacement or a new construction project in its infancy stages, Odyssey products meet an array of needs at the right time and right price.
Flexible applications
No matter what the application, Odyssey provides the solution. A broad array of models and tonnages are available with single or dual compressors, single or dual circuits and numerous accessories. Condensing units can be installed on the ground or on a rooftop along with extended piping runs, while air handlers can be free discharge on the ground or horizontally suspended with long duct runs from a ceiling. Should application challenges arise, Odyssey delivers.

©2021 Trane

SS-PRC029Y-EN

Introduction
Easy to install
Small footprints and low weights combined with factory installed components like TXVs, filter driers, etc., reduce installation time and cost. Colored connectors and wiring, as well as factorytested units make Odyssey the right choice.

Built-in reliability
Keeping in mind that productivity only occurs when equipment is operational,Trane has taken the steps to ensure that Odyssey is up and running. Early indicators such as phase/reversal monitors and loss of charge protection provide diagnostics which prevent failure and provide years of worry-free service and operation.

Easy to service
When preventive maintenance or service is required, technicians will find efficient access to both air handlers and condensers. Panels provide complete, easy access coupled with standardized cabinets in which all components are located in proximity. Odyssey's improved design results in minimum service times and costs.
With these capabilities, Odyssey provides customers high efficiency and superior performance for the best all-around value in the market today.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
· Updated SymbioTM jobsite connections · Minor edits included

SS-PRC029Y-EN

3

Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Split System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Other Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Standard and Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Additional Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 180° Blower Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Cooling Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Heating Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Air Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Zone Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Zone Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Conventional Thermostats. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 SymbioTM Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

4

SS-PRC029Y-EN

Table of Contents
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Air Handlers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

SS-PRC029Y-EN

5

Features

Split System Overview
Unlike typical split systems on the market, Odyssey offers easy servicing, built-in reliability, ease of installation and outstanding customer service. And because today's owners are very costconscious when it comes to service and maintenance, the Odyssey Split System was designed with direct input from service contractors. This valuable information helped to design a product that would get the service person off the job quicker and save the owner money.
Flexible Applications
Odyssey offers outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support. Because of this, Odyssey offers ultimate flexibility. Units are built to order in our standard "shortest in the industry" ship cycle time. Odyssey is available with single, dual and manifolded compressor options. Single compressor outdoor units feature a single refrigeration circuitry, lowering job installation costs by requiring only one set of refrigerant lines.
Equally important, Odyssey offers single refrigerant circuit/capacity unloading models. The unloading units feature dual manifolded scroll compressors with two stages of capacity modulation and a single refrigeration circuit. Dual compressor/dual circuit models give true stand-by protection - if one compressor fails, the second will automatically start-up. Also, the first compressor can be serviced without shutting down the unit since the refrigerant circuits are independent. Dual compressor models also save on energy costs. During light load conditions, only one compressor will operate to save energy.
Unmatched Product Support
One of our finest assets, Trane Sales Representatives are a support group that can assist you with:
· Product
· Application
· Service
· Training
· Special Applications
· Specifications
· Computer Programs and much more
Rigorous Testing
Our units are rigorously rain tested to ensure water integrity. Actual shipping tests are performed to determine packaging requirements. Units are test shipped around the country to determine the best packaging. Factory shake and drop tests are used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. A 100% coil leak test is performed at the factory. The condenser coils are leak tested at 660 psig and evaporators to 450 psig. All parts are inspected at the point of final assembly. Substandard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to ensure it lives up to rigorous Trane requirements.

Other Features

Microchannel Condenser Coil
Microchannel condensing coils are all-aluminum coils with fully-brazed construction. This design reduces risk of leaks and provides increased coil rigidity -- making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer. Microchannel all-aluminum construction provides several additional benefits:

6

SS-PRC029Y-EN

· Light weight (simplifies coil handling) · Easy to recycle · Minimize galvanic corrosion

Features

Standard and Optional Features
Figure 1. Compressors

Figure 2. Belt drive motor

SS-PRC029Y-EN

Airflow Distribution -- Odyssey can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.
Anti-Short Cycle Timing -- The SymbioTM 700 controller provides a 3 minute minimum "ON" time and 3 minute "OFF" time for compressors to enhance compressor reliability by assuring proper oil return.
Belt Drive Motors -- For additional static requirements, Odyssey Split Systems offer standard belt drive motors to meet and exceed a wide range of airflow needs.
Colored Connectors and Wiring -- Interconnecting wiring between components is standardized using colored and keyed connectors and colored wires, helping to save time and money tracing wires and diagnosing the unit.
Compressors -- Odyssey Split Systems contain the best compressor technology available to achieve the highest possible performance. Dual compressors perform very well under part load cooling conditions and system back- up applications. Dual compressors are available on 4.6-20.9 ton models and allow for efficient cooling utilizing 2-stages of compressor operation.
Complete CoatTM Microchannel Condenser Coil -- This cathodic, epoxy-type electrodisposition coating is formulated for high edge builds and provides excellent resistance and durability in potentially corrosive environments due to alkalies, acids, alcohols, petroleum, seawater, salty air, etc. Available for Microchannel units only.
Convertible Units -- The air handlers ship in a horizontal configuration. They can be easily converted to vertical by simply repositioning the drain pan.
7

Features

Crankcase Heaters -- These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions.
Dual Sloped Drain Pans-- Every Odyssey unit has a non-corrosive, removable, double sloped drain pan that's easy to clean and reversible to allow installation of drain trap in two positions on either side of the unit.
Duct flanges -- An optional field installed kit that can save time and money.
Easy Access Low Voltage Connections -- Thermostat and other low voltage control wiring connections are made directly to the Symbio 700 and other boards in the system. Screw-type pressure connectors are detachable from the boards for easy connection of control wires ­ saving cost and time.
Electric Heaters -- Electric heat modules are available in a variety of voltages and capacities.
Foil Faced Insulation -- All internal air handler surfaces have cleanable foil-faced insulation. All edges are either captured or sealed to ensure insulation fibers do not get into the airstream.
Hail/Vandal Guards -- These coil guards shall be either factory or field installed for condenser coil protection. This feature protects the condenser coil from vandalism and/or hail damage. When ordered factory installed, it also adds additional shipping protection.
High Static Motor -- Available on many models, this high static motor accessory extends the capability of the standard unit.
High and Low Voltage Control Panel -- High voltage components and connections are isolated from low voltage and covered with a sheet metal panel. This allows setup and test parameters at the SymbioTM 700 display and the VFD keypad display to be safely viewed and adjusted in the low voltage section of the control panel.
High Pressure Control -- All units include High Pressure Control as standard.
Low Ambient Cooling -- All Odyssey units have cooling capabilities down to 0°F as standard. At temperatures below 50°F, some reduction in cooling capacity can be expected. When the optional Low Ambient Accessory kit is field installed, the full capacity of the unit is available down to 0°F.
Low Voltage Connections -- Low voltage wiring connects directly to the control boards in the unit via detachable connectors. This makes it easy for the installer to attach the wires and then snap the connectors into place.
Phase Monitor/Reversal Protection -- Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitors are equipped with an LED that provides an ON or FAULT indicator.
Quick-Access Panels -- Remove a few screws for access to the standardized internal components and wiring.
Single Point Power -- A single electrical connection powers the unit.
Single Side Service -- Single side service is standard on all units.
Standardized Components -- Components are placed in the same location on all Odyssey units. Because of these standardized components throughout the Odyssey line, contractors/ owners can stock fewer parts.
SymbioTM 700 -- Standard on Odyssey condensers, the SymbioTM 700 controller provides exceptional machine control with a focus on system reliability and application flexibility. The Symbio controller provides direct access to the Symbio Service and Installation mobile application for easy setup and troubleshooting with no special tools. A wide range of system integration options (Non-communicating, BACnet®, LonTalk®, etc.) provide options to meet the needs of your application.
Thermal Expansion Valve with Bypass Check Valves -- This feature is standard on all indoor units.
Unit Cabinet -- The compact cabinet takes up less room and is less costly to ship. The design also ensures water integrity.

8

SS-PRC029Y-EN

Table 1. Odyssey features ­ standard and optional

1-year Limited Parts Warranty

Options(a) Standard Factory Field Features Installed Installed
X

5-year Limited Compressor Warranty

X

Belt Drive Motors

X

Colored Connectors and Wiring

X

Complete CoatTM Microchannel Condenser Coil

X

Compressor Discharge Temperature Limit (DTL)

X

Convertible Airflow

X

Crankcase Heaters

X

Easy Access Low Voltage Connections

X

Electric Heaters

X

Filters

X

Filters ­ 2" MERV 13

X

Foil-Faced and Edge Captured Insulation

X

Hail/Vandal Guards

X

X

High Pressure Control

X

High Static Motor Kit(b)

X

Hot Gas Bypass

X

IAQ Dual Sloped and Removable Drain Pans

X

Low Ambient Cooling

X

Liquid Line Refrigerant Drier

X

Low Pressure Control

X

Low Static Motor Kit(b)

X

Low Voltage Circuit Protection

X

Phase Loss/Reversal Monitor

X

Quick Access Panels

X

Scroll Compressors

X

Single Point Power

X

Single Side Service

X

Standardized Components

X

SymbioTM Controls

X

Thermal Expansion Valve

X

Vibration Isolators

X

(a) Refer to model number description for option availability or contact Product Support. (b) Available on constant volume units only. See Accessories chapter for more information.

Features

SS-PRC029Y-EN

9

Features
Standard Controls
SymbioTM 700 Controls
Figure 3. Symbio 700 board

Symbio 700 controls provide unit control for heating, cooling, and ventilating, utilizing input from sensors that measure outdoor and indoor temperature. Symbio also provides outputs for building automation systems and expanded diagnostics. Quality and reliability are enhanced through Symbio control and logic:
· Prevents the unit from short cycling, considerably improving compressor life.
· Ensures the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.
· Reduces the number of components required to operate the unit, reducing possibilities for component failure.
Installation and Service
The SymbioTM 700 control platform provides a user-friendly, onboard interface that makes setup and continued operation easy ­ or users can take advantage of the SymbioTM Service and Installation Mobile App for setup, troubleshooting, and operation. Both the Symbio onboard user interface and mobile app simplify troubleshooting by displaying active alarms. Symbio eliminates the need for field-installed, anti-short cycle timer and time delay relays. The wiring of the low voltage connections to the unit and zone sensors is simple, making installation easy.
Testing
SymbioTM 700 requires no special tools to run the unit through its paces. Simply navigate to the `Service' section of the user interface or the `Utilities' section of the SymbioTM Service and Installation Mobile App and enter the test section. Here the unit can be placed in the desired operating condition for a pre-determined amount of time supporting troubleshooting efforts in the field. The Symbio 700 will return to normal control when the user exits test mode or when the pre-determined, user-selected Service Test time has expired.
Other Benefits
· SymbioTM 700 built-in anti-shortcycle timer, time delay relay and minimum "on" time control functions are factory tested to assure proper operation.
· Symbio 700 softens electrical "spikes" by staging on fans, compressors and heaters.
· Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.

10

SS-PRC029Y-EN

Features
· Intelligent Anticipation is a standard feature. It functions continuously as Symbio 700 and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electromechanical thermostats.
· The Symbio 700 design is standardized across the board, ensuring a lower cost to owners.
Additional Controls
VariTrac® Building Automation System -- When Trane's changeover VAV System for light commercial applications is coupled with the unit, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.

FrostatTM -- This control (a standard feature on all air handlers) utilizes a capillary bulb embedded in the face of the evaporator coil which monitors coil temperature to inhibit evaporator icing and protect the compressor. Useful for applications with low leaving air temperatures, low airflow and/or high latent load applications.
LonTalk® Communications Interface -- The LonTalk communications interface allows the unit to communicate as a Tracer LON® device or directly with generic LonTalk Network Building Automation System Controls.
BACnet® Communication Interface (BCI) -- The BACnet Communication Interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP or IP Network Building Automation Control System.
Zone Sensors/Thermostats-- Available in programmable, automatic and manual styles.

Table 2. Odyssey control options ­ standard and optional

BACnet® Communication Interface (BCI)

Options(a) Standard Factory Field Features Installed Installed
X

FroststatTM - Evaporator Defrost Control (EDC)

X

LonTalk® Communications Interface (LCI)

X

SymbioTM 700 Microprocessor Controls

X

Thermostat

X

Zone Sensor

X

(a) Refer to model number description for option availability or contact Product Support.

SS-PRC029Y-EN

11

Accessories

Cooling Condenser

Table 3. TTA Accessories

Model Coil (Hail/Vandal) Guard BAYGARD063* BAYGARD064* BAYGARD065* BAYGARD066* BAYGARD067* Universal Hot Gas Bypass Kit

Used With
TTA060, TTA076 TTA101 TTA126
TTA156, TTA201 TTA251

BAYHGBP010* Rubber Isolators BAYISLT004* (blue) BAYISLT005* (black) BAYISLT009* (red) BAYISLT010* (green) Steel Spring Isolators BAYISLT023* (red) BAYISLT024* (black) BAYISLT025* (yellow)

All models
TTA060, TTA076 TTA101
TTA126, TTA156 TTA201, TTA251
TTA060, TTA076, TTA101*DA TTA101*DC/D, TTA126, TTA156
TTA201, TTA251

Service Valve Kit

BAYVALV001*

TTA0604*A, TTA0764*A, TTA1014*A/C

BAYVALV003*

TTA0604*D, TTA0764*D, TTA1014*D

BAYVALV004*

TTA1264*D

BAYVALV005*

TTA1564*D, TTA2014*D

BAYVALV007*

TTA1654*C, TTA2014*C

BAYVALV008*

TTA2514*C

Low Ambient -- On/Off Fan Control(a) (b)

BAYLOAMS10* (External Mount, small cabinets)(c)

TTA060, TTA076, TTA101, TTA126

BAYLOAMS20* (Internal mount, large cabinets)

TTA156, TTA201, TTA251

Transducer Kit for Head Pressure Control (BAYLOAM435, 436, 437)

BAYLOTR001*(d) LonTalk Communications Interface(e)

TTA060**D, TTA076**D, TTA101**D, TTA126**D

BAYLTCI005*

All Models

Expansion Module Kit

BAYMODU002* (XM30)

All Models

BAYMODU004* (XM32)

All Models

(a) Cycles fan on/off (no modulating). (b) When BAYLOAM is used, the Evaporator Defrost Control (EDC) must be disabled in the Symbio 700 controller configuration. (c) Kit mounts external to the outdoor unit and operates by sensing ambient temperature and discharge pressure. (d) BAYLOTR001* required when BAYLOAMS10* kits are used with units that have 2 compressors (dual circuit) and 1 condenser fan. (e) Field installed LonTalk interface requires installation of Symbio control board with Advanced Diagnostics (not included).

12

SS-PRC029Y-EN

Accessories

Air Handler
Table 4. TWE Accessories
Model Base (Subbase) BAYBASE009* BAYBASE0010* BAYBASE0011* BAYBASE0012* BAYBASE0013* Drip Kit BAYDRKT006* BAYDRKT007* BAYDRKT008* BAYDRKT009* BAYDRKT010* Duct Flange Kit BAYDUCT010*
BAYDUCT020*
Filters ­ 2" MERV 13 BAYFILT001* BAYFILT002* BAYFILT003* BAYFILT004* BAYFILT005* High Static Motor Kits(a) BAYHSMT105* -- 1.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT108* -- 1.5HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT110* -- 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT112* -- 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT114* -- 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT117* -- 3.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt BAYHSMT120* -- 3.0HP (50Hz) with Motor Sheave and Fan Sheave (Stock Belt used) BAYHSMT126* -- 5.0 HP (50Hz) with Motor Sheave, Fan Sheave and Belt Rubber Isolators(b) (c) (d) BAYISLT004* (Floor -- Blue) BAYISLT009* (Floor -- Red)(e) BAYISLT010* (Floor -- Green)(e)(b) BAYISLT012* (Suspended --Red/Green) BAYISLT013* (Suspended --Red/Green)(d) BAYISLT014* (Suspended -- Green)(d) BAYISLT015* (Suspended -- Green/Black)(d) BAYISLT016* (Suspended --Red/Green) Steel Spring Isolators(c) BAYISLT019* (Floor -- Red)(e)(b) BAYISLT021* (Floor -- Black)(e)(b) BAYISLT032* (Floor -- Black/Yellow)(e)(b) BAYISLT028* (Suspended -- Tan) BAYISLT029* (Suspended -- Red) BAYISLT030* (Suspended -- Black) BAYISLT031* (Suspended -- Black/Yellow)

Used With
TWE051 TWE072, TWE076
TWE101 TWE126, TWE156 TWE201, TWE251
TWE051 TWE072, TWE076
TWE101 TWE126, TWE156 TWE201, TWE251
TWE051, TWE060, TWE072, TWE076, TWE090, TWE101, TWE120 TWE126, TWE150, TWE156, TWE180, TWE201, TWE240, TWE251,
TWE300
TWE051 TWE072, TWE076
TWE101 TWE126, TWE156 TWE201, TWE251
TWE051*DA TWE072*DB, TWE076*DA/B TWE072*DB, TWE076*DA/B
TWE101*DA/B TWE126*DB TWE126*DB
TWE156*DB
TWE201*DB
TWE051, TWE072, TWE076, TWE101 TWE126, TWE156 TWE201, TWE251 TWE126, TWE156 TWE051 TWE072, TWE076 TWE101 TWE201, TWE251
TWE051, TWE072, TWE076, TWE101 TWE126, TWE156 TWE201, TWE251 TWE051
TWE072, TWE076, TWE101 TWE126, TWE156 TWE201, TWE251

SS-PRC029Y-EN

13

Accessories

Table 4. TWE Accessories (continued)

Model Low Static Drive Kit(a)

Used With

BAYLSMT001*

TWE201

Plenum(f)

BAYPLNM015* (Discharge Plenum & Grille)(f)

TWE051

BAYPLNM016* (Discharge Plenum & Grille)(f)

TWE072, TWE076

BAYPLNM017* (Discharge Plenum & Grille)(f)

TWE101

BAYPLNM018* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f)

TWE126, TWE156

BAYPLNM019* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f)

TWE201, TWE251

BAYPLNM020* (Hydronic Coil Discharge Plenum & Grille)(f)

TWE051

BAYPLNM021* (Hydronic Coil Discharge Plenum & Grille)(f)

TWE072, TWE076

BAYPLNM022* (Hydronic Coil Discharge Plenum & Grille)(f)

TWE101

BAYPLNM030* (Electric Heat Discharge Plenum & Grille)(f)

TWE051

BAYPLNM031* (Electric Heat Discharge Plenum & Grille)(f)

TWE072, TWE076

BAYPLNM032* (Electric Heat Discharge Plenum & Grille)(f)

TWE101

BAYPLNM033* (Electric Heat Discharge Plenum & Grille)(f)

TWE126, TWE156

BAYPLNM034* (Electric Heat Discharge Plenum & Grille)(f)

TWE201, TWE251

Return Air Grille

BAYGRLE001*

TWE051

BAYGRLE002*

TWE072, TWE076

BAYGRLE003* BAYGRLE004*

TWE101 TWE126, TWE156

BAYGRLE005*

TWE201, TWE251

SymbioTM Options Module Kit

BAYMODU001*

All TWE units with Digit 15 = 1 and Electric heater installed

Transformer

BAYTFMR017* - 100 VA Transformer (400 V)

All TWE072 ­ TWE251 380-415V Hz unit

Water Kits

BAYWATR022* (Steam Coil Enclosure)(f)

TWE051

BAYWATR023* (Steam Coil Enclosure)(f)

TWE072, TWE076

BAYWATR024* (Steam Coil Enclosure)(f)

TWE101

BAYWATR025* (Steam Coil Enclosure)(f)

TWE126, TWE156

BAYWATR026* (Steam Coil Enclosure)(f)

TWE201, TWE251

BAYWATR027* (Hot Water Coil Enclosure)(f)

TWE051

BAYWATR028* (Hot Water Coil Enclosure)(f)

TWE072, TWE076

BAYWATR029* (Hot Water Coil Enclosure)(f)

TWE101

BAYWATR030* (Hot Water Coil Enclosure)(f)

TWE126, TWE156

BAYWATR031* (Hot Water Coil Enclosure)(f)

TWE201, TWE251

Wire Kit -- 180° Blower Discharge Reversal Kit(g)

BAYWRKT002*

TWE051, TWE072, TWE076, TWE101

(a) Used on constant volume air handlers only. (b) Requires use of subbase accessory. (c) In units with steam or hot water coils applied vertically or horizontally, check IOM for proper Isolator Kit selection. (d) Do not use if blower will operate less than 600 RPM. (e) When the air handler is in the vertical position and close proximity trapping of condensate is required, use of subbase is required. (f) When installed horizontally, plenum/water coil must be self-supported. When adding vibration isolators, see Isolator Installation Guide (ACC-SVN92*-EN)
for isolator and location matrix. (g) Cannot be used on TWE126­201, due to motor mount location.

14

SS-PRC029Y-EN

Electric Heaters
Table 5. Electric heaters
Model 4.6­8.33 Ton Electric Heater Selection BAYHTRN405* -- 3.13/3.74 kW Heater 380/415 / 3 Phase BAYHTRR410* -- 6.25/7.46 kW Heater 380/415 / 3 Phase BAYHTRR415* -- 9.37/11.17 kW Heater 380/415 / 3 Phase BAYHTRN425* -- 15.63/18.64 kW Heater 380/415 / 3 Phase BAYHTRN435* -- 21.86/26.08 kW Heater 380/415 / 3 Phase 10.4­20.9 Ton Electric Heater Selection BAYHTRP410* -- 6.25/7.46 kW Heater 380/415 / 3 Phase BAYHTRP420* -- 12.50/14.92 kW Heater 380/415 / 3 Phase BAYHTRP430* -- 18.76/22.38 kW Heater 380/415 / 3 Phase BAYHTRP450* -- 31.26/37.29 kW Heater 380/415 / 3 Phase

Accessories
Used With
TWE051, TWE072*D, TWE076, TWE101 TWE051, TWE072*D, TWE076, TWE101 TWE051, TWE072*D, TWE076, TWE101 TWE051, TWE072*D, TWE076, TWE101
TWE101
TWE126, TWE156, TWE201, TWE251 TWE126, TWE156, TWE201, TWE251 TWE126, TWE156, TWE201, TWE251 TWE126, TWE156, TWE201, TWE251

SS-PRC029Y-EN

15

Application Considerations
Application of this product should be within the cataloged airflow and performance considerations.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local representative.
180° Blower Rotation
The 4.6, 6.25, and 8.33 ton standard air handler blower section can be rotated 180° to change the discharge pattern. This modification must be done in the field and requires an additional kit. See unit installation guide.
Low Ambient Cooling
As manufactured, all Odyssey units have cooling capabilities down to 0°F. At temperatures below 50°F, some reduction in cooling capacity can be expected. When the optional Low Ambient Accessory kit is field installed, the full capacity of the unit is available down to 0°F. When using these units with control systems such as bypass changeover Variable Air Volume, make sure to consider the requirement for a head pressure control to allow low ambient cooling.
Figure 4. Typical split system application

Split Condensing
Unit

Air Handling Unit

16

SS-PRC029Y-EN

Application Considerations
Figure 5. Typical horizontal air handler application Isolator (4X) (Spring or Rubber)
Support Rods and Attaching Hardware (by others)

Electric Heater Assembly

Heating Coil & Enclosure Assembly (Steam or Hot Water)

Air Handler

Figure 6. Typical vertical air handler application
Discharge Plenum & Grille Assembly
Heating Coil & Enclosure Assembly

Horizontal Drain
Vertical Drain

Air Handler
Return-Air Grille
Subbase Isolators (Spring or Rubber)

SS-PRC029Y-EN

17

Selection Procedure
Cooling Capacity
1. Calculate the building's total and sensible cooling loads at design conditions, using standardized calculation methods.
2. Size the equipment using the gross cooling capacity tables. Match the cooling loads at design conditions. For example, if the following specifies the building cooling requirements:
Electrical Characteristics: 415/50/3 Summer Design Conditions: Entering Evap Coil--80°F DB/67°F WB (27°C DB/19°C WB), Outdoor Ambient--95°F (35°C) Total Cooling Load: 75 MBh (22 kW) Sensible Cooling Load: 53 MBh (15.5 kW) Airflow: 2500 cfm (4248 m3/h) External Static Pressure: 0.77 inches of water gauge (192 Pa)
3. Use Table 15, p. 31 to determine that TTA0764DA with TWE0764DA has a gross cooling capacity of 82.0 MBh (24.0 kW) and 63.2 MBh (18.5 kW) sensible capacity at 95°F DB (35°C) ambient and 2500 cfm (4248 m3/h) with 80°F DB/67° F WB (27°C DB/19°C WB) air entering the evaporator.
4. To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure:
External Static Duct System: 0.84 in. (210 Pa) Standard Filter: 0.10 in. (25 Pa) Supplementary Electric Heat: 0.16 in. (57 Pa) Total Static Pressure: 1.10 in. (274 Pa)
Notes:
· The Evaporator Fan Performance Table has included the effect of a 1 in. (249 Pa) filter already. Therefore, the actual Total Static Pressure is 1.10 - 0.10 = 1.00 in. (274 - 25 = 249 Pa) . With 2500 cfm (4248 m3/h) and 1.00 inches (249 Pa), Table 87, p. 85 shows 1.51 Bhp (ultra high static drive kit required).
· This formula can be used to calculate Fan Motor Heat:
3.15 X Bhp = MBh 3.15 X 1.51 = 4.75 MBh Net Total Cooling Capacity = 82.0 MBh - 4.75 MBh = 77.25 MBh (22.6 kW) Net Sensible Cooling Capacity = 63.2 MBh - 4.75 MBh = 58.45 MBh (17.1 kW)
Heating Capacity
1. Calculate the building heating load using the Trane calculation form or any other standard accepted method.
2. Size the equipment using Table 104, p. 101 to match the heating loads at design conditions. For example, if the following specifies the building heating requirements:
Total Heating Load: 97.0 MBh (28.4 kW) Airflow: 2500 cfm (4248 m3/h) Supplementary Electric Heaters
3. Use Table 105, p. 101 to determine that the 34.88 kW heater has a capacity of 119,045 Btuh.
4. From Table 109, p. 105, the 34.88 kW heater at 460V indicates the heater model is BAYHTRN435A.

18

SS-PRC029Y-EN

Selection Procedure

Air Delivery

1. The external static pressure drop through the air distribution system is 0.84 inches of water gauge, use Table 104, p. 101 to determine that the static pressure drop through the electric heater is 0.16 inches of water (0.84 + 0.16 = 1.00 in.).
2. Enter Table 87, p. 85 for TWE0764DA at 2500 cfm (4248 m3/h) and 1.00 (249 Pa) static pressure. The high static motor at 987 RPM gives the desired airflow.

SS-PRC029Y-EN

19

Model Number Description
Cooling Condenser

Digit 1, 2, 3-- Unit Function
TTA = Split System Cooling
Digit 4, 5, 6 -- Tonnage
060 = 5 Tons (50Hz) 076 = 6.25 Tons (50Hz) 101 = 8.33 Tons (50Hz) 126 = 10.4 Tons (50Hz) 156 = 13.0 Tons (50Hz) 201 = 16.7 Tons (50Hz) 251 = 20.9 Tons (50Hz)
Digit 7 -- Refrigerant
4 = R-410A

Digit 8 -- Voltage D = 380­415 Vac- 3 PH (50Hz)

Digit 15 -- Controls S = SymbioTM

Digit 9 -- Refrigeration Circuit/Stage Digit 16 -- None

A = 1 Compressor/1 Line/1 Stage (Single) C = 2 Compressors/1 Line/2 Stage (Manifold) D = 2 Compressors/2 Line/2 Stage (Dual) Digit 10 -- Major Design Sequence
A = Rev A
Digit 11 -- Minor Design Sequence

0 = None
Digit 17 -- Coil Protection
0 = Standard Coil 1 = Standard Coil w/ Hail Guard 4 = Complete Coat Condenser Coil (MCHE) 5 = Complete Coat Condenser Coil with Hail Guard (MCHE)

A = Rev A

Digit 18, 19, 20 -- None

Digit 12, 13 -- Service Digits

0 = None

**

Digit 21 -- Communications Options

Digit 14 -- Efficiency Generation A = Generation A

0 = No Option 1 = Advanced Diagnostics and BACnet® BAS 2 = Advanced Diagnostics and LonTalk® Communications Interface (LCI)
Digit 22 to 40 -- None

0 = None

20

SS-PRC029Y-EN

Air Handler
Digit 1, 2, 3 -- Unit Function
TWE = Air Handler
Digit 4, 5, 6-- Tonnage
051 = 4.6 Tons (50Hz) 072 = 6 Tons (50Hz) 076 = 6.25 Tons (50Hz) 101 = 8.33 Tons (50Hz) 126 = 10.4 Tons (50Hz) 156 = 13.0 Tons (50Hz) 201 = 16.7 Tons (50Hz) 251 = 20.9 Tons (50Hz)
Digit 7 -- Refrigerant
4 = R-410A

Model Number Description

Digit 8 -- Voltage D = 380­415 Vac - 3 PH (50 Hz)

Digit 14 -- Efficiency Generation A = Generation A (2018 DOE)

Digit 9 -- Refrigeration Circuit/Stage A = Single Circuit B = Dual Circuit Digit 10 -- Major Design Sequence A = Rev A
Digit 11 -- Minor Design Sequence A = Rev A
Digit 12, 13 -- Service Digits **

Digit 15 -- Controls
1 = Constant Volume C = 2 Stage Airflow (Electromechanical Cond Only) D = 2 Stage Airflow/Single Zone VAV (Symbio Cond Only)
Digit 16 -- Indoor Fan Sizes
0 = Standard Motor 4 = High Static ­ (Oversized Motor for VFD Units)
Digit 17 to 40 -- None
0 = None

SS-PRC029Y-EN

21

General Data

Table 6. General data for 5 - 6.25 ton (TTA0604DA*-TTA0764DD*) condensing units, 50 Hz

Cooling Performance - Gross Cooling Capacity, Btu (kW) Matched Air Handler AHRI Rated Airflow CFM (m³/hr)
Gross Cooling Capacity - System

5 Tons

5 Tons

6.25 Tons

6.25 Tons

Single Compressor Dual Compressor Single Compressor Dual Compressor

TTA0604DA*

TTA0604DD*

TTA0764DA*

TTA0764DD*

TWE0764DA* 2,000 (3,398) 66,000 (19.3)

TWE0724DB* 2,000 (3,398) 62,000 (18.2)

TWE0764DA* 2,500 (4,248) 82,000 (24.0)

TWE0764DB* 2,500 (4,248) 78,000 (22.6)

Condensing Unit Only

58,000 (17.0)

53,500 (15.7)

74,000 (21.7)

72,000 (21.1)

AHRI Net Cooling Capacity

65,000 (19.0)

62,000 (18.2)

80,000 (23.4)

77,000 (22.6)

Efficiency

Matched Air Handler (EER)

11.8

11.8

11.8

12.2

Condensing Unit Only (EER) System Power/Condensing Unit Power (kW) Compressor

13.8 4.6 / 4.2

11.9 4.8 / 4.5

12.6 6.3 / 5.8

13.0 6.0 / 5.6

Type

Scroll

Scroll

Scroll

Scroll

No.

1

2

1

2

System Data

No. Refrigerant Circuits(a) Suction Line Connection (mm) OD(a)

1 1 1/8 (28.58)

2 7/8 (22.23)

1 1 3/8 (34.90)

2 1 1/8 (28.58)

Liquid Line Connection (mm) OD(a)

1/2 (12.70)

1/2 (12.70)

1/2 (12.70)

1/2 (12.70)

Outdoor Coil

Type Tube Size OD/Coil Width MCHE (in.) Face Area, sq ft (m2)

MCHE 0.81 (20.6) 18.5 (1.7)

MCHE 0.81 (20.6) 17.4 (1.6)

MCHE 0.81 (20.6) 18.5 (1.7)

MCHE 0.81 (20.6) 17.4 (1.6)

Rows/FPI (Fins per inch)

1/23

1/23

1/23

1/23

Outdoor Fan Type

Propeller

Propeller

Propeller

Propeller

No. Used Diameter - in. (mm)

1 26 (660.4)

1 26 (660.4)

1 26 (660.4)

1 26 (660.4)

Drive Type No. Speeds CFM (m3/h)

Direct 1
4,200 (7,136)

Direct 1
4,200 (7,136)

Direct 1
4,200 (7,136)

Direct 1
4,200 (7,136)

No. Motor

1

1

1

1

Motor HP (kW)

0.33 (0.25)

0.33 (0.25)

0.33 (0.25)

0.33 (0.25)

Motor RPM Refrigerant Charge (Field Supplied) lbs (kg) of R-410A

950 10 (4.5)

950 7.0 / 7.0 (3.2 / 3.2)

950 11.3 (5.1)

950 7.3 / 7.3 (3.3 / 3.3)

Shipping Dimensions

HxWxD - in. (mm)

45" x 45" x 38"

45" x 45" x 38"

45" x 45" x 38"

(1143 x 1143 x 965) (1143 x 1143 x 965) (1143 x 1143 x 965)

Notes:

1. 5 - 10.4 and 20.9 ton condensing units are tested in accordance with AHRI Standard 365.

45" x 45" x 38" (1143 x 1143 x 965)

2. 13 - 16.7 ton condensing units are AHRI Certified to AHRI Standard 365.

3. 5 ton single and 6.25 - 16.7 ton units are AHRI Certified to AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor

air temperature, 80°F entering dry bulb, 67°F entering wet bulb with 25ft of interconnecting refrigerant piping with minimum

external static pressure as determined by rating standard.

4. 5 ton dual and 20.9 ton units are tested in accordance with AHRI Standard 340-360.

(a) Refer to refrigerant piping applications manual for line sizing and line length.

22

SS-PRC029Y-EN

General Data

Table 7. General data for 8.33 - 10.4 ton (TTA1014DA*-TTA1264DD*) condensing units, 50 Hz

Cooling Performance - Gross Cooling Capacity, Btu (kW)
Matched Air Handler

8.33 Tons

8.33 Tons

Single Compressor Dual Compressor

TTA1014DA*

TTA1014DD*

TWE1014DA*

TWE1014DB*

8.33 Tons Manifolded Compressor TTA1014DC*
TWE1014DA*

10.4 Tons Dual Compressor
TTA1264DD*
TWE1264DB*

AHRI Rated Airflow CFM (m³/hr)

3,333 (5,663)

3,333 (5,663)

3,333 (5,663)

4,166 (7,079)

Gross Cooling Capacity - System

105,000 (30.8)

103,000 (30.2)

103,000 (30.2)

132,000 (38.7)

Condensing Unit Only

96,000 (28.1)

92,000 (27.0)

94,000 (27.5)

126,000 (36.9)

AHRI Net Cooling Capacity

104,000 (30.5)

101,000 (29.6)

102,000 (29.9)

130,000 (38.1)

Efficiency

Matched Air Handler (EER)

12.2

12.2

12.2

11.4

Condensing Unit Only (EER) System Power/Condensing Unit Power (kW) Compressor

13.0 8.2 / 7.4

12.9 7.8 / 7.2

12.8 7.9 / 7.3

11.2 11.5 / 11.3

Type

Scroll

Scroll

Manifolded Scrolls

Scroll

No. System Data

1

2

2

2

No. Refrigerant Circuits(a) Suction Line Connection (mm) OD(a)

1 1 3/8 (34.90)

2 1 1/8 (28.58)

1 1 3/8 (34.90)

2 1 1/8 (28.58)

Liquid Line Connection (mm) OD(a)

1/2 (12.70)

1/2 (12.70)

1/2 (12.70)

1/2 (12.70)

Outdoor Coil

Type

MCHE

MCHE

MCHE

MCHE

Tube Size OD/Coil Width MCHE (in.) Face Area, sq ft (m2)

0.81 (20.6) 23.8 (2.2)

0.81 (20.6) 22.7 (2.1)

0.81 (20.6) 23.8 (2.2)

1.0 (25.4) 27.0 (2.5)

Rows/FPI (Fins per inch)

1/23

1/23

1/23

1/23

Outdoor Fan Type

Propeller

Propeller

Propeller

Propeller

No. Used

1

1

1

1

Diameter - in. (mm)

28 (711.2)

28 (711.2)

28 (711.2)

28 (711.2)

Drive Type

Direct

Direct

Direct

Direct

No. Speeds CFM (m3/h)

1 6,340 (10,772)

1 6,340 (10,772)

1 6,340 (10,772)

1 6,340 (10,772)

No. Motor

1

1

1

1

Motor HP (kW)

0.75 (0.56)

0.75 (0.56)

0.75 (0.56)

0.75 (0.56)

Motor RPM Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A

925 13.6 (6.2)

925 7.6 / 7.6 (3.4 / 3.4)

925 13.1 (6.0)

925 10.1 / 9.8 (4.6 / 4.4 )

Shipping Dimensions

HxWxD - in. (mm)

45" x 55" x 42"

45" x 55" x 42"

45" x 55" x 42"

(1143 x 1397 x 1067) (1143 x 1397 x 1067) (1143 x 1397 x 1067)

Notes:

1. 5 - 10.4 and 20.9 ton condensing units are tested in accordance with AHRI Standard 365.

52.1" x 55" x 42" (1323 x 1397 x 1067)

2. 13 - 16.7 ton condensing units are AHRI Certified to AHRI Standard 365.

3. 5 ton single and 6.25 - 16.7 ton units are AHRI Certified to AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor

air temperature, 80°F entering dry bulb, 67°F entering wet bulb with 25ft of interconnecting refrigerant piping with minimum

external static pressure as determined by rating standard.

4. 5 ton dual and 20.9 ton units are tested in accordance with AHRI Standard 340-360.

(a) Refer to refrigerant piping applications manual for line sizing and line length.

SS-PRC029Y-EN

23

General Data

Table 8. General data for 13 - 20.9 ton (TTA1564DD*-TTA2514DC*) condensing units, 50 Hz

Cooling Performance - Gross Cooling Capacity, Btu (kW)
Matched Air Handler

13 Tons
Dual Compressor TTA1564DD*

13 Tons Manifolded Compressor TTA1564DC*

16.7 Tons
Dual Compressor TTA2014DD*

16.7 Tons Manifolded Compressor TTA2014DC*

TWE1564DB*

TWE1564DB*

TWE2014DB*

TWE2014DB*

20.9 Tons Manifolded Compressor TTA2514DC*
TWE2514DB*

AHRI Rated Airflow CFM (m³/hr)

5,000 (8,495)

5,000 (8,495)

6,667 (11,326)

6,666 (11,326)

8,333 (14,158)

Gross Cooling Capacity - System

164,000 (48.1)

162,000 (47.5)

206,000 (60.4)

218,000 (63.9)

260,000 (76.2)

Condensing Unit Only

152,000 (44.5)

150,000 (44.0)

216,000 (63.3)

224,000 (65.6)

260,000 (76.2)

AHRI Net Cooling Capacity

160,000 (46.9)

158,000 (46.3)

204,000 (59.8)

216,000 (63.3)

254,000 (74.4)

Efficiency

Matched Air Handler (EER)

12.3

12.0

11.4

11.2

10.7

Condensing Unit Only (EER) System Power/Condensing Unit Power (kW) Compressor

13.2 12.4 / 11.3

13.1 12.2 / 11.3

13.0 17.1 / 16.5

12.7 18.9 / 17.7

12.0 23.9 / 21.7

Type

Scroll

Manifolded Scrolls

Scroll

Manifolded Scrolls Manifolded Scrolls

No. System Data

2

2

2

2

2

No. Refrigerant Circuits(a) Suction Line Connection (mm) OD(a)

2 1 3/8 (34.90)

1 1 5/8 (41.28)

2 1 3/8 (34.90)

1 1 5/8 (41.28)

1 2 1/8 (53.98)

Liquid Line Connection (mm) OD(a)

1/2 (12.70)

5/8 (15.88)

1/2 (12.70)

5/8 (15.88)

5/8 (15.88)

Outdoor Coil

Type

MCHE

MCHE

MCHE

MCHE

MCHE

Tube Size OD/Coil Width MCHE (in.) Face Area, sq ft (m2)

0.81 (20.6) 44.3 (4.1)

0.81 (20.6) 44.3 (4.1)

0.81 (20.6) 44.3 (4.1)

0.81 (20.6) 44.3 (4.1)

1.0 (25.4) 51.3 (4.8)

Rows/FPI (Fins per inch)

1/23

1/23

1/23

1/23

1/23

Outdoor Fan Type

Propeller

Propeller

Propeller

Propeller

Propeller

No. Used

2

2

2

2

2

Diameter - in. (mm)

28 (711.2)

28 (711.2)

28 (711.2)

28 (711.2)

28 (711.2)

Drive Type

Direct

Direct

Direct

Direct

Direct

No. Speeds CFM (m3/h)

1 12,600 (21,408)

1 8,595 (14,603)

1 12,600 (21,408)

1 12,600 (21,408)

1 12,600 (21,408)

No. Motor

2

2

2

2

2

Motor HP (kW)

0.75 (0.56)

0.33 (0.25)

0.75 (0.56)

0.75 (0.56)

0.75 (0.56)

Motor RPM

925

925

925

925

925

Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A

11.2 / 11.3 (5.1 / 5.1)

22 (10)

11.6 / 12.3 (5.3 / 5.6)

23.8 (10.8)

29.8 (13.5)

Shipping Dimensions

51.1" x 96" x 48" 51.1" x 96" x 48" 51.1" x 96" x 48" 51.1" x 96" x 48" 57.1" x 96" x 48"

HxWxD - in. (mm)

(1298 x 2438 x

(1298 x 2438 x

(1298 x 2438 x

(1298 x 2438 x

(1450 x 2438 x

1219)

1219)

1219)

1219)

1219)

Notes:

1. 5 - 10.4 and 20.9 ton condensing units are tested in accordance with AHRI Standard 365.

2. 13 - 16.7 ton condensing units are AHRI Certified to AHRI Standard 365.

3. 5 ton single and 6.25 - 16.7 ton units are AHRI Certified to AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor air temperature,

80°F entering dry bulb, 67°F entering wet bulb with 25ft of interconnecting refrigerant piping with minimum external static pressure as determined by

rating standard.

4. 5 ton dual and 20.9 ton units are tested in accordance with AHRI Standard 340-360.

(a) Refer to refrigerant piping applications manual for line sizing and line length.

24

SS-PRC029Y-EN

General Data

Table 9. General data for 4.6 - 6.25 ton (TWE0514DA* - TWE0764DB*) air handler, 50 Hz

System Data

4.6 Tons Single Circuit TWE0514DA*

No. Refrigerant Circuits Suction Line Connection, in. (mm) OD

1 1 1/8 (28.58)

Liquid Line Connection, in. (mm) OD

1/2 (12.70)

Indoor Coil Type

Lanced/Intertwined

Tube Size, in. (mm) Face Area, sq. ft. (m2)

3/8 (9.50) 5.0 (0.46)

Rows/FPI

4/14

Refrigerant Control

Expansion Valve

Drain Connection Size, in. (mm)

1.0 (25.40) PVC

Indoor Fan Type
No. Used/Diameter x Width, in. (mm)
Drive Type/No. Speeds CFM (m3/h) (Nominal)

Centrifugal 1/12 x 12 (304.8 x 304.8) Belt/Adjustable
2,000 (3,398)

No. Motors Motor HP - Standard/Oversized (kw) Motor RPM

1 0.75/1.0 (0.56/0.75)
1450

Motor Frame Size

56

Filters

Type/Furnished (No.)/Size Recommended MERV 13 (No.)/Size Recommended Shipping Dimensions
HxWxD - in. (mm)

Throwaway/Yes (1) 16 x 20 x 1; (1) 20 x 20 x 1 (1) 16 x 20 x 2 (1) 20 x 20 x 2
55.1" x 27.5" x 43.5" (1399.5 x 698.5 x 1104.9)

6 Tons Dual Circuit TWE0724DB*
2 1 1/8 (25.60) 1/2 (12.70)
Lanced/Intertwined 3/8 (9.50) 8.1 (0.75) 4/14
Expansion Valve 1.0 (25.40) PVC
Centrifugal 1/15 x 15 (381.0 x 381.0) Belt/Adjustable 2,000 (3,398)
1 1.5/2.0/3.0 (1.10/1.50/2.2)
1450 56H
Throwaway/Yes (3) 16 X 25 X 1
(3) 16 x 25 x 2
61.2" x 30.5" x 53" (1554.5 x 774.7 x
1346.2)

6.25 Tons Single Circuit TWE0764DA*
1 1 3/8 (34.90) 1/2 (12.70)
Lanced/Intertwined 3/8 (9.50) 8.1 (0.75) 4/14
Expansion Valve 1.0 (25.40) PVC
Centrifugal 1/15 x 15 (381.0 x 381.0) Belt/Adjustable 2,500 (4,248)
1 1.5/2.0/3.0 (1.10/1.50/2.2)
1450 56H
Throwaway/Yes (3) 16 X 25 X 1
(3) 16 x 25 x 2
61.2" x 30.5" x 53" (1554.5 x 774.7 x
1346.2)

6.25 Tons Dual Circuit TWE0764DB*
2 1 1/8 (25.60) 1/2 (12.70)
Lanced/Intertwined 3/8 (9.50) 8.1 (0.75) 4/14
Expansion Valve 1.0 (25.40) PVC
Centrifugal 1/15 x 15 (381.0 x 381.0) Belt/Adjustable 2,500 (4,248)
1 1.5/2.0/3.0 (1.10/1.50/2.2)
1450 56H
Throwaway/Yes (3) 16 X 25 X 1
(3) 16 x 25 x 2
61.2" x 30.5" x 53" (1554.5 x 774.7 x
1346.2)

SS-PRC029Y-EN

25

SS-PRC029Y-EN

26

Table 10. General data for 8.33 - 20.9 ton (TWE1014DA* - TWE2514DB*) air handler, 50 Hz

System Data No. Refrigerant Circuits Suction Line Connection, in. (mm) OD Liquid Line Connection, in. (mm) OD

8.33 Tons Single Circuit TWE1014DA*
1 1 3/8 (34.90) 1/2 (12.70)

Indoor Coil Type Tube Size, in. (mm) Face Area, sq. ft. (m2) Rows/FPI Refrigerant Control Drain Connection Size, in. (mm) Indoor Fan Type
No. Used/Diameter x Width, in. (mm)
Drive Type/No. Speeds CFM (m3/h) (Nominal) No. Motors Motor HP - Standard/Oversized (kw)
Motor RPM Motor Frame Size Filters Type/Furnished

Lanced/Intertwined 3/8 (9.50) 11.2 (1.04) 4/14
Expansion Valve 1.0 (25.40) PVC
Centrifugal 1/15 x 15 (381.0 x 381.0) Belt/Adjustable 3,350 (5,692)
1 2.0 (1.50) 1500 56HZ
Throwaway/Yes

(No.)/Size Recommended

(4) 16 X 25 X 1

MERV 13 (No.)/Size Recommended Shipping Dimensions HxWxD - in. (mm)

(4) 16 x 25 x 2
61.2" x 30.5" x 69" (1554.5 x 774.7 x
1752.6)

8.33 Tons Dual Circuit TWE1014DB*
2 1 1/8 (25.60) 1/2 (12.70)

10.4 Tons Dual Circuit TWE1264DB*
2 1 3/8 (34.90) 1/2 (12.70)

13 Tons Dual Circuit TWE1564DB*
2 1 3/8 (34.90) 1/2 (12.70)

16.7 Tons Dual Circuit TWE2014DB*
2 1 3/8 (34.90) 5/8 (15.88)

Lanced/Intertwined 3/8 (9.50) 11.2 (1.04) 4/14
Expansion Valve 1.0 (25.40) PVC

Lanced/Intertwined 3/8 (9.50) 16.3 (1.51) 4/14
Expansion Valve 1.0 (25.40) PVC

Lanced/Intertwined 3/8 (9.50) 16.3 (1.51) 4/14
Expansion Valve 1.0 (25.40) PVC

Lanced/Intertwined 3/8 (9.50) 21.7 (2.01) 3/14
Expansion Valve 1.0 (25.40) PVC

Centrifugal 1/15 x 15 (381.0 x 381.0) Belt/Adjustable
3,350 (5,692)
1 2.0/3.0 (1.50/2.20)
1500
56HZ

Centrifugal 2/15 x 15 (381.0 x 381.0) Belt/Adjustable
4,200 (7,136)
1 2.0/3.0/5.0 (1.50/2.20/3.70)
1500
145T

Centrifugal 2/15 x 15 (381.0 x 381.0) Belt/Adjustable
5,000 (8,495)
1 3.0/5.0 (2.20/3.70) 1,450/1,500
56HZ

Centrifugal 2/15 x 15 (381.0 x 381.0) Belt/Adjustable
6,675 (11,341)
1 3.0/5.0/7.5 (2.20/
3.70/5.60) 1,500/2,930
184T

Throwaway/Yes (4) 16 X 25 X 1 (4) 16 x 25 x 2

Throwaway/Yes (8) 15 X 20 X 2 (8) 15 x 20 x 2

Throwaway/Yes (8) 15 X 20 X 2 (8) 15 x 20 x 2

Throwaway/Yes
(4) 16 X 25 X 2; (4) 16 X 20 X 2 (4) 16 x 25 x 2 (4) 16 x 20 x 2

61.2" x 30.5" x 69" (1554.5 x 774.7 x
1752.6)

76.3" x 33.8" x 85" 76.3" x 33.8" x 85" (1938 x 850.9 x 2159) (1938 x 850.9 x 2159)

79.1" x 35.8" x 95" (2009.1 x 909.3 x
2413)

20.9 Tons Dual Circuit TWE2514DB*
2 2 1/8 (53.98) 5/8 (15.88)
Lanced/Face Split 3/8 (9.50) 21.7 (2.01) 4/14
Expansion Valve 1.0 (25.40) PVC
Centrifugal 2/15 x 15 (381.0 x 381.0) Belt/Adjustable 8,350 (14,186)
1 5.0 (3.70) 2930 184T
Throwaway/Yes (4) 16 X 25 X 2; (4) 16 X 20 X 2 (4) 16 x 25 x 2 (4) 16 x 20 x 2
79.1" x 35.8" x 95" (2009.1 x 909.3 x
2413)

General Data

Performance Data

Gross Cooling Capacities

Table 11. Gross cooling capacities (MBH) TTA0604DA condensing unit with TWE0764DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

61.8 52.2 67.8 40.1 73.8 27.3

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

59.3 51.0 65.0 39.0 70.9 26.3

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

56.6 49.8 62.1 37.8 67.7 25.1

80 62.5 62.0 67.7 49.9 73.6 37.2 60.2 60.2 65.0 48.7 70.7 36.1 57.9 57.9 62.1 47.5 67.5 35.0 1800
85 65.5 65.5 67.9 59.5 73.4 47.0 63.3 63.3 65.2 58.3 70.5 45.9 60.9 60.9 62.3 57.1 67.4 44.8

90 68.6 68.6 68.8 68.8 73.4 56.7 66.3 66.3 66.4 66.4 70.5 55.5 63.8 63.8 64.0 64.0 67.3 54.4

75 63.0 55.3 68.7 42.0 74.7 27.8 60.4 54.1 65.9 40.8 71.7 26.7 57.7 52.9 62.9 39.7 68.4 25.6

80 64.4 64.4 68.8 52.7 74.4 38.7 62.2 62.2 66.0 51.5 71.4 37.6 59.7 59.7 63.0 50.2 68.2 36.5 2000
85 67.7 67.7 69.1 63.4 74.3 49.6 65.3 65.3 66.4 62.2 71.3 48.6 62.8 62.8 63.4 61.0 68.1 47.3

90 70.8 70.8 70.9 70.9 74.3 60.2 68.3 68.3 68.5 68.5 71.3 59.1 65.7 65.7 65.8 65.8 68.1 57.9

75 64.0 58.4 69.5 43.8 75.4 28.2 61.4 57.2 66.7 42.7 72.3 27.2 58.6 55.9 63.6 41.5 69.0 26.0

80 66.2 66.2 69.6 55.4 75.1 40.2 63.8 63.8 66.8 54.2 72.1 39.2 61.3 61.3 63.8 53.0 68.8 38.1 2200
85 69.5 69.5 70.2 67.2 75.0 52.3 67.0 67.0 67.4 66.1 71.9 51.2 64.4 64.4 64.5 64.5 68.7 49.8

90 72.6 72.6 72.7 72.7 75.1 63.8 70.0 70.0 70.1 70.1 72.0 62.6 67.3 67.3 67.4 67.4 68.8 61.5

75 64.9 61.5 70.2 45.6 76.0 28.6 62.3 60.2 67.3 44.4 72.9 27.6 59.5 58.9 64.2 43.3 69.6 26.5

80 67.7 67.7 70.4 58.2 75.7 41.7 65.3 65.3 67.5 57.0 72.6 40.7 62.7 62.7 64.4 55.7 69.3 39.6 2400
85 71.0 71.0 71.2 71.1 75.6 54.5 68.5 68.5 68.6 68.6 72.5 53.4 65.7 65.7 65.8 65.8 69.2 52.2

90 74.0 74.0 74.1 74.1 75.8 67.3 71.4 71.4 71.5 71.5 72.7 66.2 68.6 68.6 68.6 68.6 69.4 65.0

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

53.8 48.5 59.0 36.6 64.3 24.0

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

50.9 47.1 55.7 35.3 60.7 22.7

80 55.5 55.5 59.0 46.2 64.1 33.8 52.9 52.9 55.7 44.8 60.5 32.5 1800
85 58.4 58.4 59.3 55.8 64.0 43.6 55.6 55.6 56.1 54.4 60.3 42.2

90 61.2 61.2 61.3 61.3 64.0 53.1 58.2 58.2 58.3 58.3 60.4 51.7

75 54.8 51.5 59.8 38.4 65.0 24.4 51.9 50.1 56.4 37.1 61.3 23.1

80 57.2 57.2 59.9 48.9 64.8 35.3 54.4 54.4 56.5 47.5 61.1 34.1 2000
85 60.1 60.1 60.4 59.7 64.7 46.0 57.2 57.2 57.3 57.3 60.9 44.7

90 62.9 62.9 63.0 63.0 64.8 56.7 59.8 59.8 59.9 59.9 61.0 55.3

75 55.8 54.6 60.4 40.2 65.6 24.9 52.8 52.8 56.9 38.9 61.8 23.6

80 58.6 58.6 60.6 51.7 65.3 36.9 55.7 55.7 57.1 50.2 61.5 35.6 2200
85 61.6 61.6 61.7 61.7 65.2 48.5 58.5 58.5 58.6 58.6 61.4 47.1

90 64.3 64.3 64.4 64.4 65.4 60.2 61.1 61.1 61.1 61.1 61.6 58.8

75 56.7 56.7 60.9 42.0 66.0 25.3 53.9 53.9 57.4 40.2 62.2 24.0

80 59.9 59.9 61.2 54.4 65.8 38.4 56.8 56.8 57.7 52.9 61.9 37.1 2400
85 62.8 62.8 62.9 62.9 65.7 50.9 59.6 59.6 59.7 59.7 61.9 49.5

Notes: 1.
2.

90 65.5 65.5 65.6 65.6 66.0 63.7 62.1 62.1 62.1 62.1 62.2 62.2
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

27

Performance Data

Table 12. Gross cooling capacities (kW) TTA0604DA condensing unit with TWE0764DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 18.1 15.3 19.9 11.8 21.6 8.0

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

17.4 15.0 19.0 11.4 20.8 7.7

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

16.6 14.6 18.2 11.1 19.8 7.4

3058

27 18.3 18.2 19.8 14.6 21.6 10.9 17.6 17.6 19.0 14.3 20.7 10.6 17.0 17.0 18.2 13.9 19.8 10.2 30 19.2 19.2 19.9 17.4 21.5 13.8 18.5 18.5 19.1 17.1 20.7 13.5 17.9 17.9 18.3 16.7 19.7 13.1

33 20.1 20.1 20.1 20.1 21.5 16.6 19.4 19.4 19.5 19.5 20.7 16.3 18.7 18.7 18.7 18.7 19.7 15.9

24 18.4 16.2 20.1 12.3 21.9 8.1 17.7 15.9 19.3 12.0 21.0 7.8 16.9 15.5 18.4 11.6 20.1 7.5

3398

27 18.9 18.9 20.2 15.4 21.8 11.3 18.2 18.2 19.3 15.1 20.9 11.0 17.5 17.5 18.5 14.7 20.0 10.7 30 19.8 19.8 20.3 18.6 21.8 14.5 19.1 19.1 19.4 18.2 20.9 14.2 18.4 18.4 18.6 17.9 20.0 13.9

33 20.7 20.7 20.8 20.8 21.8 17.6 20.0 20.0 20.1 20.1 20.9 17.3 19.3 19.3 19.3 19.3 20.0 17.0

24 18.7 17.1 20.4 12.8 22.1 8.3 18.0 16.8 19.5 12.5 21.2 8.0 17.2 16.4 18.6 12.1 20.2 7.6

3738

27 19.4 19.4 20.4 16.2 22.0 11.8 18.7 18.7 19.6 15.9 21.1 11.5 18.0 18.0 18.7 15.5 20.2 11.1 30 20.4 20.4 20.6 19.7 22.0 15.3 19.6 19.6 19.7 19.4 21.1 15.0 18.9 18.9 18.9 18.9 20.1 14.6

33 21.3 21.3 21.3 21.3 22.0 18.7 20.5 20.5 20.5 20.5 21.1 18.4 19.7 19.7 19.7 19.7 20.2 18.0

24 19.0 18.0 20.6 13.4 22.3 8.4 18.2 17.6 19.7 13.0 21.4 8.1 17.4 17.3 18.8 12.7 20.4 7.8

4078

27 19.8 19.8 20.6 17.0 22.2 12.2 19.1 19.1 19.8 16.7 21.3 11.9 18.4 18.4 18.9 16.3 20.3 11.6 30 20.8 20.8 20.9 20.8 22.1 16.0 20.1 20.1 20.1 20.1 21.2 15.6 19.3 19.3 19.3 19.3 20.3 15.3

33 21.7 21.7 21.7 21.7 22.2 19.7 20.9 20.9 20.9 20.9 21.3 19.4 20.1 20.1 20.1 20.1 20.3 19.0

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 15.8 14.2 17.3 10.7 18.9 7.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

14.9 13.8 16.3 10.3 17.8 6.6

3058

27 16.3 16.3 17.3 13.5 18.8 9.9 15.5 15.5 16.3 13.1 17.7 9.5 30 17.1 17.1 17.4 16.3 18.8 12.8 16.3 16.3 16.4 15.9 17.7 12.4

33 17.9 17.9 18.0 18.0 18.8 15.6 17.1 17.1 17.1 17.1 17.7 15.2

24 16.1 15.1 17.5 11.3 19.0 7.2 15.2 14.7 16.5 10.9 18.0 6.8

3398

27 16.8 16.8 17.5 14.3 19.0 10.4 15.9 15.9 16.5 13.9 17.9 10.0 30 17.6 17.6 17.7 17.5 19.0 13.5 16.8 16.8 16.8 16.8 17.9 13.1

33 18.4 18.4 18.5 18.5 19.0 16.6 17.5 17.5 17.5 17.5 17.9 16.2

24 16.3 16.0 17.7 11.8 19.2 7.3 15.5 15.5 16.7 11.4 18.1 6.9

3738

27 17.2 17.2 17.7 15.1 19.1 10.8 16.3 16.3 16.7 14.7 18.0 10.4 30 18.0 18.0 18.1 18.1 19.1 14.2 17.1 17.1 17.2 17.2 18.0 13.8

33 18.8 18.8 18.9 18.9 19.2 17.6 17.9 17.9 17.9 17.9 18.1 17.2

24 16.6 16.6 17.8 12.3 19.3 7.4 15.8 15.8 16.8 11.8 18.2 7.0

4078

27 17.5 17.5 17.9 15.9 19.3 11.3 16.7 16.7 16.9 15.5 18.1 10.9 30 18.4 18.4 18.4 18.4 19.3 14.9 17.5 17.5 17.5 17.5 18.1 14.5

Notes: 1.
2.

33 19.2 19.2 19.2 19.2 19.3 18.7 18.2 18.2 18.2 18.2 18.2 18.2
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity,

28

SS-PRC029Y-EN

Performance Data

Table 13. Gross cooling capacities (MBH) TTA0604DD condensing unit with TWE0724DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

CFM

Ent DB (°F)
75

61 MBH SHC 57.4 49.8

67 MBH SHC 64.2 38.4

73 MBH SHC 71.7 26.5

61 MBH SHC 54.6 48.5

67 MBH SHC 61.0 37.1

73 MBH SHC 68.2 25.3

61 MBH SHC 51.7 47.2

67 MBH SHC 57.8 35.8

73 MBH SHC 64.6 24.0

80 58.5 58.5 64.1 48.0 71.6 36.2 56.1 56.1 60.9 46.6 68.1 34.9 53.7 53.7 57.7 45.4 64.3 33.6 1800
85 61.9 61.9 64.3 57.4 71.4 45.8 59.5 59.5 61.2 56.1 67.9 44.5 56.9 56.9 58.0 54.8 64.2 43.2

90 65.4 65.4 65.6 65.6 71.4 55.3 62.9 62.9 63.0 63.0 67.9 54.0 60.2 60.2 60.4 60.4 64.2 52.7

75 58.6 52.9 65.3 40.2 72.8 27.1 55.7 51.5 62.0 38.9 69.2 25.8 52.8 50.2 58.7 37.6 65.6 24.6

80 60.5 60.5 65.3 50.9 72.4 37.7 58.1 58.1 62.0 49.4 69.1 36.5 55.5 55.5 58.7 48.1 65.5 35.3 2000
85 64.2 64.2 65.6 61.3 72.3 48.3 61.6 61.6 62.5 60.0 69.0 47.2 58.9 58.9 59.3 58.5 65.3 45.9

90 67.9 67.9 68.1 68.1 72.6 58.9 65.3 65.3 65.4 65.4 69.1 57.6 62.5 62.5 62.5 62.5 65.5 56.4

75 59.6 55.9 66.2 42.0 73.5 27.5 56.8 54.6 62.8 40.7 70.0 26.3 53.8 52.6 59.4 39.4 66.3 25.0

80 62.4 62.4 66.3 53.6 73.3 39.2 59.8 59.8 62.9 52.2 70.0 38.1 57.1 57.1 59.6 50.8 66.3 36.8 2200
85 66.2 66.2 66.9 65.1 73.2 50.9 63.5 63.5 63.8 63.0 69.8 49.7 60.7 60.7 60.8 60.8 66.2 48.4

90 70.1 70.1 70.3 70.3 73.4 62.4 67.3 67.3 67.4 67.4 70.1 61.2 64.2 64.2 64.3 64.3 66.5 59.9

75 60.6 58.8 67.0 43.8 74.2 27.9 57.6 57.6 63.5 42.4 70.5 26.7 54.9 54.9 60.0 41.0 67.0 25.5

80 64.1 64.1 67.1 56.2 74.1 40.7 61.3 61.3 63.8 54.9 70.4 39.5 58.5 58.5 60.3 53.5 66.9 38.3 2400
85 68.0 68.0 68.3 68.0 74.0 53.3 65.2 65.2 65.3 65.3 70.6 52.1 62.2 62.2 62.3 62.3 66.9 50.8

90 72.1 72.1 72.2 72.2 74.3 65.9 69.1 69.1 69.2 69.2 70.7 64.6 66.1 66.1 66.0 66.0 67.4 63.4

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

CFM

Ent DB (°F)
75

61 MBH SHC 49.0 45.9

67 MBH SHC 54.6 34.6

73 MBH SHC 60.9 22.8

61 MBH SHC 46.4 44.7

67 MBH SHC 51.7 33.5

73 MBH SHC 57.6 21.6

80 51.3 51.3 54.6 44.0 60.8 32.4 49.0 49.0 51.7 42.9 57.5 31.3 1800
85 54.5 54.5 55.0 53.5 60.7 42.0 52.1 52.1 52.3 52.0 57.3 40.8

90 57.7 57.7 57.8 57.8 60.7 51.4 55.2 55.2 55.3 55.3 57.4 50.2

75 50.0 48.9 55.5 36.4 61.7 23.2 47.4 47.4 52.4 35.2 58.3 22.1

80 53.0 53.0 55.5 46.8 61.6 33.9 50.6 50.6 52.5 45.6 58.2 32.8 2000
85 56.3 56.3 56.4 56.4 61.5 44.5 53.8 53.8 53.9 53.9 58.1 43.3

90 59.6 59.6 59.7 59.7 61.7 55.0 56.9 56.9 57.0 57.0 58.3 53.8

75 51.1 51.1 56.1 38.1 62.4 23.7 48.7 48.7 53.0 36.9 58.9 22.6

80 54.5 54.5 56.3 49.7 62.3 35.5 52.0 52.0 53.3 48.3 58.8 34.3 2200
85 57.9 57.9 58.0 58.0 62.2 47.0 55.3 55.3 55.3 55.3 58.7 45.7

90 61.3 61.3 61.4 61.4 62.6 58.5 58.5 58.5 58.5 58.5 59.1 56.8

75 52.3 52.3 56.7 39.7 62.9 24.2 49.8 49.8 53.5 38.5 59.3 23.0

80 55.8 55.8 57.0 52.2 62.8 37.0 53.2 53.2 53.9 50.9 59.2 35.8 2400
85 59.3 59.3 59.4 59.4 62.8 49.4 56.5 56.5 56.6 56.6 59.3 48.1

Notes: 1.
2.

90 62.8 62.8 62.9 62.9 63.4 61.4 59.8 59.8 59.8 59.8 59.9 59.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

29

Performance Data

Table 14. Gross cooling capacities (kW) TTA0604DD condensing unit with TWE0724DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Air-
flow m3/
hr

Ent DB (°C)
24

27 3058
30

33

24

27 3398
30

33

24

27 3738
30

33

24

27 4078
30

33

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC 17.1 14.8 19.1 11.4 21.4 7.9 17.4 17.4 19.1 14.3 21.3 10.8 18.4 18.4 19.1 17.1 21.3 13.6 19.5 19.5 19.5 19.5 21.2 16.5 17.5 15.7 19.4 12.0 21.7 8.1 18.0 18.0 19.4 15.1 21.6 11.2 19.1 19.1 19.5 18.2 21.5 14.4 20.2 20.2 20.3 20.3 21.6 17.5 17.8 16.6 19.7 12.5 21.9 8.2 18.6 18.6 19.7 16.0 21.8 11.7 19.7 19.7 19.9 19.4 21.8 15.1 20.9 20.9 20.9 20.9 21.8 18.6 18.0 17.5 20.0 13.0 22.1 8.3 19.1 19.1 20.0 16.7 22.1 12.1 20.3 20.3 20.3 20.2 22.0 15.9 21.5 21.5 21.5 21.5 22.1 19.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC 16.3 14.4 18.2 11.0 20.3 7.5 16.7 16.7 18.1 13.9 20.3 10.4 17.7 17.7 18.2 16.7 20.2 13.3 18.7 18.7 18.8 18.8 20.2 16.1 16.6 15.3 18.5 11.6 20.6 7.7 17.3 17.3 18.5 14.7 20.6 10.9 18.3 18.3 18.6 17.9 20.5 14.0 19.4 19.4 19.5 19.5 20.6 17.2 16.9 16.2 18.7 12.1 20.9 7.8 17.8 17.8 18.7 15.5 20.8 11.3 18.9 18.9 19.0 18.8 20.8 14.8 20.0 20.0 20.1 20.1 20.9 18.2 17.2 17.2 18.9 12.6 21.0 7.9 18.3 18.3 19.0 16.3 21.0 11.8 19.4 19.4 19.4 19.4 21.0 15.5 20.6 20.6 20.6 20.6 21.1 19.2

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC 15.4 14.0 17.2 10.7 19.2 7.2 16.0 16.0 17.2 13.5 19.1 10.0 17.0 17.0 17.3 16.3 19.1 12.9 17.9 17.9 18.0 18.0 19.1 15.7 15.7 14.9 17.5 11.2 19.5 7.3 16.5 16.5 17.5 14.3 19.5 10.5 17.5 17.5 17.7 17.4 19.4 13.7 18.6 18.6 18.6 18.6 19.5 16.8 16.0 15.7 17.7 11.7 19.7 7.5 17.0 17.0 17.7 15.1 19.7 11.0 18.1 18.1 18.1 18.1 19.7 14.4 19.1 19.1 19.2 19.2 19.8 17.8 16.3 16.3 17.9 12.2 19.9 7.6 17.4 17.4 18.0 15.9 19.9 11.4 18.5 18.5 18.5 18.5 19.9 15.1 19.7 19.7 19.6 19.6 20.1 18.9

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Air-
flow m3/
hr

Ent DB (°C)
24

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC 14.6 13.7 16.3 10.3 18.1 6.8

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC 13.8 13.3 15.4 10.0 17.1 6.4

27 15.3 15.3 16.2 13.1 18.1 9.6 14.6 14.6 15.4 12.8 17.1 9.3 3058
30 16.2 16.2 16.4 15.9 18.1 12.5 15.5 15.5 15.6 15.3 17.1 12.2

33 17.2 17.2 17.2 17.2 18.1 15.3 16.4 16.4 16.5 16.5 17.1 15.0

24 14.9 14.6 16.5 10.8 18.4 6.9 14.1 14.1 15.6 10.5 17.4 6.6

27 15.8 15.8 16.5 13.9 18.3 10.1 15.1 15.1 15.6 13.6 17.3 9.8 3398
30 16.8 16.8 16.8 16.8 18.3 13.3 16.0 16.0 16.0 16.0 17.3 12.9

33 17.8 17.8 17.8 17.8 18.4 16.4 17.0 17.0 17.0 17.0 17.4 16.0

24 15.2 15.1 16.7 11.4 18.6 7.1 14.5 14.5 15.8 11.0 17.5 6.7

27 16.2 16.2 16.8 14.7 18.5 10.6 15.5 15.5 15.9 14.4 17.5 10.2 3738
30 17.2 17.2 17.3 17.3 18.5 14.0 16.5 16.5 16.5 16.5 17.5 13.6

33 18.3 18.3 18.3 18.3 18.6 17.4 17.4 17.4 17.4 17.4 17.6 16.9

24 15.6 15.6 16.9 11.8 18.7 7.2 14.8 14.8 15.9 11.5 17.7 6.9

27 16.6 16.6 17.0 15.5 18.7 11.0 15.8 15.8 16.1 15.2 17.6 10.6 4078
30 17.7 17.7 17.7 17.7 18.7 14.7 16.8 16.8 16.8 16.8 17.6 14.3

Notes: 1.
2.

33 18.7 18.7 18.7 18.7 18.9 18.3 17.8 17.8 17.8 17.8 17.8 17.8
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity,

30

SS-PRC029Y-EN

Performance Data

Table 15. Gross cooling capacities (MBH) TTA0764DA condensing unit with TWE0764DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

76.4 64.1 84.5 49.6 92.6 34.2

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

73.2 62.6 80.9 48.1 88.7 32.8

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

69.8 61.0 77.2 46.6 84.5 31.4

80 76.7 76.7 84.4 61.3 92.4 46.1 74.0 74.0 80.8 59.9 88.5 44.7 71.1 71.1 77.0 58.3 84.3 43.2 2250
85 80.7 80.7 84.4 72.9 92.2 57.9 77.9 77.9 80.8 71.4 88.2 56.5 74.9 74.9 77.1 69.9 84.1 55.1

90 84.7 84.7 85.2 84.8 91.9 69.7 81.8 81.8 81.9 81.9 88.0 68.3 78.7 78.7 78.8 78.8 83.9 66.7

75 77.9 67.6 85.8 51.7 93.8 34.8 74.6 66.1 82.1 50.2 89.8 33.4 71.1 64.5 78.2 48.6 85.5 31.9

80 79.2 79.2 85.6 64.6 93.5 47.9 76.3 76.3 82.0 63.2 89.5 46.5 73.3 73.3 78.1 61.6 85.3 45.0 2500
85 83.4 83.4 85.9 77.4 93.3 60.9 80.4 80.4 82.2 75.8 89.3 59.5 77.2 77.2 78.5 74.3 85.1 58.0

90 87.5 87.5 87.6 87.6 93.2 73.8 84.4 84.4 84.5 84.5 89.2 72.3 81.0 81.0 81.2 81.2 85.0 70.8

75 79.1 71.1 86.9 53.7 94.7 35.3 75.7 69.5 83.1 52.2 90.6 33.9 72.2 67.9 79.2 50.6 86.3 32.4

80 81.4 81.4 86.7 67.7 94.5 49.6 78.4 78.4 83.0 66.1 90.4 48.2 75.2 75.2 79.0 64.5 86.1 46.7 2750
85 85.6 85.6 87.2 81.7 94.3 63.8 82.5 82.5 83.5 80.2 90.2 62.4 79.2 79.2 79.7 78.6 85.8 60.9

90 89.7 89.7 89.9 89.9 94.2 77.7 86.5 86.5 86.6 86.6 90.1 76.3 83.0 83.0 83.1 83.1 85.8 74.7

75 80.2 74.4 87.8 55.6 95.5 35.8 76.8 72.9 84.0 54.1 91.4 34.4 72.7 72.7 79.9 52.6 87.0 32.9

80 83.2 83.2 87.7 70.7 95.3 51.2 80.1 80.1 83.9 69.2 91.1 49.8 76.8 76.8 79.9 67.5 86.7 48.3 3000
85 87.5 87.5 88.3 85.9 95.0 66.6 84.3 84.3 84.7 84.4 90.9 65.2 80.9 80.9 81.0 81.0 86.5 63.7

90 91.7 91.7 91.8 91.8 95.0 81.6 88.3 88.3 88.4 88.4 90.9 80.1 84.7 84.7 84.8 84.8 86.6 78.6

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

66.3 59.3 73.2 45.0 80.1 29.8

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

62.9 57.8 68.8 43.3 75.2 28.1

80 68.1 68.1 73.0 56.8 79.9 41.7 65.0 65.0 68.7 55.1 75.0 40.0 2250
85 71.7 71.7 73.2 68.2 79.6 53.5 68.2 68.2 69.0 66.5 74.8 51.8

90 75.3 75.3 75.4 75.4 79.5 65.1 71.6 71.6 71.7 71.7 74.7 63.3

75 67.5 62.8 74.1 47.0 81.0 30.3 64.0 61.2 69.7 45.3 76.0 28.6

80 70.1 70.1 74.0 59.8 80.7 43.4 66.7 66.7 69.6 58.0 75.7 41.7 2500
85 73.8 73.8 74.5 72.6 80.5 56.5 70.1 70.1 70.3 70.3 75.5 54.8

90 77.5 77.5 77.5 77.5 80.4 69.1 73.5 73.5 73.5 73.5 75.5 67.3

75 68.5 66.2 74.9 49.0 81.7 30.8 64.8 64.8 70.4 47.3 76.6 29.1

80 71.8 71.8 74.9 62.8 81.4 45.1 68.2 68.2 70.4 61.0 76.4 43.4 2750
85 75.6 75.6 75.8 75.8 81.2 59.3 71.7 71.7 71.8 71.8 76.1 57.6

90 79.2 79.2 79.3 79.3 81.3 73.1 75.0 75.0 75.1 75.1 76.3 71.3

75 69.4 69.4 75.6 51.0 82.3 31.3 66.0 66.0 71.0 49.2 77.1 29.6

80 73.3 73.3 75.6 65.8 82.0 46.8 69.5 69.5 71.1 64.0 76.9 45.1 3000
85 77.1 77.1 77.2 77.2 81.8 62.2 73.0 73.0 73.1 73.1 76.6 60.5

Notes: 1.
2.

90 80.7 80.7 80.8 80.8 82.0 76.9 76.3 76.3 76.4 76.4 76.9 75.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

31

Performance Data

Table 16. Gross cooling capacities (kW) TTA0764DA condensing unit with TWE0764DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 22.4 18.8 24.8 14.5 27.1 10.0

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

21.5 18.3 23.7 14.1 26.0 9.6

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

20.5 17.9 22.6 13.7 24.8 9.2

3823

27 22.5 22.5 24.7 18.0 27.1 13.5 21.7 21.7 23.7 17.5 25.9 13.1 20.8 20.8 22.6 17.1 24.7 12.7 30 23.7 23.7 24.7 21.4 27.0 17.0 22.8 22.8 23.7 20.9 25.9 16.6 22.0 22.0 22.6 20.5 24.6 16.1

33 24.8 24.8 25.0 24.8 26.9 20.4 24.0 24.0 24.0 24.0 25.8 20.0 23.1 23.1 23.1 23.1 24.6 19.6

24 22.8 19.8 25.2 15.1 27.5 10.2 21.9 19.4 24.1 14.7 26.3 9.8 20.8 18.9 22.9 14.3 25.1 9.3

4248

27 23.2 23.2 25.1 18.9 27.4 14.0 22.4 22.4 24.0 18.5 26.2 13.6 21.5 21.5 22.9 18.1 25.0 13.2 30 24.4 24.4 25.2 22.7 27.4 17.9 23.6 23.6 24.1 22.2 26.2 17.4 22.6 22.6 23.0 21.8 24.9 17.0

33 25.6 25.6 25.7 25.7 27.3 21.6 24.7 24.7 24.8 24.8 26.1 21.2 23.8 23.8 23.8 23.8 24.9 20.7

24 23.2 20.8 25.5 15.7 27.8 10.3 22.2 20.4 24.4 15.3 26.6 9.9 21.2 19.9 23.2 14.8 25.3 9.5

4672

27 23.8 23.8 25.4 19.8 27.7 14.5 23.0 23.0 24.3 19.4 26.5 14.1 22.0 22.0 23.2 18.9 25.2 13.7 30 25.1 25.1 25.5 23.9 27.6 18.7 24.2 24.2 24.5 23.5 26.4 18.3 23.2 23.2 23.4 23.0 25.2 17.9

33 26.3 26.3 26.3 26.3 27.6 22.8 25.3 25.3 25.4 25.4 26.4 22.3 24.3 24.3 24.4 24.4 25.2 21.9

24 23.5 21.8 25.7 16.3 28.0 10.5 22.5 21.4 24.6 15.9 26.8 10.1 21.3 21.3 23.4 15.4 25.5 9.6

5097

27 24.4 24.4 25.7 20.7 27.9 15.0 23.5 23.5 24.6 20.3 26.7 14.6 22.5 22.5 23.4 19.8 25.4 14.2 30 25.7 25.7 25.9 25.2 27.8 19.5 24.7 24.7 24.8 24.7 26.6 19.1 23.7 23.7 23.7 23.7 25.3 18.7

33 26.9 26.9 26.9 26.9 27.9 23.9 25.9 25.9 25.9 25.9 26.7 23.5 24.8 24.8 24.8 24.8 25.4 23.0

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 19.4 17.4 21.4 13.2 23.5 8.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

18.4 16.9 20.2 12.7 22.0 8.2

3823

27 20.0 20.0 21.4 16.6 23.4 12.2 19.0 19.0 20.1 16.1 22.0 11.7 30 21.0 21.0 21.5 20.0 23.3 15.7 20.0 20.0 20.2 19.5 21.9 15.2

33 22.1 22.1 22.1 22.1 23.3 19.1 21.0 21.0 21.0 21.0 21.9 18.6

24 19.8 18.4 21.7 13.8 23.7 8.9 18.8 17.9 20.4 13.3 22.3 8.4

4248

27 20.5 20.5 21.7 17.5 23.7 12.7 19.6 19.6 20.4 17.0 22.2 12.2 30 21.6 21.6 21.8 21.3 23.6 16.5 20.5 20.5 20.6 20.6 22.1 16.0

33 22.7 22.7 22.7 22.7 23.6 20.3 21.5 21.5 21.6 21.6 22.1 19.7

24 20.1 19.4 22.0 14.4 23.9 9.0 19.0 19.0 20.6 13.9 22.4 8.5

4672

27 21.1 21.1 21.9 18.4 23.9 13.2 20.0 20.0 20.6 17.9 22.4 12.7 30 22.2 22.2 22.2 22.2 23.8 17.4 21.0 21.0 21.0 21.0 22.3 16.9

33 23.2 23.2 23.2 23.2 23.8 21.4 22.0 22.0 22.0 22.0 22.3 20.9

24 20.3 20.3 22.2 14.9 24.1 9.2 19.3 19.3 20.8 14.4 22.6 8.7

5097

27 21.5 21.5 22.2 19.3 24.0 13.7 20.4 20.4 20.8 18.8 22.5 13.2 30 22.6 22.6 22.6 22.6 24.0 18.2 21.4 21.4 21.4 21.4 22.5 17.7

Notes: 1.
2.

33 23.7 23.7 23.7 23.7 24.0 22.5 22.4 22.4 22.4 22.4 22.6 22.0
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity,

32

SS-PRC029Y-EN

Performance Data

Table 17. Gross cooling capacities (MBH) TTA0764DA condensing unit with TWE1014DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

79.2 70.1 86.2 53.1 93.5 34.9

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

75.9 68.5 82.6 51.7 89.7 33.6

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

72.4 66.9 78.8 50.2 85.7 32.2

80 81.2 81.2 86.2 66.6 93.2 48.9 78.3 78.3 82.7 65.1 89.3 47.5 75.1 75.1 78.9 63.5 85.3 46.1 2550
85 85.1 85.1 86.7 80.2 92.9 62.9 82.2 82.2 83.2 78.8 89.1 61.2 78.9 78.9 79.5 77.2 85.1 59.7

90 88.9 88.9 89.0 89.0 92.9 76.1 85.8 85.8 85.9 85.9 89.1 74.7 82.5 82.5 82.6 82.6 85.2 73.2

75 80.6 74.6 87.3 55.8 94.6 35.6 77.3 73.0 83.7 54.4 90.7 34.2 73.8 71.4 79.8 52.9 86.5 32.8

80 83.6 83.6 87.4 70.7 94.1 51.2 80.6 80.6 83.8 69.1 90.2 49.8 77.4 77.4 80.0 67.5 86.1 48.4 2850
85 87.6 87.6 88.2 86.0 93.9 66.3 84.5 84.5 84.7 84.5 90.0 64.8 81.1 81.1 81.2 81.2 86.0 63.3

90 91.3 91.3 91.4 91.4 94.2 81.5 88.1 88.1 88.2 88.2 90.1 80.0 84.6 84.6 84.7 84.7 86.1 78.5

75 81.9 79.1 88.2 58.1 95.4 36.2 78.6 77.5 84.5 56.6 91.5 34.9 75.1 75.1 80.6 54.9 87.3 33.5

80 85.7 85.6 88.4 74.7 94.9 53.4 82.5 82.5 84.8 73.2 91.0 52.1 79.1 79.1 80.9 71.5 86.8 50.8 3150
85 89.6 89.6 89.7 89.7 94.8 69.9 86.4 86.4 86.5 86.5 90.8 68.4 82.9 82.9 83.0 83.0 86.6 66.9

90 93.4 93.4 93.6 93.6 95.4 86.8 89.9 89.9 90.0 90.0 91.1 85.2 86.3 86.3 86.3 86.3 87.0 83.7

75 83.1 83.1 89.0 60.5 96.2 36.9 80.0 80.0 85.2 58.9 92.2 35.6 76.6 76.6 81.2 57.3 87.9 34.2

80 87.4 87.4 89.3 78.7 95.5 55.7 84.1 84.1 85.6 77.1 91.6 54.4 80.6 80.6 81.7 75.5 87.4 53.0 3450
85 91.3 91.3 91.4 91.4 95.7 73.6 88.0 88.0 88.0 88.0 91.4 72.0 84.4 84.4 84.4 84.4 87.2 70.5

90 95.5 95.5 95.6 95.6 96.6 92.1 91.5 91.5 91.6 91.6 92.1 90.5 87.6 87.6 87.7 87.7 87.8 87.8

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

68.7 65.1 74.6 48.6 81.2 30.6

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

64.9 63.3 70.2 46.8 76.2 29.0

80 71.8 71.8 74.8 61.8 80.9 44.6 68.1 68.1 70.4 59.9 76.0 43.0 2550
85 75.4 75.4 75.6 75.5 80.7 58.1 71.5 71.5 71.6 71.6 75.8 56.2

90 78.8 78.8 78.9 78.9 80.8 71.6 74.7 74.7 74.8 74.8 76.0 69.8

75 70.0 69.6 75.5 50.8 82.0 31.3 66.2 66.2 71.0 48.9 77.0 29.7

80 73.8 73.8 75.8 65.8 81.6 46.9 69.9 69.9 71.3 63.9 76.7 45.3 2850
85 77.4 77.4 77.5 77.5 81.5 61.7 73.3 73.3 73.4 73.4 76.5 59.8

90 80.7 80.7 80.8 80.8 81.7 76.8 76.4 76.4 76.5 76.5 76.9 75.0

75 71.5 71.5 76.3 53.2 82.7 32.0 67.7 67.7 71.6 51.2 77.6 30.3

80 75.4 75.4 76.7 69.8 82.3 49.2 71.4 71.4 72.1 67.9 77.2 47.6 3150
85 79.0 79.0 79.1 79.1 82.1 65.2 74.8 74.8 74.8 74.8 77.1 63.4

90 82.2 82.2 82.3 82.3 82.5 82.0 77.7 77.7 77.8 77.8 77.9 77.9

75 72.9 72.9 76.9 55.5 83.2 32.7 68.9 68.9 72.2 53.5 78.0 31.0

80 76.8 76.8 77.5 73.7 82.8 50.8 72.6 72.6 72.9 71.8 77.7 48.9 3450
85 80.4 80.4 80.5 80.5 82.6 68.8 76.0 76.0 76.0 76.0 77.6 66.9

Notes: 1.
2.

90 83.5 83.5 83.5 83.5 83.6 83.6 78.8 78.8 78.9 78.9 78.9 78.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

33

Performance Data

Table 18. Gross cooling capacities (kW) TTA0764DA condensing unit with TWE1014DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 124.6 107.0 137.0 81.4 148.6 54.5 118.5 104.2 130.4 78.8 141.5 52.0 111.8 101.2 123.2 75.9 133.8 49.4

4332

27 125.1 124.8 136.8 101.8 148.3 75.1 119.3 119.3 130.3 99.2 141.3 72.6 113.3 113.3 123.1 96.3 133.6 70.0 30 129.9 129.9 136.7 122.1 148.1 95.6 124.8 124.8 130.2 119.5 141.1 93.1 119.1 119.1 123.1 116.7 133.4 90.5

33 136.0 136.0 137.3 135.3 147.9 116.0 130.7 130.7 131.4 131.1 140.9 113.5 124.8 124.8 124.9 124.9 133.3 110.9

24 126.9 114.1 139.1 85.5 150.5 55.5 120.6 111.3 132.4 82.8 143.1 53.0 113.8 108.4 125.0 80.0 135.2 50.3

4842

27 128.1 128.1 138.9 108.3 150.3 78.6 122.5 122.5 132.2 105.7 142.9 76.0 116.7 116.7 124.9 102.8 135.0 73.4 30 134.1 134.1 138.8 131.1 150.0 101.5 128.7 128.7 132.2 128.5 142.7 99.0 122.7 122.7 125.0 123.2 134.9 96.3

33 140.2 140.2 140.5 140.5 149.8 124.4 134.6 134.6 134.6 134.6 142.5 121.9 128.3 128.3 128.5 128.5 134.7 119.2

24 128.8 121.2 140.8 89.5 152.1 56.5 122.4 118.4 133.9 86.9 144.4 53.9 115.5 113.8 126.4 84.0 136.4 51.2

5352

27 131.1 131.1 140.6 114.8 151.9 82.1 125.7 125.7 133.8 112.1 144.2 79.5 119.7 119.7 126.3 109.3 136.2 76.8 30 137.6 137.6 140.7 139.1 151.7 107.5 131.9 131.9 134.0 133.3 144.0 104.9 125.7 125.7 126.8 126.8 136.0 102.2

33 143.6 143.6 143.7 143.7 151.4 132.8 137.7 137.7 137.9 137.9 143.8 130.2 131.2 131.2 131.4 131.4 135.8 127.5

24 130.4 128.3 142.2 93.5 153.5 57.5 124.0 122.9 135.2 90.8 145.6 54.9 117.1 117.1 127.6 88.0 137.3 52.2

5862

27 134.1 134.1 142.0 121.2 153.2 85.5 128.4 128.4 135.1 118.6 145.3 82.9 122.2 122.2 127.4 115.7 137.1 80.2 30 140.5 140.5 142.3 142.3 153.0 113.4 134.7 134.7 135.7 135.7 145.1 110.8 128.2 128.2 128.6 128.6 136.9 108.1

33 146.4 146.4 146.6 146.6 152.7 141.2 140.4 140.4 140.5 140.5 145.0 138.6 133.6 133.6 133.7 133.7 136.7 134.2

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 104.7 98.1 115.5 72.9 125.4 46.5

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

97.2 94.9 106.9 69.6 116.1 43.4

4332

27 107.0 107.0 115.4 93.3 125.2 67.1 100.6 100.6 106.8 90.0 116.0 63.9 30 112.8 112.8 115.5 113.3 125.1 87.6 105.9 105.9 107.1 106.1 115.8 84.5

33 118.3 118.3 118.4 118.4 124.9 108.0 111.0 111.0 111.1 111.1 115.6 104.9

24 106.5 104.3 117.0 76.9 126.6 47.4 98.9 98.3 108.2 73.6 117.2 44.3

4842

27 110.4 110.4 116.9 99.8 126.5 70.5 103.4 103.4 108.1 96.5 117.1 67.4 30 116.1 116.1 117.3 117.2 126.3 93.5 108.8 108.8 109.2 109.2 116.9 90.3

33 121.5 121.5 121.6 121.6 126.1 116.3 113.8 113.8 113.9 113.9 116.8 113.0

24 108.2 108.2 118.3 80.9 127.6 48.4 100.6 100.6 109.3 77.6 118.0 45.2

5352

27 113.1 113.1 118.2 106.2 127.5 73.9 105.7 105.7 109.2 102.9 117.9 70.8 30 118.8 118.8 119.3 119.3 127.3 99.3 111.1 111.1 111.1 111.1 117.7 96.2

33 124.1 124.1 124.2 124.2 127.2 123.9 116.0 116.0 116.1 116.1 117.7 115.9

24 109.7 109.7 119.3 84.9 128.5 49.3 102.2 102.2 110.2 81.6 118.7 46.2

5862

27 115.4 115.4 119.2 112.6 128.3 77.3 107.8 107.8 110.2 107.2 118.7 74.2 30 121.1 121.1 121.1 121.1 128.1 105.2 113.1 113.1 113.2 113.2 118.4 102.1

Notes: 1.
2.

33 126.2 126.2 126.3 126.3 128.1 126.8 117.8 117.8 117.9 117.9 118.7 117.6
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

34

SS-PRC029Y-EN

Performance Data

Table 19. Gross cooling capacities (MBH) TTA0764DD condensing unit with TWE0764DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

85

95

105

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Ent

DB

61

67

73

61

67

73

61

67

73

(°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 74.5 64.4 81.6 49.0 88.7 32.9 71.1 62.8 77.7 47.5 84.5 31.4 67.4 61.1 73.6 45.8 80.0 29.8

2250

80 76.0 76.0 81.8 61.4 88.6 45.3 73.0 73.0 77.9 59.8 84.3 43.8 69.8 69.8 73.8 58.1 79.8 42.3 85 80.0 80.0 82.3 73.7 88.5 57.7 76.8 76.8 78.5 72.1 84.2 56.2 73.4 73.4 74.5 70.4 79.8 54.7

90 83.9 83.9 84.0 84.0 88.6 70.0 80.5 80.5 80.7 80.7 84.4 68.5 77.0 77.0 77.1 77.1 80.0 66.9

75 75.9 68.3 82.7 51.3 89.6 33.4 72.4 66.7 78.7 49.7 85.2 31.9 68.7 65.0 74.5 48.1 80.7 30.3

2500

80 78.3 78.3 82.9 64.9 89.4 47.2 75.1 75.1 79.0 63.3 85.1 45.7 71.8 71.8 74.8 61.6 80.5 44.1 85 82.5 82.5 83.7 78.6 89.3 60.9 79.1 79.1 79.8 77.0 85.0 59.4 75.5 75.5 75.8 75.4 80.5 57.8

90 86.3 86.3 86.4 86.4 89.6 74.4 82.7 82.7 82.8 82.8 85.3 72.9 78.9 78.9 79.0 79.0 80.8 71.3

75 77.1 72.1 83.6 53.5 90.2 33.9 73.5 70.5 79.5 51.9 85.8 32.4 69.8 68.8 75.2 50.3 81.2 30.8

2750

80 80.4 80.4 83.9 68.4 90.1 49.0 77.0 77.0 79.9 66.7 85.6 47.5 73.4 73.4 75.6 65.1 81.0 46.0 85 84.5 84.5 85.0 83.4 90.0 64.0 80.9 80.9 81.1 81.1 85.6 62.5 77.2 77.2 77.2 77.2 81.0 60.9

90 88.2 88.2 88.3 88.3 90.4 78.9 84.4 84.4 84.5 84.5 86.0 77.3 80.4 80.4 80.5 80.5 81.4 75.7

75 78.1 76.0 84.3 55.6 90.7 34.3 74.4 74.4 80.2 54.0 86.3 32.9 70.9 70.9 75.8 52.3 81.6 31.3

3000

80 82.1 82.1 84.8 71.8 90.5 50.8 78.6 78.6 80.7 70.2 86.1 49.3 74.9 74.9 76.4 68.5 81.4 47.8 85 86.1 86.1 86.3 86.3 90.6 67.1 82.4 82.4 82.5 82.5 86.1 65.5 78.5 78.5 78.6 78.6 81.5 63.9

90 89.6 89.6 89.7 89.7 91.4 83.4 85.7 85.7 85.8 85.8 86.7 81.7 81.5 81.5 81.6 81.6 81.9 79.7

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Ent

DB

61

67

73

61

67

73

(°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 63.6 59.4 69.4 44.2 75.2 28.2 59.7 57.6 64.9 42.5 70.1 26.5

2250

80 66.4 66.4 69.6 56.4 75.1 40.6 62.7 62.7 65.1 54.6 70.0 38.9 85 69.8 69.8 70.3 68.7 75.0 53.0 66.0 66.0 66.1 66.1 69.9 51.2

90 73.1 73.1 73.2 73.2 75.2 65.2 68.8 68.8 68.9 68.9 70.2 63.4

75 64.7 63.2 70.1 46.4 75.8 28.7 60.8 60.8 65.5 44.7 70.6 27.0

2500

80 68.2 68.2 70.4 59.9 75.7 42.5 64.3 64.3 65.9 58.1 70.5 40.8 85 71.6 71.6 71.7 71.7 75.7 56.1 67.5 67.5 67.5 67.5 70.5 54.3

90 74.8 74.8 74.9 74.9 76.0 69.6 70.2 70.2 70.3 70.3 70.8 67.8

75 66.0 66.0 70.7 48.5 76.3 29.2 62.2 62.2 66.1 46.7 71.1 27.5

2750

80 69.7 69.7 71.2 63.3 76.1 44.3 65.7 65.7 66.6 61.5 70.9 42.6 85 73.1 73.1 73.2 73.2 76.1 59.2 68.7 68.7 68.8 68.8 70.9 57.4

90 76.1 76.1 76.1 76.1 76.6 74.0 71.3 71.3 71.3 71.3 71.4 71.4

75 67.2 67.2 71.3 50.6 76.7 29.7 63.3 63.3 66.6 48.8 71.4 28.0

3000

80 70.9 70.9 71.9 66.7 76.5 46.2 66.7 66.7 67.2 64.9 71.2 44.5 85 74.3 74.3 74.4 74.4 76.5 62.2 69.7 69.7 69.8 69.8 71.2 60.4

Notes: 1.
2.

90 77.0 77.0 77.1 77.1 77.1 77.1 72.0 72.0 72.0 72.0 72.1 72.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

35

Performance Data

Table 20. Gross cooling capacities (kW) TTA0764DD condensing unit with TWE0764DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 21.8 18.9 23.9 14.4 26.0 9.6

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

20.8 18.4 22.8 13.9 24.7 9.2

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

19.8 17.9 21.6 13.4 23.4 8.7

3823

27 22.3 22.3 24.0 18.0 26.0 13.3 21.4 21.4 22.8 17.5 24.7 12.8 20.4 20.4 21.6 17.0 23.4 12.4 30 23.4 23.4 24.1 21.6 25.9 16.9 22.5 22.5 23.0 21.1 24.7 16.5 21.5 21.5 21.8 20.6 23.4 16.0

33 24.6 24.6 24.6 24.6 26.0 20.5 23.6 23.6 23.6 23.6 24.7 20.1 22.5 22.5 22.6 22.6 23.4 19.6

24 22.2 20.0 24.2 15.0 26.2 9.8 21.2 19.5 23.1 14.6 25.0 9.3 20.1 19.0 21.8 14.1 23.6 8.9

4248

27 23.0 23.0 24.3 19.0 26.2 13.8 22.0 22.0 23.1 18.5 24.9 13.4 21.0 21.0 21.9 18.1 23.6 12.9 30 24.2 24.2 24.5 23.0 26.2 17.9 23.2 23.2 23.4 22.6 24.9 17.4 22.1 22.1 22.2 22.1 23.6 16.9

33 25.3 25.3 25.3 25.3 26.2 21.8 24.2 24.2 24.3 24.3 25.0 21.4 23.1 23.1 23.1 23.1 23.7 20.9

24 22.6 21.1 24.5 15.7 26.4 9.9 21.5 20.7 23.3 15.2 25.1 9.5 20.4 20.2 22.0 14.7 23.8 9.0

4672

27 23.5 23.5 24.6 20.0 26.4 14.4 22.6 22.6 23.4 19.6 25.1 13.9 21.5 21.5 22.2 19.1 23.7 13.5 30 24.8 24.8 24.9 24.4 26.4 18.8 23.7 23.7 23.8 23.8 25.1 18.3 22.6 22.6 22.6 22.6 23.7 17.8

33 25.8 25.8 25.9 25.9 26.5 23.1 24.7 24.7 24.8 24.8 25.2 22.7 23.6 23.6 23.6 23.6 23.8 22.2

24 22.9 22.3 24.7 16.3 26.6 10.1 21.8 21.8 23.5 15.8 25.3 9.6 20.8 20.8 22.2 15.3 23.9 9.2

5097

27 24.1 24.1 24.8 21.0 26.5 14.9 23.0 23.0 23.6 20.6 25.2 14.5 21.9 21.9 22.4 20.1 23.9 14.0 30 25.2 25.2 25.3 25.3 26.6 19.7 24.2 24.2 24.2 24.2 25.2 19.2 23.0 23.0 23.0 23.0 23.9 18.7

33 26.3 26.3 26.3 26.3 26.8 24.4 25.1 25.1 25.1 25.1 25.4 24.0 23.9 23.9 23.9 23.9 24.0 23.4

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 18.6 17.4 20.3 12.9 22.0 8.3

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

17.5 16.9 19.0 12.4 20.6 7.8

3823

27 19.4 19.4 20.4 16.5 22.0 11.9 18.4 18.4 19.1 16.0 20.5 11.4 30 20.5 20.5 20.6 20.1 22.0 15.5 19.3 19.3 19.4 19.4 20.5 15.0

33 21.4 21.4 21.4 21.4 22.0 19.1 20.2 20.2 20.2 20.2 20.6 18.6

24 19.0 18.5 20.5 13.6 22.2 8.4 17.8 17.8 19.2 13.1 20.7 7.9

4248

27 20.0 20.0 20.6 17.5 22.2 12.5 18.9 18.9 19.3 17.0 20.6 11.9 30 21.0 21.0 21.0 21.0 22.2 16.4 19.8 19.8 19.8 19.8 20.6 15.9

33 21.9 21.9 21.9 21.9 22.3 20.4 20.6 20.6 20.6 20.6 20.7 19.9

24 19.3 19.3 20.7 14.2 22.4 8.6 18.2 18.2 19.4 13.7 20.8 8.1

4672

27 20.4 20.4 20.9 18.6 22.3 13.0 19.2 19.2 19.5 18.0 20.8 12.5 30 21.4 21.4 21.4 21.4 22.3 17.3 20.1 20.1 20.2 20.2 20.8 16.8

33 22.3 22.3 22.3 22.3 22.4 21.7 20.9 20.9 20.9 20.9 20.9 20.9

24 19.7 19.7 20.9 14.8 22.5 8.7 18.6 18.6 19.5 14.3 20.9 8.2

5097

27 20.8 20.8 21.1 19.6 22.4 13.5 19.6 19.6 19.7 19.0 20.9 13.0 30 21.8 21.8 21.8 21.8 22.4 18.2 20.4 20.4 20.4 20.4 20.9 17.7

Notes: 1.
2.

33 22.6 22.6 22.6 22.6 22.6 22.6 21.1 21.1 21.1 21.1 21.1 21.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity,

36

SS-PRC029Y-EN

Performance Data

Table 21. Gross cooling capacities (MBH) TTA1014DA condensing unit with TWE1014DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Ent

DB

61

67

73

61

67

73

61

67

73

CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

75 100.4 86.1 110.1 66.1 119.3 44.4 95.9 84.0 105.0 64.1 113.8 42.4 91.3 81.8 99.5 61.9 107.9 40.4

80 102.4 102.4 110.5 82.4 119.2 61.1 98.4 98.4 105.5 80.3 113.7 59.1 94.3 94.3 100.1 78.0 107.8 57.1 3025
85 108.1 108.1 111.5 98.7 119.2 77.7 103.9 103.9 106.5 96.6 113.7 75.6 99.5 99.5 101.2 94.3 107.8 73.4

90 113.4 113.4 113.6 113.6 119.4 93.6 109.1 109.1 109.2 109.2 113.8 91.5 104.3 104.3 104.5 104.5 107.9 89.3

75 102.3 91.1 111.6 69.1 120.3 45.0 97.6 88.9 106.3 67.0 114.7 43.1 92.9 86.6 100.8 64.9 108.7 41.0

80 105.6 105.6 112.1 86.8 120.1 63.4 101.4 101.4 107.0 84.7 114.5 61.5 96.9 96.9 101.5 82.4 108.5 59.4 3350
85 111.3 111.3 113.3 104.9 120.1 81.4 106.9 106.9 108.3 102.8 114.4 79.3 102.2 102.2 102.9 100.5 108.4 77.1

90 116.4 116.4 116.5 116.5 120.1 99.1 111.7 111.7 111.9 111.9 114.4 96.9 106.6 106.6 106.7 106.7 108.3 94.6

75 103.9 95.9 112.8 71.9 121.1 45.6 99.1 93.7 107.4 69.6 115.4 43.7 94.3 91.4 101.7 67.3 109.3 41.6

80 108.3 108.3 113.5 91.2 120.8 65.7 103.9 103.9 108.2 89.0 115.1 63.8 99.2 99.2 102.6 86.7 109.0 61.8 3675
85 114.0 114.0 114.9 111.0 120.7 85.1 109.4 109.4 109.8 108.9 114.9 83.0 104.4 104.4 104.5 104.5 108.7 80.7

90 118.6 118.6 118.7 118.7 120.8 104.5 113.5 113.5 113.6 113.6 114.7 102.2 108.0 108.0 108.0 108.0 108.3 99.8

75 105.4 100.7 113.8 74.8 121.7 46.2 100.6 98.5 108.3 72.2 115.9 44.3 95.6 95.6 102.6 69.8 109.8 42.3

80 110.6 110.6 114.6 95.5 121.3 68.1 106.0 106.0 109.3 93.3 115.5 66.1 101.2 101.2 103.6 90.9 109.3 64.1 4000
85 116.1 116.1 116.4 116.4 121.0 88.8 111.3 111.3 111.4 111.4 115.1 86.6 106.1 106.1 106.2 106.2 108.8 84.3

90 120.0 120.0 120.0 120.0 121.8 110.1 114.5 114.5 114.5 114.5 115.4 107.7 108.3 108.3 108.2 108.2 108.7 105.2

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Entering Wet Bulb (°F)

Ent

DB

61

67

73

(°F) MBH SHC MBH SHC MBH SHC

75 86.7 79.6 94.0 59.8 101.5 38.2

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

82.6 77.7 88.6 57.7 94.5 35.8

80 90.1 90.1 94.5 75.6 101.4 54.9 85.8 85.8 88.9 73.3 94.3 52.5 3025
85 94.7 94.7 95.7 92.0 101.3 70.9 89.6 89.6 89.8 89.5 94.1 68.3

90 99.1 99.1 99.2 99.2 101.3 86.8 93.0 93.0 93.1 93.1 93.9 84.1

75 88.2 84.4 95.0 62.6 102.1 38.8 83.8 82.4 89.4 59.9 95.0 36.5

80 92.4 92.4 95.7 80.0 101.9 57.2 87.7 87.7 89.8 77.5 94.7 54.8 3350
85 97.1 97.1 97.3 97.3 101.7 74.6 91.5 91.5 91.5 91.5 94.3 71.9

90 100.8 100.8 100.9 100.9 101.4 92.1 93.9 93.9 93.8 93.8 93.6 89.2

75 89.6 89.2 95.8 64.8 102.7 39.5 85.1 85.1 90.0 62.4 95.4 37.1

80 94.3 94.3 96.8 84.2 102.3 59.5 89.2 89.2 90.4 81.6 94.9 57.1 3675
85 99.0 99.0 99.1 99.1 101.9 78.2 92.9 92.9 92.9 92.9 94.3 75.4

90 101.4 101.4 101.4 101.4 101.2 97.2 93.1 93.1 93.1 93.1 93.0 93.0

75 91.0 91.0 96.6 67.3 103.1 40.1 86.4 86.4 90.5 64.8 95.7 37.7

80 96.0 96.0 97.6 88.5 102.5 61.9 90.3 90.3 91.2 85.8 95.0 59.5 4000
85 100.3 100.3 100.4 100.4 101.9 81.7 93.7 93.7 93.8 93.8 94.1 78.8

Notes: 1.
2.

90 101.3 101.3 101.4 101.4 101.4 101.4 92.9 92.9 92.8 92.8 92.7 92.7
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

37

Performance Data

Table 22. Gross cooling capacities (kW) TTA1014DA condensing unit with TWE1014DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 29.4 25.2 32.3 19.4 35.0 13.0

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

28.1 24.6 30.8 18.8 33.3 12.4

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

26.7 24.0 29.2 18.1 31.6 11.8

5148

27 30.0 30.0 32.4 24.1 34.9 17.9 28.8 28.8 30.9 23.5 33.3 17.3 27.6 27.6 29.3 22.9 31.6 16.7 30 31.7 31.7 32.7 28.9 34.9 22.8 30.4 30.4 31.2 28.3 33.3 22.1 29.1 29.1 29.7 27.6 31.6 21.5

33 33.2 33.2 33.3 33.3 35.0 27.4 32.0 32.0 32.0 32.0 33.3 26.8 30.6 30.6 30.6 30.6 31.6 26.2

24 30.0 26.7 32.7 20.2 35.3 13.2 28.6 26.0 31.2 19.6 33.6 12.6 27.2 25.4 29.5 19.0 31.8 12.0

5692

27 30.9 30.9 32.9 25.4 35.2 18.6 29.7 29.7 31.3 24.8 33.6 18.0 28.4 28.4 29.7 24.1 31.8 17.4 30 32.6 32.6 33.2 30.7 35.2 23.9 31.3 31.3 31.7 30.1 33.5 23.2 30.0 30.0 30.2 29.4 31.8 22.6

33 34.1 34.1 34.1 34.1 35.2 29.0 32.7 32.7 32.8 32.8 33.5 28.4 31.2 31.2 31.3 31.3 31.7 27.7

24 30.4 28.1 33.0 21.1 35.5 13.4 29.0 27.4 31.5 20.4 33.8 12.8 27.6 26.8 29.8 19.7 32.0 12.2

6252

27 31.7 31.7 33.2 26.7 35.4 19.3 30.4 30.4 31.7 26.1 33.7 18.7 29.1 29.1 30.1 25.4 31.9 18.1 30 33.4 33.4 33.7 32.5 35.4 24.9 32.0 32.0 32.2 31.9 33.7 24.3 30.6 30.6 30.6 30.6 31.9 23.7

33 34.7 34.7 34.8 34.8 35.4 30.6 33.3 33.3 33.3 33.3 33.6 29.9 31.6 31.6 31.6 31.6 31.7 29.3

24 30.9 29.5 33.3 21.9 35.7 13.5 29.5 28.9 31.7 21.1 34.0 13.0 28.0 28.0 30.1 20.5 32.2 12.4

6796

27 32.4 32.4 33.6 28.0 35.5 19.9 31.1 31.1 32.0 27.3 33.8 19.4 29.6 29.6 30.4 26.6 32.0 18.8 30 34.0 34.0 34.1 34.1 35.5 26.0 32.6 32.6 32.6 32.6 33.7 25.4 31.1 31.1 31.1 31.1 31.9 24.7

33 35.2 35.2 35.2 35.2 35.7 32.2 33.5 33.5 33.5 33.5 33.8 31.5 31.7 31.7 31.7 31.7 31.8 30.8

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 25.4 23.3 27.5 17.5 29.7 11.2

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24.2 22.8 26.0 16.9 27.7 10.5

5148

27 26.4 26.4 27.7 22.2 29.7 16.1 25.1 25.1 26.1 21.5 27.6 15.4 30 27.8 27.8 28.0 26.9 29.7 20.8 26.3 26.3 26.3 26.2 27.6 20.0

33 29.0 29.0 29.1 29.1 29.7 25.4 27.3 27.3 27.3 27.3 27.5 24.6

24 25.8 24.7 27.8 18.4 29.9 11.4 24.6 24.1 26.2 17.6 27.8 10.7

5692

27 27.1 27.1 28.0 23.4 29.9 16.8 25.7 25.7 26.3 22.7 27.7 16.1 30 28.5 28.5 28.5 28.5 29.8 21.9 26.8 26.8 26.8 26.8 27.6 21.1

33 29.5 29.5 29.6 29.6 29.7 27.0 27.5 27.5 27.5 27.5 27.4 26.1

24 26.2 26.1 28.1 19.0 30.1 11.6 24.9 24.9 26.4 18.3 28.0 10.9

6252

27 27.6 27.6 28.3 24.7 30.0 17.4 26.1 26.1 26.5 23.9 27.8 16.7 30 29.0 29.0 29.0 29.0 29.9 22.9 27.2 27.2 27.2 27.2 27.6 22.1

33 29.7 29.7 29.7 29.7 29.6 28.5 27.3 27.3 27.3 27.3 27.2 27.2

24 26.7 26.7 28.3 19.7 30.2 11.7 25.3 25.3 26.5 19.0 28.1 11.1

6796

27 28.1 28.1 28.6 25.9 30.0 18.1 26.5 26.5 26.7 25.1 27.8 17.4 30 29.4 29.4 29.4 29.4 29.9 24.0 27.5 27.5 27.5 27.5 27.6 23.1

Notes: 1.
2.

33 29.7 29.7 29.7 29.7 29.7 29.7 27.2 27.2 27.2 27.2 27.2 27.2
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

38

SS-PRC029Y-EN

Performance Data

Table 23. Gross cooling capacities (MBH) TTA1014DD condensing unit with TWE1014DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ent DB CFM (°F) 75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

97.7 84.9 106.5 64.6 114.6 42.7

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

93.3 82.8 101.8 62.8 110.5 41.2

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

88.9 80.7 97.1 60.9 105.6 39.5

80 99.8 99.8 106.7 80.9 114.5 59.3 96.0 96.0 102.1 78.9 109.3 57.5 92.2 92.2 97.5 77.0 105.5 56.2 3025
85 104.9 104.9 107.5 97.1 114.4 75.9 101.1 101.1 103.0 95.2 109.3 74.0 97.1 97.1 98.4 93.2 105.4 72.6

90 109.8 109.8 110.0 110.0 114.7 92.0 105.8 105.8 106.0 106.0 109.6 90.1 101.8 101.8 101.9 101.9 105.7 88.6

75 99.4 89.8 107.8 67.5 115.8 43.4 95.0 87.7 103.0 65.6 110.5 41.6 90.5 85.6 98.2 63.7 106.6 40.2

80 102.6 102.6 108.2 85.3 115.7 61.8 98.8 98.8 103.5 83.3 110.4 60.0 94.7 94.7 98.7 81.3 106.4 58.7 3350
85 107.8 107.8 109.2 103.3 115.7 79.9 103.8 103.8 104.6 101.3 110.4 78.0 99.7 99.7 100.1 99.4 106.4 76.5

90 111.8 111.8 112.0 112.0 116.1 97.7 107.5 107.5 107.6 107.6 110.9 95.8 104.2 104.2 104.3 104.3 106.7 94.2

75 100.8 94.6 108.9 70.3 116.8 44.1 96.5 92.5 104.1 68.3 111.4 42.3 92.0 90.4 99.2 66.3 107.4 40.9

80 105.1 105.1 109.4 89.6 116.7 64.3 101.0 101.0 104.6 87.6 111.3 62.5 96.9 96.9 99.8 85.6 107.2 61.1 3675
85 110.3 110.3 110.8 109.4 116.7 83.8 106.1 106.1 106.3 106.3 111.4 81.9 101.8 101.8 101.9 101.9 107.2 80.3

90 114.3 114.3 114.4 114.4 117.5 103.4 109.8 109.8 109.9 109.9 112.0 101.4 106.2 106.2 106.3 106.3 107.7 99.8

75 102.1 99.5 109.8 72.9 117.7 44.8 97.6 97.6 104.9 70.9 112.2 43.0 93.4 93.4 100.0 68.9 108.1 41.6

80 107.2 107.2 110.4 93.9 117.5 66.8 103.0 103.0 105.6 91.9 112.0 64.9 98.7 98.7 100.8 89.9 107.8 63.4 4000
85 111.4 111.4 111.6 111.6 117.6 87.7 107.9 107.9 108.0 108.0 112.2 85.7 103.6 103.6 103.7 103.7 107.8 84.1

90 116.5 116.5 116.7 116.7 118.8 109.1 111.8 111.8 111.9 111.9 113.0 106.9 107.8 107.8 107.9 107.9 108.5 105.3

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

Ent DB CFM (°F) 75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

84.1 78.4 91.8 58.8 100.1 37.7

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

78.7 75.9 86.0 56.5 93.9 35.6

80 3025
85

87.9 87.9 92.3 74.8 100.1 54.3 83.1 83.1 86.5 72.4 93.9 52.3 92.8 92.8 93.5 91.1 100.1 70.6 87.8 87.8 88.1 87.6 94.0 68.4

90 97.3 97.3 97.4 97.4 100.4 86.6 92.2 92.2 92.3 92.3 94.4 84.4

75 85.7 83.3 92.9 61.5 101.1 38.4 80.2 80.2 87.0 59.1 94.8 36.3

80 3350
85

90.3 90.3 93.6 79.2 101.0 56.8 85.3 85.3 87.7 76.7 94.7 54.7 95.2 95.2 95.3 95.3 101.0 74.5 90.0 90.0 90.2 90.2 94.9 72.2

90 99.6 99.6 99.7 99.7 101.4 92.2 94.3 94.3 94.4 94.4 95.4 90.0

75 87.1 87.1 93.9 64.1 101.8 39.1 82.1 82.1 87.8 61.6 95.5 37.0

80 3675
85

92.4 92.4 94.6 83.5 101.7 59.2 87.2 87.2 88.7 81.0 95.4 57.0 97.2 97.2 97.3 97.3 101.7 78.3 91.9 91.9 91.9 91.9 95.6 76.0

90 101.4 101.4 101.5 101.5 102.3 97.8 96.0 96.0 95.0 95.0 95.4 93.5

75 88.8 88.8 94.6 66.7 102.5 39.8 83.6 83.6 88.5 64.2 96.0 37.7

80 4000
85

94.1 94.1 95.5 87.7 102.3 61.4 88.8 88.8 89.6 85.2 96.0 59.1 98.8 98.8 98.9 98.9 101.2 81.7 93.4 93.4 93.5 93.5 96.2 79.8

Notes: 1.
2.

90 102.9 102.9 102.9 102.9 102.3 102.3 96.3 96.3 96.4 96.4 96.5 96.5
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

39

Performance Data

Table 24. Gross cooling capacities (kW) TTA1014DD condensing unit with TWE1014DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 28.6 24.9 31.2 18.9 33.6 12.5

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

27.4 24.3 29.8 18.4 32.4 12.1

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

26.1 23.7 28.4 17.9 30.9 11.6

5148

27 29.2 29.2 31.3 23.7 33.5 17.4 28.1 28.1 29.9 23.1 32.0 16.9 27.0 27.0 28.6 22.6 30.9 16.5 30 30.8 30.8 31.5 28.5 33.5 22.3 29.6 29.6 30.2 27.9 32.0 21.7 28.5 28.5 28.8 27.3 30.9 21.3

33 32.2 32.2 32.2 32.2 33.6 27.0 31.0 31.0 31.1 31.1 32.1 26.4 29.8 29.8 29.9 29.9 31.0 26.0

24 29.1 26.3 31.6 19.8 33.9 12.7 27.8 25.7 30.2 19.2 32.4 12.2 26.5 25.1 28.8 18.7 31.2 11.8

5692

27 30.1 30.1 31.7 25.0 33.9 18.1 28.9 28.9 30.3 24.4 32.3 17.6 27.8 27.8 28.9 23.8 31.2 17.2 30 31.6 31.6 32.0 30.3 33.9 23.4 30.4 30.4 30.7 29.7 32.4 22.9 29.2 29.2 29.3 29.1 31.2 22.4

33 32.8 32.8 32.8 32.8 34.0 28.6 31.5 31.5 31.5 31.5 32.5 28.1 30.5 30.5 30.6 30.6 31.3 27.6

24 29.6 27.7 31.9 20.6 34.2 12.9 28.3 27.1 30.5 20.0 32.6 12.4 27.0 26.5 29.1 19.4 31.5 12.0

6252

27 30.8 30.8 32.1 26.3 34.2 18.8 29.6 29.6 30.7 25.7 32.6 18.3 28.4 28.4 29.2 25.1 31.4 17.9 30 32.3 32.3 32.5 32.1 34.2 24.6 31.1 31.1 31.1 31.1 32.6 24.0 29.8 29.8 29.9 29.9 31.4 23.5

33 33.5 33.5 33.5 33.5 34.4 30.3 32.2 32.2 32.2 32.2 32.8 29.7 31.1 31.1 31.2 31.2 31.6 29.2

24 29.9 29.2 32.2 21.4 34.5 13.1 28.6 28.6 30.8 20.8 32.9 12.6 27.4 27.4 29.3 20.2 31.7 12.2

6796

27 31.4 31.4 32.4 27.5 34.4 19.6 30.2 30.2 30.9 26.9 32.8 19.0 28.9 28.9 29.5 26.3 31.6 18.6 30 32.6 32.6 32.7 32.7 34.5 25.7 31.6 31.6 31.7 31.7 32.9 25.1 30.4 30.4 30.4 30.4 31.6 24.6

33 34.1 34.1 34.2 34.2 34.8 32.0 32.8 32.8 32.8 32.8 33.1 31.3 31.6 31.6 31.6 31.6 31.8 30.8

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 24.6 23.0 26.9 17.2 29.3 11.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

23.1 22.2 25.2 16.5 27.5 10.4

5148

27 25.8 25.8 27.1 21.9 29.3 15.9 24.3 24.3 25.4 21.2 27.5 15.3 30 27.2 27.2 27.4 26.7 29.3 20.7 25.7 25.7 25.8 25.7 27.5 20.0

33 28.5 28.5 28.6 28.6 29.4 25.4 27.0 27.0 27.1 27.1 27.7 24.7

24 25.1 24.4 27.2 18.0 29.6 11.3 23.5 23.5 25.5 17.3 27.8 10.6

5692

27 26.5 26.5 27.4 23.2 29.6 16.7 25.0 25.0 25.7 22.5 27.8 16.0 30 27.9 27.9 27.9 27.9 29.6 21.8 26.4 26.4 26.4 26.4 27.8 21.2

33 29.2 29.2 29.2 29.2 29.7 27.0 27.6 27.6 27.7 27.7 28.0 26.4

24 25.5 25.5 27.5 18.8 29.8 11.5 24.0 24.0 25.7 18.1 28.0 10.9

6252

27 27.1 27.1 27.7 24.5 29.8 17.3 25.5 25.5 26.0 23.7 28.0 16.7 30 28.5 28.5 28.5 28.5 29.8 23.0 26.9 26.9 26.9 26.9 28.0 22.3

33 29.7 29.7 29.7 29.7 30.0 28.7 28.1 28.1 27.8 27.8 28.0 27.4

24 26.0 26.0 27.7 19.5 30.0 11.7 24.5 24.5 26.0 18.8 28.1 11.1

6796

27 27.6 27.6 28.0 25.7 30.0 18.0 26.0 26.0 26.3 25.0 28.1 17.3 30 29.0 29.0 29.0 29.0 29.7 23.9 27.4 27.4 27.4 27.4 28.2 23.4

Notes: 1.
2.

33 30.1 30.1 30.2 30.2 30.0 30.0 28.2 28.2 28.3 28.3 28.3 28.3
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

40

SS-PRC029Y-EN

Performance Data

Table 25. Gross cooling capacities (MBH) one compressor - TTA1014DC condensing unit with TWE1014DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Entering Wet Bulb (°F)

Ent

DB

61

67

73

(°F) MBH SHC MBH SHC MBH SHC

75 60.1 60.1 63.7 47.0 69.8 27.5

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

57.8 57.8 60.8 45.9 66.7 26.4

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

55.6 55.6 58.3 44.9 63.9 25.5

80 63.7 63.7 63.7 63.7 69.4 43.6 61.2 61.2 61.3 61.3 66.3 42.6 59.0 59.0 59.0 59.0 63.6 41.7 3025
85 67.1 67.1 67.2 67.2 69.2 58.9 64.5 64.5 64.6 64.6 66.2 57.9 62.2 62.2 62.2 62.2 63.5 56.9

90 70.3 70.3 70.4 70.4 70.4 70.4 67.5 67.5 67.5 67.5 67.6 67.6 65.1 65.1 65.1 65.1 65.2 65.2

75 61.4 61.4 64.2 49.5 70.3 28.2 59.0 59.0 61.4 48.4 67.1 27.1 56.8 56.8 58.8 47.3 64.3 26.2

80 65.0 65.0 65.1 65.1 69.9 45.9 62.4 62.4 62.5 62.5 66.8 44.9 60.1 60.1 60.2 60.2 64.0 44.0 3350
85 68.4 68.4 68.5 68.5 69.7 62.7 65.7 65.7 65.8 65.8 66.7 61.6 63.3 63.3 63.4 63.4 64.0 60.6

90 71.7 71.7 71.8 71.8 71.9 71.9 68.7 68.7 68.8 68.8 68.8 68.8 66.1 66.1 66.2 66.2 66.2 66.2

75 62.5 62.5 64.7 52.0 70.7 28.8 60.0 60.0 61.8 50.8 67.5 27.8 57.7 57.7 59.3 49.8 64.6 26.9

80 66.1 66.1 66.2 66.2 70.3 48.2 63.5 63.5 63.5 63.5 67.2 46.3 61.1 61.1 61.2 61.2 64.4 45.2 3675
85 69.5 69.5 69.6 69.6 70.3 66.4 66.7 66.7 66.8 66.8 66.8 66.8 64.3 64.3 64.3 64.3 64.4 64.4

90 73.0 73.0 73.0 73.0 73.1 73.1 69.8 69.8 69.9 69.9 69.9 69.9 67.1 67.1 67.1 67.1 67.2 67.2

75 63.4 63.4 65.2 54.4 71.1 29.5 60.8 60.8 62.3 53.2 67.8 28.5 58.5 58.5 59.6 52.1 64.9 27.5

80 67.1 67.1 67.1 67.1 70.6 49.4 64.4 64.4 64.4 64.4 67.5 48.3 61.9 61.9 62.0 62.0 64.7 47.2 4000
85 70.5 70.5 70.5 70.5 70.6 70.6 67.6 67.6 67.6 67.6 67.7 67.7 65.1 65.1 65.1 65.1 65.2 65.2

90 74.0 74.0 74.1 74.1 74.1 74.1 70.8 70.8 70.8 70.8 70.9 70.9 67.9 67.9 68.0 68.0 68.0 68.0

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Entering Wet Bulb (°F)

Ent

DB

61

67

73

(°F) MBH SHC MBH SHC MBH SHC

75 53.5 53.5 55.8 43.8 61.1 24.6

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

51.2 51.2 53.1 42.8 58.2 23.7

80 56.8 56.8 56.8 56.8 60.9 40.9 54.4 54.4 54.5 54.5 58.1 39.9 3025
85 59.9 59.9 60.0 60.0 60.9 56.0 57.5 57.5 57.5 57.5 58.2 55.0

90 62.8 62.8 62.8 62.8 62.9 62.9 60.3 60.3 60.4 60.4 60.4 60.4

75 54.5 54.5 56.3 46.3 61.5 25.3 52.2 52.2 53.6 45.2 58.5 24.4

80 57.9 57.9 57.9 57.9 61.4 42.2 55.4 55.4 55.5 55.5 58.5 41.2 3350
85 61.0 61.0 61.1 61.1 61.5 59.7 58.6 58.6 58.6 58.6 58.6 58.6

90 63.8 63.8 63.9 63.9 63.9 63.9 61.3 61.3 61.3 61.3 61.4 61.4

75 55.4 55.4 56.7 48.7 61.7 26.0 53.0 53.0 54.0 47.6 58.7 25.0

80 58.8 58.8 58.8 58.8 61.7 44.3 56.3 56.3 56.3 56.3 58.9 43.2 3675
85 62.0 62.0 62.0 62.0 62.0 62.0 59.4 59.4 59.5 59.5 59.5 59.5

90 64.6 64.6 64.7 64.7 64.7 64.7 62.1 62.1 62.1 62.1 62.1 62.1

75 56.2 56.2 57.1 51.0 61.9 26.6 53.7 53.7 54.4 49.9 58.8 25.7

80 59.6 59.6 59.6 59.6 62.0 46.2 57.0 57.0 57.1 57.1 59.1 45.1 4000
85 62.7 62.7 62.8 62.8 62.8 62.8 60.2 60.2 60.2 60.2 60.2 60.2

Notes: 1.
2.

90 65.3 65.3 65.4 65.4 65.4 65.4 62.7 62.7 62.7 62.7 62.8 62.8
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

41

Performance Data

Table 26. Gross cooling capacities (kW) one compressor - TTA1014DC condensing unit with TWE1014DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 17.6 17.6 18.6 13.8 20.5 8.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

16.9 16.9 17.8 13.4 19.5 7.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

16.3 16.3 17.1 13.1 18.7 7.5

5148

27 18.7 18.7 18.7 18.7 20.3 12.8 17.9 17.9 17.9 17.9 19.4 12.5 17.3 17.3 17.3 17.3 18.6 12.2 30 19.7 19.7 19.7 19.7 20.3 17.3 18.9 18.9 18.9 18.9 19.4 17.0 18.2 18.2 18.2 18.2 18.6 16.7

33 20.6 20.6 20.6 20.6 20.6 20.6 19.8 19.8 19.8 19.8 19.8 19.8 19.1 19.1 19.1 19.1 19.1 19.1

24 18.0 18.0 18.8 14.5 20.6 8.2 17.3 17.3 18.0 14.2 19.7 8.0 16.6 16.6 17.2 13.9 18.8 7.7

5692

27 19.0 19.0 19.1 19.1 20.5 13.5 18.3 18.3 18.3 18.3 19.6 13.2 17.6 17.6 17.6 17.6 18.8 12.9 30 20.0 20.0 20.1 20.1 20.4 18.4 19.3 19.3 19.3 19.3 19.5 18.1 18.6 18.6 18.6 18.6 18.8 17.8

33 21.0 21.0 21.0 21.0 21.1 21.1 20.1 20.1 20.2 20.2 20.2 20.2 19.4 19.4 19.4 19.4 19.4 19.4

24 18.3 18.3 19.0 15.2 20.7 8.4 17.6 17.6 18.1 14.9 19.8 8.1 16.9 16.9 17.4 14.6 18.9 7.9

6252

27 19.4 19.4 19.4 19.4 20.6 14.1 18.6 18.6 18.6 18.6 19.7 13.6 17.9 17.9 17.9 17.9 18.9 13.3 30 20.4 20.4 20.4 20.4 20.6 19.5 19.6 19.6 19.6 19.6 19.6 19.6 18.8 18.8 18.9 18.9 18.9 18.9

33 21.4 21.4 21.4 21.4 21.4 21.4 20.5 20.5 20.5 20.5 20.5 20.5 19.7 19.7 19.7 19.7 19.7 19.7

24 18.6 18.6 19.1 15.9 20.8 8.6 17.8 17.8 18.2 15.6 19.9 8.3 17.1 17.1 17.5 15.3 19.0 8.1

6796

27 19.7 19.7 19.7 19.7 20.7 14.5 18.9 18.9 18.9 18.9 19.8 14.1 18.2 18.2 18.2 18.2 19.0 13.8 30 20.6 20.6 20.7 20.7 20.7 20.7 19.8 19.8 19.8 19.8 19.8 19.8 19.1 19.1 19.1 19.1 19.1 19.1

33 21.7 21.7 21.7 21.7 21.7 21.7 20.7 20.7 20.8 20.8 20.8 20.8 19.9 19.9 19.9 19.9 19.9 19.9

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 15.7 15.7 16.3 12.8 17.9 7.2

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

15.0 15.0 15.6 12.5 17.0 6.9

5148

27 16.6 16.6 16.6 16.6 17.9 12.0 15.9 15.9 16.0 16.0 17.0 11.7 30 17.6 17.6 17.6 17.6 17.9 16.4 16.8 16.8 16.9 16.9 17.1 16.1

33 18.4 18.4 18.4 18.4 18.4 18.4 17.7 17.7 17.7 17.7 17.7 17.7

24 16.0 16.0 16.5 13.6 18.0 7.4 15.3 15.3 15.7 13.2 17.1 7.1

5692

27 17.0 17.0 17.0 17.0 18.0 12.4 16.2 16.2 16.3 16.3 17.1 12.1 30 17.9 17.9 17.9 17.9 18.0 17.5 17.2 17.2 17.2 17.2 17.2 17.2

33 18.7 18.7 18.7 18.7 18.7 18.7 18.0 18.0 18.0 18.0 18.0 18.0

24 16.2 16.2 16.6 14.3 18.1 7.6 15.5 15.5 15.8 13.9 17.2 7.3

6252

27 17.2 17.2 17.2 17.2 18.1 13.0 16.5 16.5 16.5 16.5 17.2 12.6 30 18.2 18.2 18.2 18.2 18.2 18.2 17.4 17.4 17.4 17.4 17.4 17.4

33 18.9 18.9 18.9 18.9 19.0 19.0 18.2 18.2 18.2 18.2 18.2 18.2

24 16.5 16.5 16.7 15.0 18.1 7.8 15.7 15.7 15.9 14.6 17.2 7.5

6796

27 17.5 17.5 17.5 17.5 18.2 13.5 16.7 16.7 16.7 16.7 17.3 13.2 30 18.4 18.4 18.4 18.4 18.4 18.4 17.6 17.6 17.6 17.6 17.6 17.6

Notes: 1.
2.

33 19.1 19.1 19.2 19.2 19.2 19.2 18.4 18.4 18.4 18.4 18.4 18.4
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

42

SS-PRC029Y-EN

Performance Data

Table 27. Gross cooling capacities (MBH) both compressors - TTA1014DC condensing unit with TWE1014DA air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Entering Wet Bulb (°F)

Ent

DB

61

67

73

(°F) MBH SHC MBH SHC MBH SHC

75 98.7 84.7 108.4 64.7 117.5 43.5

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

94.8 82.8 104.1 63.0 112.8 41.8

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

90.6 80.8 99.6 61.2 108.2 40.2

80 99.8 99.8 107.9 80.6 117.0 59.6 96.4 96.4 103.6 78.8 112.3 57.9 92.8 92.8 99.2 76.9 107.7 56.3 3025
85 104.7 104.7 108.0 96.3 116.6 75.7 101.2 101.2 103.7 94.5 111.8 74.0 97.5 97.5 99.4 92.7 107.2 72.4

90 109.4 109.4 109.5 109.5 116.2 91.5 105.7 105.7 105.8 105.8 111.5 89.7 102.0 102.0 102.1 102.1 106.9 88.0

75 100.5 89.3 109.8 67.5 118.8 44.2 96.4 87.4 105.4 65.7 113.9 42.5 92.2 85.5 100.9 63.9 109.2 40.8

80 102.7 102.7 109.4 84.8 118.4 62.0 99.2 99.2 105.0 83.0 113.4 60.2 95.5 95.5 100.5 81.1 108.7 58.6 3350
85 107.7 107.7 109.6 102.2 118.0 79.7 104.0 104.0 105.3 100.3 112.7 78.3 100.2 100.2 101.0 98.5 108.1 76.3

90 112.3 112.3 112.4 112.4 117.8 97.0 108.4 108.4 108.6 108.6 112.6 95.1 104.5 104.5 104.7 104.7 107.9 93.3

75 101.9 93.9 110.9 70.1 120.0 44.9 97.8 92.0 106.4 68.4 114.8 43.1 93.6 90.0 101.9 66.6 110.1 41.5

80 105.2 105.2 110.6 88.9 119.6 64.3 101.5 101.5 106.1 87.1 114.3 62.5 97.7 97.7 101.6 85.2 109.5 60.8 3675
85 110.2 110.2 111.1 107.9 119.1 83.5 106.3 106.3 106.8 106.1 113.8 81.5 102.4 102.4 102.6 102.6 108.9 79.7

90 114.7 114.7 114.8 114.8 119.1 102.3 110.6 110.6 110.8 110.8 113.8 100.4 106.6 106.6 106.7 106.7 108.8 98.5

75 103.3 98.4 111.9 72.7 121.0 45.6 98.5 98.5 107.3 71.0 115.6 43.8 94.6 94.6 102.7 69.2 110.8 42.1

80 107.4 107.4 111.6 92.9 120.6 66.6 103.6 103.6 107.1 91.1 115.2 64.8 99.7 99.7 102.6 89.2 110.1 63.1 4000
85 112.3 112.3 112.5 112.5 120.1 87.1 108.3 108.3 108.4 108.4 114.7 85.2 104.3 104.3 104.4 104.4 109.6 83.3

90 117.1 117.1 117.2 117.2 120.3 107.6 112.6 112.6 112.7 112.7 114.9 105.6 108.3 108.3 108.4 108.4 109.7 103.7

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Entering Wet Bulb (°F)

Ent

DB

61

67

73

(°F) MBH SHC MBH SHC MBH SHC

75 86.0 78.6 94.8 59.2 103.2 38.4

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

80.9 76.2 89.2 57.1 97.4 36.4

80 88.9 88.9 94.4 74.9 102.7 54.5 84.4 84.4 88.9 72.6 96.9 52.5 3025
85 93.5 93.5 94.7 90.7 102.2 70.6 88.9 88.9 89.4 88.4 96.4 68.6

90 97.9 97.9 98.0 98.0 101.9 86.1 93.1 93.1 93.2 93.2 96.2 84.0

75 87.6 83.3 95.9 62.0 104.1 39.1 82.0 82.0 90.3 59.8 98.3 37.1

80 91.4 91.4 95.7 79.1 103.6 56.8 86.8 86.8 90.1 76.8 97.8 54.9 3350
85 96.1 96.1 96.4 96.4 103.1 74.2 91.3 91.3 91.4 91.4 97.2 72.1

90 100.3 100.3 100.4 100.4 102.9 91.4 95.3 95.3 95.4 95.4 97.1 89.3

75 88.6 88.6 96.9 64.7 105.0 39.8 83.9 83.9 91.1 62.5 99.0 37.8

80 93.5 93.5 96.7 83.2 104.4 59.1 88.7 88.7 91.1 80.9 98.5 57.1 3675
85 98.1 98.1 98.3 98.3 103.8 77.9 93.2 93.2 93.3 93.3 97.9 75.7

90 102.2 102.2 102.3 102.3 103.7 96.7 97.1 97.1 97.2 97.2 97.9 94.5

75 90.4 90.4 97.7 67.3 105.6 40.4 85.6 85.6 91.9 65.1 99.6 38.4

80 95.4 95.4 97.6 87.2 105.0 61.3 90.4 90.4 92.0 84.8 99.0 59.4 4000
85 99.9 99.9 100.0 100.0 104.4 81.4 94.8 94.8 94.9 94.9 98.5 79.3

Notes: 1.
2.

90 103.8 103.8 103.8 103.8 104.5 101.8 98.5 98.5 98.6 98.6 98.7 98.7
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

43

Performance Data

Table 28. Gross cooling capacities (kW) both compressors - TTA1014DC condensing unit with TWE1014DA air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 28.9 24.8 31.8 19.0 34.4 12.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

27.8 24.3 30.5 18.4 33.1 12.2

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

26.6 23.7 29.2 17.9 31.7 11.8

5148

27 29.2 29.2 31.6 23.6 34.3 17.5 28.2 28.2 30.4 23.1 32.9 17.0 27.2 27.2 29.1 22.5 31.6 16.5 30 30.7 30.7 31.6 28.2 34.2 22.2 29.6 29.6 30.4 27.7 32.8 21.7 28.6 28.6 29.1 27.1 31.4 21.2

33 32.0 32.0 32.1 32.1 34.1 26.8 31.0 31.0 31.0 31.0 32.7 26.3 29.9 29.9 29.9 29.9 31.3 25.8

24 29.4 26.2 32.2 19.8 34.8 12.9 28.2 25.6 30.9 19.3 33.4 12.4 27.0 25.0 29.6 18.7 32.0 12.0

5692

27 30.1 30.1 32.0 24.9 34.7 18.2 29.1 29.1 30.8 24.3 33.2 17.6 28.0 28.0 29.5 23.8 31.8 17.2 30 31.5 31.5 32.1 29.9 34.6 23.4 30.5 30.5 30.9 29.4 33.0 22.9 29.4 29.4 29.6 28.9 31.7 22.4

33 32.9 32.9 32.9 32.9 34.5 28.4 31.8 31.8 31.8 31.8 33.0 27.9 30.6 30.6 30.7 30.7 31.6 27.3

24 29.9 27.5 32.5 20.5 35.2 13.1 28.7 27.0 31.2 20.0 33.6 12.6 27.4 26.4 29.8 19.5 32.2 12.2

6252

27 30.8 30.8 32.4 26.1 35.0 18.8 29.8 29.8 31.1 25.5 33.5 18.3 28.6 28.6 29.8 25.0 32.1 17.8 30 32.3 32.3 32.6 31.6 34.9 24.5 31.2 31.2 31.3 31.1 33.3 23.9 30.0 30.0 30.1 30.1 31.9 23.4

33 33.6 33.6 33.6 33.6 34.9 30.0 32.4 32.4 32.5 32.5 33.3 29.4 31.2 31.2 31.3 31.3 31.9 28.9

24 30.3 28.8 32.8 21.3 35.4 13.4 28.9 28.9 31.4 20.8 33.9 12.8 27.7 27.7 30.1 20.3 32.5 12.3

6796

27 31.5 31.5 32.7 27.2 35.3 19.5 30.3 30.3 31.4 26.7 33.7 19.0 29.2 29.2 30.1 26.1 32.3 18.5 30 32.9 32.9 33.0 33.0 35.2 25.5 31.7 31.7 31.8 31.8 33.6 25.0 30.6 30.6 30.6 30.6 32.1 24.4

33 34.3 34.3 34.3 34.3 35.2 31.5 33.0 33.0 33.0 33.0 33.7 31.0 31.7 31.7 31.8 31.8 32.1 30.4

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 25.2 23.0 27.8 17.4 30.2 11.3

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

23.7 22.3 26.1 16.7 28.5 10.7

5148

27 26.0 26.0 27.7 22.0 30.1 16.0 24.7 24.7 26.1 21.3 28.4 15.4 30 27.4 27.4 27.8 26.6 29.9 20.7 26.1 26.1 26.2 25.9 28.2 20.1

33 28.7 28.7 28.7 28.7 29.9 25.2 27.3 27.3 27.3 27.3 28.2 24.6

24 25.7 24.4 28.1 18.2 30.5 11.5 24.0 24.0 26.5 17.5 28.8 10.9

5692

27 26.8 26.8 28.0 23.2 30.4 16.7 25.4 25.4 26.4 22.5 28.6 16.1 30 28.1 28.1 28.2 28.2 30.2 21.8 26.7 26.7 26.8 26.8 28.5 21.1

33 29.4 29.4 29.4 29.4 30.1 26.8 27.9 27.9 28.0 28.0 28.5 26.2

24 26.0 26.0 28.4 18.9 30.8 11.7 24.6 24.6 26.7 18.3 29.0 11.1

6252

27 27.4 27.4 28.3 24.4 30.6 17.3 26.0 26.0 26.7 23.7 28.8 16.7 30 28.8 28.8 28.8 28.8 30.4 22.8 27.3 27.3 27.3 27.3 28.7 22.2

33 29.9 29.9 30.0 30.0 30.4 28.3 28.4 28.4 28.5 28.5 28.7 27.7

24 26.5 26.5 28.6 19.7 31.0 11.8 25.1 25.1 26.9 19.1 29.2 11.3

6796

27 27.9 27.9 28.6 25.5 30.8 18.0 26.5 26.5 26.9 24.9 29.0 17.4 30 29.3 29.3 29.3 29.3 30.6 23.9 27.8 27.8 27.8 27.8 28.9 23.2

Notes: 1.
2.

33 30.4 30.4 30.4 30.4 30.6 29.8 28.9 28.9 28.9 28.9 28.9 28.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

44

SS-PRC029Y-EN

Performance Data

Table 29. Gross cooling capacities (MBH) TTA1264DD condensing unit with TWE1264DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

122.4 106.6 133.7 80.4 144.2 53.0

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

116.8 104.0 127.7 78.0 137.4 50.7

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

110.7 101.3 121.2 75.5 130.4 48.2

80 122.9 121.5 133.6 101.0 143.9 73.8 117.8 117.6 127.6 98.6 137.2 71.5 112.4 112.4 121.1 96.1 130.2 69.1 3750
85 128.0 128.0 133.4 121.5 143.7 94.5 123.2 123.2 127.4 119.2 137.0 92.2 117.9 117.9 121.1 116.6 130.0 89.8

90 133.5 133.5 134.3 133.3 143.4 115.2 128.5 128.5 128.8 128.8 136.7 112.8 123.1 123.1 123.0 123.0 129.8 110.4

75 124.5 113.7 135.5 84.4 145.9 54.0 118.7 111.2 129.4 82.1 138.9 51.6 112.5 108.5 122.8 79.5 131.6 49.1

80 126.0 126.0 135.3 107.5 145.6 77.3 120.8 120.8 129.2 105.1 138.6 74.9 115.6 115.6 122.6 102.6 131.3 72.4 4200
85 131.7 131.7 135.3 130.5 145.4 100.5 126.7 126.7 129.3 127.4 138.4 98.1 121.1 121.1 122.8 121.7 131.1 95.7

90 137.2 137.2 137.2 137.2 0.0 0.0 131.9 131.9 132.0 132.0 138.1 121.2 126.2 126.2 126.3 126.3 130.9 118.8

75 126.2 120.8 136.9 88.4 147.2 54.9 120.4 118.3 130.7 86.0 140.1 52.6 114.1 113.0 124.0 83.5 132.6 50.1

80 129.0 129.0 136.8 114.0 147.0 80.8 123.9 123.9 130.5 111.6 139.9 78.4 118.3 118.3 123.8 109.1 132.3 75.9 4650
85 134.8 134.8 136.9 135.8 146.7 106.4 129.5 129.5 130.8 130.8 139.6 104.1 123.8 123.8 124.4 124.1 132.1 101.6

90 140.1 140.1 140.3 140.3 146.4 132.0 134.6 134.6 134.7 134.7 139.3 129.7 128.6 128.6 128.7 128.7 131.9 127.2

75 127.7 126.1 138.1 92.4 148.4 55.9 121.8 121.6 131.8 90.0 141.2 53.5 115.6 115.6 125.0 87.5 133.5 51.0

80 131.6 131.6 137.9 120.4 148.1 84.2 126.3 126.3 131.6 118.1 140.9 81.8 120.6 120.6 124.8 115.5 133.2 79.3 5100
85 137.3 137.3 138.3 138.3 147.8 112.4 131.9 131.9 132.4 132.4 140.5 110.0 125.9 125.9 126.0 126.0 132.9 107.5

90 142.8 142.8 142.9 142.9 147.6 140.5 136.9 136.9 137.0 137.0 140.4 137.5 130.6 130.6 130.6 130.6 132.9 130.8

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

104.3 98.5 114.3 72.8 122.9 45.7

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

97.7 95.0 106.6 69.8 114.6 42.9

80 106.9 106.9 114.1 93.4 122.7 66.5 100.9 100.9 106.5 90.4 114.5 63.7 3750
85 112.2 112.2 114.2 111.9 122.5 87.2 105.8 105.8 106.8 105.6 114.3 84.5

90 117.1 117.1 117.2 117.2 122.3 107.9 110.4 110.4 110.5 110.5 114.1 105.1

75 106.0 104.2 115.6 76.8 123.9 46.6 99.2 98.7 107.8 73.8 115.5 43.8

80 109.9 109.9 115.5 99.9 123.8 69.9 103.5 103.5 107.7 96.9 115.4 67.1 4200
85 115.1 115.1 115.9 115.6 123.5 93.1 108.4 108.4 108.7 108.7 115.1 90.4

90 119.9 119.9 120.0 120.0 122.3 113.3 112.8 112.8 112.9 112.9 114.9 111.9

75 107.6 107.6 116.7 80.8 124.8 47.5 100.8 100.8 108.8 77.8 116.2 44.8

80 112.3 112.3 116.6 106.3 124.5 73.3 105.7 105.7 108.7 103.4 116.1 70.6 4650
85 117.5 117.5 117.7 117.7 124.3 99.0 110.5 110.5 110.6 110.6 115.8 96.2

90 122.0 122.0 122.1 122.1 124.1 122.0 114.6 114.6 114.7 114.7 115.7 114.2

75 109.1 109.1 117.6 84.8 125.4 48.4 102.3 102.3 109.6 81.8 116.8 45.7

80 114.4 114.4 117.5 112.8 125.2 76.7 107.5 107.5 109.5 106.9 116.6 74.0 5100
85 119.4 119.4 119.4 119.4 124.9 104.9 112.2 112.2 112.2 112.2 116.3 102.1

Notes: 1.
2.

90 123.7 123.7 123.7 123.7 124.9 124.4 116.0 116.0 116.0 116.0 116.4 116.4
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

45

Performance Data

Table 30. Gross cooling capacities (kW) TTA1264DD condensing unit with TWE1264DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 36.5 31.4 40.1 23.9 43.5 16.0

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

34.7 30.5 38.2 23.1 41.5 15.3

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

32.8 29.7 36.1 22.3 39.2 14.5

6371

27 36.7 36.6 40.1 29.8 43.5 22.0 35.0 35.0 38.2 29.1 41.4 21.3 33.2 33.2 36.1 28.2 39.2 20.5 30 38.1 38.1 40.1 35.8 43.4 28.0 36.6 36.6 38.2 35.0 41.4 27.3 34.9 34.9 36.1 34.2 39.1 26.5

33 39.9 39.9 40.2 39.7 43.4 34.0 38.3 38.3 38.5 38.4 41.3 33.3 36.6 36.6 36.6 36.6 39.1 32.5

24 37.2 33.4 40.8 25.1 44.1 16.3 35.3 32.6 38.8 24.3 41.9 15.5 33.3 31.8 36.6 23.4 39.6 14.7

7136

27 37.6 37.6 40.7 31.7 44.0 23.0 35.9 35.9 38.8 31.0 41.9 22.3 34.2 34.2 36.6 30.1 39.6 21.5 30 39.3 39.3 40.7 38.4 44.0 29.8 37.7 37.7 38.8 37.7 41.8 29.0 36.0 36.0 36.6 36.1 39.5 28.2

33 41.1 41.1 41.2 41.2 43.9 36.5 39.4 39.4 39.4 39.4 41.8 35.7 37.6 37.6 37.7 37.7 39.5 34.9

24 37.7 35.5 41.3 26.2 44.6 16.6 35.9 34.7 39.2 25.5 42.3 15.8 33.8 33.4 37.0 24.6 40.0 15.0

7900

27 38.4 38.4 41.2 33.6 44.5 24.0 36.8 36.8 39.2 32.9 42.3 23.3 35.1 35.1 37.0 32.0 39.9 22.5 30 40.3 40.3 41.2 40.8 44.4 31.5 38.7 38.7 39.3 39.1 42.2 30.7 36.8 36.8 37.2 37.2 39.9 30.0

33 42.1 42.1 42.1 42.1 44.4 38.9 40.4 40.4 40.4 40.4 42.1 38.2 38.5 38.5 38.5 38.5 39.8 37.4

24 38.2 37.6 41.7 27.4 45.0 16.9 36.3 36.0 39.6 26.6 42.7 16.1 34.3 34.3 37.4 25.8 40.2 15.3

8665

27 39.3 39.3 41.6 35.5 44.9 25.1 37.6 37.6 39.6 34.7 42.6 24.3 35.8 35.8 37.3 33.9 40.2 23.5 30 41.2 41.2 41.7 41.7 44.8 33.2 39.5 39.5 39.8 39.8 42.5 32.5 37.6 37.6 37.7 37.7 40.1 31.7

33 42.9 42.9 43.0 43.0 44.8 41.4 41.1 41.1 41.2 41.2 42.5 40.6 39.2 39.2 39.2 39.2 40.1 39.3

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 30.7 28.8 33.8 21.4 36.8 13.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

28.5 27.8 31.3 20.4 34.0 12.7

6371

27 31.4 31.4 33.8 27.3 36.7 19.7 29.5 29.5 31.3 26.4 34.0 18.7 30 33.1 33.1 33.8 33.2 36.7 25.7 31.0 31.0 31.4 31.1 33.9 24.8

33 34.7 34.7 34.7 34.7 36.6 31.7 32.5 32.5 32.6 32.6 33.9 30.7

24 31.2 30.6 34.3 22.5 37.1 13.9 29.0 28.8 31.7 21.6 34.3 13.0

7136

27 32.4 32.4 34.3 29.2 37.1 20.7 30.3 30.3 31.7 28.3 34.3 19.7 30 34.0 34.0 34.4 34.3 37.0 27.4 31.9 31.9 32.0 32.0 34.3 26.5

33 35.6 35.6 35.6 35.6 37.0 34.1 33.3 33.3 33.4 33.4 34.2 33.1

24 31.7 31.7 34.7 23.7 37.4 14.2 29.5 29.5 32.0 22.7 34.6 13.3

7900

27 33.1 33.1 34.6 31.1 37.4 21.7 31.0 31.0 32.0 30.2 34.6 20.7 30 34.8 34.8 35.0 35.0 37.3 29.1 32.6 32.6 32.6 32.6 34.5 28.2

33 36.4 36.4 36.4 36.4 37.3 36.3 34.0 34.0 34.0 34.0 34.5 34.0

24 32.2 32.2 35.0 24.9 37.7 14.5 29.9 29.9 32.3 23.9 34.8 13.5

8665

27 33.8 33.8 34.9 33.0 37.6 22.7 31.6 31.6 32.3 31.4 34.8 21.7 30 35.5 35.5 35.5 35.5 37.5 30.8 33.1 33.1 33.2 33.2 34.7 29.9

Notes: 1.
2.

33 37.0 37.0 37.0 37.0 37.5 37.2 34.5 34.5 34.5 34.5 34.8 34.5
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

46

SS-PRC029Y-EN

Performance Data

Table 31. Gross cooling capacities (MBH) TTA1564DD condensing unit with TWE1564DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

153.9 131.4 169.9 100.4 185.0 67.8

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

147.5 128.4 162.7 97.5 177.1 65.0

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

140.5 125.3 155.0 94.5 168.9 62.1

80 155.3 155.3 169.6 125.3 184.6 92.9 149.1 149.1 162.4 122.4 176.8 90.1 142.9 142.9 154.8 119.3 168.5 87.2 4500
85 162.2 162.2 169.6 150.1 184.4 117.9 156.6 156.6 162.6 147.3 176.5 115.1 150.5 150.5 155.1 144.3 168.2 112.2

90 170.0 170.0 171.2 171.2 184.1 142.8 164.2 164.2 164.8 164.8 176.2 140.0 157.8 157.8 158.1 158.1 167.9 137.1

75 156.8 139.6 172.3 105.0 187.4 69.0 150.1 136.6 165.0 102.1 179.1 66.1 143.0 133.4 157.1 99.0 170.6 63.2

80 159.1 159.1 172.1 132.6 187.0 96.9 153.4 153.4 164.7 129.7 178.7 94.0 147.2 147.2 156.9 126.6 170.3 91.1 5000
85 167.3 167.3 172.4 160.4 186.7 124.7 161.3 161.3 165.2 157.5 178.4 121.8 154.9 154.9 157.6 153.5 169.9 118.8

90 175.1 175.1 175.4 175.4 186.5 152.4 169.0 169.0 169.2 169.2 178.2 149.5 162.3 162.3 162.5 162.5 169.8 146.6

75 159.2 147.7 174.4 109.6 189.4 70.1 152.4 144.7 166.9 106.7 180.8 67.2 145.2 140.6 158.9 103.6 172.0 64.2

80 163.3 163.3 174.1 139.9 189.0 100.8 157.3 157.3 166.6 137.0 180.4 97.9 150.9 150.9 158.7 134.0 171.7 94.9 5500
85 171.6 171.6 174.8 169.6 188.8 131.4 165.4 165.3 167.6 166.6 180.1 128.5 158.7 158.7 159.9 159.9 171.3 125.5

90 179.4 179.4 179.6 179.6 188.8 162.0 172.9 172.9 173.1 173.1 180.1 159.0 165.9 165.9 166.1 166.1 171.3 156.0

75 161.4 155.2 176.0 114.1 191.2 71.3 154.5 151.6 168.4 111.2 182.3 68.3 147.2 147.2 160.3 108.1 173.2 65.3

80 166.9 166.9 175.8 147.2 190.8 104.8 160.7 160.7 168.3 144.3 181.9 101.8 154.0 154.0 160.2 141.3 172.8 98.8 6000
85 175.2 175.2 177.0 177.0 190.6 138.2 168.8 168.8 169.8 169.8 181.5 135.1 161.8 161.8 162.2 162.2 172.4 132.1

90 183.0 183.0 183.2 183.2 190.9 171.6 176.2 176.2 176.4 176.4 181.8 168.6 168.9 168.9 169.1 169.1 172.8 165.6

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

133.1 122.0 146.7 91.2 159.9 59.0

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

125.1 118.1 137.7 87.7 149.9 55.6

80 136.5 136.5 146.5 116.0 159.5 84.1 129.5 129.5 137.5 112.5 149.6 80.7 4500
85 143.8 143.8 147.0 140.6 159.2 109.1 136.5 136.5 138.2 136.6 149.2 105.7

90 150.9 150.9 151.1 151.1 159.0 134.0 143.1 143.1 143.3 143.3 149.1 130.6

75 135.4 130.1 148.6 95.7 161.4 60.1 127.3 125.6 139.4 92.2 151.3 56.7

80 140.5 140.5 148.4 123.4 161.1 88.0 133.1 133.1 139.2 119.9 150.9 84.5 5000
85 147.9 147.9 149.4 149.4 160.7 115.7 140.1 140.1 140.6 140.6 150.5 112.3

90 154.9 154.9 155.1 155.1 160.6 143.5 146.7 146.7 146.8 146.8 150.6 140.1

75 137.5 137.1 150.2 100.3 162.7 61.1 129.3 129.3 140.7 96.7 152.4 57.7

80 143.9 143.9 150.1 130.7 162.3 91.8 136.2 136.2 140.7 127.2 152.0 88.4 5500
85 151.3 151.3 151.7 151.7 161.9 122.3 143.2 143.2 143.3 143.3 151.6 118.9

90 158.2 158.2 158.3 158.3 162.0 152.9 149.6 149.6 149.7 149.7 151.9 148.1

75 139.5 139.5 151.5 104.8 163.7 62.2 131.4 131.4 141.9 101.2 153.3 58.8

80 146.8 146.8 151.5 138.0 163.3 95.6 138.8 138.8 142.0 133.2 152.9 92.2 6000
85 154.2 154.2 154.3 154.3 162.9 128.9 145.7 145.7 145.8 145.8 152.5 125.6

Notes: 1.
2.

90 160.9 160.9 161.0 161.0 163.2 160.8 151.9 151.9 152.0 152.0 153.1 153.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

47

Performance Data

Table 32. Gross cooling capacities (kW) TTA1564DD condensing unit with TWE1564DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 45.1 38.5 49.8 29.4 54.2 19.9

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

43.2 37.6 47.7 28.6 51.9 19.1

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

41.2 36.7 45.4 27.7 49.5 18.2

7646

27 45.5 45.5 49.7 36.7 54.1 27.2 43.7 43.7 47.6 35.9 51.8 26.4 41.9 41.9 45.4 35.0 49.4 25.6 30 47.5 47.5 49.7 44.0 54.0 34.6 45.9 45.9 47.7 43.2 51.7 33.7 44.1 44.1 45.5 42.3 49.3 32.9

33 49.8 49.8 50.2 50.2 53.9 41.9 48.1 48.1 48.3 48.3 51.6 41.0 46.3 46.3 46.3 46.3 49.2 40.2

24 46.0 40.9 50.5 30.8 54.9 20.2 44.0 40.0 48.4 29.9 52.5 19.4 41.9 39.1 46.1 29.0 50.0 18.5

8495

27 46.6 46.6 50.4 38.9 54.8 28.4 44.9 44.9 48.3 38.0 52.4 27.5 43.1 43.1 46.0 37.1 49.9 26.7 30 49.0 49.0 50.5 47.0 54.7 36.5 47.3 47.3 48.4 46.2 52.3 35.7 45.4 45.4 46.2 45.0 49.8 34.8

33 51.3 51.3 51.4 51.4 54.7 44.7 49.5 49.5 49.6 49.6 52.2 43.8 47.6 47.6 47.6 47.6 49.8 43.0

24 46.7 43.3 51.1 32.1 55.5 20.6 44.7 42.4 48.9 31.3 53.0 19.7 42.6 41.2 46.6 30.4 50.4 18.8

9345

27 47.9 47.9 51.0 41.0 55.4 29.5 46.1 46.1 48.8 40.2 52.9 28.7 44.2 44.2 46.5 39.3 50.3 27.8 30 50.3 50.3 51.2 49.7 55.3 38.5 48.5 48.5 49.1 48.8 52.8 37.6 46.5 46.5 46.9 46.9 50.2 36.8

33 52.6 52.6 52.6 52.6 55.3 47.5 50.7 50.7 50.7 50.7 52.8 46.6 48.6 48.6 48.7 48.7 50.2 45.7

24 47.3 45.5 51.6 33.4 56.0 20.9 45.3 44.4 49.4 32.6 53.4 20.0 43.1 43.1 47.0 31.7 50.8 19.1

10194

27 48.9 48.9 51.5 43.2 55.9 30.7 47.1 47.1 49.3 42.3 53.3 29.8 45.1 45.1 47.0 41.4 50.6 28.9 30 51.3 51.3 51.9 51.9 55.9 40.5 49.5 49.5 49.8 49.8 53.2 39.6 47.4 47.4 47.5 47.5 50.5 38.7

33 53.6 53.6 53.7 53.7 55.9 50.3 51.6 51.6 51.7 51.7 53.3 49.4 49.5 49.5 49.6 49.6 50.6 48.5

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 39.0 35.8 43.0 26.7 46.9 17.3

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

36.7 34.6 40.4 25.7 43.9 16.3

7646

27 40.0 40.0 42.9 34.0 46.7 24.6 38.0 38.0 40.3 33.0 43.8 23.6 30 42.1 42.1 43.1 41.2 46.7 32.0 40.0 40.0 40.5 40.0 43.7 31.0

33 44.2 44.2 44.3 44.3 46.6 39.3 41.9 41.9 42.0 42.0 43.7 38.3

24 39.7 38.1 43.6 28.1 47.3 17.6 37.3 36.8 40.8 27.0 44.3 16.6

8495

27 41.2 41.2 43.5 36.2 47.2 25.8 39.0 39.0 40.8 35.1 44.2 24.8 30 43.3 43.3 43.8 43.8 47.1 33.9 41.1 41.1 41.2 41.2 44.1 32.9

33 45.4 45.4 45.5 45.5 47.1 42.0 43.0 43.0 43.0 43.0 44.1 41.1

24 40.3 40.2 44.0 29.4 47.7 17.9 37.9 37.9 41.2 28.3 44.7 16.9

9345

27 42.2 42.2 44.0 38.3 47.6 26.9 39.9 39.9 41.2 37.3 44.5 25.9 30 44.3 44.3 44.5 44.5 47.4 35.9 42.0 42.0 42.0 42.0 44.4 34.9

33 46.4 46.4 46.4 46.4 47.5 44.8 43.8 43.8 43.9 43.9 44.5 43.4

24 40.9 40.9 44.4 30.7 48.0 18.2 38.5 38.5 41.6 29.7 44.9 17.2

10194

27 43.0 43.0 44.4 40.5 47.9 28.0 40.7 40.7 41.6 39.0 44.8 27.0 30 45.2 45.2 45.2 45.2 47.7 37.8 42.7 42.7 42.7 42.7 44.7 36.8

Notes: 1.
2.

33 47.2 47.2 47.2 47.2 47.8 47.1 44.5 44.5 44.5 44.5 44.9 44.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

48

SS-PRC029Y-EN

Performance Data

Table 33. Gross cooling capacities (MBH) TTA1564DD condensing unit with TWE2014DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

154.5 143.2 170.7 106.8 185.9 68.7

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

147.9 140.2 163.4 103.9 177.6 65.9

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

140.8 137.2 155.5 100.9 169.2 63.0

80 156.9 156.9 170.4 136.2 185.5 98.4 151.0 151.0 163.0 133.4 177.2 95.6 145.0 145.0 155.2 130.3 168.8 92.7 4500
85 165.0 165.0 170.3 165.6 185.1 128.0 159.1 159.1 163.1 162.8 176.9 125.2 152.8 152.8 155.5 155.5 168.4 122.3

90 172.9 172.9 173.1 173.1 184.7 157.5 166.8 166.8 167.0 167.0 176.5 154.7 160.2 160.2 160.3 160.3 168.0 151.8

75 155.6 147.2 171.7 109.1 186.8 69.3 148.9 144.2 164.3 106.2 178.4 66.4 141.8 141.2 156.4 103.2 169.8 63.5

80 158.7 158.7 171.3 139.9 186.4 100.4 152.9 152.9 163.9 137.0 178.0 97.5 146.7 146.7 156.0 134.0 169.4 94.7 5000
85 167.0 167.0 171.4 170.7 186.0 131.4 161.0 161.0 164.2 164.2 177.6 128.5 154.5 154.5 156.5 156.5 169.1 125.7

90 174.9 174.9 175.1 175.1 185.7 162.3 168.7 168.7 168.8 168.8 177.3 159.4 161.9 161.9 162.1 162.1 168.7 156.5

75 156.6 151.2 172.6 111.4 187.6 69.8 149.9 148.3 165.1 108.5 179.2 67.0 142.7 142.7 157.1 105.5 170.4 64.1

80 160.5 160.5 172.2 143.5 187.2 102.4 154.6 154.6 164.8 140.7 178.7 99.5 148.3 148.3 156.8 137.6 170.0 96.6 5500
85 168.8 168.8 172.4 172.4 186.9 134.7 162.7 162.7 165.2 165.2 178.4 131.9 156.1 156.1 157.5 157.5 169.7 129.0

90 176.8 176.8 176.9 176.9 186.5 167.0 170.4 170.4 170.5 170.5 178.0 164.1 163.5 163.5 163.6 163.6 169.3 161.2

75 157.6 155.2 173.4 113.6 188.4 70.4 150.8 150.8 165.9 110.7 179.9 67.5 143.7 143.7 157.8 107.7 171.0 64.6

80 162.2 162.2 173.1 147.2 188.0 104.3 156.2 156.2 165.5 144.3 179.4 101.4 149.8 149.8 157.5 141.3 170.6 98.5 6000
85 170.6 170.6 173.4 173.4 187.6 138.1 164.4 164.4 166.1 166.1 179.1 135.2 157.6 157.6 158.5 158.5 170.2 132.3

90 178.5 178.5 178.6 178.6 187.3 171.7 172.0 172.0 172.1 172.1 176.5 165.3 164.9 164.9 165.1 165.1 169.9 165.9

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

133.3 133.1 147.1 97.7 159.9 59.9

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

125.3 125.3 137.8 94.2 149.8 56.5

80 138.4 138.4 146.7 127.1 159.5 89.6 131.2 131.2 137.5 123.6 149.4 86.3 4500
85 145.9 145.9 147.3 147.3 159.1 119.2 138.2 138.2 138.6 138.6 149.0 115.9

90 152.9 152.9 153.0 153.0 158.8 148.7 144.7 144.7 144.8 144.8 148.8 145.4

75 134.2 134.2 147.8 99.9 160.5 60.4 126.2 126.2 138.5 96.5 150.3 57.1

80 140.0 140.0 147.5 130.7 160.1 91.6 132.6 132.6 138.2 127.3 149.9 88.2 5000
85 147.4 147.4 148.3 148.3 159.7 122.6 139.6 139.6 139.8 139.8 149.5 119.2

90 154.4 154.4 154.6 154.6 158.0 149.0 146.1 146.1 146.2 146.2 149.4 149.3

75 135.1 135.1 148.5 102.2 161.1 61.0 127.1 127.1 139.1 98.7 150.8 57.6

80 141.5 141.5 148.1 134.4 160.7 93.5 133.9 133.9 138.7 130.9 150.3 90.1 5500
85 148.9 148.9 149.4 149.4 160.3 125.9 140.9 140.9 140.9 140.9 149.9 122.5

90 155.8 155.8 156.0 156.0 160.0 158.2 147.3 147.3 147.4 147.4 149.9 149.9

75 136.0 136.0 149.1 104.5 161.5 61.5 128.0 128.0 139.6 100.9 151.2 58.1

80 142.8 142.8 148.8 138.0 161.1 95.4 135.1 135.1 139.3 134.5 150.8 92.0 6000
85 150.3 150.3 150.5 150.5 160.7 129.2 142.1 142.1 142.2 142.2 150.4 125.8

Notes: 1.
2.

90 157.1 157.1 157.3 157.3 159.7 155.1 148.4 148.4 148.5 148.5 150.4 150.4
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

49

Performance Data

Table 34. Gross cooling capacities (kW) TTA1564DD condensing unit with TWE2014DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 45.3 42.0 50.0 31.3 54.5 20.1

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

43.3 41.1 47.9 30.5 52.1 19.3

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

41.3 40.2 45.6 29.6 49.6 18.5

7646

27 46.0 46.0 49.9 39.9 54.4 28.8 44.3 44.3 47.8 39.1 51.9 28.0 42.5 42.5 45.5 38.2 49.5 27.2 30 48.3 48.3 49.9 48.5 54.2 37.5 46.6 46.6 47.8 47.7 51.8 36.7 44.8 44.8 45.6 45.6 49.4 35.9

33 50.7 50.7 50.7 50.7 54.1 46.2 48.9 48.9 48.9 48.9 51.7 45.3 46.9 46.9 47.0 47.0 49.3 44.5

24 45.6 43.1 50.3 32.0 54.7 20.3 43.6 42.3 48.1 31.1 52.3 19.5 41.6 41.4 45.8 30.2 49.8 18.6

8495

27 46.5 46.5 50.2 41.0 54.6 29.4 44.8 44.8 48.0 40.2 52.2 28.6 43.0 43.0 45.7 39.3 49.7 27.7 30 48.9 48.9 50.2 50.0 54.5 38.5 47.2 47.2 48.1 48.1 52.1 37.7 45.3 45.3 45.9 45.9 49.5 36.8

33 51.3 51.3 51.3 51.3 54.4 47.6 49.4 49.4 49.5 49.5 52.0 46.7 47.4 47.4 47.5 47.5 49.4 45.9

24 45.9 44.3 50.6 32.6 55.0 20.5 43.9 43.5 48.4 31.8 52.5 19.6 41.8 41.8 46.0 30.9 49.9 18.8

9345

27 47.0 47.0 50.5 42.1 54.9 30.0 45.3 45.3 48.3 41.2 52.4 29.2 43.5 43.5 46.0 40.3 49.8 28.3 30 49.5 49.5 50.5 50.5 54.8 39.5 47.7 47.7 48.4 48.4 52.3 38.6 45.8 45.8 46.2 46.2 49.7 37.8

33 51.8 51.8 51.9 51.9 54.7 48.9 49.9 49.9 50.0 50.0 52.2 48.1 47.9 47.9 48.0 48.0 49.6 47.3

24 46.2 45.5 50.8 33.3 55.2 20.6 44.2 44.2 48.6 32.5 52.7 19.8 42.1 42.1 46.2 31.6 50.1 18.9

10194

27 47.5 47.5 50.7 43.1 55.1 30.6 45.8 45.8 48.5 42.3 52.6 29.7 43.9 43.9 46.2 41.4 50.0 28.9 30 50.0 50.0 50.8 50.8 55.0 40.5 48.2 48.2 48.7 48.7 52.5 39.6 46.2 46.2 46.5 46.5 49.9 38.8

33 52.3 52.3 52.4 52.4 54.9 50.3 50.4 50.4 50.4 50.4 51.7 48.4 48.3 48.3 48.4 48.4 49.8 48.6

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 39.1 39.0 43.1 28.6 46.9 17.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

36.7 36.7 40.4 27.6 43.9 16.6

7646

27 40.6 40.6 43.0 37.2 46.8 26.3 38.4 38.4 40.3 36.2 43.8 25.3 30 42.7 42.7 43.2 43.2 46.6 34.9 40.5 40.5 40.6 40.6 43.7 34.0

33 44.8 44.8 44.8 44.8 46.5 43.6 42.4 42.4 42.5 42.5 43.6 42.6

24 39.3 39.3 43.3 29.3 47.0 17.7 37.0 37.0 40.6 28.3 44.0 16.7

8495

27 41.0 41.0 43.2 38.3 46.9 26.8 38.9 38.9 40.5 37.3 43.9 25.8 30 43.2 43.2 43.5 43.5 46.8 35.9 40.9 40.9 41.0 41.0 43.8 34.9

33 45.3 45.3 45.3 45.3 46.3 43.7 42.8 42.8 42.8 42.8 43.8 43.7

24 39.6 39.6 43.5 30.0 47.2 17.9 37.2 37.2 40.8 28.9 44.2 16.9

9345

27 41.5 41.5 43.4 39.4 47.1 27.4 39.2 39.2 40.7 38.4 44.1 26.4 30 43.6 43.6 43.8 43.8 47.0 36.9 41.3 41.3 41.3 41.3 43.9 35.9

33 45.7 45.7 45.7 45.7 46.9 46.4 43.2 43.2 43.2 43.2 43.9 43.9

24 39.9 39.9 43.7 30.6 47.3 18.0 37.5 37.5 40.9 29.6 44.3 17.0

10194

27 41.9 41.9 43.6 40.4 47.2 28.0 39.6 39.6 40.8 39.4 44.2 27.0 30 44.0 44.0 44.1 44.1 47.1 37.9 41.7 41.7 41.7 41.7 44.1 36.9

Notes: 1.
2.

33 46.1 46.1 46.1 46.1 46.8 45.5 43.5 43.5 43.5 43.5 44.1 44.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

50

SS-PRC029Y-EN

Performance Data

Table 35. Gross cooling capacities (MBH) one compressor - TTA1564DC condensing unit with TWE1564DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

91.2 91.2 97.5 71.0 107.4 41.7

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

87.2 87.2 92.6 69.2 101.8 39.8

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

83.0 83.0 87.4 67.3 96.4 38.1

80 97.0 97.0 97.1 97.1 106.9 65.3 92.8 92.8 92.9 92.9 101.3 63.4 88.4 88.4 88.5 88.5 95.9 61.7 5350
85 102.5 102.5 102.6 102.6 106.6 88.9 98.2 98.2 98.2 98.2 101.1 87.1 93.6 93.6 93.7 93.7 95.8 85.4

90 108.2 108.2 108.3 108.3 108.5 108.5 103.3 103.3 103.4 103.4 103.6 103.6 98.4 98.4 98.5 98.5 98.6 98.6

75 93.4 93.4 98.4 74.9 108.4 42.7 89.2 89.2 93.4 73.1 102.5 40.8 84.8 84.8 88.3 71.2 97.0 39.1

80 99.2 99.2 99.3 99.3 107.8 68.7 94.9 94.9 95.0 95.0 102.0 66.8 90.3 90.3 90.4 90.4 96.5 65.1 5600
85 104.7 104.7 104.8 104.8 107.7 94.7 100.1 100.1 100.2 100.2 102.1 92.8 95.5 95.5 95.6 95.6 96.6 91.1

90 110.8 110.8 111.0 111.0 111.1 111.1 105.7 105.7 105.8 105.8 105.9 105.9 100.5 100.5 100.5 100.5 100.6 100.6

75 95.2 95.2 99.2 78.7 109.1 43.7 90.9 90.9 94.2 76.9 103.2 41.8 86.4 86.4 88.9 75.1 97.5 40.0

80 101.0 101.0 101.1 101.1 108.6 72.0 96.6 96.6 96.6 96.6 102.7 70.2 91.9 91.9 92.0 92.0 97.0 68.4 5850
85 106.8 106.8 106.9 106.9 108.7 100.4 101.9 101.9 101.9 101.9 102.0 102.0 97.0 97.0 97.0 97.0 97.1 97.1

90 113.1 113.1 113.2 113.2 113.3 113.3 107.7 107.7 107.8 107.8 107.9 107.9 102.2 102.2 102.3 102.3 102.4 102.4

75 96.7 96.7 99.8 82.5 109.8 44.7 92.3 92.3 94.8 80.7 103.8 42.8 87.7 87.7 89.6 78.8 98.0 40.9

80 102.5 102.5 102.6 102.6 109.2 75.3 98.0 98.0 98.1 98.1 103.2 73.4 93.3 93.3 93.3 93.3 97.4 71.6 6100
85 108.6 108.6 108.7 108.7 108.8 108.8 103.5 103.5 103.5 103.5 103.6 103.6 98.3 98.3 98.3 98.3 98.4 98.4

90 115.0 115.0 115.2 115.2 115.3 115.3 109.5 109.5 109.6 109.6 109.7 109.7 103.8 103.8 103.8 103.8 103.9 103.9

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

78.5 78.5 82.1 65.3 90.7 36.3

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

73.7 73.7 76.4 63.3 84.6 34.3

80 83.8 83.8 83.8 83.8 90.2 59.9 78.7 78.7 78.8 78.8 84.1 57.9 5350
85 88.8 88.8 88.9 88.9 90.2 83.5 83.5 83.5 83.6 83.6 83.7 83.7

90 93.2 93.2 93.3 93.3 93.4 93.4 87.7 87.7 87.8 87.8 87.9 87.9

75 80.2 80.2 82.8 69.3 91.3 37.2 75.2 75.2 77.1 67.2 85.1 35.3

80 85.5 85.5 85.6 85.6 90.8 63.2 80.3 80.3 80.4 80.4 84.6 61.3 5600
85 90.5 90.5 90.5 90.5 90.6 90.6 85.1 85.1 85.1 85.1 85.2 85.2

90 94.9 94.9 95.0 95.0 95.1 95.1 89.1 89.1 89.2 89.2 89.2 89.2

75 81.6 81.6 83.5 73.1 91.8 38.2 76.5 76.5 77.7 71.0 85.5 36.2

80 87.0 87.0 87.0 87.0 91.2 66.6 81.6 81.6 81.7 81.7 85.1 64.6 5850
85 91.8 91.8 91.9 91.9 92.0 92.0 86.3 86.3 86.4 86.4 86.4 86.4

90 96.5 96.5 96.5 96.5 96.6 96.6 90.4 90.4 90.4 90.4 90.5 90.5

75 82.8 82.8 84.1 76.8 92.1 39.1 77.6 77.6 77.6 77.6 85.8 37.2

80 88.2 88.2 88.2 88.2 91.6 69.8 82.7 82.7 82.8 82.8 85.4 67.9 6100
85 93.0 93.0 93.0 93.0 93.0 93.0 87.3 87.3 87.4 87.4 87.4 87.4

Notes: 1.
2.

90 97.8 97.8 97.8 97.8 97.9 97.9 91.5 91.5 91.5 91.5 91.6 91.6
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

51

Performance Data

Table 36. Gross cooling capacities (kW) one compressor - TTA1564DC condensing unit with TWE1564DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 26.7 26.7 28.6 20.8 31.5 12.2

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

25.6 25.6 27.1 20.3 29.8 11.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24.3 24.3 25.6 19.7 28.3 11.2

9090

27 28.4 28.4 28.5 28.5 31.3 19.1 27.2 27.2 27.2 27.2 29.7 18.6 25.9 25.9 25.9 25.9 28.1 18.1 30 30.0 30.0 30.1 30.1 31.3 26.0 28.8 28.8 28.8 28.8 29.6 25.5 27.4 27.4 27.5 27.5 28.1 25.0

33 31.7 31.7 31.7 31.7 31.8 31.8 30.3 30.3 30.3 30.3 30.4 30.4 28.8 28.8 28.9 28.9 28.9 28.9

24 27.4 27.4 28.8 22.0 31.8 12.5 26.1 26.1 27.4 21.4 30.1 12.0 24.9 24.9 25.9 20.9 28.4 11.4

9514

27 29.1 29.1 29.1 29.1 31.6 20.1 27.8 27.8 27.8 27.8 29.9 19.6 26.5 26.5 26.5 26.5 28.3 19.1 30 30.7 30.7 30.7 30.7 31.6 27.8 29.3 29.3 29.4 29.4 29.9 27.2 28.0 28.0 28.0 28.0 28.3 26.7

33 32.5 32.5 32.5 32.5 32.6 32.6 31.0 31.0 31.0 31.0 31.0 31.0 29.4 29.4 29.5 29.5 29.5 29.5

24 27.9 27.9 29.1 23.1 32.0 12.8 26.6 26.6 27.6 22.5 30.2 12.3 25.3 25.3 26.1 22.0 28.6 11.7

9939

27 29.6 29.6 29.6 29.6 31.8 21.1 28.3 28.3 28.3 28.3 30.1 20.6 26.9 26.9 27.0 27.0 28.4 20.0 30 31.3 31.3 31.3 31.3 31.9 29.4 29.9 29.9 29.9 29.9 29.9 29.9 28.4 28.4 28.4 28.4 28.5 28.5

33 33.1 33.1 33.2 33.2 33.2 33.2 31.6 31.6 31.6 31.6 31.6 31.6 30.0 30.0 30.0 30.0 30.0 30.0

24 28.3 28.3 29.3 24.2 32.2 13.1 27.1 27.1 27.8 23.6 30.4 12.5 25.7 25.7 26.2 23.1 28.7 12.0

10364

27 30.0 30.0 30.1 30.1 32.0 22.1 28.7 28.7 28.7 28.7 30.2 21.5 27.3 27.3 27.4 27.4 28.6 21.0 30 31.8 31.8 31.9 31.9 31.9 31.9 30.3 30.3 30.3 30.3 30.4 30.4 28.8 28.8 28.8 28.8 28.8 28.8

33 33.7 33.7 33.8 33.8 33.8 33.8 32.1 32.1 32.1 32.1 32.1 32.1 30.4 30.4 30.4 30.4 30.5 30.5

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 23.0 23.0 24.1 19.1 26.6 10.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

21.6 21.6 22.4 18.5 24.8 10.0

9090

27 24.5 24.5 24.6 24.6 26.4 17.5 23.1 23.1 23.1 23.1 24.7 17.0 30 26.0 26.0 26.0 26.0 26.4 24.5 24.5 24.5 24.5 24.5 24.5 24.5

33 27.3 27.3 27.3 27.3 27.4 27.4 25.7 25.7 25.7 25.7 25.8 25.8

24 23.5 23.5 24.3 20.3 26.8 10.9 22.1 22.1 22.6 19.7 24.9 10.3

9514

27 25.1 25.1 25.1 25.1 26.6 18.5 23.5 23.5 23.6 23.6 24.8 18.0 30 26.5 26.5 26.5 26.5 26.6 26.6 24.9 24.9 25.0 25.0 25.0 25.0

33 27.8 27.8 27.8 27.8 27.9 27.9 26.1 26.1 26.1 26.1 26.1 26.1

24 23.9 23.9 24.5 21.4 26.9 11.2 22.4 22.4 22.8 20.8 25.1 10.6

9939

27 25.5 25.5 25.5 25.5 26.7 19.5 23.9 23.9 23.9 23.9 24.9 18.9 30 26.9 26.9 26.9 26.9 27.0 27.0 25.3 25.3 25.3 25.3 25.3 25.3

33 28.3 28.3 28.3 28.3 28.3 28.3 26.5 26.5 26.5 26.5 26.5 26.5

24 24.3 24.3 24.6 22.5 27.0 11.5 22.7 22.7 22.8 22.8 25.2 10.9

10364

27 25.8 25.8 25.9 25.9 26.9 20.5 24.3 24.3 24.3 24.3 25.0 19.9 30 27.2 27.2 27.3 27.3 27.3 27.3 25.6 25.6 25.6 25.6 25.6 25.6

Notes: 1.
2.

33 28.7 28.7 28.7 28.7 28.7 28.7 26.8 26.8 26.8 26.8 26.8 26.8
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

52

SS-PRC029Y-EN

Performance Data

Table 37. Gross cooling capacities (MBH) TTA1564DC condensing unit with TWE1564DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

150.9 127.0 168.2 98.4 185.2 68.2

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

143.8 123.7 160.2 95.1 176.7 65.1

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

136.2 120.3 151.8 91.7 167.5 61.8

80 151.7 151.7 167.7 121.7 184.7 91.8 145.8 145.8 159.8 118.5 176.2 88.7 139.5 139.5 151.3 115.1 167.0 85.5 4500
85 160.2 160.2 167.7 145.2 184.3 115.3 154.1 154.1 159.9 142.0 175.7 112.3 147.5 147.5 151.7 138.7 166.6 109.0

90 168.6 168.6 169.5 169.3 183.8 138.8 162.3 162.3 162.5 162.5 175.3 135.7 155.5 155.5 155.7 155.7 166.3 132.5

75 153.9 134.3 170.9 102.5 187.6 69.3 146.5 131.0 162.7 99.2 178.9 66.2 138.8 127.5 154.0 95.8 169.5 62.9

80 156.9 156.9 170.4 128.3 187.1 95.3 150.7 150.7 162.2 125.0 178.4 92.2 144.0 144.0 153.6 121.6 169.0 88.9 5000
85 165.7 165.7 170.8 154.2 186.6 121.2 159.2 159.2 162.9 151.0 177.9 118.1 152.3 152.3 154.5 147.7 168.5 114.8

90 174.3 174.3 174.5 174.5 186.3 147.1 167.6 167.6 167.8 167.8 177.7 144.0 160.4 160.4 160.6 160.6 168.4 140.8

75 156.5 141.3 173.1 106.5 189.5 70.3 149.0 138.0 164.8 103.2 180.7 67.2 141.2 134.5 155.9 99.7 171.1 63.9

80 161.4 161.4 172.6 134.6 189.0 98.6 154.9 154.9 164.4 131.3 180.2 95.5 147.9 147.9 155.6 127.9 170.6 92.2 5500
85 170.3 170.3 173.6 163.1 188.5 126.9 163.6 163.6 165.6 159.9 179.7 123.8 156.3 156.3 157.2 156.6 170.1 120.5

90 179.0 179.0 179.3 179.3 188.4 155.2 172.1 172.1 172.3 172.3 179.7 152.1 164.5 164.5 164.7 164.7 170.3 148.8

75 158.8 148.2 174.9 110.4 191.1 71.2 149.5 149.5 166.5 107.1 182.1 68.1 142.6 142.6 157.4 103.6 172.4 64.9

80 165.3 165.3 174.6 140.8 190.6 101.9 158.5 158.5 166.2 137.5 181.6 98.8 151.3 151.3 157.3 134.1 171.9 95.5 6000
85 174.4 174.4 176.1 171.7 190.1 132.4 167.4 167.4 168.2 168.2 181.1 129.3 159.8 159.8 160.0 160.0 171.4 126.0

90 183.1 183.1 183.3 183.3 190.2 163.0 175.9 175.9 176.1 176.1 181.4 160.0 168.0 168.0 168.2 168.2 171.9 156.7

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

128.3 116.7 142.9 88.1 157.8 58.4

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

120.0 113.0 133.4 84.4 147.1 54.7

80 132.8 132.8 142.4 111.5 157.3 82.0 125.5 125.5 133.0 107.8 146.7 78.3 4500
85 140.5 140.5 143.1 135.2 156.8 105.5 132.9 132.9 134.0 131.6 146.2 101.9

90 148.1 148.1 148.4 148.4 156.6 129.1 140.1 140.1 140.3 140.3 146.1 125.4

75 130.8 124.0 144.9 92.2 159.5 59.4 121.7 121.7 135.1 88.4 148.6 55.7

80 136.9 136.9 144.6 118.0 159.0 85.5 129.3 129.3 134.9 114.3 148.2 81.7 5000
85 144.9 144.9 145.9 144.3 158.6 111.4 136.8 136.8 137.0 137.0 147.7 107.7

90 152.6 152.6 152.8 152.8 158.6 137.4 144.1 144.1 144.2 144.2 147.9 133.7

75 132.3 132.3 146.5 96.1 160.9 60.4 124.7 124.7 136.5 92.3 149.9 56.7

80 140.5 140.5 146.4 124.3 160.5 88.8 132.5 132.5 136.5 120.6 149.4 85.1 5500
85 148.6 148.6 148.7 148.7 160.0 117.0 140.1 140.1 140.3 140.3 149.0 113.3

90 156.4 156.4 156.5 156.5 160.3 145.4 147.3 147.3 147.5 147.5 149.6 141.8

75 135.2 135.2 147.9 99.9 162.1 61.4 127.3 127.3 137.7 96.1 150.9 57.7

80 143.6 143.6 148.0 130.5 161.6 92.0 135.2 135.2 138.0 126.8 150.4 88.3 6000
85 151.8 151.8 151.9 151.9 161.2 122.6 142.9 142.9 143.1 143.1 150.0 118.9

Notes: 1.
2.

90 159.5 159.5 159.7 159.7 161.9 153.3 150.1 150.1 150.2 150.2 151.1 149.7
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

53

Performance Data

Table 38. Gross cooling capacities (kW) TTA1564DC condensing unit with TWE1564DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 44.2 37.2 49.3 28.8 54.3 20.0

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

42.1 36.3 47.0 27.9 51.8 19.1

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

39.9 35.3 44.5 26.9 49.1 18.1

7646

27 44.5 44.5 49.1 35.7 54.1 26.9 42.7 42.7 46.8 34.7 51.6 26.0 40.9 40.9 44.3 33.7 49.0 25.0 30 47.0 47.0 49.1 42.6 54.0 33.8 45.2 45.2 46.9 41.6 51.5 32.9 43.2 43.2 44.5 40.6 48.8 31.9

33 49.4 49.4 49.7 49.6 53.9 40.7 47.6 47.6 47.6 47.6 51.4 39.8 45.6 45.6 45.6 45.6 48.7 38.8

24 45.1 39.4 50.1 30.0 55.0 20.3 43.0 38.4 47.7 29.1 52.4 19.4 40.7 37.4 45.1 28.1 49.7 18.4

8495

27 46.0 46.0 49.9 37.6 54.8 27.9 44.2 44.2 47.5 36.6 52.3 27.0 42.2 42.2 45.0 35.6 49.5 26.1 30 48.6 48.6 50.1 45.2 54.7 35.5 46.7 46.7 47.7 44.3 52.1 34.6 44.6 44.6 45.3 43.3 49.4 33.6

33 51.1 51.1 51.2 51.2 54.6 43.1 49.1 49.1 49.2 49.2 52.1 42.2 47.0 47.0 47.1 47.1 49.4 41.3

24 45.9 41.4 50.7 31.2 55.5 20.6 43.7 40.4 48.3 30.3 52.9 19.7 41.4 39.4 45.7 29.2 50.1 18.7

9345

27 47.3 47.3 50.6 39.4 55.4 28.9 45.4 45.4 48.2 38.5 52.8 28.0 43.3 43.3 45.6 37.5 50.0 27.0 30 49.9 49.9 50.9 47.8 55.3 37.2 47.9 47.9 48.5 46.9 52.7 36.3 45.8 45.8 46.1 45.9 49.9 35.3

33 52.5 52.5 52.5 52.5 55.2 45.5 50.4 50.4 50.5 50.5 52.7 44.6 48.2 48.2 48.3 48.3 49.9 43.6

24 46.5 43.4 51.3 32.3 56.0 20.9 43.8 43.8 48.8 31.4 53.4 20.0 41.8 41.8 46.1 30.4 50.5 19.0

10194

27 48.4 48.4 51.2 41.3 55.9 29.9 46.5 46.5 48.7 40.3 53.2 29.0 44.3 44.3 46.1 39.3 50.4 28.0 30 51.1 51.1 51.6 50.3 55.7 38.8 49.1 49.1 49.3 49.3 53.1 37.9 46.8 46.8 46.9 46.9 50.2 36.9

33 53.7 53.7 53.7 53.7 55.8 47.8 51.5 51.5 51.6 51.6 53.2 46.9 49.2 49.2 49.3 49.3 50.4 45.9

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 37.6 34.2 41.9 25.8 46.2 17.1

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

35.2 33.1 39.1 24.7 43.1 16.0

7646

27 38.9 38.9 41.7 32.7 46.1 24.0 36.8 36.8 39.0 31.6 43.0 23.0 30 41.2 41.2 41.9 39.6 46.0 30.9 38.9 38.9 39.3 38.6 42.8 29.9

33 43.4 43.4 43.5 43.5 45.9 37.8 41.1 41.1 41.1 41.1 42.8 36.8

24 38.3 36.3 42.5 27.0 46.8 17.4 35.7 35.7 39.6 25.9 43.6 16.3

8495

27 40.1 40.1 42.4 34.6 46.6 25.0 37.9 37.9 39.5 33.5 43.4 24.0 30 42.5 42.5 42.7 42.3 46.5 32.6 40.1 40.1 40.1 40.1 43.3 31.6

33 44.7 44.7 44.8 44.8 46.5 40.3 42.2 42.2 42.3 42.3 43.4 39.2

24 38.8 38.8 42.9 28.2 47.2 17.7 36.5 36.5 40.0 27.1 43.9 16.6

9345

27 41.2 41.2 42.9 36.4 47.0 26.0 38.8 38.8 40.0 35.3 43.8 24.9 30 43.5 43.5 43.6 43.6 46.9 34.3 41.1 41.1 41.1 41.1 43.7 33.2

33 45.8 45.8 45.9 45.9 47.0 42.6 43.2 43.2 43.2 43.2 43.8 41.6

24 39.6 39.6 43.3 29.3 47.5 18.0 37.3 37.3 40.4 28.2 44.2 16.9

10194

27 42.1 42.1 43.4 38.2 47.4 27.0 39.6 39.6 40.4 37.2 44.1 25.9 30 44.5 44.5 44.5 44.5 47.2 35.9 41.9 41.9 41.9 41.9 44.0 34.9

Notes: 1.
2.

33 46.7 46.7 46.8 46.8 47.5 44.9 44.0 44.0 44.0 44.0 44.3 43.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

54

SS-PRC029Y-EN

Performance Data

Table 39. Gross cooling capacities (MBH) TTA2014DD condensing unit with TWE2014DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

CFM

Ent DB (°F)
75

85 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

199.9 160.5 217.3 124.2 233.7 86.3

95 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

190.8 156.2 207.2 119.9 221.5 81.8

105 Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

181.2 151.5 196.4 115.4 208.5 77.1

80 197.4 197.4 217.1 152.1 233.5 114.2 190.0 190.0 207.0 147.8 221.2 109.7 181.9 181.9 196.1 143.3 208.3 105.0 6000
85 206.7 206.7 216.9 179.5 233.3 142.1 198.8 198.8 206.8 175.2 221.0 137.6 190.2 190.2 196.1 170.6 208.0 132.9

90 215.2 215.2 215.4 215.4 233.0 170.2 206.8 206.8 206.9 206.9 220.8 165.6 197.3 197.3 197.4 197.4 207.8 160.8

75 203.1 167.9 219.8 128.2 236.6 87.4 191.0 171.4 209.3 124.0 223.9 82.9 181.9 164.8 198.2 119.4 210.4 78.1

80 203.1 203.1 219.5 158.6 236.4 117.9 195.2 195.2 209.1 154.5 223.6 113.3 186.6 186.6 197.9 149.9 210.1 108.5 6680
85 212.2 212.2 219.4 188.5 236.2 148.3 203.8 203.8 209.1 184.1 223.3 144.0 194.6 194.6 198.0 179.5 209.8 139.2

90 220.2 220.2 220.4 220.4 235.9 178.8 210.9 210.9 211.1 211.1 223.2 174.1 200.9 200.9 201.0 201.0 206.6 180.3

75 203.1 183.0 221.7 132.1 239.0 88.5 194.3 176.7 210.9 127.7 225.8 83.8 184.9 169.9 199.5 123.1 211.8 79.0

80 207.7 207.7 221.5 164.8 238.7 121.4 199.5 199.5 210.7 160.5 225.5 116.7 190.4 190.4 199.2 155.9 211.6 111.8 7350
85 216.6 216.6 221.5 197.0 238.4 154.5 207.6 207.6 210.9 192.6 225.2 149.8 197.8 197.8 199.6 188.0 211.3 145.1

90 224.5 224.5 224.6 224.6 238.3 186.9 214.7 214.7 214.8 214.8 221.5 193.9 204.0 204.0 204.1 204.1 209.1 185.8

75 206.2 188.1 223.6 135.9 240.9 89.5 193.9 193.9 212.5 131.5 227.4 84.8 185.1 185.1 200.7 127.3 213.0 79.8

80 211.7 211.7 223.4 171.1 240.7 124.7 203.0 203.0 212.2 166.5 227.1 120.0 193.6 193.6 198.0 173.8 212.8 115.1 8030
85 220.1 220.1 223.7 205.5 240.4 160.5 210.6 210.6 212.8 201.1 226.8 155.6 200.3 200.3 201.3 196.1 212.5 150.6

90 228.5 228.5 228.7 228.7 236.4 207.2 218.3 218.3 218.5 218.5 224.2 199.4 207.2 207.2 207.3 207.3 207.5 207.5

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

169.0 152.5 184.7 110.7 194.5 72.2

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

158.9 145.3 171.9 105.6 179.0 66.7

80 173.2 173.2 184.5 138.7 194.3 100.1 163.5 163.5 171.6 133.4 178.7 94.7 6000
85 180.8 180.8 184.5 165.8 194.0 128.2 170.0 170.0 171.9 160.6 178.4 122.7

90 186.7 186.7 186.7 186.7 193.8 155.7 174.3 174.3 174.4 174.4 177.0 157.3

75 172.3 157.9 186.1 114.6 195.9 73.0 159.5 159.5 172.9 109.4 179.7 67.5

80 177.3 177.3 185.9 145.0 195.6 103.5 166.9 166.9 172.7 139.6 179.5 98.0 6680
85 184.3 184.3 186.2 174.7 195.3 134.4 172.6 172.6 173.2 168.7 179.2 128.7

90 189.6 189.6 189.7 189.7 193.5 171.9 176.4 176.4 176.4 176.4 178.6 162.3

75 172.6 172.6 187.2 118.3 196.9 73.8 162.6 162.6 173.7 113.4 180.2 68.2

80 180.6 180.6 186.9 150.9 196.6 106.7 169.5 169.5 172.3 153.6 180.0 101.1 7350
85 186.8 186.8 187.6 182.8 196.3 139.8 174.3 174.3 174.4 172.2 179.7 134.0

90 192.2 192.2 192.3 192.3 192.4 192.4 178.3 178.3 178.3 178.3 178.4 178.4

75 175.6 175.6 188.1 122.3 197.6 74.6 165.1 165.1 174.4 117.3 180.6 69.0

80 183.2 183.2 186.4 165.9 197.4 109.9 171.5 171.5 173.4 157.2 180.3 104.7 8030
85 188.9 188.8 189.0 186.0 197.1 145.2 175.8 175.8 175.6 175.6 180.0 139.3

Notes: 1.
2.

90 194.7 194.7 194.7 194.7 194.8 194.8 179.5 179.5 179.5 179.5 179.5 179.5
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

55

Performance Data

Table 40. Gross cooling capacities (kW) TTA2014DD condensing unit with TWE2014DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 58.6 47.0 63.7 36.4 68.5 25.3

35 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

55.9 45.8 60.7 35.2 64.9 24.0

40 Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

53.1 44.4 57.6 33.8 61.1 22.6

10194

27 57.9 57.9 63.6 44.6 68.4 33.5 55.7 55.7 60.7 43.3 64.8 32.2 53.3 53.3 57.5 42.0 61.0 30.8 30 60.6 60.6 63.6 52.6 68.4 41.6 58.3 58.3 60.6 51.3 64.8 40.3 55.7 55.7 57.5 50.0 61.0 38.9

33 63.1 63.1 63.1 63.1 68.3 49.9 60.6 60.6 60.6 60.6 64.7 48.5 57.8 57.8 57.9 57.9 60.9 47.1

24 59.5 49.2 64.4 37.6 69.4 25.6 56.0 50.2 61.4 36.3 65.6 24.3 53.3 48.3 58.1 35.0 61.7 22.9

11349

27 59.5 59.5 64.3 46.5 69.3 34.6 57.2 57.2 61.3 45.3 65.5 33.2 54.7 54.7 58.0 43.9 61.6 31.8 30 62.2 62.2 64.3 55.2 69.2 43.5 59.7 59.7 61.3 54.0 65.5 42.2 57.0 57.0 58.0 52.6 61.5 40.8

33 64.5 64.5 64.6 64.6 69.1 52.4 61.8 61.8 61.9 61.9 65.4 51.0 58.9 58.9 58.9 58.9 60.5 52.8

24 59.5 53.6 65.0 38.7 70.0 25.9 57.0 51.8 61.8 37.4 66.2 24.6 54.2 49.8 58.5 36.1 62.1 23.1

12488

27 60.9 60.9 64.9 48.3 70.0 35.6 58.5 58.5 61.7 47.0 66.1 34.2 55.8 55.8 58.4 45.7 62.0 32.8 30 63.5 63.5 64.9 57.7 69.9 45.3 60.9 60.9 61.8 56.4 66.0 43.9 58.0 58.0 58.5 55.1 61.9 42.5

33 65.8 65.8 65.8 65.8 69.8 54.8 62.9 62.9 63.0 63.0 64.9 56.8 59.8 59.8 59.8 59.8 61.3 54.5

24 60.4 55.1 65.5 39.8 70.6 26.2 56.8 56.8 62.3 38.5 66.6 24.8 54.2 54.2 58.8 37.3 62.4 23.4

13643

27 62.0 62.0 65.5 50.1 70.5 36.6 59.5 59.5 62.2 48.8 66.6 35.2 56.7 56.7 58.0 50.9 62.4 33.7 30 64.5 64.5 65.6 60.2 70.4 47.0 61.7 61.7 62.4 58.9 66.5 45.6 58.7 58.7 59.0 57.5 62.3 44.1

33 67.0 67.0 67.0 67.0 69.3 60.7 64.0 64.0 64.0 64.0 65.7 58.4 60.7 60.7 60.8 60.8 60.8 60.8

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 49.5 44.7 54.1 32.4 57.0 21.1

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

46.6 42.6 50.4 30.9 52.4 19.6

10194

27 50.8 50.8 54.1 40.6 56.9 29.3 47.9 47.9 50.3 39.1 52.4 27.7 30 53.0 53.0 54.1 48.6 56.9 37.6 49.8 49.8 50.4 47.1 52.3 36.0

33 54.7 54.7 54.7 54.7 56.8 45.6 51.1 51.1 51.1 51.1 51.9 46.1

24 50.5 46.3 54.6 33.6 57.4 21.4 46.8 46.8 50.7 32.1 52.7 19.8

11349

27 52.0 52.0 54.5 42.5 57.3 30.3 48.9 48.9 50.6 40.9 52.6 28.7 30 54.0 54.0 54.6 51.2 57.2 39.4 50.6 50.6 50.8 49.5 52.5 37.7

33 55.6 55.6 55.6 55.6 56.7 50.4 51.7 51.7 51.7 51.7 52.3 47.6

24 50.6 50.6 54.9 34.7 57.7 21.6 47.6 47.6 50.9 33.2 52.8 20.0

12488

27 52.9 52.9 54.8 44.2 57.6 31.3 49.7 49.7 50.5 45.0 52.7 29.6 30 54.7 54.7 55.0 53.6 57.5 41.0 51.1 51.1 51.1 50.5 52.7 39.3

33 56.3 56.3 56.4 56.4 56.4 56.4 52.3 52.3 52.3 52.3 52.3 52.3

24 51.5 51.5 55.1 35.8 57.9 21.9 48.4 48.4 51.1 34.4 52.9 20.2

13643

27 53.7 53.7 54.6 48.6 57.8 32.2 50.3 50.3 50.8 46.1 52.8 30.7 30 55.3 55.3 55.4 54.5 57.8 42.5 51.5 51.5 51.5 51.5 52.7 40.8

Notes: 1.
2.

33 57.1 57.1 57.1 57.1 57.1 57.1 52.6 52.6 52.6 52.6 52.6 52.6
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

56

SS-PRC029Y-EN

Performance Data

Table 41. Gross cooling capacities (MBH) one compressor - TTA2014DC condensing unit with TWE2014DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

130.6 130.6 144.4 94.8 157.6 59.4

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

125.3 125.3 137.5 92.2 150.3 56.9

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

119.4 119.4 129.8 89.3 142.0 54.2

80 138.6 138.6 144.1 122.2 157.3 87.3 133.1 133.1 137.3 119.5 149.9 84.8 126.8 126.8 126.9 126.9 141.6 82.1 6000
85 146.5 146.5 146.4 146.4 156.9 115.1 140.7 140.7 140.8 140.8 149.5 112.6 134.1 134.1 134.2 134.2 141.3 109.9

90 153.7 153.7 153.9 153.9 156.8 142.4 147.6 147.6 147.7 147.7 149.6 139.8 140.6 140.6 140.7 140.7 141.6 137.0

75 133.8 133.8 145.9 99.1 158.7 60.4 128.3 128.3 138.9 96.4 151.3 57.9 122.1 122.1 131.1 93.5 142.9 55.2

80 142.0 142.0 142.1 142.1 158.3 90.9 136.2 136.2 136.3 136.3 150.9 88.4 129.7 129.7 129.8 129.8 142.5 85.6 6680
85 149.9 149.9 150.0 150.0 157.9 121.2 143.8 143.8 143.9 143.9 150.5 118.7 136.9 136.9 137.0 137.0 142.1 115.9

90 156.7 156.7 156.8 156.8 158.1 150.8 150.3 150.3 150.3 150.3 150.9 148.3 142.8 142.8 142.8 142.8 142.9 142.9

75 136.5 136.5 147.2 103.1 159.6 61.4 130.8 130.8 140.1 100.4 152.1 58.9 124.4 124.4 132.2 97.5 143.6 56.1

80 144.8 144.8 144.9 144.9 159.2 94.2 138.8 138.8 138.9 138.9 151.6 91.7 132.1 132.1 132.2 132.2 143.2 89.0 7350
85 152.6 152.6 152.7 152.7 158.7 126.9 146.3 146.3 146.4 146.4 151.2 124.4 139.2 139.2 139.3 139.3 142.8 121.7

90 158.9 158.9 158.9 158.9 159.2 158.8 152.1 152.1 152.1 152.1 152.0 152.0 144.1 144.1 144.1 144.1 144.1 144.1

75 138.9 138.9 148.3 107.0 160.3 62.3 133.0 133.0 141.1 104.3 152.7 59.8 126.4 126.4 133.0 101.4 144.2 57.1

80 147.3 147.3 147.4 147.4 159.8 97.5 141.1 141.1 141.2 141.2 152.3 95.0 134.1 134.1 134.2 134.2 143.7 92.3 8030
85 154.9 154.9 155.0 155.0 159.3 132.5 148.4 148.4 148.5 148.5 148.5 148.5 141.0 141.0 141.1 141.1 141.1 141.1

90 160.3 160.3 160.3 160.3 160.2 160.2 153.1 153.1 153.1 153.1 153.1 153.1 144.7 144.7 144.7 144.7 144.7 144.7

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

113.0 113.0 121.6 86.2 132.9 51.2

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

106.6 106.6 113.3 83.1 123.5 48.1

80 120.0 120.0 120.1 120.1 132.6 79.1 113.0 113.0 113.0 113.0 123.1 76.0 6000
85 126.9 126.9 127.0 127.0 132.2 106.9 119.2 119.2 119.3 119.3 122.8 103.8

90 132.7 132.7 132.7 132.7 132.9 132.9 124.0 124.0 124.0 124.0 124.0 124.0

75 115.4 115.4 122.7 90.4 133.7 52.2 108.7 108.7 114.2 87.3 124.1 49.1

80 122.6 122.6 122.7 122.7 133.4 82.6 115.2 115.2 115.3 115.3 123.7 79.5 6680
85 129.4 129.4 129.4 129.4 133.0 113.0 121.3 121.3 121.3 121.3 121.4 121.4

90 134.3 134.3 134.3 134.3 134.4 134.4 124.7 124.7 124.7 124.7 124.7 124.7

75 117.5 117.5 123.7 94.4 134.3 53.2 110.4 110.4 115.0 91.2 124.7 50.1

80 124.7 124.7 124.8 124.8 133.9 86.0 117.1 117.1 117.1 117.1 124.2 82.9 7350
85 131.3 131.3 131.4 131.4 131.4 131.4 122.8 122.8 122.9 122.9 122.9 122.9

90 135.0 135.0 135.0 135.0 134.9 134.9 124.6 124.6 124.5 124.5 124.5 124.5

75 119.3 119.3 124.4 98.2 134.9 54.1 111.9 111.9 115.7 94.5 125.1 51.0

80 126.6 126.6 126.6 126.6 134.4 89.3 118.6 118.6 118.7 118.7 124.6 86.2 8030
85 132.8 132.8 132.8 132.8 132.9 132.9 123.9 123.9 123.9 123.9 124.0 124.0

Notes: 1.
2.

90 135.4 135.4 135.4 135.4 135.4 135.4 124.9 124.9 124.9 124.9 124.9 124.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

57

Performance Data

Table 42. Gross cooling capacities (kW) one compressor - TTA2014DC condensing unit with TWE2014DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 38.3 38.3 42.3 27.8 46.2 17.4

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

36.7 36.7 40.3 27.0 44.0 16.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

35.0 35.0 38.0 26.2 41.6 15.9

10194

27 40.6 40.6 42.2 35.8 46.1 25.6 39.0 39.0 40.2 35.0 43.9 24.9 37.2 37.2 37.2 37.2 41.5 24.0 30 42.9 42.9 42.9 42.9 46.0 33.7 41.2 41.2 41.2 41.2 43.8 33.0 39.3 39.3 39.3 39.3 41.4 32.2

33 45.0 45.0 45.1 45.1 45.9 41.7 43.2 43.2 43.3 43.3 43.8 41.0 41.2 41.2 41.2 41.2 41.5 40.1

24 39.2 39.2 42.8 29.0 46.5 17.7 37.6 37.6 40.7 28.3 44.3 17.0 35.8 35.8 38.4 27.4 41.9 16.2

11349

27 41.6 41.6 41.6 41.6 46.4 26.6 39.9 39.9 39.9 39.9 44.2 25.9 38.0 38.0 38.0 38.0 41.8 25.1 30 43.9 43.9 43.9 43.9 46.3 35.5 42.1 42.1 42.2 42.2 44.1 34.8 40.1 40.1 40.1 40.1 41.6 34.0

33 45.9 45.9 46.0 46.0 46.3 44.2 44.0 44.0 44.0 44.0 44.2 43.4 41.8 41.8 41.9 41.9 41.9 41.9

24 40.0 40.0 43.1 30.2 46.8 18.0 38.3 38.3 41.0 29.4 44.6 17.3 36.4 36.4 38.7 28.6 42.1 16.5

12488

27 42.4 42.4 42.5 42.5 46.6 27.6 40.7 40.7 40.7 40.7 44.4 26.9 38.7 38.7 38.7 38.7 42.0 26.1 30 44.7 44.7 44.7 44.7 46.5 37.2 42.9 42.9 42.9 42.9 44.3 36.5 40.8 40.8 40.8 40.8 41.8 35.7

33 46.5 46.5 46.6 46.6 46.6 46.5 44.6 44.6 44.6 44.6 44.5 44.5 42.2 42.2 42.2 42.2 42.2 42.2

24 40.7 40.7 43.4 31.3 47.0 18.2 39.0 39.0 41.3 30.6 44.7 17.5 37.0 37.0 39.0 29.7 42.2 16.7

13643

27 43.1 43.1 43.2 43.2 46.8 28.6 41.3 41.3 41.4 41.4 44.6 27.8 39.3 39.3 39.3 39.3 42.1 27.0 30 45.4 45.4 45.4 45.4 46.7 38.8 43.5 43.5 43.5 43.5 43.5 43.5 41.3 41.3 41.3 41.3 41.3 41.3

33 47.0 47.0 47.0 47.0 46.9 46.9 44.9 44.9 44.9 44.9 44.9 44.9 42.4 42.4 42.4 42.4 42.4 42.4

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 33.1 33.1 35.6 25.3 38.9 15.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

31.2 31.2 33.2 24.4 36.2 14.1

10194

27 35.2 35.2 35.2 35.2 38.8 23.2 33.1 33.1 33.1 33.1 36.1 22.3 30 37.2 37.2 37.2 37.2 38.7 31.3 34.9 34.9 35.0 35.0 36.0 30.4

33 38.9 38.9 38.9 38.9 38.9 38.9 36.3 36.3 36.3 36.3 36.3 36.3

24 33.8 33.8 36.0 26.5 39.2 15.3 31.8 31.8 33.5 25.6 36.4 14.4

11349

27 35.9 35.9 35.9 35.9 39.1 24.2 33.8 33.8 33.8 33.8 36.3 23.3 30 37.9 37.9 37.9 37.9 39.0 33.1 35.5 35.5 35.6 35.6 35.6 35.6

33 39.4 39.4 39.4 39.4 39.4 39.4 36.5 36.5 36.5 36.5 36.5 36.5

24 34.4 34.4 36.2 27.6 39.4 15.6 32.4 32.4 33.7 26.7 36.5 14.7

12488

27 36.5 36.5 36.6 36.6 39.2 25.2 34.3 34.3 34.3 34.3 36.4 24.3 30 38.5 38.5 38.5 38.5 38.5 38.5 36.0 36.0 36.0 36.0 36.0 36.0

33 39.6 39.6 39.5 39.5 39.5 39.5 36.5 36.5 36.5 36.5 36.5 36.5

24 34.9 34.9 36.5 28.8 39.5 15.8 32.8 32.8 33.9 27.7 36.6 14.9

13643

27 37.1 37.1 37.1 37.1 39.4 26.2 34.8 34.8 34.8 34.8 36.5 25.2 30 38.9 38.9 38.9 38.9 38.9 38.9 36.3 36.3 36.3 36.3 36.3 36.3

Notes: 1.
2.

33 39.7 39.7 39.7 39.7 39.7 39.7 36.6 36.6 36.6 36.6 36.6 36.6
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

58

SS-PRC029Y-EN

Performance Data

Table 43. Gross cooling capacities (MBH) both compressors - TTA2014DC condensing unit with TWE2014DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

211.1 166.1 230.8 129.9 247.2 91.2

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

201.5 161.3 219.9 125.1 233.8 86.2

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

190.9 156.2 207.5 119.9 219.1 80.8

80 206.7 206.7 230.5 157.5 246.8 119.1 198.8 198.8 219.5 152.8 233.5 114.1 190.1 190.1 207.2 147.6 218.7 108.7 6000
85 216.7 216.7 230.2 185.3 246.5 146.9 208.4 208.4 219.2 180.5 233.1 141.9 199.0 199.0 206.8 175.2 218.4 136.5

90 226.1 226.1 230.5 212.5 246.0 175.4 217.1 217.1 219.7 207.8 232.7 170.2 206.8 206.8 207.7 202.6 218.0 164.6

75 215.0 173.4 233.8 134.0 250.3 92.3 204.9 168.8 222.3 129.2 236.3 87.2 193.9 163.5 209.5 123.9 220.9 81.6

80 213.1 213.1 233.4 164.2 249.9 122.8 204.7 204.7 222.0 159.4 235.9 117.6 195.4 195.4 209.2 154.1 220.5 112.1 6680
85 223.1 223.1 233.1 194.3 249.6 153.1 214.1 214.1 221.7 189.4 235.3 148.7 203.9 203.9 208.9 184.0 220.2 142.4

90 232.0 232.0 233.9 224.2 249.1 183.9 222.2 222.2 222.9 219.4 235.2 178.6 210.7 210.7 210.5 210.5 219.8 172.9

75 218.0 180.6 236.0 137.8 252.8 93.3 207.7 175.8 224.2 133.0 238.3 88.1 196.3 170.6 211.0 127.6 222.3 82.4

80 218.4 218.4 235.6 170.4 252.4 126.2 209.6 209.6 223.9 165.6 237.9 121.0 199.7 199.7 210.6 160.2 221.9 115.3 7350
85 228.2 228.2 235.3 202.8 252.0 158.9 218.7 218.7 223.6 197.8 237.5 153.7 207.7 207.7 210.6 192.4 221.5 148.1

90 236.5 236.5 236.8 235.3 251.6 191.9 225.7 225.7 225.6 225.6 237.1 186.5 213.3 213.3 213.4 213.4 221.2 180.7

75 220.6 187.5 237.7 141.5 254.8 94.3 210.0 182.7 225.7 136.7 239.8 89.0 194.1 194.1 212.1 131.3 223.3 83.2

80 223.0 223.0 237.4 176.5 254.4 129.5 213.7 213.7 225.3 171.9 239.4 124.2 203.2 203.2 211.7 166.2 223.0 118.5 8030
85 232.4 232.4 237.2 211.0 254.1 164.6 222.3 222.3 225.2 206.0 239.1 159.3 210.5 210.5 211.8 200.5 222.6 153.6

90 240.1 240.1 239.8 239.8 253.7 199.8 229.1 229.1 229.2 229.2 238.7 194.3 216.4 216.4 216.5 216.5 222.2 188.3

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

179.6 150.8 194.3 114.4 203.1 75.0

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

168.4 145.5 180.7 108.9 186.2 69.1

80 180.6 180.6 193.9 142.1 202.7 102.9 170.9 170.9 180.3 137.0 185.9 97.0 6000
85 188.6 188.6 193.6 169.5 202.4 130.7 177.6 177.6 180.1 163.8 185.5 124.8

90 195.0 195.0 194.9 194.9 202.0 158.7 181.6 181.6 181.6 181.6 185.1 152.5

75 182.2 158.2 195.8 118.3 204.2 75.7 167.0 167.0 181.7 112.7 186.7 69.7

80 185.2 185.2 195.4 148.5 203.8 106.2 174.6 174.6 181.3 142.9 186.3 100.1 6680
85 192.6 192.6 195.3 178.3 203.5 136.5 180.3 180.3 181.2 172.4 185.9 130.4

90 197.2 197.2 197.2 197.2 203.1 166.7 183.1 183.1 183.1 183.1 185.4 160.4

75 180.4 180.4 196.9 122.0 205.0 76.4 170.3 170.3 182.4 116.3 186.8 70.3

80 188.8 188.8 196.5 154.6 204.6 109.3 177.4 177.4 181.9 148.9 186.5 103.1 7350
85 195.4 195.4 196.5 186.5 204.2 142.0 181.8 181.8 181.9 180.5 186.0 135.8

90 199.8 199.8 199.9 199.9 203.8 174.4 184.8 184.8 184.8 184.8 185.4 167.8

75 183.7 183.7 197.7 125.6 205.5 77.1 173.0 173.0 182.8 119.8 186.9 70.8

80 191.8 191.8 197.2 160.4 205.2 112.4 179.6 179.6 182.3 154.4 186.5 106.1 8030
85 197.1 197.1 197.3 194.5 204.7 147.4 182.7 182.7 182.6 182.6 185.9 141.1

Notes: 1.
2.

90 202.1 202.1 202.2 202.2 204.3 181.9 185.4 185.4 185.4 185.4 185.1 175.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

59

Performance Data

Table 44. Gross cooling capacities (kW) both compressors - TTA2014DC condensing unit with TWE2014DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 61.9 48.7 67.6 38.0 72.4 26.7

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

59.0 47.3 64.4 36.7 68.5 25.3

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

55.9 45.8 60.8 35.1 64.2 23.7

10194

27 60.6 60.6 67.5 46.2 72.3 34.9 58.3 58.3 64.3 44.8 68.4 33.4 55.7 55.7 60.7 43.2 64.1 31.8 30 63.5 63.5 67.4 54.3 72.2 43.1 61.1 61.1 64.2 52.9 68.3 41.6 58.3 58.3 60.6 51.3 64.0 40.0

33 66.2 66.2 67.5 62.3 72.1 51.4 63.6 63.6 64.4 60.9 68.2 49.9 60.6 60.6 60.9 59.4 63.9 48.2

24 63.0 50.8 68.5 39.3 73.3 27.1 60.0 49.5 65.1 37.9 69.2 25.5 56.8 47.9 61.4 36.3 64.7 23.9

11349

27 62.4 62.4 68.4 48.1 73.2 36.0 60.0 60.0 65.0 46.7 69.1 34.5 57.2 57.2 61.3 45.2 64.6 32.8 30 65.4 65.4 68.3 56.9 73.1 44.9 62.7 62.7 65.0 55.5 68.9 43.6 59.8 59.8 61.2 53.9 64.5 41.7

33 68.0 68.0 68.5 65.7 73.0 53.9 65.1 65.1 65.3 64.3 68.9 52.3 61.7 61.7 61.7 61.7 64.4 50.7

24 63.9 52.9 69.1 40.4 74.1 27.3 60.8 51.5 65.7 39.0 69.8 25.8 57.5 50.0 61.8 37.4 65.1 24.2

12488

27 64.0 64.0 69.0 49.9 74.0 37.0 61.4 61.4 65.6 48.5 69.7 35.4 58.5 58.5 61.7 46.9 65.0 33.8 30 66.9 66.9 68.9 59.4 73.8 46.6 64.1 64.1 65.5 58.0 69.6 45.0 60.9 60.9 61.7 56.4 64.9 43.4

33 69.3 69.3 69.4 68.9 73.7 56.2 66.1 66.1 66.1 66.1 69.5 54.7 62.5 62.5 62.5 62.5 64.8 52.9

24 64.6 54.9 69.7 41.5 74.7 27.6 61.5 53.5 66.1 40.0 70.3 26.1 56.9 56.9 62.2 38.5 65.4 24.4

13643

27 65.3 65.3 69.6 51.7 74.6 37.9 62.6 62.6 66.0 50.4 70.2 36.4 59.5 59.5 62.0 48.7 65.3 34.7 30 68.1 68.1 69.5 61.8 74.4 48.2 65.1 65.1 66.0 60.4 70.0 46.7 61.7 61.7 62.1 58.7 65.2 45.0

33 70.4 70.4 70.3 70.3 74.3 58.5 67.1 67.1 67.2 67.2 69.9 56.9 63.4 63.4 63.4 63.4 65.1 55.2

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 52.6 44.2 56.9 33.5 59.5 22.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

49.4 42.6 52.9 31.9 54.6 20.2

10194

27 52.9 52.9 56.8 41.6 59.4 30.2 50.1 50.1 52.8 40.1 54.5 28.4 30 55.3 55.3 56.7 49.7 59.3 38.3 52.0 52.0 52.8 48.0 54.3 36.6

33 57.1 57.1 57.1 57.1 59.2 46.5 53.2 53.2 53.2 53.2 54.2 44.7

24 53.4 46.3 57.4 34.7 59.8 22.2 48.9 48.9 53.2 33.0 54.7 20.4

11349

27 54.3 54.3 57.3 43.5 59.7 31.1 51.2 51.2 53.1 41.9 54.6 29.3 30 56.4 56.4 57.2 52.2 59.6 40.0 52.8 52.8 53.1 50.5 54.5 38.2

33 57.8 57.8 57.8 57.8 59.5 48.9 53.6 53.6 53.7 53.7 54.3 47.0

24 52.9 52.9 57.7 35.7 60.1 22.4 49.9 49.9 53.4 34.1 54.7 20.6

12488

27 55.3 55.3 57.6 45.3 60.0 32.0 52.0 52.0 53.3 43.6 54.6 30.2 30 57.3 57.3 57.6 54.7 59.8 41.6 53.3 53.3 53.3 52.9 54.5 39.8

33 58.5 58.5 58.6 58.6 59.7 51.1 54.1 54.1 54.1 54.1 54.3 49.2

24 53.8 53.8 57.9 36.8 60.2 22.6 50.7 50.7 53.6 35.1 54.7 20.8

13643

27 56.2 56.2 57.8 47.0 60.1 32.9 52.6 52.6 53.4 45.3 54.6 31.1 30 57.8 57.8 57.8 57.0 60.0 43.2 53.5 53.5 53.5 53.5 54.5 41.3

Notes: 1.
2.

33 59.2 59.2 59.2 59.2 59.9 53.3 54.3 54.3 54.3 54.3 54.2 51.3
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

60

SS-PRC029Y-EN

Performance Data

Table 45. Gross cooling capacities (MBH) one compressor - TTA2514DC condensing unit with TWE2514DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

152.9 152.9 166.6 114.1 183.1 69.7

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

147.1 147.1 159.1 111.3 175.0 67.0

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

140.5 140.5 150.8 108.1 165.8 64.0

80 162.2 162.2 166.3 148.8 182.3 105.1 156.0 156.0 156.2 156.2 174.1 102.4 149.1 149.1 149.2 149.2 165.0 99.3 7500
85 171.4 171.4 171.6 171.6 181.5 140.4 164.9 164.9 165.1 165.1 173.4 137.6 157.6 157.6 157.7 157.7 164.3 134.6

90 180.1 180.1 180.3 180.3 181.8 175.1 173.2 173.2 173.3 173.3 174.0 172.4 165.4 165.4 165.5 165.5 165.6 165.6

75 156.4 156.4 168.3 119.6 184.5 71.1 150.4 150.4 160.7 116.7 176.2 68.4 143.5 143.5 152.2 113.5 167.0 65.3

80 166.0 166.0 166.1 166.1 183.7 109.7 159.6 159.6 159.7 159.7 175.4 107.0 152.3 152.3 152.4 152.4 166.2 104.0 8350
85 175.3 175.3 175.4 175.4 182.9 148.3 168.5 168.5 168.7 168.7 174.7 145.1 160.9 160.9 161.0 161.0 165.5 142.0

90 183.7 183.7 183.8 183.8 184.0 184.0 176.4 176.4 176.5 176.5 176.5 176.5 168.2 168.2 168.2 168.2 168.3 168.3

75 159.5 159.5 169.7 124.8 185.6 72.4 153.2 153.2 162.0 121.9 177.3 69.7 146.1 146.1 153.3 118.7 167.9 66.6

80 169.2 169.2 169.3 169.3 184.8 114.2 162.6 162.6 162.7 162.7 176.4 111.5 155.1 155.1 155.1 155.1 167.1 108.4 9200
85 178.5 178.5 178.6 178.6 184.0 155.3 171.5 171.5 171.6 171.6 171.7 171.7 163.6 163.6 163.6 163.6 163.7 163.7

90 186.3 186.3 186.4 186.4 186.5 186.5 178.7 178.7 178.7 178.7 178.8 178.8 170.0 170.0 170.0 170.0 170.0 170.0

75 162.1 162.1 170.9 129.8 186.5 73.6 155.7 155.7 163.1 126.9 178.1 70.9 148.3 148.3 154.3 123.7 168.7 67.9

80 171.9 171.9 172.1 172.1 185.7 118.5 165.1 165.1 165.2 165.2 177.3 115.8 157.4 157.4 157.5 157.5 167.8 112.7 10050
85 181.2 181.2 181.3 181.3 181.4 181.4 173.9 173.9 174.0 174.0 174.1 174.1 165.7 165.7 165.8 165.8 165.9 165.9

90 188.2 188.2 188.2 188.2 188.2 188.2 180.2 180.2 180.2 180.2 180.2 180.2 171.0 171.0 170.9 170.9 170.9 170.9

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

133.5 133.5 141.8 104.8 155.8 60.7

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

126.9 126.9 133.4 101.7 145.8 57.4

80 141.5 141.5 141.6 141.6 155.1 96.1 134.1 134.1 134.2 134.2 145.0 92.8 7500
85 149.5 149.5 149.7 149.7 154.4 130.9 141.3 141.3 141.4 141.4 144.4 127.5

90 156.6 156.6 156.7 156.7 156.8 156.8 147.2 147.2 147.2 147.2 147.3 147.3

75 136.2 136.2 143.1 110.2 156.9 62.0 129.2 129.2 134.4 107.0 146.7 58.8

80 144.4 144.4 144.5 144.5 156.1 100.7 136.5 136.5 136.6 136.6 145.8 97.4 8350
85 152.5 152.5 152.5 152.5 152.6 152.6 143.7 143.7 143.8 143.8 143.9 143.9

90 158.8 158.8 158.8 158.8 158.8 158.8 148.5 148.5 148.4 148.4 148.4 148.4

75 138.5 138.5 144.1 115.4 157.7 63.3 131.2 131.2 135.2 112.1 147.3 60.0

80 146.9 146.9 147.0 147.0 156.9 105.2 138.7 138.7 138.7 138.7 146.5 101.8 9200
85 154.8 154.8 154.9 154.9 154.9 154.9 145.6 145.6 145.7 145.7 145.7 145.7

90 159.9 159.9 159.9 159.9 159.9 159.9 149.4 149.4 149.4 149.4 149.5 149.5

75 140.5 140.5 145.0 120.4 158.4 64.6 132.9 132.9 135.9 116.3 147.9 61.3

80 149.0 149.0 149.1 149.1 157.5 109.5 140.5 140.5 140.5 140.5 147.0 106.1 10050
85 156.6 156.6 156.7 156.7 156.8 156.8 147.1 147.1 147.1 147.1 147.2 147.2

Notes: 1.
2.

90 160.1 160.1 160.0 160.0 159.9 159.9 150.4 150.4 150.4 150.4 150.4 150.4
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

61

Performance Data

Table 46. Gross cooling capacities (kW) one compressor - TTA2514DC condensing unit with TWE2514DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 44.8 44.8 48.8 33.4 53.6 20.4

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

43.1 43.1 46.6 32.6 51.3 19.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

41.2 41.2 44.2 31.7 48.6 18.7

12742

27 47.5 47.5 48.7 43.6 53.4 30.8 45.7 45.7 45.8 45.8 51.0 30.0 43.7 43.7 43.7 43.7 48.3 29.1 30 50.2 50.2 50.3 50.3 53.2 41.1 48.3 48.3 48.4 48.4 50.8 40.3 46.2 46.2 46.2 46.2 48.1 39.4

33 52.8 52.8 52.8 52.8 53.3 51.3 50.8 50.8 50.8 50.8 51.0 50.5 48.5 48.5 48.5 48.5 48.5 48.5

24 45.8 45.8 49.3 35.0 54.1 20.8 44.1 44.1 47.1 34.2 51.6 20.0 42.1 42.1 44.6 33.3 48.9 19.1

14187

27 48.6 48.6 48.7 48.7 53.8 32.2 46.8 46.8 46.8 46.8 51.4 31.4 44.6 44.6 44.7 44.7 48.7 30.5 30 51.4 51.4 51.4 51.4 53.6 43.4 49.4 49.4 49.4 49.4 51.2 42.5 47.1 47.1 47.2 47.2 48.5 41.6

33 53.8 53.8 53.8 53.8 53.9 53.9 51.7 51.7 51.7 51.7 51.7 51.7 49.3 49.3 49.3 49.3 49.3 49.3

24 46.7 46.7 49.7 36.6 54.4 21.2 44.9 44.9 47.5 35.7 51.9 20.4 42.8 42.8 44.9 34.8 49.2 19.5

15631

27 49.6 49.6 49.6 49.6 54.1 33.5 47.6 47.6 47.7 47.7 51.7 32.7 45.4 45.4 45.5 45.5 49.0 31.8 30 52.3 52.3 52.3 52.3 53.9 45.5 50.2 50.2 50.3 50.3 50.3 50.3 47.9 47.9 47.9 47.9 48.0 48.0

33 54.6 54.6 54.6 54.6 54.6 54.6 52.4 52.4 52.4 52.4 52.4 52.4 49.8 49.8 49.8 49.8 49.8 49.8

24 47.5 47.5 50.1 38.0 54.7 21.6 45.6 45.6 47.8 37.2 52.2 20.8 43.5 43.5 45.2 36.3 49.4 19.9

17075

27 50.4 50.4 50.4 50.4 54.4 34.7 48.4 48.4 48.4 48.4 51.9 33.9 46.1 46.1 46.1 46.1 49.2 33.0 30 53.1 53.1 53.1 53.1 53.1 53.1 51.0 51.0 51.0 51.0 51.0 51.0 48.6 48.6 48.6 48.6 48.6 48.6

33 55.1 55.1 55.1 55.1 55.2 55.2 52.8 52.8 52.8 52.8 52.8 52.8 50.1 50.1 50.1 50.1 50.1 50.1

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 39.1 39.1 41.6 30.7 45.7 17.8

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

37.2 37.2 39.1 29.8 42.7 16.8

12742

27 41.5 41.5 41.5 41.5 45.4 28.1 39.3 39.3 39.3 39.3 42.5 27.2 30 43.8 43.8 43.8 43.8 45.2 38.3 41.4 41.4 41.4 41.4 42.3 37.4

33 45.9 45.9 45.9 45.9 45.9 45.9 43.1 43.1 43.1 43.1 43.1 43.1

24 39.9 39.9 41.9 32.3 46.0 18.2 37.9 37.9 39.4 31.4 43.0 17.2

14187

27 42.3 42.3 42.3 42.3 45.7 29.5 40.0 40.0 40.0 40.0 42.7 28.5 30 44.7 44.7 44.7 44.7 44.7 44.7 42.1 42.1 42.1 42.1 42.2 42.2

33 46.5 46.5 46.5 46.5 46.5 46.5 43.5 43.5 43.5 43.5 43.5 43.5

24 40.6 40.6 42.2 33.8 46.2 18.6 38.4 38.4 39.6 32.9 43.2 17.6

15631

27 43.0 43.0 43.1 43.1 46.0 30.8 40.6 40.6 40.6 40.6 42.9 29.8 30 45.4 45.4 45.4 45.4 45.4 45.4 42.7 42.7 42.7 42.7 42.7 42.7

33 46.9 46.9 46.9 46.9 46.8 46.8 43.8 43.8 43.8 43.8 43.8 43.8

24 41.2 41.2 42.5 35.3 46.4 18.9 38.9 38.9 39.8 34.1 43.3 17.9

17075

27 43.7 43.7 43.7 43.7 46.2 32.1 41.2 41.2 41.2 41.2 43.1 31.1 30 45.9 45.9 45.9 45.9 45.9 45.9 43.1 43.1 43.1 43.1 43.1 43.1

Notes: 1.
2.

33 46.9 46.9 46.9 46.9 46.9 46.9 44.1 44.1 44.1 44.1 44.1 44.1
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

62

SS-PRC029Y-EN

Performance Data

Table 47. Gross cooling capacities (MBH) both compressors - TTA2514DC condensing unit with TWE2514DB air handler (IP)

Ambient Temperature (°F)

Ambient Temperature (°F)

Ambient Temperature (°F)

85

95

105

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

Entering Wet Bulb (°F)

61

67

73

61

67

73

61

67

73

MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC

249.7 201.8 274.4 156.9 293.2 108.0 238.3 196.3 261.6 151.5 278.1 102.4 226.1 190.5 247.5 145.6 261.1 96.2

80 247.0 247.0 273.7 191.9 292.4 143.4 237.7 237.7 260.8 186.5 277.4 137.8 227.5 227.5 246.8 180.7 260.3 131.6 7500
85 259.2 259.2 272.9 226.9 291.7 178.6 249.4 249.4 260.1 221.4 276.6 173.1 238.4 238.4 246.2 215.5 259.5 166.9

90 270.8 270.8 273.8 261.8 290.9 214.3 260.3 260.3 261.5 256.5 275.8 208.6 248.3 248.3 248.3 248.3 258.7 202.2

75 254.0 211.5 278.1 162.4 295.1 108.8 242.3 206.0 264.8 156.9 279.5 103.2 229.6 200.0 250.3 151.0 262.2 97.0

80 254.6 254.6 277.2 201.2 294.3 147.5 244.7 244.7 264.0 195.7 278.7 141.8 233.8 233.8 249.5 189.6 261.4 135.7 8350
85 266.9 266.9 276.7 238.7 293.4 186.0 256.3 256.3 263.6 233.2 277.6 181.2 244.6 244.6 249.3 227.2 260.5 174.2

90 278.1 278.1 278.7 277.3 292.6 224.7 266.7 266.7 266.5 266.5 277.0 218.9 253.5 253.5 253.7 253.7 259.7 212.5

75 257.7 220.7 281.0 167.6 297.3 109.9 245.6 215.1 267.4 162.0 281.1 104.2 227.6 227.6 252.4 156.0 263.3 98.0

80 261.0 261.0 280.2 209.4 296.5 151.8 250.6 250.6 266.6 203.8 280.3 146.0 239.1 239.1 251.7 197.6 262.5 139.8 9200
85 273.2 273.2 279.9 250.1 295.7 193.4 262.0 262.0 266.5 244.5 279.5 187.7 249.4 249.4 251.8 238.5 261.6 181.5

90 283.8 283.8 283.6 283.6 294.9 235.1 271.4 271.4 271.5 271.5 278.7 229.1 256.9 256.9 257.0 257.0 260.9 222.7

75 260.8 229.9 283.4 172.5 299.3 111.1 243.3 243.3 269.4 166.9 282.6 105.3 232.1 232.1 254.2 160.9 264.4 99.0

80 266.5 266.5 282.6 217.2 298.4 156.0 255.6 255.6 268.7 211.5 281.8 150.1 243.5 243.5 253.4 205.3 263.5 143.9 10050
85 278.4 278.4 282.6 261.1 297.6 200.7 266.6 266.6 268.9 255.4 281.0 194.9 253.2 253.2 254.0 249.3 262.7 188.6

90 288.0 288.0 288.2 288.2 296.9 245.1 274.6 274.6 274.7 274.7 280.2 239.1 258.6 258.6 258.6 258.6 262.0 232.6

Ambient Temperature (°F)

Ambient Temperature (°F)

115

125

CFM

Ent DB (°F)
75

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

213.7 184.6 232.9 139.6 243.0 89.8

Entering Wet Bulb (°F)

61

67

73

MBH SHC MBH SHC MBH SHC

203.4 179.9 218.8 133.9 224.9 83.4

80 216.9 216.9 232.1 174.7 242.2 125.2 206.9 206.9 218.0 169.3 224.1 118.8 7500
85 226.9 226.9 231.7 209.4 241.3 160.4 215.3 215.3 217.8 203.6 223.1 154.0

90 235.2 235.2 235.3 235.3 240.5 195.5 221.3 221.3 221.3 221.3 222.2 188.9

75 216.9 194.1 235.1 144.9 243.7 90.6 203.0 203.0 220.5 139.1 224.9 84.1

80 222.5 222.5 234.3 183.4 242.9 129.2 211.4 211.4 219.7 177.4 224.1 122.8 8350
85 232.0 232.0 234.3 221.0 242.0 167.7 219.2 219.2 219.8 215.1 223.1 161.2

90 238.8 238.8 238.8 238.8 241.1 205.8 222.4 222.4 222.3 222.3 222.1 199.1

75 216.5 216.5 236.8 149.9 244.4 91.5 206.4 206.4 221.7 144.0 225.0 84.9

80 227.0 227.0 236.1 191.3 243.6 133.3 215.1 215.1 220.9 185.2 224.2 126.7 9200
85 235.8 235.8 236.5 232.2 242.7 174.9 221.7 221.7 221.6 221.6 223.1 168.3

90 240.2 240.2 240.2 240.2 241.9 215.9 222.0 222.0 221.9 221.9 221.9 208.9

75 220.5 220.5 238.2 154.7 244.9 92.4 209.4 209.4 222.7 148.7 225.0 85.7

80 230.7 230.7 237.4 198.9 244.1 137.3 218.0 218.0 221.9 193.2 224.1 130.6 10050
85 238.5 238.5 238.4 238.4 243.1 181.9 223.0 223.0 223.0 223.0 223.0 175.2

Notes: 1.
2.

90 241.3 241.2 241.3 241.3 242.3 225.7 221.9 221.9 221.8 221.8 221.2 218.2
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SS-PRC029Y-EN

63

Performance Data

Table 48. Gross cooling capacities (kW) both compressors - TTA2514DC condensing unit with TWE2514DB air handler (SI)

Ambient Temperature (°C)

Ambient Temperature (°C)

Ambient Temperature (°C)

30

35

40

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 73.1 59.1 80.4 46.0 85.9 31.6

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

69.8 57.5 76.6 44.4 81.5 30.0

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

66.2 55.8 72.5 42.7 76.5 28.2

12742

27 72.4 72.4 80.2 56.2 85.7 42.0 69.7 69.7 76.4 54.6 81.3 40.4 66.7 66.7 72.3 52.9 76.3 38.6 30 76.0 76.0 80.0 66.5 85.5 52.3 73.1 73.1 76.2 64.9 81.0 50.7 69.9 69.9 72.1 63.1 76.0 48.9

33 79.4 79.4 80.2 76.7 85.2 62.8 76.3 76.3 76.6 75.2 80.8 61.1 72.8 72.8 72.8 72.8 75.8 59.3

24 74.4 62.0 81.5 47.6 86.5 31.9 71.0 60.3 77.6 46.0 81.9 30.2 67.3 58.6 73.3 44.2 76.8 28.4

14187

27 74.6 74.6 81.2 59.0 86.2 43.2 71.7 71.7 77.4 57.3 81.7 41.6 68.5 68.5 73.1 55.6 76.6 39.8 30 78.2 78.2 81.1 70.0 86.0 54.5 75.1 75.1 77.2 68.3 81.3 53.1 71.7 71.7 73.0 66.6 76.3 51.0

33 81.5 81.5 81.7 81.2 85.7 65.8 78.1 78.1 78.1 78.1 81.2 64.1 74.3 74.3 74.3 74.3 76.1 62.3

24 75.5 64.7 82.3 49.1 87.1 32.2 72.0 63.0 78.3 47.5 82.4 30.5 66.7 66.7 74.0 45.7 77.2 28.7

15631

27 76.5 76.5 82.1 61.4 86.9 44.5 73.4 73.4 78.1 59.7 82.1 42.8 70.1 70.1 73.7 57.9 76.9 41.0 30 80.0 80.0 82.0 73.3 86.7 56.7 76.8 76.8 78.1 71.6 81.9 55.0 73.1 73.1 73.8 69.9 76.7 53.2

33 83.1 83.1 83.1 83.1 86.4 68.9 79.5 79.5 79.6 79.6 81.6 67.1 75.3 75.3 75.3 75.3 76.4 65.3

24 76.4 67.4 83.0 50.5 87.7 32.5 71.3 71.3 78.9 48.9 82.8 30.8 68.0 68.0 74.5 47.1 77.5 29.0

17075

27 78.1 78.1 82.8 63.7 87.4 45.7 74.9 74.9 78.7 62.0 82.6 44.0 71.4 71.4 74.2 60.2 77.2 42.1 30 81.6 81.6 82.8 76.5 87.2 58.8 78.1 78.1 78.8 74.8 82.3 57.1 74.2 74.2 74.4 73.0 77.0 55.3

33 84.4 84.4 84.4 84.4 87.0 71.8 80.5 80.5 80.5 80.5 82.1 70.1 75.8 75.8 75.8 75.8 76.8 68.2

Ambient Temperature (°C)

Ambient Temperature (°C)

45

52

Ent
Airflow DB m3/hr (°C)

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

24 62.6 54.1 68.2 40.9 71.2 26.3

Entering Wet Bulb (°C)

16

19

22

kW SHC kW SHC kW SHC

59.6 52.7 64.1 39.2 65.9 24.4

12742

27 63.6 63.6 68.0 51.2 71.0 36.7 60.6 60.6 63.9 49.6 65.7 34.8 30 66.5 66.5 67.9 61.4 70.7 47.0 63.1 63.1 63.8 59.7 65.4 45.1

33 68.9 68.9 69.0 69.0 70.5 57.3 64.8 64.8 64.8 64.8 65.1 55.4

24 63.5 56.9 68.9 42.4 71.4 26.5 59.5 59.5 64.6 40.7 65.9 24.6

14187

27 65.2 65.2 68.7 53.7 71.2 37.9 61.9 61.9 64.4 52.0 65.7 36.0 30 68.0 68.0 68.7 64.8 70.9 49.1 64.2 64.2 64.4 63.0 65.4 47.2

33 70.0 70.0 70.0 70.0 70.6 60.3 65.2 65.2 65.1 65.1 65.1 58.3

24 63.4 63.4 69.4 43.9 71.6 26.8 60.5 60.5 65.0 42.2 65.9 24.9

15631

27 66.5 66.5 69.2 56.0 71.4 39.1 63.0 63.0 64.7 54.3 65.7 37.1 30 69.1 69.1 69.3 68.0 71.1 51.3 65.0 65.0 64.9 64.9 65.4 49.3

33 70.4 70.4 70.4 70.4 70.9 63.3 65.1 65.1 65.0 65.0 65.0 61.2

24 64.6 64.6 69.8 45.3 71.8 27.1 61.3 61.3 65.2 43.6 65.9 25.1

17075

27 67.6 67.6 69.5 58.3 71.5 40.2 63.9 63.9 65.0 56.6 65.7 38.3 30 69.9 69.9 69.9 69.9 71.2 53.3 65.3 65.3 65.3 65.3 65.3 51.3

Notes: 1.
2.

33 70.7 70.7 70.7 70.7 71.0 66.1 65.0 65.0 65.0 65.0 64.8 63.9
All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

64

SS-PRC029Y-EN

Performance Data

Table 49. Gross cooling capacities (MBH) TTA0604DA condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

242.7

247.8

253.1

258.5

264.1

65

Capacity (Btuh/1000)

52.3

57.8

63.6

69.8

76.3

Unit Power (kW)

2.8

2.8

2.9

2.9

3.0

Head Press (psig)

279.6

284.9

290.4

296.1

301.7

75

Capacity (Btuh/1000)

49.5

54.7

60.2

66.0

72.1

Unit Power (kW)

3.2

3.2

3.2

3.3

3.4

Head Press (psig)

320.1

325.6

331.3

337.1

342.9

85

Capacity (Btuh/1000)

46.5

51.4

56.6

62.1

67.8

Unit Power (kW)

3.6

3.6

3.7

3.7

3.8

Head Press (psig)

364.4

370.1

376.0

381.9

387.7

95

Capacity (Btuh/1000)

43.4

48.0

52.9

58.0

63.3

Unit Power (kW)

4.1

4.1

4.2

4.2

4.3

Head Press (psig)

412.6

418.4

424.4

430.4

436.2

105

Capacity (Btuh/1000)

40.1

44.5

49.0

53.8

58.8

Unit Power (kW)

4.6

4.7

4.7

4.7

4.8

Head Press (psig)

464.7

470.6

476.6

482.6

488.3

115

Capacity (Btuh/1000)

36.7

40.8

45.1

49.6

54.1

Unit Power (kW)

5.2

5.3

5.3

5.4

5.4

Head Press (psig)

520.7

526.5

532.3

538.1

543.5

125

Capacity (Btuh/1000)

33.2

37.1

41.1

45.2

49.3

Unit Power (kW)

6.0

6.0

6.0

6.1

6.1

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 269.6 83.1
3.0 307.3 78.4
3.4 348.6 73.6
3.8 393.4 68.7
4.3 441.8 63.7
4.8 493.8 58.6
5.4 548.6 53.3
6.1

Table 50. Gross cooling capacities (kW) TTA0604DA condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1673.3

1708.2

1744.8

1782.6

1820.8

18.3

Capacity (kW)

15.3

16.9

18.6

20.5

22.4

Unit Power (kW)

2.8

2.8

2.9

2.9

3.0

Head Press (kPa)

1927.8

1964.3

2002.3

2041.2

2080.4

23.9

Capacity (kW)

14.5

16.0

17.6

19.3

21.1

Unit Power (kW)

3.2

3.2

3.2

3.3

3.4

Head Press (kPa)

2207.1

2245.2

2284.5

2324.4

2364.3

29.4

Capacity (kW)

13.6

15.1

16.6

18.2

19.9

Unit Power (kW)

3.6

3.6

3.7

3.7

3.8

Head Press (kPa)

2512.5

2551.9

2592.3

2633.0

2673.3

35

Capacity (kW)

12.7

14.1

15.5

17.0

18.6

Unit Power (kW)

4.1

4.1

4.2

4.2

4.3

Head Press (kPa)

2844.5

2885.1

2926.3

2967.4

3007.8

40.6

Capacity (kW)

11.8

13.0

14.4

15.8

17.2

Unit Power (kW)

4.6

4.7

4.7

4.7

4.8

Head Press (kPa)

3203.7

3244.8

3286.2

3327.2

3366.9

46.1

Capacity (kW)

10.8

12.0

13.2

14.5

15.9

Unit Power (kW)

5.2

5.3

5.3

5.4

5.4

Head Press (kPa)

3590.1

3630.1

3670.3

3709.8

3747.6

51.7

Capacity (kW)

9.7

10.9

12.0

13.2

14.4

Unit Power (kW)

6.0

6.0

6.0

6.1

6.1

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1858.7
24.3 3.0 2118.9 23.0 3.4 2403.2 21.6 3.8 2712.3 20.1 4.3 3046.3 18.7 4.8 3404.3 17.2 5.4 3782.8 15.6 6.1

SS-PRC029Y-EN

65

Performance Data

Table 51. Gross cooling capacities (MBH) TTA0604DD condensing unit only (IP)

Outdoor Temp (°F)
65 75 85 95 105 115 125

Head Press (psig) Capacity (Btuh/1000)
Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW)

30 262.2 54.8
3.1 301.8 51.7
3.5 344.8 48.2
4.0 391.5 44.5
4.4 442.0 40.7
5.0 499.4 36.9
5.6 583.6 33.7
6.6

35 268.0 60.7
3.2 308.2 57.3
3.5 352.0 53.6
4.0 399.5 49.6
4.5 450.7 45.6
5.0 505.5 41.8
5.7 585.4 38.5
6.6

Suction Temperature (°F)

40

45

273.8

279.2

67.1

74.0

3.2

3.2

314.6

320.7

63.3

69.9

3.6

3.6

359.1

365.9

59.3

65.5

4.0

4.1

407.3

414.9

55.1

61.0

4.5

4.6

459.2

467.5

50.9

56.6

5.1

5.2

514.6

523.2

46.9

52.4

5.7

5.8

585.2

584.0

43.6

48.8

6.5

6.5

50 284.3 81.4
3.2 326.3 76.9
3.6 372.1 72.2
4.1 421.8 67.3
4.6 475.0 62.7
5.2 531.0 58.3
5.8 589.0 54.4
6.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 288.6 89.5
3.2 331.0 84.5
3.6 377.4 79.4
4.1 427.6 74.2
4.7 481.3 69.2
5.2 537.6 64.7
5.9 595.5 60.5
6.5

Table 52. Gross cooling capacities (kW) TTA0604DD condensing unit only (SI)

Outdoor Temp (°C)
18.3 23.9 29.4
35 40.6 46.1 51.7

Head Press (kPa) Capacity (kW)
Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW)

-1.1 1807.7
16.1 3.1 2080.7 15.1 3.5 2377.6 14.1 4.0 2699.6 13.0 4.4 3047.4 11.9 5.0 3443.5 10.8 5.6 4023.6 9.9 6.6

1.7 1847.9
17.8 3.2 2125.3 16.8 3.5 2427.1 15.7 4.0 2754.2 14.5 4.5 3107.1 13.4 5.0 3485.3 12.2 5.7 4036.2 11.3 6.6

Suction Temperature (°C)

4.4

7.2

1887.5

1925.3

19.7

21.7

3.2

3.2

2169.4

2211.4

18.6

20.5

3.6

3.6

2476.1

2523.0

17.4

19.2

4.0

4.1

2808.5

2860.5

16.1

17.9

4.5

4.6

3166.3

3223.0

14.9

16.6

5.1

5.2

3547.8

3607.2

13.7

15.4

5.7

5.8

4034.7

4026.3

12.8

14.3

6.5

6.5

10 1959.9
23.9 3.2 2249.8 22.6 3.6 2565.8 21.2 4.1 2908.2 19.7 4.6 3274.7 18.4 5.2 3661.2 17.1 5.8 4060.7 16.0 6.5

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1989.5
26.2 3.2 2282.3 24.8 3.6 2602.0 23.3 4.1 2948.4 21.7 4.7 3318.5 20.3 5.2 3706.6 19.0 5.9 4105.8 17.7 6.5

66

SS-PRC029Y-EN

Performance Data

Table 53. Gross cooling capacities (MBH) TTA0764DA condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

260.6

267.6

274.9

282.4

290.1

65

Capacity (Btuh/1000)

66.8

73.7

81.1

89.0

97.3

Unit Power (kW)

3.9

4.0

4.0

4.0

4.0

Head Press (psig)

298.4

305.7

313.2

321.0

328.8

75

Capacity (Btuh/1000)

63.2

69.7

76.8

84.2

91.9

Unit Power (kW)

4.5

4.5

4.5

4.6

4.6

Head Press (psig)

339.9

347.4

355.2

363.1

371.0

85

Capacity (Btuh/1000)

59.4

65.6

72.2

79.1

86.4

Unit Power (kW)

5.1

5.1

5.2

5.2

5.2

Head Press (psig)

385.3

393.0

400.9

408.9

416.8

95

Capacity (Btuh/1000)

55.5

61.3

67.5

74.0

80.8

Unit Power (kW)

5.8

5.8

5.8

5.9

5.9

Head Press (psig)

436.1

442.3

450.3

458.3

466.1

105

Capacity (Btuh/1000)

51.4

56.9

62.7

68.7

75.0

Unit Power (kW)

6.6

6.6

6.6

6.7

6.7

Head Press (psig)

491.5

496.4

503.3

511.1

518.6

115

Capacity (Btuh/1000)

47.3

52.4

57.8

63.4

69.1

Unit Power (kW)

7.5

7.5

7.5

7.5

7.5

Head Press (psig)

551.5

555.7

560.2

566.5

573.5

125

Capacity (Btuh/1000)

43.1

47.9

52.7

57.8

62.9

Unit Power (kW)

8.6

8.5

8.5

8.5

8.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 297.8 105.9
4.0 336.5 99.9
4.6 378.6 93.8
5.2 424.3 87.6
5.9 473.4 81.3
6.7 525.6 74.9
7.5 579.9 68.0
8.4

Table 54. Gross cooling capacities (kW) TTA0764DA condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1796.8

1844.7

1895.1

1947.3

2000.4

18.3

Capacity (kW)

19.6

21.6

23.8

26.1

28.5

Unit Power (kW)

3.9

4.0

4.0

4.0

4.0

Head Press (kPa)

2057.7

2107.5

2159.6

2213.1

2267.0

23.9

Capacity (kW)

18.5

20.4

22.5

24.7

26.9

Unit Power (kW)

4.5

4.5

4.5

4.6

4.6

Head Press (kPa)

2343.8

2395.5

2449.0

2503.5

2557.9

29.4

Capacity (kW)

17.4

19.2

21.2

23.2

25.3

Unit Power (kW)

5.1

5.1

5.2

5.2

5.2

Head Press (kPa)

2656.4

2709.5

2764.0

2819.2

2873.5

35

Capacity (kW)

16.3

18.0

19.8

21.7

23.7

Unit Power (kW)

5.8

5.8

5.8

5.9

5.9

Head Press (kPa)

3006.8

3049.8

3105.0

3159.9

3213.4

40.6

Capacity (kW)

15.1

16.7

18.4

20.1

22.0

Unit Power (kW)

6.6

6.6

6.6

6.7

6.7

Head Press (kPa)

3389.1

3422.3

3470.0

3523.7

3575.4

46.1

Capacity (kW)

13.9

15.4

16.9

18.6

20.3

Unit Power (kW)

7.5

7.5

7.5

7.5

7.5

Head Press (kPa)

3802.8

3831.6

3862.2

3905.8

3953.9

51.7

Capacity (kW)

12.6

14.0

15.5

16.9

18.4

Unit Power (kW)

8.6

8.5

8.5

8.5

8.5

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 2053.0
31.0 4.0 2320.0 29.3 4.6 2610.7 27.5 5.2 2925.6 25.7 5.9 3264.2 23.8 6.7 3623.6 21.9 7.5 3997.9 19.9 8.4

SS-PRC029Y-EN

67

Performance Data

Table 55. Gross cooling capacities (MBH) TTA0764DD condensing unit only (IP)

Outdoor Temp (°F)
65 75 85 95 105 115 125

Head Press (psig) Capacity (Btuh/1000)
Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW) Head Press (psig) Capacity (Btuh/1000) Unit Power (kW)

30 263.5 64.3
3.9 303.0 60.6
4.4 346.1 56.5
4.9 376.9 52.4
5.4 427.3 48.0
6.1 481.9 43.6
7.0 540.5 39.2
8.0

35 267.2 71.6
3.9 306.8 67.5
4.4 350.1 63.1
4.9 397.4 58.5
5.6 431.2 53.9
6.1 485.8 49.2
6.9 544.3 44.5
7.9

Suction Temperature (°F)

40

45

270.4

274.9

79.3

87.4

3.9

3.9

310.1

313.5

74.8

82.5

4.4

4.4

353.4

356.2

70.1

77.3

4.9

4.9

400.9

403.4

65.2

72.0

5.6

5.5

452.2

454.7

60.1

66.7

6.3

6.3

507.1

496.3

55.2

60.8

7.2

6.9

547.7

552.2

49.9

55.2

7.9

7.8

50 281.9 95.9
3.9 313.2 89.7
4.3 354.8 84.0
4.8 400.1 78.2
5.4 449.0 72.4
6.1 501.6 66.6
6.9 557.3 60.6
7.8

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 279.4 102.9
3.9 317.5 96.9
4.3 359.1 90.8
4.8 404.3 84.6
5.4 453.2 78.3
6.1 505.7 72.0
6.9 561.2 65.4
7.8

Table 56. Gross cooling capacities (kW) TTA0764DD condensing unit only (SI)

Outdoor Temp (°C)
18.3 23.9 29.4
35 40.6 46.1 51.7

Head Press (kPa) Capacity (kW)
Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW) Head Press (kPa)
Capacity (kW) Unit Power (kW)

-1.1 1817.0
18.8 3.9 2089.2 17.7 4.4 2386.5 16.6 4.9 2598.9 15.4 5.4 2946.2 14.1 6.1 3322.5 12.8 7.0 3726.5 11.5 8.0

1.7 1842.0
21.0 3.9 2115.6 19.8 4.4 2414.1 18.5 4.9 2740.3 17.1 5.6 2973.0 15.8 6.1 3349.6 14.4 6.9 3753.1 13.0 7.9

Suction Temperature (°C)

4.4

7.2

1864.3

1895.6

23.2

25.6

3.9

3.9

2137.9

2161.2

21.9

24.2

4.4

4.4

2436.9

2455.8

20.5

22.7

4.9

4.9

2763.9

2781.6

19.1

21.1

5.6

5.5

3117.5

3134.7

17.6

19.5

6.3

6.3

3496.6

3422.1

16.2

17.8

7.2

6.9

3776.2

3807.4

14.6

16.2

7.9

7.8

10 1944.0
28.1 3.9 2159.6 26.3 4.3 2446.4 24.6 4.8 2758.3 22.9 5.4 3096.0 21.2 6.1 3458.5 19.5 6.9 3842.6 17.7 7.8

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1926.4
30.2 3.9 2189.3 28.4 4.3 2476.1 26.6 4.8 2787.7 24.8 5.4 3124.9 22.9 6.1 3486.7 21.1 6.9 3869.1 19.2 7.8

68

SS-PRC029Y-EN

Performance Data

Table 57. Gross cooling capacities (MBH) TTA1014DA condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

273.4

274.8

275.6

276.0

281.0

65

Capacity (Btuh/1000)

86.0

94.8

104.3

114.3

124.8

Unit Power (kW)

5.5

5.5

5.5

5.5

5.6

Head Press (psig)

315.1

315.7

315.9

315.5

319.4

75

Capacity (Btuh/1000)

81.5

90.0

99.0

108.4

118.2

Unit Power (kW)

6.1

6.1

6.1

6.1

6.1

Head Press (psig)

361.5

361.2

360.3

358.9

361.5

85

Capacity (Btuh/1000)

76.8

84.8

93.4

102.3

111.5

Unit Power (kW)

6.8

6.8

6.7

6.7

6.7

Head Press (psig)

413.2

411.5

409.2

406.5

407.3

95

Capacity (Btuh/1000)

71.7

79.4

87.6

96.0

104.5

Unit Power (kW)

7.5

7.5

7.4

7.4

7.4

Head Press (psig)

470.5

466.7

462.6

458.3

456.7

105

Capacity (Btuh/1000)

66.5

73.9

81.6

89.6

97.4

Unit Power (kW)

8.4

8.3

8.2

8.2

8.1

Head Press (psig)

532.9

526.5

520.2

514.1

509.5

115

Capacity (Btuh/1000)

61.6

68.5

75.8

83.1

90.2

Unit Power (kW)

9.4

9.3

9.1

9.0

8.9

Head Press (psig)

599.3

590.2

581.6

573.4

565.7

125

Capacity (Btuh/1000)

57.3

63.6

70.2

76.7

82.8

Unit Power (kW)

10.4

10.2

10.1

9.9

9.8

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 285.5 135.6
5.6 323.3 128.3
6.1 364.8 120.7
6.7 409.8 113.0
7.4 458.3 105.1
8.1 510.0 97.0
8.9 564.2 88.4
9.8

Table 58. Gross cooling capacities (kW) TTA1014DA condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1885.1

1894.4

1900.4

1903.2

1937.2

18.3

Capacity (kW)

25.2

27.8

30.6

33.5

36.6

Unit Power (kW)

5.5

5.5

5.5

5.5

5.6

Head Press (kPa)

2172.5

2176.9

2177.7

2175.1

2202.0

23.9

Capacity (kW)

23.9

26.4

29.0

31.8

34.7

Unit Power (kW)

6.1

6.1

6.1

6.1

6.1

Head Press (kPa)

2492.8

2490.3

2484.2

2474.7

2492.1

29.4

Capacity (kW)

22.5

24.9

27.4

30.0

32.7

Unit Power (kW)

6.8

6.8

6.7

6.7

6.7

Head Press (kPa)

2849.2

2836.9

2821.3

2803.0

2807.9

35

Capacity (kW)

21.0

23.3

25.7

28.1

30.6

Unit Power (kW)

7.5

7.5

7.4

7.4

7.4

Head Press (kPa)

3243.9

3217.5

3189.5

3160.2

3148.9

40.6

Capacity (kW)

19.5

21.6

23.9

26.2

28.6

Unit Power (kW)

8.4

8.3

8.2

8.2

8.1

Head Press (kPa)

3674.5

3630.4

3587.0

3544.8

3512.7

46.1

Capacity (kW)

18.1

20.1

22.2

24.4

26.4

Unit Power (kW)

9.4

9.3

9.1

9.0

8.9

Head Press (kPa)

4132.2

4069.3

4009.8

3953.5

3900.7

51.7

Capacity (kW)

16.8

18.6

20.6

22.5

24.3

Unit Power (kW)

10.4

10.2

10.1

9.9

9.8

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1968.2
39.7 5.6 2229.3 37.6 6.1 2514.9 35.4 6.7 2825.3 33.1 7.4 3159.9 30.8 8.1 3516.6 28.4 8.9 3890.3 25.9 9.8

SS-PRC029Y-EN

69

Performance Data

Table 59. Gross cooling capacities (MBH) TTA1014DD condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

255.5

260.7

265.8

270.8

275.7

65

Capacity (Btuh/1000)

85.6

94.3

103.4

113.0

123.1

Unit Power (kW)

4.9

5.0

5.0

5.1

5.1

Head Press (psig)

292.0

297.2

302.4

307.5

312.3

75

Capacity (Btuh/1000)

79.9

88.0

96.5

105.4

114.7

Unit Power (kW)

5.5

5.6

5.6

5.6

5.7

Head Press (psig)

332.3

337.7

343.0

348.1

352.8

85

Capacity (Btuh/1000)

74.6

82.2

90.2

98.6

107.4

Unit Power (kW)

6.2

6.3

6.3

6.3

6.4

Head Press (psig)

376.4

381.9

387.4

392.5

397.2

95

Capacity (Btuh/1000)

69.2

76.4

84.0

92.0

100.5

Unit Power (kW)

7.0

7.1

7.1

7.1

7.1

Head Press (psig)

423.7

429.5

435.1

440.3

445.0

105

Capacity (Btuh/1000)

63.4

70.4

77.6

85.5

93.5

Unit Power (kW)

7.9

7.9

8.0

8.0

8.0

Head Press (psig)

473.9

480.0

485.8

491.1

495.9

115

Capacity (Btuh/1000)

56.9

63.7

70.9

78.5

86.1

Unit Power (kW)

8.8

8.8

8.8

8.9

8.9

Head Press (psig)

527.1

533.2

539.0

544.4

549.3

125

Capacity (Btuh/1000)

49.6

56.3

63.4

70.7

77.9

Unit Power (kW)

9.6

9.7

9.7

9.8

9.8

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 280.1 133.5
5.2 316.6 124.5
5.7 357.0 116.5
6.4 401.4 109.0
7.1 449.2 101.4
8.0 500.2 93.5
8.9 553.6 84.7
9.8

Table 60. Gross cooling capacities (kW) TTA1014DD condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1761.7

1797.1

1832.6

1867.4

1900.7

18.3

Capacity (kW)

25.1

27.6

30.3

33.1

36.1

Unit Power (kW)

4.9

5.0

5.0

5.1

5.1

Head Press (kPa)

2013.1

2049.1

2084.9

2119.9

2153.0

23.9

Capacity (kW)

23.4

25.8

28.3

30.9

33.6

Unit Power (kW)

5.5

5.6

5.6

5.6

5.7

Head Press (kPa)

2291.5

2328.3

2364.8

2400.1

2432.7

29.4

Capacity (kW)

21.9

24.1

26.4

28.9

31.5

Unit Power (kW)

6.2

6.3

6.3

6.3

6.4

Head Press (kPa)

2595.0

2633.3

2670.8

2706.5

2738.6

35

Capacity (kW)

20.3

22.4

24.6

27.0

29.4

Unit Power (kW)

7.0

7.1

7.1

7.1

7.1

Head Press (kPa)

2921.1

2961.2

3000.1

3036.0

3068.4

40.6

Capacity (kW)

18.6

20.6

22.8

25.0

27.4

Unit Power (kW)

7.9

7.9

8.0

8.0

8.0

Head Press (kPa)

3267.6

3309.6

3349.6

3386.1

3419.2

46.1

Capacity (kW)

16.7

18.7

20.8

23.0

25.2

Unit Power (kW)

8.8

8.8

8.8

8.9

8.9

Head Press (kPa)

3634.5

3676.6

3716.5

3753.4

3787.1

51.7

Capacity (kW)

14.5

16.5

18.6

20.7

22.8

Unit Power (kW)

9.6

9.7

9.7

9.8

9.8

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1931.4
39.1 5.2 2182.7 36.5 5.7 2461.7 34.2 6.4 2767.2 31.9 7.1 3097.2 29.7 8.0 3448.5 27.4 8.9 3816.8 24.8 9.8

70

SS-PRC029Y-EN

Performance Data

Table 61. Gross cooling capacities (MBH) one compressor - TTA1014DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

220.4

223.2

226.1

229.1

232.1

65

Capacity (Btuh/1000)

45.0

49.8

54.9

60.4

66.3

Unit Power (kW)

2.6

2.6

2.6

2.7

2.7

Head Press (psig)

254.7

257.4

260.3

263.2

266.3

75

Capacity (Btuh/1000)

41.4

45.8

50.5

55.6

61.0

Unit Power (kW)

2.9

2.9

2.9

2.9

2.9

Head Press (psig)

293.0

295.8

298.7

301.6

304.6

85

Capacity (Btuh/1000)

38.5

42.6

46.9

51.6

56.5

Unit Power (kW)

3.2

3.2

3.2

3.2

3.2

Head Press (psig)

335.6

338.4

341.3

344.2

347.2

95

Capacity (Btuh/1000)

35.8

39.6

43.7

48.0

52.6

Unit Power (kW)

3.5

3.5

3.5

3.5

3.5

Head Press (psig)

382.3

385.2

388.1

391.1

394.1

105

Capacity (Btuh/1000)

33.0

36.7

40.5

44.6

48.9

Unit Power (kW)

4.0

3.9

3.9

3.9

3.9

Head Press (psig)

433.1

436.1

439.2

442.2

445.2

115

Capacity (Btuh/1000)

30.0

33.5

37.2

41.1

45.1

Unit Power (kW)

4.4

4.4

4.4

4.4

4.4

Head Press (psig)

488.1

491.2

494.2

497.3

500.3

125

Capacity (Btuh/1000)

26.5

29.9

33.5

37.3

41.1

Unit Power (kW)

4.9

4.9

4.9

4.9

4.8

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 235.2 72.5
2.7 269.3 66.6
2.9 307.5 61.7
3.2 350.1 57.4
3.5 397.0 53.3
3.9 448.1 49.2
4.4 503.2 44.8
4.8

Table 62. Gross cooling capacities (kW) one compressor - TTA1014DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1519.5

1538.7

1558.7

1579.4

1600.6

18.3

Capacity (kW)

13.2

14.6

16.1

17.7

19.4

Unit Power (kW)

2.6

2.6

2.6

2.7

2.7

Head Press (kPa)

1755.8

1774.8

1794.6

1815.0

1835.8

23.9

Capacity (kW)

12.1

13.4

14.8

16.3

17.9

Unit Power (kW)

2.9

2.9

2.9

2.9

2.9

Head Press (kPa)

2020.4

2039.4

2059.2

2079.4

2099.9

29.4

Capacity (kW)

11.3

12.5

13.7

15.1

16.6

Unit Power (kW)

3.2

3.2

3.2

3.2

3.2

Head Press (kPa)

2313.7

2333.1

2353.0

2373.2

2393.5

35

Capacity (kW)

10.5

11.6

12.8

14.1

15.4

Unit Power (kW)

3.5

3.5

3.5

3.5

3.5

Head Press (kPa)

2635.9

2655.7

2676.0

2696.5

2716.9

40.6

Capacity (kW)

9.7

10.7

11.9

13.1

14.3

Unit Power (kW)

4.0

3.9

3.9

3.9

3.9

Head Press (kPa)

2986.4

3007.0

3027.9

3048.8

3069.4

46.1

Capacity (kW)

8.8

9.8

10.9

12.0

13.2

Unit Power (kW)

4.4

4.4

4.4

4.4

4.4

Head Press (kPa)

3365.5

3386.4

3407.7

3428.8

3449.5

51.7

Capacity (kW)

7.8

8.8

9.8

10.9

12.0

Unit Power (kW)

4.9

4.9

4.9

4.9

4.8

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1621.9
21.2 2.7 1856.6 19.5 2.9 2120.3 18.1 3.2 2413.7 16.8 3.5 2736.9 15.6 3.9 3089.5 14.4 4.4 3469.7 13.1 4.8

SS-PRC029Y-EN

71

Performance Data

Table 63. Gross cooling capacities (MBH) both compressors - TTA1014DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

256.2

262.5

269.1

275.9

282.5

65

Capacity (Btuh/1000)

86.8

95.6

105.0

114.9

125.3

Unit Power (kW)

5.0

5.1

5.2

5.2

5.3

Head Press (psig)

292.7

299.3

306.0

312.8

319.4

75

Capacity (Btuh/1000)

81.1

89.4

98.2

107.5

117.2

Unit Power (kW)

5.6

5.7

5.8

5.8

5.9

Head Press (psig)

333.8

340.2

347.0

353.9

360.5

85

Capacity (Btuh/1000)

75.8

83.6

91.9

100.7

109.8

Unit Power (kW)

6.3

6.4

6.5

6.5

6.6

Head Press (psig)

379.2

384.9

392.0

399.0

405.7

95

Capacity (Btuh/1000)

70.4

77.8

85.7

94.0

102.6

Unit Power (kW)

7.2

7.2

7.3

7.3

7.4

Head Press (psig)

428.3

433.2

440.5

447.7

454.4

105

Capacity (Btuh/1000)

64.5

71.7

79.3

87.2

95.4

Unit Power (kW)

8.0

8.1

8.1

8.2

8.2

Head Press (psig)

480.6

485.5

491.9

499.2

506.0

115

Capacity (Btuh/1000)

57.9

65.0

72.3

80.0

87.8

Unit Power (kW)

8.9

9.0

9.0

9.1

9.1

Head Press (psig)

535.9

540.9

545.7

552.9

559.6

125

Capacity (Btuh/1000)

50.4

57.5

64.7

72.0

79.4

Unit Power (kW)

9.9

9.9

9.9

10.0

10.0

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 288.9 136.1
5.4 325.6 127.2
6.0 366.6 119.1
6.6 411.7 111.3
7.4 460.3 103.5
8.3 511.8 95.3
9.1 565.3 86.3 10.0

Table 64. Gross cooling capacities (kW) both compressors - TTA1014DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1766.1

1810.1

1855.6

1902.0

1947.9

18.3

Capacity (kW)

25.4

28.0

30.8

33.7

36.7

Unit Power (kW)

5.0

5.1

5.2

5.2

5.3

Head Press (kPa)

2018.4

2063.4

2109.7

2156.4

2202.1

23.9

Capacity (kW)

23.8

26.2

28.8

31.5

34.4

Unit Power (kW)

5.6

5.7

5.8

5.8

5.9

Head Press (kPa)

2301.3

2345.3

2392.8

2440.0

2485.6

29.4

Capacity (kW)

22.2

24.5

26.9

29.5

32.2

Unit Power (kW)

6.3

6.4

6.5

6.5

6.6

Head Press (kPa)

2614.6

2654.0

2703.0

2751.2

2796.9

35

Capacity (kW)

20.6

22.8

25.1

27.6

30.1

Unit Power (kW)

7.2

7.2

7.3

7.3

7.4

Head Press (kPa)

2953.2

2986.5

3037.3

3086.7

3132.7

40.6

Capacity (kW)

18.9

21.0

23.2

25.6

28.0

Unit Power (kW)

8.0

8.1

8.1

8.2

8.2

Head Press (kPa)

3313.9

3347.6

3391.7

3442.2

3488.5

46.1

Capacity (kW)

17.0

19.0

21.2

23.4

25.7

Unit Power (kW)

8.9

9.0

9.0

9.1

9.1

Head Press (kPa)

3695.1

3729.1

3762.5

3812.3

3858.2

51.7

Capacity (kW)

14.8

16.9

19.0

21.1

23.3

Unit Power (kW)

9.9

9.9

9.9

10.0

10.0

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1991.8
39.9 5.4 2245.1 37.3 6.0 2527.8 34.9 6.6 2838.3 32.6 7.4 3173.6 30.3 8.3 3528.8 27.9 9.1 3897.4 25.3 10.0

72

SS-PRC029Y-EN

Performance Data

Table 65. Gross cooling capacities (MBH) TTA1264DD condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

275.4

283.4

291.8

300.5

309.5

65

Capacity (Btuh/1000)

115.4

127.1

139.9

153.3

167.2

Unit Power (kW)

7.4

7.5

7.5

7.6

7.6

Head Press (psig)

315.0

323.3

332.1

341.2

350.5

75

Capacity (Btuh/1000)

108.7

119.9

132.0

144.7

157.7

Unit Power (kW)

8.5

8.5

8.6

8.6

8.7

Head Press (psig)

358.5

366.7

375.8

385.2

394.6

85

Capacity (Btuh/1000)

101.5

112.3

123.7

135.5

147.7

Unit Power (kW)

9.7

9.7

9.8

9.9

9.9

Head Press (psig)

408.0

413.6

422.8

432.4

441.9

95

Capacity (Btuh/1000)

94.1

104.2

114.9

126.0

137.3

Unit Power (kW)

11.1

11.1

11.2

11.3

11.3

Head Press (psig)

463.2

467.7

473.1

482.5

492.0

105

Capacity (Btuh/1000)

86.2

95.9

105.8

116.2

126.8

Unit Power (kW)

12.7

12.7

12.7

12.8

12.8

Head Press (psig)

524.3

531.7

533.0

537.0

545.1

115

Capacity (Btuh/1000)

78.1

87.2

96.6

106.2

115.8

Unit Power (kW)

14.6

14.6

14.6

14.5

14.5

Head Press (psig)

584.8

592.1

599.5

604.2

604.4

125

Capacity (Btuh/1000)

70.0

78.5

87.1

95.9

104.5

Unit Power (kW)

16.6

16.6

16.7

16.6

16.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 318.4 181.4
7.7 359.6 170.8
8.7 403.9 159.9 10.0 451.2 148.7 11.3 501.1 137.2 12.9 553.4 125.4 14.5 607.7 112.8 16.3

Table 66. Gross cooling capacities (kW) TTA1264DD condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1899.1

1954.0

2011.8

2072.2

2134.0

18.3

Capacity (kW)

33.8

37.2

41.0

44.9

49.0

Unit Power (kW)

7.4

7.5

7.5

7.6

7.6

Head Press (kPa)

2171.6

2229.3

2289.8

2352.6

2416.3

23.9

Capacity (kW)

31.8

35.1

38.7

42.4

46.2

Unit Power (kW)

8.5

8.5

8.6

8.6

8.7

Head Press (kPa)

2471.7

2528.0

2591.0

2655.8

2721.0

29.4

Capacity (kW)

29.7

32.9

36.3

39.7

43.3

Unit Power (kW)

9.7

9.7

9.8

9.9

9.9

Head Press (kPa)

2812.8

2851.8

2914.9

2981.1

3047.1

35

Capacity (kW)

27.6

30.6

33.7

36.9

40.2

Unit Power (kW)

11.1

11.1

11.2

11.3

11.3

Head Press (kPa)

3193.3

3224.6

3261.7

3327.1

3392.5

40.6

Capacity (kW)

25.3

28.1

31.0

34.1

37.1

Unit Power (kW)

12.7

12.7

12.7

12.8

12.8

Head Press (kPa)

3615.2

3665.7

3675.2

3702.4

3758.0

46.1

Capacity (kW)

22.9

25.6

28.3

31.1

34.0

Unit Power (kW)

14.6

14.6

14.6

14.5

14.5

Head Press (kPa)

4031.8

4082.3

4133.7

4165.5

4167.0

51.7

Capacity (kW)

20.5

23.0

25.5

28.1

30.6

Unit Power (kW)

16.6

16.6

16.7

16.6

16.5

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 2195.5
53.2 7.7 2479.1 50.1 8.7 2784.5 46.9 10.0 3110.6 43.6 11.3 3454.8 40.2 12.9 3815.9 36.7 14.5 4189.7 33.1 16.3

SS-PRC029Y-EN

73

Performance Data

Table 67. Gross cooling capacities (MBH) TTA1564DD condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

239.0

243.7

248.7

253.9

259.3

65

Capacity (Btuh/1000)

135.4

149.7

165.2

181.8

199.5

Unit Power (kW)

8.1

8.0

8.0

8.0

8.0

Head Press (psig)

275.4

280.4

285.5

290.9

296.3

75

Capacity (Btuh/1000)

128.2

141.8

156.5

172.2

188.9

Unit Power (kW)

9.1

9.1

9.1

9.0

9.0

Head Press (psig)

315.6

320.7

326.0

331.5

336.9

85

Capacity (Btuh/1000)

120.8

133.6

147.5

162.3

178.0

Unit Power (kW)

10.2

10.2

10.2

10.2

10.2

Head Press (psig)

359.7

365.0

370.4

375.9

381.3

95

Capacity (Btuh/1000)

113.0

125.1

138.1

152.0

166.7

Unit Power (kW)

11.5

11.5

11.5

11.5

11.5

Head Press (psig)

407.8

413.1

418.6

424.1

429.5

105

Capacity (Btuh/1000)

104.8

116.2

128.4

141.4

155.1

Unit Power (kW)

13.0

13.0

13.0

13.0

13.0

Head Press (psig)

460.0

465.3

470.8

476.2

481.3

115

Capacity (Btuh/1000)

96.4

107.1

118.5

130.6

143.3

Unit Power (kW)

14.7

14.7

14.7

14.7

14.6

Head Press (psig)

517.8

522.0

527.0

531.9

536.7

125

Capacity (Btuh/1000)

87.6

97.6

108.2

119.4

130.9

Unit Power (kW)

16.7

16.6

16.6

16.5

16.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 264.5 218.2
7.9 301.6 206.4
8.9 342.2 194.4 10.1 386.5 182.0 11.4 434.6 169.2 12.9 486.2 156.2 14.5 541.0 142.4 16.3

Table 68. Gross cooling capacities (kW) TTA1564DD condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1647.8

1680.4

1714.9

1750.9

1787.5

18.3

Capacity (kW)

39.7

43.9

48.4

53.3

58.5

Unit Power (kW)

8.1

8.0

8.0

8.0

8.0

Head Press (kPa)

1899.0

1933.0

1968.6

2005.5

2042.7

23.9

Capacity (kW)

37.6

41.6

45.9

50.5

55.4

Unit Power (kW)

9.1

9.1

9.1

9.0

9.0

Head Press (kPa)

2176.1

2211.3

2248.0

2285.4

2322.9

29.4

Capacity (kW)

35.4

39.2

43.2

47.6

52.2

Unit Power (kW)

10.2

10.2

10.2

10.2

10.2

Head Press (kPa)

2480.0

2516.3

2553.7

2591.6

2629.1

35

Capacity (kW)

33.1

36.7

40.5

44.5

48.8

Unit Power (kW)

11.5

11.5

11.5

11.5

11.5

Head Press (kPa)

2811.6

2848.5

2886.4

2924.3

2961.2

40.6

Capacity (kW)

30.7

34.1

37.6

41.5

45.5

Unit Power (kW)

13.0

13.0

13.0

13.0

13.0

Head Press (kPa)

3171.7

3208.5

3245.9

3283.0

3318.7

46.1

Capacity (kW)

28.2

31.4

34.7

38.3

42.0

Unit Power (kW)

14.7

14.7

14.7

14.7

14.6

Head Press (kPa)

3570.1

3599.0

3633.4

3667.5

3700.3

51.7

Capacity (kW)

25.7

28.6

31.7

35.0

38.4

Unit Power (kW)

16.7

16.6

16.6

16.5

16.5

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1824.0
63.9 7.9 2079.3 60.5 8.9 2359.4 57.0 10.1 2665.0 53.3 11.4 2996.2 49.6 12.9 3352.0 45.8 14.5 3730.4 41.7 16.3

74

SS-PRC029Y-EN

Performance Data

Table 69. Gross cooling capacities (MBH) one compressor - TTA1564DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

213.8

215.9

218.2

220.7

223.3

65

Capacity (Btuh/1000)

67.2

74.3

82.0

90.4

99.4

Unit Power (kW)

4.2

4.2

4.1

4.1

4.0

Head Press (psig)

248.7

250.9

253.3

255.9

258.7

75

Capacity (Btuh/1000)

63.5

70.3

77.7

85.6

94.1

Unit Power (kW)

4.7

4.7

4.6

4.6

4.5

Head Press (psig)

287.5

289.8

292.3

295.0

297.8

85

Capacity (Btuh/1000)

59.9

66.3

73.2

80.7

88.8

Unit Power (kW)

5.2

5.2

5.1

5.1

5.0

Head Press (psig)

330.4

332.7

335.3

338.0

340.9

95

Capacity (Btuh/1000)

56.1

62.1

68.7

75.7

83.4

Unit Power (kW)

5.8

5.8

5.8

5.7

5.6

Head Press (psig)

377.6

380.0

382.6

385.4

388.3

105

Capacity (Btuh/1000)

52.1

57.8

63.9

70.6

77.8

Unit Power (kW)

6.5

6.5

6.4

6.4

6.3

Head Press (psig)

429.5

431.8

434.3

437.1

439.9

115

Capacity (Btuh/1000)

47.9

53.3

59.1

65.3

72.1

Unit Power (kW)

7.4

7.3

7.2

7.2

7.1

Head Press (psig)

485.3

488.8

490.9

493.4

496.1

125

Capacity (Btuh/1000)

43.6

48.5

54.0

59.8

66.1

Unit Power (kW)

8.3

8.2

8.2

8.1

8.0

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 226.1 109.1
3.9 261.6 103.3
4.4 300.8 97.6
5.0 343.9 91.6
5.6 391.2 85.5
6.3 442.9 79.3
7.0 498.8 72.7
7.9

Table 70. Gross cooling capacities (kW) one compressor - TTA1564DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1474.0

1488.5

1504.4

1521.5

1539.8

18.3

Capacity (kW)

19.7

21.8

24.0

26.5

29.1

Unit Power (kW)

4.2

4.2

4.1

4.1

4.0

Head Press (kPa)

1714.8

1730.1

1746.7

1764.6

1783.6

23.9

Capacity (kW)

18.6

20.6

22.8

25.1

27.6

Unit Power (kW)

4.7

4.7

4.6

4.6

4.5

Head Press (kPa)

1982.2

1998.1

2015.3

2033.8

2053.4

29.4

Capacity (kW)

17.5

19.4

21.5

23.7

26.0

Unit Power (kW)

5.2

5.2

5.1

5.1

5.0

Head Press (kPa)

2277.8

2294.1

2311.8

2330.8

2350.7

35

Capacity (kW)

16.4

18.2

20.1

22.2

24.4

Unit Power (kW)

5.8

5.8

5.8

5.7

5.6

Head Press (kPa)

2603.5

2619.9

2637.8

2656.9

2676.9

40.6

Capacity (kW)

15.3

16.9

18.7

20.7

22.8

Unit Power (kW)

6.5

6.5

6.4

6.4

6.3

Head Press (kPa)

2961.3

2977.0

2994.7

3013.5

3033.2

46.1

Capacity (kW)

14.0

15.6

17.3

19.1

21.1

Unit Power (kW)

7.4

7.3

7.2

7.2

7.1

Head Press (kPa)

3345.7

3369.9

3384.7

3401.7

3420.2

51.7

Capacity (kW)

12.8

14.2

15.8

17.5

19.4

Unit Power (kW)

8.3

8.2

8.2

8.1

8.0

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1559.2
32.0 3.9 1803.6 30.3 4.4 2073.8 28.6 5.0 2371.4 26.9 5.6 2697.5 25.1 6.3 3053.4 23.2 7.0 3439.0 21.3 7.9

SS-PRC029Y-EN

75

Performance Data

Table 71. Gross cooling capacities (MBH) both compressors - TTA1564DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

241.0

244.6

249.8

255.5

261.5

65

Capacity (Btuh/1000)

133.4

147.5

162.7

179.2

196.8

Unit Power (kW)

8.0

7.9

7.9

7.9

7.9

Head Press (psig)

278.5

282.2

287.1

293.0

299.2

75

Capacity (Btuh/1000)

126.3

139.7

154.2

169.8

186.4

Unit Power (kW)

9.0

9.0

9.0

8.9

8.9

Head Press (psig)

320.0

323.8

328.0

334.2

340.5

85

Capacity (Btuh/1000)

119.0

131.7

145.3

160.1

175.8

Unit Power (kW)

10.2

10.2

10.1

10.1

10.1

Head Press (psig)

365.7

369.5

373.3

379.2

385.6

95

Capacity (Btuh/1000)

111.3

123.3

136.2

150.0

164.8

Unit Power (kW)

11.6

11.5

11.5

11.5

11.4

Head Press (psig)

416.0

419.7

423.4

428.1

434.6

105

Capacity (Btuh/1000)

103.2

114.5

126.7

139.7

153.5

Unit Power (kW)

13.1

13.1

13.0

13.0

12.9

Head Press (psig)

471.3

474.6

477.9

481.2

487.2

115

Capacity (Btuh/1000)

94.9

105.6

117.0

129.1

142.0

Unit Power (kW)

14.9

14.9

14.8

14.7

14.6

Head Press (psig)

534.2

535.5

537.6

540.0

543.3

125

Capacity (Btuh/1000)

86.4

96.5

107.2

118.5

130.2

Unit Power (kW)

17.1

16.9

16.8

16.6

16.5

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 267.7 215.6
7.8 305.5 204.2
8.9 346.9 192.5 10.1 392.0 180.4 11.4 440.9 168.1 12.9 493.3 155.6 14.6 548.9 142.5 16.4

Table 72. Gross cooling capacities (kW) both compressors - TTA1564DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1661.9

1686.8

1722.5

1761.8

1803.1

18.3

Capacity (kW)

39.1

43.2

47.7

52.5

57.7

Unit Power (kW)

8.0

7.9

7.9

7.9

7.9

Head Press (kPa)

1920.2

1945.7

1979.2

2020.0

2062.6

23.9

Capacity (kW)

37.0

40.9

45.2

49.8

54.6

Unit Power (kW)

9.0

9.0

9.0

8.9

8.9

Head Press (kPa)

2206.3

2232.2

2261.8

2304.0

2347.6

29.4

Capacity (kW)

34.9

38.6

42.6

46.9

51.5

Unit Power (kW)

10.2

10.2

10.1

10.1

10.1

Head Press (kPa)

2521.7

2547.7

2574.0

2614.5

2658.8

35

Capacity (kW)

32.6

36.1

39.9

44.0

48.3

Unit Power (kW)

11.6

11.5

11.5

11.5

11.4

Head Press (kPa)

2868.1

2893.6

2919.1

2951.8

2996.3

40.6

Capacity (kW)

30.2

33.6

37.1

40.9

45.0

Unit Power (kW)

13.1

13.1

13.0

13.0

12.9

Head Press (kPa)

3249.8

3272.0

3294.9

3318.1

3359.2

46.1

Capacity (kW)

27.8

30.9

34.3

37.8

41.6

Unit Power (kW)

14.9

14.9

14.8

14.7

14.6

Head Press (kPa)

3683.5

3692.1

3706.5

3723.4

3745.8

51.7

Capacity (kW)

25.3

28.3

31.4

34.7

38.2

Unit Power (kW)

17.1

16.9

16.8

16.6

16.5

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1845.9
63.2 7.8 2106.2 59.8 8.9 2391.7 56.4 10.1 2703.0 52.9 11.4 3040.0 49.3 12.9 3401.3 45.6 14.6 3784.4 41.8 16.4

76

SS-PRC029Y-EN

Performance Data

Table 73. Gross cooling capacities (MBH) TTA2014DD condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

267.6

274.1

280.2

285.3

288.8

65

Capacity (Btuh/1000)

197.5

217.1

237.8

259.4

280.7

Unit Power (kW)

12.0

12.2

12.4

12.7

12.9

Head Press (psig)

306.0

312.5

318.5

323.3

326.4

75

Capacity (Btuh/1000)

187.5

205.9

225.4

245.5

264.9

Unit Power (kW)

13.2

13.4

13.6

13.8

14.0

Head Press (psig)

347.9

354.5

360.3

364.8

367.4

85

Capacity (Btuh/1000)

176.6

194.1

212.3

231.0

248.6

Unit Power (kW)

14.5

14.7

14.9

15.1

15.3

Head Press (psig)

393.4

400.0

405.7

409.8

412.0

95

Capacity (Btuh/1000)

165.1

181.7

198.8

216.0

231.9

Unit Power (kW)

16.1

16.2

16.4

16.6

16.7

Head Press (psig)

442.5

449.0

454.5

458.2

459.8

105

Capacity (Btuh/1000)

153.2

168.9

184.8

200.7

214.8

Unit Power (kW)

17.9

18.0

18.1

18.3

18.4

Head Press (psig)

495.1

501.3

506.4

509.7

510.8

115

Capacity (Btuh/1000)

141.2

155.9

170.7

185.2

197.4

Unit Power (kW)

19.9

20.0

20.0

20.2

20.2

Head Press (psig)

553.2

556.3

560.9

563.5

563.9

125

Capacity (Btuh/1000)

129.3

142.8

156.3

168.8

179.0

Unit Power (kW)

22.1

22.1

22.1

22.2

22.2

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 290.5 299.2 13.0 327.6 280.8 14.1 368.1 262.1 15.4 412.3 243.2 16.8 461.0 224.9 18.4 512.4 205.9 20.2 565.3 185.8 22.2

Table 74. Gross cooling capacities (kW) TTA2014DD condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1845.3

1890.0

1931.9

1967.1

1991.4

18.3

Capacity (kW)

57.9

63.6

69.7

76.0

82.3

Unit Power (kW)

12.0

12.2

12.4

12.7

12.9

Head Press (kPa)

2109.8

2154.8

2195.9

2229.2

2250.5

23.9

Capacity (kW)

54.9

60.3

66.1

71.9

77.6

Unit Power (kW)

13.2

13.4

13.6

13.8

14.0

Head Press (kPa)

2398.7

2444.0

2484.2

2515.3

2533.5

29.4

Capacity (kW)

51.8

56.9

62.2

67.7

72.9

Unit Power (kW)

14.5

14.7

14.9

15.1

15.3

Head Press (kPa)

2712.5

2757.8

2796.9

2825.5

2840.3

35

Capacity (kW)

48.4

53.2

58.2

63.3

68.0

Unit Power (kW)

16.1

16.2

16.4

16.6

16.7

Head Press (kPa)

3050.8

3096.0

3133.4

3159.1

3170.5

40.6

Capacity (kW)

44.9

49.5

54.2

58.8

63.0

Unit Power (kW)

17.9

18.0

18.1

18.3

18.4

Head Press (kPa)

3413.5

3456.6

3491.6

3513.9

3521.5

46.1

Capacity (kW)

41.4

45.7

50.0

54.3

57.8

Unit Power (kW)

19.9

20.0

20.0

20.2

20.2

Head Press (kPa)

3814.3

3835.8

3867.3

3885.4

3888.1

51.7

Capacity (kW)

37.9

41.9

45.8

49.5

52.5

Unit Power (kW)

22.1

22.1

22.1

22.2

22.2

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 2003.0
87.7 13.0 2258.5 82.3 14.1 2537.7 76.8 15.4 2843.0 71.3 16.8 3178.6 65.9 18.4 3532.7 60.4 20.2 3897.7 54.4 22.2

SS-PRC029Y-EN

77

Performance Data

Table 75. Gross cooling capacities (MBH) one compressor - TTA2014DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

226.6

230.0

233.4

236.8

239.8

65

Capacity (Btuh/1000)

102.0

112.9

124.5

136.7

149.6

Unit Power (kW)

6.4

6.5

6.6

6.6

6.7

Head Press (psig)

262.6

266.2

269.7

273.2

276.2

75

Capacity (Btuh/1000)

97.3

107.7

118.8

130.5

142.7

Unit Power (kW)

6.9

7.0

7.0

7.1

7.2

Head Press (psig)

302.3

306.0

309.6

313.1

316.0

85

Capacity (Btuh/1000)

92.1

102.0

112.6

123.6

135.1

Unit Power (kW)

7.4

7.5

7.6

7.7

7.8

Head Press (psig)

345.8

349.6

353.3

356.7

359.5

95

Capacity (Btuh/1000)

86.4

95.7

105.6

116.0

126.8

Unit Power (kW)

8.1

8.2

8.3

8.4

8.5

Head Press (psig)

393.4

397.2

400.8

404.1

406.6

105

Capacity (Btuh/1000)

80.1

88.9

98.2

107.8

117.7

Unit Power (kW)

8.9

9.0

9.1

9.2

9.2

Head Press (psig)

445.2

448.9

452.3

455.3

457.6

115

Capacity (Btuh/1000)

73.6

81.7

90.3

99.2

108.1

Unit Power (kW)

9.7

9.8

9.9

10.0

10.1

Head Press (psig)

501.4

504.8

507.9

510.5

512.3

125

Capacity (Btuh/1000)

66.8

74.3

82.1

90.3

98.2

Unit Power (kW)

10.7

10.8

10.9

10.9

11.0

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 242.1 162.7
6.7 278.4 155.1
7.3 318.1 146.6
7.9 361.3 137.3
8.5 408.2 127.2
9.3 458.8 116.4 10.1 513.1 105.0 11.1

Table 76. Gross cooling capacities (kW) one compressor - TTA2014DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1562.2

1585.6

1609.3

1632.5

1653.3

18.3

Capacity (kW)

29.9

33.1

36.5

40.1

43.8

Unit Power (kW)

6.4

6.5

6.6

6.6

6.7

Head Press (kPa)

1810.5

1835.1

1859.7

1883.4

1904.2

23.9

Capacity (kW)

28.5

31.6

34.8

38.3

41.8

Unit Power (kW)

6.9

7.0

7.0

7.1

7.2

Head Press (kPa)

2084.2

2109.6

2134.9

2158.6

2179.0

29.4

Capacity (kW)

27.0

29.9

33.0

36.2

39.6

Unit Power (kW)

7.4

7.5

7.6

7.7

7.8

Head Press (kPa)

2384.5

2410.4

2435.8

2459.2

2478.6

35

Capacity (kW)

25.3

28.1

31.0

34.0

37.1

Unit Power (kW)

8.1

8.2

8.3

8.4

8.5

Head Press (kPa)

2712.6

2738.6

2763.5

2785.9

2803.7

40.6

Capacity (kW)

23.5

26.1

28.8

31.6

34.5

Unit Power (kW)

8.9

9.0

9.1

9.2

9.2

Head Press (kPa)

3069.6

3094.8

3118.6

3139.2

3154.8

46.1

Capacity (kW)

21.6

23.9

26.5

29.1

31.7

Unit Power (kW)

9.7

9.8

9.9

10.0

10.1

Head Press (kPa)

3457.2

3480.5

3502.0

3519.9

3532.4

51.7

Capacity (kW)

19.6

21.8

24.1

26.5

28.8

Unit Power (kW)

10.7

10.8

10.9

10.9

11.0

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1669.3
47.7 6.7 1919.5 45.5 7.3 2193.3 43.0 7.9 2491.4 40.2 8.5 2814.5 37.3 9.3 3163.1 34.1 10.1 3537.7 30.8 11.1

78

SS-PRC029Y-EN

Performance Data

Table 77. Gross cooling capacities (MBH) both compressors - TTA2014DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

276.5

278.9

285.4

292.5

297.5

65

Capacity (Btuh/1000)

204.2

225.2

247.4

270.3

292.9

Unit Power (kW)

12.8

13.0

13.3

13.5

13.8

Head Press (psig)

317.1

319.0

324.7

331.6

336.2

75

Capacity (Btuh/1000)

193.8

213.8

234.6

256.1

276.8

Unit Power (kW)

14.0

14.2

14.4

14.7

15.0

Head Press (psig)

361.6

362.9

367.2

373.8

377.8

85

Capacity (Btuh/1000)

182.4

201.3

220.7

240.6

259.5

Unit Power (kW)

15.5

15.6

15.8

16.1

16.3

Head Press (psig)

410.1

410.5

412.9

419.1

422.4

95

Capacity (Btuh/1000)

169.9

187.8

205.8

224.2

241.3

Unit Power (kW)

17.1

17.2

17.3

17.6

17.8

Head Press (psig)

462.7

461.9

461.9

467.5

469.9

105

Capacity (Btuh/1000)

157.2

173.9

190.4

207.2

222.4

Unit Power (kW)

18.9

18.9

19.0

19.2

19.4

Head Press (psig)

519.8

517.4

515.0

518.8

520.2

115

Capacity (Btuh/1000)

145.1

160.4

175.3

190.4

203.5

Unit Power (kW)

20.8

20.8

20.8

21.0

21.1

Head Press (psig)

582.2

577.6

573.4

573.3

573.4

125

Capacity (Btuh/1000)

135.4

148.9

161.7

174.2

184.8

Unit Power (kW)

23.0

22.9

22.8

22.8

22.9

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 299.1 312.1 13.9 337.0 293.7 15.1 377.8 273.9 16.4 421.5 253.1 17.9 468.0 231.6 19.4 517.3 209.7 21.1 569.3 188.0 22.8

Table 78. Gross cooling capacities (kW) both compressors - TTA2014DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1906.4

1922.6

1967.8

2016.5

2051.5

18.3

Capacity (kW)

59.8

66.0

72.5

79.2

85.8

Unit Power (kW)

12.8

13.0

13.3

13.5

13.8

Head Press (kPa)

2186.3

2199.6

2238.5

2286.2

2317.9

23.9

Capacity (kW)

56.8

62.7

68.8

75.1

81.1

Unit Power (kW)

14.0

14.2

14.4

14.7

15.0

Head Press (kPa)

2492.9

2501.9

2531.7

2577.4

2604.9

29.4

Capacity (kW)

53.4

59.0

64.7

70.5

76.1

Unit Power (kW)

15.5

15.6

15.8

16.1

16.3

Head Press (kPa)

2827.3

2830.1

2847.1

2889.8

2912.3

35

Capacity (kW)

49.8

55.0

60.3

65.7

70.7

Unit Power (kW)

17.1

17.2

17.3

17.6

17.8

Head Press (kPa)

3190.5

3184.7

3184.6

3223.1

3239.6

40.6

Capacity (kW)

46.1

51.0

55.8

60.7

65.2

Unit Power (kW)

18.9

18.9

19.0

19.2

19.4

Head Press (kPa)

3584.2

3567.3

3550.7

3577.2

3586.6

46.1

Capacity (kW)

42.5

47.0

51.4

55.8

59.6

Unit Power (kW)

20.8

20.8

20.8

21.0

21.1

Head Press (kPa)

4014.4

3982.5

3953.4

3952.5

3953.7

51.7

Capacity (kW)

39.7

43.6

47.4

51.0

54.2

Unit Power (kW)

23.0

22.9

22.8

22.8

22.9

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 2061.9
91.5 13.9 2323.3 86.1 15.1 2604.7 80.3 16.4 2906.0 74.2 17.9 3226.8 67.9 19.4 3566.9 61.5 21.1 3925.2 55.1 22.8

SS-PRC029Y-EN

79

Performance Data

Table 79. Gross cooling capacities (MBH) one compressor - TTA2514DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

232.0

235.4

239.4

243.5

247.4

65

Capacity (Btuh/1000)

117.1

129.1

141.9

155.4

169.7

Unit Power (kW)

7.4

7.5

7.6

7.6

7.7

Head Press (psig)

268.9

272.3

276.5

280.7

284.7

75

Capacity (Btuh/1000)

112.2

123.8

136.0

149.0

162.8

Unit Power (kW)

8.0

8.1

8.2

8.3

8.4

Head Press (psig)

309.6

312.8

317.2

321.5

325.5

85

Capacity (Btuh/1000)

106.6

117.6

129.3

141.8

154.9

Unit Power (kW)

8.7

8.8

8.9

9.0

9.1

Head Press (psig)

354.4

357.2

361.7

366.0

369.8

95

Capacity (Btuh/1000)

100.3

110.7

121.8

133.6

145.9

Unit Power (kW)

9.5

9.6

9.7

9.8

9.9

Head Press (psig)

403.4

405.7

410.0

414.2

417.8

105

Capacity (Btuh/1000)

93.2

103.1

113.6

124.6

136.1

Unit Power (kW)

10.5

10.5

10.7

10.8

10.9

Head Press (psig)

457.0

458.9

462.3

466.2

469.4

115

Capacity (Btuh/1000)

85.7

95.0

104.8

115.1

125.7

Unit Power (kW)

11.5

11.6

11.7

11.8

11.9

Head Press (psig)

515.7

516.8

518.6

522.1

524.8

125

Capacity (Btuh/1000)

78.1

86.7

95.8

105.3

114.9

Unit Power (kW)

12.7

12.7

12.8

12.9

13.0

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 250.8 184.6
7.8 288.0 177.0
8.4 328.6 168.3
9.2 372.7 158.4 10.0 420.4 147.7 11.0 471.5 136.1 12.0 526.2 124.2 13.1

Table 80. Gross cooling capacities (kW) one compressors - TTA2514DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

1599.3

1622.8

1650.5

1678.6

1705.7

18.3

Capacity (kW)

34.3

37.8

41.6

45.5

49.7

Unit Power (kW)

7.4

7.5

7.6

7.6

7.7

Head Press (kPa)

1854.0

1877.2

1906.3

1935.5

1962.9

23.9

Capacity (kW)

32.9

36.3

39.9

43.7

47.7

Unit Power (kW)

8.0

8.1

8.2

8.3

8.4

Head Press (kPa)

2134.9

2156.9

2187.1

2216.8

2244.0

29.4

Capacity (kW)

31.2

34.5

37.9

41.6

45.4

Unit Power (kW)

8.7

8.8

8.9

9.0

9.1

Head Press (kPa)

2443.6

2463.0

2493.7

2523.3

2549.8

35

Capacity (kW)

29.4

32.4

35.7

39.2

42.8

Unit Power (kW)

9.5

9.6

9.7

9.8

9.9

Head Press (kPa)

2781.6

2797.3

2826.9

2855.7

2880.6

40.6

Capacity (kW)

27.3

30.2

33.3

36.5

39.9

Unit Power (kW)

10.5

10.5

10.7

10.8

10.9

Head Press (kPa)

3150.9

3163.8

3187.3

3214.3

3236.7

46.1

Capacity (kW)

25.1

27.8

30.7

33.7

36.8

Unit Power (kW)

11.5

11.6

11.7

11.8

11.9

Head Press (kPa)

3555.8

3563.0

3575.6

3599.6

3618.1

51.7

Capacity (kW)

22.9

25.4

28.1

30.9

33.7

Unit Power (kW)

12.7

12.7

12.8

12.9

13.0

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 1729.2
54.1 7.8 1985.8 51.9 8.4 2265.9 49.3 9.2 2569.9 46.4 10.0 2898.2 43.3 11.0 3250.9 39.9 12.0 3628.1 36.4 13.1

80

SS-PRC029Y-EN

Performance Data

Table 81. Gross cooling capacities (MBH) both compressors - TTA2514DC condensing unit only (IP)

Outdoor Temp (°F)

Suction Temperature (°F)

30

35

40

45

50

Head Press (psig)

306.8

309.2

310.8

311.7

317.9

65

Capacity (Btuh/1000)

236.7

260.8

285.6

310.5

336.4

Unit Power (kW)

16.0

16.2

16.3

16.4

16.7

Head Press (psig)

350.8

352.4

353.2

353.2

358.3

75

Capacity (Btuh/1000)

224.9

247.9

271.6

295.1

319.2

Unit Power (kW)

17.7

17.8

17.9

18.0

18.2

Head Press (psig)

399.0

399.4

399.1

398.0

401.7

85

Capacity (Btuh/1000)

211.5

233.4

255.9

278.2

300.3

Unit Power (kW)

19.5

19.6

19.7

19.7

19.9

Head Press (psig)

451.3

450.2

448.5

446.2

447.9

95

Capacity (Btuh/1000)

197.4

218.1

239.3

260.2

280.4

Unit Power (kW)

21.6

21.6

21.7

21.6

21.8

Head Press (psig)

507.7

504.8

501.5

497.6

496.8

105

Capacity (Btuh/1000)

184.2

203.5

223.2

242.2

260.2

Unit Power (kW)

23.9

23.8

23.8

23.7

23.8

Head Press (psig)

568.1

563.1

558.1

552.6

548.5

115

Capacity (Btuh/1000)

174.3

191.7

209.1

225.7

240.6

Unit Power (kW)

26.4

26.2

26.1

25.9

25.8

Head Press (psig)

633.8

627.0

620.0

612.4

604.1

125

Capacity (Btuh/1000)

171.2

185.5

199.5

212.3

222.6

Unit Power (kW)

29.0

28.8

28.6

28.3

28.1

Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

55 323.5 361.7 16.9 363.1 342.3 18.5 405.5 321.4 20.1 450.5 299.3 22.0 498.1 276.8 23.9 548.4 254.3 25.9 601.2 232.5 28.0

Table 82. Gross cooling capacities (kW) both compressors - TTA2514DC condensing unit only (SI)

Outdoor Temp (°C)

-1.1

Suction Temperature (°C)

1.7

4.4

7.2

10

Head Press (kPa)

2115.6

2131.8

2143.0

2148.8

2191.9

18.3

Capacity (kW)

69.4

76.4

83.7

91.0

98.6

Unit Power (kW)

16.0

16.2

16.3

16.4

16.7

Head Press (kPa)

2418.8

2429.5

2435.2

2435.2

2470.7

23.9

Capacity (kW)

65.9

72.6

79.6

86.5

93.5

Unit Power (kW)

17.7

17.8

17.9

18.0

18.2

Head Press (kPa)

2750.7

2753.7

2751.8

2744.4

2769.5

29.4

Capacity (kW)

62.0

68.4

75.0

81.5

88.0

Unit Power (kW)

19.5

19.6

19.7

19.7

19.9

Head Press (kPa)

3111.8

3104.3

3092.6

3076.3

3087.9

35

Capacity (kW)

57.8

63.9

70.1

76.2

82.2

Unit Power (kW)

21.6

21.6

21.7

21.6

21.8

Head Press (kPa)

3500.7

3480.4

3457.4

3431.0

3425.4

40.6

Capacity (kW)

54.0

59.6

65.4

71.0

76.3

Unit Power (kW)

23.9

23.8

23.8

23.7

23.8

Head Press (kPa)

3916.7

3882.7

3847.8

3810.3

3782.0

46.1

Capacity (kW)

51.1

56.2

61.3

66.1

70.5

Unit Power (kW)

26.4

26.2

26.1

25.9

25.8

Head Press (kPa)

4370.0

4323.3

4274.9

4222.6

4165.2

51.7

Capacity (kW)

50.2

54.4

58.5

62.2

65.2

Unit Power (kW)

29.0

28.8

28.6

28.3

28.1

Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

12.8 2230.1 106.0
16.9 2503.4 100.3
18.5 2795.5
94.2 20.1 3106.0 87.7 22.0 3434.4 81.1 23.9 3780.9 74.5 25.9 4145.4 68.1 28.0

SS-PRC029Y-EN

81

Performance Data

Fan Performance
Table 83. Evaporator fan performance -- TWE051 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor

1.5 HP High Static Motor

1600 -- -- -- -- 550 0.33 629 0.39 695 0.46 747 0.52 807 0.72 854 0.77 887 0.80 906 0.81 912 0.82

1700 -- -- -- -- 559 0.35 634 0.43 697 0.48 751 0.61 809 0.75 857 0.81 894 0.84 920 0.87 985 1.07

1800 -- -- -- -- 569 0.38 640 0.46 701 0.53 756 0.64 813 0.77 861 0.85 901 0.90 952 1.07 991 1.14

1900 -- -- -- -- 578 0.41 647 0.50 707 0.58 761 0.68 817 0.81 866 0.90 912 1.01 957 1.13 996 1.21

2000 -- -- 522 0.34 590 0.45 654 0.52 711 1 768 0.73 821 0.84 870 0.95 917 1.06 962 1.20 1002 1.27

2100 -- -- 534 0.38 599 0.48 662 0.59 719 0.67 774 0.77 826 0.88 875 1.00 921 1.11 968 1.27 1007 1.35

2200 474 0.30 547 0.43 610 0.52 671 0.64 727 0.72 781 0.82 832 0.93 881 1.06 926 1.17 973 1.33 1013 1.42

2300 489 0.35 560 0.47 621 0.56 680 0.69 736 0.77 788 0.87 838 0.98 886 1.12 932 1.23 979 1.40 1018 1.50

2400 505 0.41 573 0.52 632 0.61 690 0.74 745 0.83 796 0.93 844 1.04 893 1.18 937 1.30 969 1.47 1023 1.57 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Ultra High Static Motor

1600 1018 1.09 1060 1.21 1094 1.29 -- -- -- -- -- --
1700 1024 1.16 1065 1.28 1099 1.37 -- -- -- -- -- --
1800 1029 1.24 1070 1.35 1105 1.45 -- -- -- -- -- --
1900 1035 1.31 1075 1.42 1110 1.53 -- -- -- -- -- --
2000 1040 1.38 1080 1.50 1116 1.61 -- -- -- -- -- --
2100 1046 1.46 1085 1.58 1122 1.69 -- -- -- -- -- --
2200 1052 1.54 1090 1.66 -- -- -- -- -- -- -- --
2300 1057 1.62 1095 1.74 -- -- -- -- -- -- -- --
2400 1063 1.70 1101 1.82 -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

Table 84. Evaporator fan performance -- TWE051 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

0.38 kW Standard Motor

.75 kW High Static Motor

2379 2549 2719

612 0.15 674 0.18 731 0.22 786 0.25 840 0.29 891 0.34 941 0.38 989 0.43 1034 0.48 1077 0.53 1117 0.58 647 0.18 705 0.21 760 0.25 812 0.29 863 0.33 912 0.37 960 0.42 1006 0.47 1051 0.52 1094 0.58 -- -- 683 0.21 738 0.25 790 0.29 840 0.33 888 0.37 936 0.42 980 0.46 1025 0.51 1070 0.57 1111 0.62 -- --

2889 719 0.25 771 0.29 821 0.33 869 0.37 914 0.41 959 0.46 1003 0.51 1047 0.56 1089 0.61 -- -- -- -- 3059 756 0.29 804 0.33 853 0.37 898 0.42 942 0.46 985 0.51 1028 0.56 1068 0.61 1109 0.66 -- -- -- --

3228 792 0.34 838 0.38 884 0.42 928 0.47 971 0.52 1012 0.57 1052 0.62 1092 0.67 -- -- -- -- -- --

3398 829 0.39 873 0.43 917 0.48 959 0.53 1000 0.58 1040 0.63 1079 0.68 1117 0.73 -- -- -- -- -- --
3568 866 0.45 908 0.49 950 0.54 991 0.59 1030 0.64 1069 0.69 1106 0.75 1144 0.80 -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

82

SS-PRC029Y-EN

Performance Data

Table 85. Evaporator fan performance -- TWE072 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor

1.5 HP High Static Motor

1600 -- -- -- -- 550 0.33 629 0.39 695 0.46 747 0.52 807 0.72 854 0.77 887 0.80 906 0.81 912 0.82

1700 -- -- -- -- 559 0.35 634 0.43 697 0.48 751 0.61 809 0.75 857 0.81 894 0.84 920 0.87 985 1.07

1800 -- -- -- -- 569 0.38 640 0.46 701 0.53 756 0.64 813 0.77 861 0.85 901 0.90 952 1.07 991 1.14

1900 -- -- -- -- 578 0.41 647 0.50 707 0.58 761 0.68 817 0.81 866 0.90 912 1.01 957 1.13 996 1.21

2000 -- -- 522 0.34 590 0.45 654 0.52 711 1 768 0.73 821 0.84 870 0.95 917 1.06 962 1.20 1002 1.27

2100 -- -- 534 0.38 599 0.48 662 0.59 719 0.67 774 0.77 826 0.88 875 1.00 921 1.11 968 1.27 1007 1.35

2200 474 0.30 547 0.43 610 0.52 671 0.64 727 0.72 781 0.82 832 0.93 881 1.06 926 1.17 973 1.33 1013 1.42

2300 489 0.35 560 0.47 621 0.56 680 0.69 736 0.77 788 0.87 838 0.98 886 1.12 932 1.23 979 1.40 1018 1.50

2400 505 0.41 573 0.52 632 0.61 690 0.74 745 0.83 796 0.93 844 1.04 893 1.18 937 1.30 969 1.47 1023 1.57

External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Ultra High Static Motor

1600 1018 1.09 1060 1.21 1094 1.29 -- -- -- -- -- --
1700 1024 1.16 1065 1.28 1099 1.37 -- -- -- -- -- --
1800 1029 1.24 1070 1.35 1105 1.45 -- -- -- -- -- --
1900 1035 1.31 1075 1.42 1110 1.53 -- -- -- -- -- --
2000 1040 1.38 1080 1.50 1116 1.61 -- -- -- -- -- --
2100 1046 1.46 1085 1.58 1122 1.69 -- -- -- -- -- --
2200 1052 1.54 1090 1.66 -- -- -- -- -- -- -- --
2300 1057 1.62 1095 1.74 -- -- -- -- -- -- -- --
2400 1063 1.70 1101 1.82 -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

83

Performance Data

Table 86. Evaporator fan performance -- TWE072 -- air handler (SI)
External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

.75 kW Standard Motor

1.12 kW High Static Motor

1.5 kW Ultra High Static Motor

2718 -- -- -- -- 550 0.25 629 0.29 695 0.34 747 0.39 807 0.54 854 0.58 887 0.60 906 0.61 912 0.61

2888 -- -- -- -- 559 0.26 634 0.32 697 0.36 751 0.45 809 0.56 857 0.61 894 0.62 920 0.65 985 0.80

3058 -- -- -- -- 569 0.29 640 0.34 701 0.39 756 0.48 813 0.58 861 0.64 901 0.67 952 0.80 991 0.85

3228 -- -- -- -- 578 0.31 647 0.37 707 0.43 761 0.51 817 0.60 866 0.67 912 0.75 957 0.84 996 0.90

3398 -- -- 522 0.26 590 0.34 654 0.39 711 0.46 768 0.54 821 0.63 870 0.71 917 0.79 962 0.89 1002 0.95

3568 -- -- 534 0.29 599 0.36 662 0.44 719 0.50 774 0.57 826 0.66 875 0.75 921 0.83 968 0.94 1007 1.01

3738 474 0.22 547 0.32 610 0.39 671 0.47 727 0.54 781 0.61 832 0.69 881 0.79 926 0.87 973 1.00 1013 1.06

3908 489 0.26 560 0.35 621 0.42 680 0.51 736 0.58 788 0.65 838 0.73 886 0.83 932 0.92 979 1.05 1018 1.12

4078 505 0.30 573 0.39 632 0.46 690 0.55 745 0.62 796 0.69 844 0.78 893 0.88 937 0.97 969 1.10 1023 1.17

External Static Pressure (Pascals)

299

324

349

m3/hr RPM kW RPM kW RPM kW

1.5 kW Ultra High Static Motor

2718 1018 0.81 1060 0.90 1094 0.96
2888 1024 0.87 1065 0.95 1099 1.02
3058 1029 0.92 1070 1.00 1105 1.08
3228 1035 0.98 1075 1.06 1110 1.14
3398 1040 1.03 1080 1.12 1116 1.20
3568 1046 1.09 1085 1.18 1122 1.26
3738 1052 1.15 1090 1.24 -- --
3908 1057 1.21 1095 1.30 -- --
4078 1063 1.27 1101 1.36 -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

84

SS-PRC029Y-EN

Performance Data

Table 87. Evaporator fan performance -- TWE076 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor

1.5 HP High Static Motor

2 HP Ultra High Static Motor

2000 -- -- 522 0.34 590 0.44 654 0.52 711 0.62 768 0.73 821 0.84 870 0.95 916 1.06 959 1.16 1001 1.27

2125 -- -- 537 0.39 604 0.48 664 0.58 721 0.68 775 0.78 828 0.90 877 1.01 923 1.13 966 1.25 1009 1.36

2250 481 0.33 553 0.44 617 0.53 675 0.64 731 0.74 784 0.84 834 0.96 884 1.09 929 1.21 973 1.33 1016 1.46

2375 501 0.39 569 0.49 631 0.59 688 0.70 742 0.81 794 0.91 842 1.03 891 1.16 937 1.29 981 1.42 1022 1.55

2500 521 0.47 585 0.55 646 0.65 701 0.77 754 0.89 804 0.99 852 1.11 898 1.23 944 1.37 987 1.51 1028 1.64

2625 540 0.53 602 0.61 661 0.72 715 0.84 767 0.97 816 1.08 862 1.19 908 1.32 950 1.45 994 1.60 1036 1.74

2750 559 0.60 619 0.66 677 0.80 729 0.91 780 1.05 827 1.17 872 1.29 916 1.41 960 1.55 1001 1.69 1043 1.84

2875 579 0.67 636 0.72 692 0.88 744 1.00 793 1.13 840 1.27 885 1.40 928 1.52 969 1.65 1009 1.79 1049 1.94

3000 599 0.74 654 0.79 709 0.96 760 1.09 807 1.22 852 1.36 896 1.51 939 1.63 980 1.76 1019 1.90 1057 2.05 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Ultra High Static Motor

2000 1040 1.38 1080 1.50 1116 1.61 -- -- -- -- -- -- 2125 1048 1.48 1085 1.59 1123 1.71 -- -- -- -- -- -- 2250 1054 1.58 1093 1.70 -- -- -- -- -- -- -- --

2375 1062 1.68 1099 1.80 -- -- -- -- -- -- -- -- 2500 1068 1.78 1107 1.92 -- -- -- -- -- -- -- --

2625 1075 1.88 1113 2.02 -- -- -- -- -- -- -- --

2750 1083 1.99 -- -- -- -- -- -- -- -- -- -- 2875 1090 2.10 -- -- -- -- -- -- -- -- -- --

3000 1097 2.21 -- -- -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

85

Performance Data

Table 88. Evaporator fan performance -- TWE076 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

.75 kW Standard Motor

1.12 kW High Static Motor

1.5 kW Ultra High Static Motor

3398 -- 0.18 522 0.25 590 0.33 654 0.39 711 0.46 768 0.54 821 0.62 870 0.71 916 0.79 959 0.87 1001 0.95

3611 -- 0.21 537 0.29 604 0.36 664 0.43 721 0.50 775 0.58 828 0.67 877 0.76 923 0.84 966 0.93 1009 1.02

3823 481 0.24 553 0.32 617 0.40 675 0.48 731 0.55 784 0.63 834 0.72 884 0.81 929 0.90 973 0.99 1016 1.09

4036 501 0.29 569 0.36 631 0.44 688 0.53 742 0.60 794 0.68 842 0.77 891 0.87 937 0.96 981 1.06 1022 1.15

4248 521 0.35 585 0.41 646 0.49 701 0.57 754 0.66 804 0.74 852 0.83 898 0.92 944 1.02 987 1.12 1028 1.22

4460 540 0.40 602 0.46 661 0.54 715 0.62 767 0.72 816 0.81 862 0.89 908 0.99 950 1.08 994 1.19 1036 1.30

4673 559 0.45 619 0.50 677 0.59 729 0.68 780 0.78 827 0.88 872 0.96 916 1.05 960 1.15 1001 1.26 1043 1.37

4885 579 0.50 636 0.54 692 0.65 744 0.74 793 0.84 840 0.95 885 1.04 928 1.13 969 1.23 1009 1.33 1049 1.45

5098 599 0.55 654 0.59 709 0.72 760 0.81 807 0.91 852 1.02 896 1.12 939 1.22 980 1.32 1019 1.42 1057 1.53 External Static Pressure (Pascals)

299

324

349

m3/hr RPM kW RPM kW RPM kW

1.5 kW Ultra High Static Motor

3398 3611 3823

1040 1.03 1080 1.12 1116 1.20 1048 1.10 1085 1.19 1123 1.28 1054 1.18 1093 1.27 -- --

4036 1062 1.25 1099 1.35 -- -- 4248 1068 1.33 1107 1.43 -- --

4460 1075 1.40 1113 1.51 -- --

4673 1083 1.49 -- -- -- -- 4885 1090 1.57 -- -- -- --

5098 1097 1.65 -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

86

SS-PRC029Y-EN

Performance Data

Table 89. Evaporator fan performance -- TWE101 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP Standard Motor

2 HP High Static Motor

2600 ­

­

­

­

524 0.46 564 0.52 602 0.59 639 0.66 675 0.73 710 0.81 745 0.90 779 0.98 812 1.07

2775 ­

­

497 0.46 542 0.52 581 0.60 618 0.67 653 0.74 687 0.81 721 0.89 754 0.97 787 1.07 819 1.16

2950 ­

­

518 0.53 560 0.60 599 0.68 635 0.75 669 0.83 701 0.90 733 0.98 765 1.07 796 1.16 827 1.25

3125 498 0.54 540 0.62 578 0.68 617 0.76 652 0.84 685 0.92 717 1.00 747 1.08 778 1.17 808 1.26 837 1.35

3300 521 0.63 562 0.71 597 0.78 636 0.86 670 0.95 702 1.03 733 1.12 763 1.20 792 1.28 820 1.37 849 1.47

3475 544 0.73 583 0.81 618 0.89 654 0.97 688 1.06 720 1.15 750 1.23 779 1.32 806 1.41 834 1.50 861 1.59

3650 567 0.83 605 0.92 639 1.01 672 1.08 707 1.18 738 1.27 767 1.36 795 1.46 823 1.55 849 1.64 875 1.73

3825 591 0.95 627 1.04 661 1.14 691 1.21 725 1.30 756 1.40 785 1.50 813 1.60 839 1.70 865 1.79 890 1.89

4000 614 1.07 650 1.18 683 1.27 712 1.36 742 1.44 774 1.55 803 1.65 830 1.75 856 1.86 881 1.96 906 2.06 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

1.80"

1.90"

2.00"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP High Static Motor w/ Field Supplied Sheave & Belt

2600 843 1.16 873 1.24 902 1.33 930 1.41 956 1.50 982 1.59 1008 1.67 1032 1.76 1056 1.84

2775 851 1.25 880 1.34 909 1.44 937 1.53 964 1.62 990 1.71 1015 1.80 1040 1.89 1064 1.99

2950 858 1.35 888 1.45 917 1.55 944 1.64 971 1.74 997 1.84 1023 1.94 1047 2.04 1071 2.13

3125
3300
3475
3650
3825
4000 Notes:
1. 2. 3.

866 1.45 876 1.57 888 1.69 901 1.83 915 1.99 930 2.16

895 1.55 904 1.67 915 1.80 927 1.93 940 2.09 954 2.26

924 1.66 932 1.78 941 1.90 952 2.04 965 2.20 978 2.36

952 1.76 979 1.87 1005 1.97 1030 2.07 1055 2.18 1078 2.28

959 1.89 986 2.00 1012 2.11 1037 2.22 1062 2.33 ­

­

967 2.01 994 2.13 1020 2.25 1045 2.36 ­

­

­

­

977 2.15 1002 2.27 ­

­

­

­

­

­

­

­

989 2.31 ­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

­

Data includes pressure drop due to wet coil and 1" filter. Fan motor heat (MBh) = 3.15 x BHP. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

87

Performance Data

Table 90. Evaporator fan performance -- TWE101 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

1.5 HP Standard Motor

2 HP High Static Motor

4418 ­

­

­

­ 524 0.34 564 0.39 602 0.44 639 0.49 675 0.54 710 0.60 745 0.67 779 0.73 812 0.80

4715 ­

­

497 0.34 542 0.39 581 0.44 618 0.50 653 0.55 687 0.60 721 0.66 754 0.73 787 0.79 819 0.86

5013 ­

­

518 0.40 560 0.45 599 0.50 635 0.56 669 0.62 701 0.67 733 0.73 765 0.79 796 0.86 827 0.93

5310 498 0.41 540 0.46 578 0.51 617 0.57 652 0.63 685 0.69 717 0.75 747 0.81 778 0.87 808 0.94 837 1.01

5607 521 0.47 562 0.53 597 0.58 636 0.64 670 0.70 702 0.77 733 0.83 763 0.89 792 0.96 820 1.02 849 1.09

5905 544 0.54 583 0.61 618 0.66 654 0.72 688 0.79 720 0.85 750 0.92 779 0.99 806 1.05 834 1.12 861 1.19

6202 567 0.62 605 0.69 639 0.75 672 0.81 707 0.88 738 0.95 767 1.02 795 1.09 823 1.15 849 1.22 875 1.29

6499 591 0.71 627 0.78 661 0.85 691 0.90 725 0.97 756 1.05 785 1.12 813 1.19 839 1.27 865 1.34 890 1.41

6797 614 0.80 650 0.88 683 0.95 712 1.01 742 1.08 774 1.15 803 1.23 830 1.31 856 1.38 881 1.46 906 1.53 External Static Pressure (Pascals)

299

324

349

374

398

423

448

473

498

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW rpm kW

2 HP High Static Motor w/ Field Supplied Sheave & Belt

4418 843 0.86 873 0.93 902 0.99 930 1.05 956 1.12 982 1.18 1008 1.25 1032 1.31 1056 1.38

4715 851 0.93 880 1.00 909 1.07 937 1.14 964 1.21 990 1.28 1015 1.34 1040 1.41 1064 1.48

5013 858 1.01 888 1.08 917 1.15 944 1.23 971 1.30 997 1.37 1023 1.44 1047 1.52 1071 1.59

5310 866 1.08 895 1.16 924 1.24 952 1.32 979 1.39 1005 1.47 1030 1.55 1055 1.62 1078 1.70

5607 876 1.17 904 1.24 932 1.32 959 1.41 986 1.49 1012 1.57 1037 1.65 1062 1.73 ­

­

5905 888 1.26 915 1.34 941 1.42 967 1.50 994 1.59 1020 1.67 1045 1.76 ­

­

­

­

6202 901 1.37 927 1.44 952 1.52 977 1.61 1002 1.69 ­

­

­

­

­

­

­

­

6499 915 1.48 940 1.56 965 1.64 989 1.72 ­

­

­

­

­

­

­

­

­

­

6797 930 1.61 954 1.68 978 1.76 ­

­

­

­

­

­

­

­

­

­

­

­

Notes:

1. Data includes pressure drop due to wet coil and 1" filter.

2. Fan motor heat (kW) = 1.238 x kW.

3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and

continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance

tripping or premature motor failure. Our product's warranty will not be affected.

88

SS-PRC029Y-EN

Performance Data

Table 91. Evaporator fan performance --TWE126 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP Standard Motor w/

2 HP High Static

1.5 HP Standard Motor

Field Supplied Sheave & Belt

Motor

3200 -- -- -- -- 515 0.51 565 0.63 601 0.71 638 0.81 678 0.93 718 1.06 759 1.21 794 1.35 826 1.49

3400 -- -- 472 0.46 528 0.57 578 0.69 617 0.80 650 0.89 686 1.00 724 1.13 762 1.27 800 1.42 834 1.57

3600 -- -- 486 0.51 541 0.63 590 0.76 633 0.89 666 0.98 697 1.08 732 1.20 767 1.34 804 1.49 840 1.65

3800 -- -- 500 0.57 554 0.70 601 0.82 646 0.97 682 1.09 712 1.19 742 1.29 776 1.43 810 1.57 843 1.72

4000 -- -- 515 0.64 567 0.78 614 0.91 658 1.05 698 1.20 728 1.31 756 1.41 786 1.53 817 1.66 849 1.82

4200 477 0.58 531 0.71 581 0.85 627 1.00 669 1.13 710 1.29 744 1.43 772 1.55 799 1.65 827 1.78 858 1.93

4400 494 0.65 546 0.79 595 0.94 640 1.09 682 1.23 722 1.39 758 1.55 789 1.69 814 1.80 840 1.92 867 2.05

4600 513 0.73 563 0.87 609 1.03 653 1.19 695 1.34 732 1.48 771 1.66 804 1.83 831 1.96 856 2.08 880 2.20

4800 531 0.82 579 0.96 624 1.13 667 1.29 707 1.45 745 1.60 783 1.77 817 1.96 847 2.12 872 2.25 896 2.37 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP High Static

Motor

3 HP Ultra High Static Motor

3200 857 1.63 887 1.78 916 1.93 943 2.08 970 2.23 996 2.39

3400 865 1.72 895 1.88 924 2.03 952 2.19 978 2.35 1003 2.50

3600 873 1.81 903 1.97 931 2.13 959 2.29 986 2.46 1012 2.62

3800 877 1.89 912 2.08 940 2.24 967 2.41 994 2.58 -- --

4000 882 1.98 915 2.16 947 2.34 976 2.53 1002 2.70 -- --

4200 888 2.08 919 2.25 950 2.44 980 2.63 1010 2.82 -- --

4400 896 2.20 925 2.37 955 2.55 985 2.73 1013 2.92 -- --

4600 906 2.34 934 2.50 961 2.67 989 2.85 -- -- -- --

4800 918 2.50 944 2.65 970 2.81 996 2.98 -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

89

Performance Data

Table 92. Evaporator fan performance -- TWE126 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

1.12 kW Standard Motor

1.12 kW Standard Motor w/ 1.49 kW High Static

Field Supplied Sheave & Belt

Motor

5437 -- -- -- -- 515 0.38 565 0.47 601 0.53 638 0.60 678 0.69 718 0.79 759 0.90 794 1.01 826 1.11

5777 -- -- 472 0.34 528 0.42 578 0.52 617 0.60 650 0.66 686 0.74 724 0.84 762 0.94 800 1.06 834 1.17

6117 -- -- 486 0.38 541 0.47 590 0.56 633 0.66 666 0.73 697 0.81 732 0.90 767 1.00 804 1.11 840 1.23

6457 -- -- 500 0.43 554 0.52 601 0.61 646 0.72 682 0.81 712 0.89 742 0.97 776 1.06 810 1.17 843 1.29

6797 -- -- 515 0.48 567 0.58 614 0.68 658 0.78 698 0.89 728 0.98 756 1.05 786 1.14 817 1.24 849 1.35

7137 477 0.43 531 0.53 581 0.64 627 0.74 669 0.84 710 0.96 744 1.07 772 1.15 799 1.23 827 1.33 858 1.44

7476 494 0.48 546 0.59 595 0.70 640 0.81 682 0.92 722 1.03 758 1.16 789 1.26 814 1.34 840 1.43 867 1.53

7816 513 0.54 563 0.65 609 0.77 653 0.88 695 1.00 732 1.10 771 1.24 804 1.36 831 1.46 856 1.55 880 1.64

8156 531 0.61 579 0.72 624 0.84 667 0.96 707 1.08 745 1.19 783 1.32 817 1.46 847 1.58 872 1.68 896 1.77 External Static Pressure (Pascals)

299

324

349

374

398

423

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

1.49 kW High Static Motor

2.24 kW Ultra High Static Motor

5437 857 1.22 887 1.33 916 1.44 943 1.55 970 1.66 996 1.78

5777 865 1.29 895 1.40 924 1.51 952 1.63 978 1.75 1003 1.87

6117 873 1.35 903 1.47 931 1.59 959 1.71 986 1.83 1012 1.96

6457 877 1.41 912 1.55 940 1.67 967 1.80 994 1.92 -- --

6797 882 1.48 915 1.61 947 1.75 976 1.88 1002 2.01 -- --

7137 888 1.55 919 1.68 950 1.82 980 1.96 1010 2.11 -- --

7476 896 1.64 925 1.76 955 1.90 985 2.04 1013 2.18 -- --

7816 906 1.74 934 1.86 961 1.99 989 2.12 -- -- -- --

8156 918 1.86 944 1.97 970 2.10 996 2.22 -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

90

SS-PRC029Y-EN

Performance Data

Table 93. Evaporator fan performance --TWE156 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP Standard Motor w/ Field Supplied 1.5 HP Standard Motor w/

2 HP High Static

Sheave & Belt

Field Supplied Sheave & Belt

Motor

4000 428 0.5 482 0.62 531 0.72 576 0.84 621 0.98 663 1.11 701 1.25 737 1.38 771 1.51 803 1.64 833 1.77

4250 448 0.58 499 0.71 546 0.82 590 0.94 633 1.08 674 1.22 712 1.37 748 1.51 782 1.65 814 1.79 845 1.93

4500 468 0.68 517 0.81 563 0.93 605 1.05 646 1.19 686 1.34 724 1.50 760 1.65 793 1.80 825 1.95 855 2.09

4750 488 0.78 535 0.91 579 1.06 621 1.18 660 1.32 698 1.46 735 1.63 772 1.79 805 1.95 837 2.11 867 2.27

5000 509 0.90 554 1.03 596 1.19 637 1.32 675 1.46 712 1.61 748 1.77 783 1.94 817 2.11 848 2.28 878 2.44

5250 530 1.02 573 1.16 614 1.32 653 1.47 691 1.61 726 1.76 760 1.92 795 2.10 828 2.28 859 2.45 890 2.64

5500 551 1.16 593 1.31 632 1.47 670 1.64 706 1.78 741 1.93 774 2.09 807 2.26 840 2.46 871 2.64 902 2.83

5750 572 1.32 612 1.47 651 1.63 687 1.81 722 1.97 757 2.12 789 2.28 821 2.45 852 2.64 883 2.84 912 3.03

6000 593 1.48 632 1.64 670 1.81 705 1.99 739 2.17 772 2.32 804 2.48 835 2.66 865 2.84 895 3.04 924 3.24 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 HP High Static

Motor

3 HP Ultra High Static Motor

4000 863 1.9 891 2.03 919 2.15 944 2.28 970 2.40 994 2.53

4250 874 2.07 902 2.20 928 2.33 955 2.47 981 2.61 1004 2.74

4500 884 2.24 913 2.38 939 2.53 966 2.68 991 2.82 1015 2.96

4750 895 2.42 924 2.58 951 2.74 977 2.88 1002 3.04 -- --

5000 907 2.61 934 2.77 962 2.94 -- -- -- -- -- --

5250 918 2.81 946 2.98 973 3.16 -- -- -- -- -- --

5500 931 3.02 958 3.20 -- -- -- -- -- -- -- --

5750 941 3.23 -- -- -- -- -- -- -- -- -- --

6000 Notes:
1.
2.
3.

------------------------
Data includes pressure drop due to wet coil and 1" filter. Fan motor heat (MBh) = 3.15 x BHP. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

91

Performance Data

Table 94. Evaporator fan performance -- TWE156 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

1.49 kW Standard Motor w/ Field Supplied Sheave & Belt

1.49 kW Standard Motor

2.24 kW High Static Motor

6797 428 0.37 482 0.46 531 0.54 576 0.63 621 0.73 663 0.83 701 0.93 737 1.03 771 1.13 803 1.22 833 1.32

7222 448 0.43 499 0.53 546 0.61 590 0.70 633 0.80 674 0.91 712 1.02 748 1.13 782 1.23 814 1.33 845 1.44 7646 468 0.50 517 0.60 563 0.70 605 0.79 646 0.89 686 1.00 724 1.12 760 1.23 793 1.34 825 1.45 855 1.56

8071 488 0.58 535 0.68 579 0.79 621 0.88 660 0.98 698 1.09 735 1.21 772 1.34 805 1.46 837 1.57 867 1.69

8496 509 0.67 554 0.77 596 0.88 637 0.99 675 1.09 712 1.20 748 1.32 783 1.45 817 1.58 848 1.70 878 1.82 8921 530 0.76 573 0.87 614 0.99 653 1.10 691 1.20 726 1.31 760 1.43 795 1.57 828 1.70 859 1.83 890 1.97

9346 551 0.87 593 0.97 632 1.10 670 1.22 706 1.33 741 1.44 774 1.56 807 1.69 840 1.83 871 1.97 902 2.11

9770 572 0.98 612 1.09 651 1.22 687 1.35 722 1.47 757 1.58 789 1.70 821 1.83 852 1.97 883 2.11 912 2.26
10195 593 1.11 632 1.22 670 1.35 705 1.49 739 1.61 772 1.73 804 1.85 835 1.98 865 2.12 895 2.27 924 2.42 External Static Pressure (Pascals)

299

324

349

374

398

423

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

2.24 kW High Static Motor w/ Field Supplied Sheave & Belt

6797 863 1.42 891 1.51 919 1.61 944 1.70 970 1.79 994 1.88
7222 874 1.54 902 1.64 928 1.74 955 1.84 981 1.95 1004 2.04
7646 884 1.67 913 1.78 939 1.88 966 2.00 991 2.10 1015 2.21
8071 895 1.80 924 1.92 951 2.04 977 2.15 1002 2.26 -- --
8496 907 1.95 934 2.07 962 2.19 -- -- -- -- -- --
8921 918 2.09 946 2.22 973 2.35 -- -- -- -- -- --
9346 931 2.25 958 2.39 -- -- -- -- -- -- -- --
9770 941 2.41 -- -- -- -- -- -- -- -- -- --
10195 -- -- -- -- -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

92

SS-PRC029Y-EN

Performance Data

Table 95. Evaporator fan performance --TWE201 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3.5 HP

Standard

Motor w/ Field

Supplied

2 HP Low Static Motor

3.5 HP Standard Motor

Sheave & Belt

5200 -- -- 531 0.83 580 0.96 627 1.09 666 1.21 707 1.37 748 1.54 787 1.71 825 1.88 864 2.06 902 2.24

5525 -- -- 551 0.96 599 1.10 644 1.23 684 1.37 722 1.51 760 1.68 799 1.87 834 2.04 872 2.23 909 2.42

5850 -- -- 572 1.10 619 1.25 662 1.39 703 1.54 738 1.68 774 1.84 810 2.02 846 2.22 880 2.40 916 2.60

6175 543 1.11 593 1.26 638 1.42 680 1.57 720 1.72 757 1.87 790 2.02 824 2.20 859 2.40 893 2.61 926 2.81

6500 566 1.28 614 1.43 659 1.61 699 1.77 737 1.92 775 2.08 807 2.24 839 2.40 871 2.59 904 2.80 936 3.02

6825 590 1.47 636 1.62 679 1.80 718 1.98 755 2.14 792 2.31 826 2.48 857 2.64 886 2.81 918 3.02 950 3.25

7150 614 1.67 658 1.83 700 2.02 738 2.21 774 2.38 809 2.55 844 2.73 875 2.90 903 3.07 932 3.26 962 3.47

7475 638 1.89 680 2.06 720 2.25 758 2.45 794 2.63 827 2.81 861 2.99 893 3.18 921 3.36 949 3.54 976 3.73

7800 662 2.13 702 2.31 742 2.50 779 2.71 814 2.91 846 3.09 879 3.28 910 3.48 940 3.67 967 3.86 993 4.04 External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

1.80"

1.90"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5 HP High Static Motor w/

5 HP High Static Motor

Field Supplied Sheave & Belt

5200 937 2.42 972 2.59 1004 2.77 1036 2.95 1066 3.12 1095 3.29 1125 3.46 1152 3.63 5525 943 2.60 978 2.80 1012 2.99 1042 3.17 1072 3.35 1102 3.54 1132 3.73 1159 3.91

5850 951 2.80 984 3.00 1018 3.21 1050 3.41 1080 3.60 1109 3.80 1138 4.00 1166 4.19 6175 958 3.00 992 3.22 1024 3.43 1056 3.64 1086 3.86 1115 4.06 1143 4.27 -- --

6500 967 3.22 998 3.44 1030 3.65 1063 3.89 1093 4.11 1122 4.33 1151 4.56 -- --

6825 980 3.47 1010 3.69 1039 3.90 1069 4.13 1098 4.36 1129 4.61 1158 4.85 -- -- 7150 991 3.70 1021 3.94 1051 4.18 1078 4.41 1107 4.65 1135 4.88 1165 5.14 -- --

7475 1005 3.97 1034 4.21 1062 4.46 1090 4.71 1117 4.94 1144 5.19 -- -- -- --

7800 1019 4.24 1047 4.49 1074 4.74 1102 5.01 1128 5.25 1154 5.51 -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

93

Performance Data

Table 96. Evaporator fan performance -- TWE201 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

2.24 kW Standard

1.49 kW Low Static Motor

2.24 kW Standard Motor

Motor w/ Field Supplied Sheave &

Belt

8836 -- -- 531 0.62 580 0.71 627 0.81 666 0.90 707 1.02 748 1.15 787 1.27 825 1.40 864 1.54 902 1.67

9388 -- -- 551 0.72 599 0.82 644 0.92 684 1.02 722 1.12 760 1.25 799 1.39 834 1.52 872 1.66 909 1.80

9940 -- -- 572 0.82 619 0.94 662 1.04 703 1.15 738 1.25 774 1.37 810 1.51 846 1.65 880 1.79 916 1.94

10493 543 0.83 593 0.94 638 1.06 680 1.17 720 1.29 757 1.40 790 1.51 824 1.64 859 1.79 893 1.94 926 2.09

11045 566 0.95 614 1.07 659 1.20 699 1.32 737 1.43 775 1.55 807 1.67 839 1.79 871 1.93 904 2.09 936 2.25

11597 590 1.09 636 1.21 679 1.34 718 1.48 755 1.59 792 1.72 826 1.85 857 1.97 886 2.09 918 2.25 950 2.42

12149 614 1.25 658 1.37 700 1.50 738 1.65 774 1.77 809 1.90 844 2.03 875 2.16 903 2.29 932 2.43 962 2.59

12702 638 1.41 680 1.54 720 1.68 758 1.83 794 1.96 827 2.09 861 2.23 893 2.37 921 2.51 949 2.64 976 2.79

13254 662 1.59 702 1.72 742 1.86 779 2.02 814 2.17 846 2.31 879 2.45 910 2.59 940 2.74 967 2.88 993 3.02 External Static Pressure (Pascals)

299

324

349

374

398

423

448

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

3.73 kW Ultra High 3.73 kW Ultra High Static Motor w/ Field Supplied

Static Motor

Sheave & Belt

8836 937 1.80 972 1.94 1004 2.07 1036 2.20 1066 2.33 1095 2.45 1125 2.58

9388 943 1.94 978 2.09 1012 2.23 1042 2.36 1072 2.50 1102 2.64 1132 2.78

9940 951 2.09 984 2.24 1018 2.39 1050 2.54 1080 2.69 1109 2.83 -- --

10493 958 2.24 992 2.40 1024 2.56 1056 2.72 1086 2.88 1115 3.03 -- --

11045 967 2.40 998 2.56 1030 2.73 1063 2.90 1093 3.07 1122 3.23 -- --

11597 980 2.59 1010 2.75 1039 2.91 1069 3.08 1098 3.26 1129 3.44 -- --

12149 991 2.76 1021 2.94 1051 3.12 1078 3.29 1107 3.47 -- -- -- --

12702 1005 2.96 1034 3.14 1062 3.32 1090 3.51 1117 3.69 -- -- -- --

13254 1019 3.17 1047 3.35 1074 3.54 1102 3.74 1128 3.92 -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

94

SS-PRC029Y-EN

Performance Data

Table 97. Evaporator fan performance --TWE251 -- air handler (IP)

External Static Pressure (Inches of Water Gauge)

0.10"

0.20"

0.30"

0.40"

0.50"

0.60"

0.70"

0.80"

0.90"

1.00"

1.10"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5 HP Standard Motor &

Low Static Drive Field

Installed Sheaves

5 HP Standard Motor & Drive

6500 -- -- -- -- 618 1.50 657 1.71 693 1.95 735 2.25 774 2.56 806 2.83 835 3.09 864 3.32 894 3.55

7000 -- -- 610 1.56 648 1.77 685 2.00 719 2.23 754 2.49 793 2.83 830 3.17 860 3.46 887 3.73 914 4.00

7500 604 1.64 642 1.86 679 2.08 714 2.31 748 2.55 779 2.81 812 3.11 848 3.46 883 3.83 913 4.16 939 4.45

8000 639 1.96 676 2.19 710 2.42 743 2.67 776 2.92 807 3.18 836 3.46 868 3.79 902 4.17 935 4.57 965 4.93

8500 674 2.33 709 2.57 742 2.81 774 3.07 804 3.33 835 3.60 863 3.88 890 4.17 920 4.53 953 4.93 985 5.35

9000 709 2.73 743 2.98 775 3.24 805 3.51 834 3.78 863 4.06 891 4.35 918 4.65 944 4.97 972 5.34 -- --

9500 745 3.18 777 3.44 808 3.72 837 4.00 865 4.28 892 4.57 920 4.88 946 5.18 971 5.50 -- -- -- --

10000 780 3.68 812 3.95 841 4.25 869 4.53 896 4.83 922 5.13 949 5.45 -- -- -- -- -- -- -- --

10500 816 4.23 846 4.52 875 4.82 902 5.13 927 5.43 953 5.74 -- -- -- -- -- -- -- -- -- -- External Static Pressure (Inches of Water Gauge)

1.20"

1.30"

1.40"

1.50"

1.60"

1.70"

1.80"

1.90"

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5 HP Standard Motor & High Static Drive Field Supplied Sheaves

6500 923 3.78 952 4.03 982 4.28 1012 4.55 1042 4.82 1071 5.09 1099 5.37 1129 5.67
7000 941 4.24 969 4.49 997 4.75 1023 5.01 1051 5.29 1079 5.57 -- -- -- --
7500 964 4.74 989 5.01 1015 5.28 1041 5.55 -- -- -- -- -- -- -- --
8000 990 5.25 1013 5.55 -- -- -- -- -- -- -- -- -- -- -- --
8500 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
9000 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
9500 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
10000 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
10500 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (MBh) = 3.15 x BHP. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

SS-PRC029Y-EN

95

Performance Data

Table 98. Evaporator fan performance -- TWE251 -- air handler (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

3.73 kW Standard

Motor w/ Low Static Drive Field Installed

3.73 kW Standard Motor & Drive

Sheaves

11044 -- -- -- -- 618 1.12 657 1.28 693 1.45 735 1.68 774 1.91 806 2.11 835 2.30 864 2.47 894 2.65

11893 -- -- 610 1.17 648 1.32 685 1.49 719 1.66 754 1.86 793 2.11 830 2.36 860 2.58 887 2.78 914 2.98

12742 604 1.23 642 1.39 679 1.55 714 1.72 748 1.90 779 2.09 812 2.32 848 2.58 883 2.86 913 3.10 939 3.32

13592 639 1.47 676 1.64 710 1.81 743 1.99 776 2.18 807 2.37 836 2.58 868 2.82 902 3.11 935 3.40 965 3.68

14441 674 1.74 709 1.91 742 2.10 774 2.29 804 2.48 835 2.68 863 2.89 890 3.11 920 3.38 953 3.68 985 3.99

15291 709 2.04 743 2.22 775 2.42 805 2.61 834 2.82 863 3.03 891 3.24 918 3.47 944 3.71 972 3.98 -- --

16140 745 2.37 777 2.57 808 2.78 837 2.98 865 3.19 892 3.41 920 3.64 946 3.86 971 4.10 -- -- -- --

16990 780 2.75 812 2.95 841 3.17 869 3.38 896 3.60 922 3.83 949 4.06 -- -- -- -- -- -- -- --

17840 816 3.16 846 3.37 875 3.60 902 3.82 927 4.05 953 4.28 -- -- -- -- -- -- -- -- -- -- External Static Pressure (Pascals)

299

324

349

374

398

423

448

473

m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

3.73 kW Standard Motor w/ High Static Drive Field Supplied Sheaves

11044 923 2.82 952 3.00 982 3.19 1012 3.39 1042 3.59 1071 3.80 1099 4.00 1129 4.22
11893 941 3.16 969 3.35 997 3.54 1023 3.73 1051 3.94 1079 4.15 -- -- -- --
12742 964 3.54 989 3.73 1015 3.94 1041 4.14 -- -- -- -- -- -- -- --
13592 990 3.91 1013 4.14 -- -- -- -- -- -- -- -- -- -- -- --
14441 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
15291 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
16140 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
16990 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
17840 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- Notes:
1. Data includes pressure drop due to wet coil and 1" filter. 2. Fan motor heat (kW) = 1.238 x kW. 3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

Table 99.
Model
TWE201

Low static fan motors - constant volume air handlers

Motor

Motor Sheave Turns
Open
0

Nominal RPM
712

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

1

677

Low Static Motor 2 HP (1.5 kW)

2

641

3

605

N/A

N/A

N/A

4

569

5

533

96

SS-PRC029Y-EN

Performance Data

Table 100. Standard fan motors - constant volume air handlers

Model

Motor

Motor Sheave Turns
Open

Nominal RPM

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

0

892

1

833

TWE051

Standard Motor .5 HP (.38 kW)

2

773

3

714

N/A

N/A

N/A

4

654

5

595

0

706

1

659

TWE072

Standard Motor 1 HP (.75 kW)

2

612

3

565

N/A

N/A

N/A

4

518

5

471

0

706

1

659

TWE076

Standard Motor 1 HP (.75 kW)

2

612

3

565

N/A

N/A

N/A

4

518

5

471

0

682

1

644

TWE101

Standard Motor 1.5 HP (1.13 kW)

2

606

3

568

N/A

N/A

N/A

4

530

5

492

0

640

1

604

TWE126

Standard Motor 1.5 HP (1.13 kW)

2

569

3

533

N/A

N/A

N/A

4

498

5

462

0

Standard Motor

1

with Field Supplied

2

TWE126

Components

3

1.5 HP (1.13 kW) (high static)

4

5

761

718 Variable Pitch (2.4 - 3.4 Fixed Pitch (6.7 Inch

671

Inch Pitch Diameter), Pitch Diameter),

0.875 Inch Bore,

1.4375 Inch Bore,

624 Single Groove,

Single Groove,

577 Browning 1VL40

Browning AK71

549

Browning A55

0

704

1

676

2

648

TWE156

Standard Motor 2 HP (1.49 kW)

3

620

N/A

4

592

N/A

N/A

5

565

6

537

0

Standard Motor

1

TWE156

with Field Supplied Components

2 3

2 HP (1.49 kW) (high static)

4

5

809

770 Variable Pitch (3.2 - 4.2 Fixed Pitch (7.4 Inch

732

Inch Pitch Diameter), Pitch Diameter), 0.875 Inch Bore, Single 1.4375 Inch Bore,

693 Groove, Browning

Single Groove,

655 1VL44

Browning BK80

616

Browning BX58

0

814

1

780

TWE201

Standard Motor 3.5 HP (2.61 kW)

2

746

3

713

N/A

N/A

N/A

4

679

5

645

SS-PRC029Y-EN

97

Performance Data

Table 100. Standard fan motors - constant volume air handlers (continued)

Model TWE201 TWE251 TWE251 TWE251

Motor
Standard Motor with Field Supplied
Components 3.5 HP (2.61 kW) (high static)
Standard Motor with Field Supplied
Components 5 HP (3.73 kW) (low static)
Standard Motor 5 HP (3.73 kW)
Standard Motor with Field Supplied
Components 5 HP (3.73 kW) (high static)

Motor Sheave Turns
Open 0 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5
6

Nominal RPM

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

924 886 847 809 770 732 713 679 645 611 577 543 896 853 809 765 722 678 1084 1044 1004 963 923
883

Variable Pitch (2.8 - 3.8 Fixed Pitch (10.4 Inch

Inch Pitch Diameter), Pitch Diameter),

1.125 Inch Bore,

1.4375 Inch Bore,

Single Groove,

Single Groove,

Browning 1VP50

Browning BK80

Variable Pitch (3.2 - 4.2 Fixed Pitch (8.4 Inch

Inch Pitch Diameter), Pitch Diameter),

1.125 Inch Bore,

1.4375 Inch Bore,

Single Groove,

Single Groove,

Browning 1VP44

Browning BK90

N/A

N/A

Variable Pitch (4.4 - 5.4 Fixed Pitch (7.1 Inch

Inch Pitch Diameter), Pitch Diameter),

1.125 Inch Bore,

1.4375 Inch Bore,

Single Groove,

Single Groove,

Browning 1VP56

Browning BK110

Browning BX62 Browning BX70
N/A Browning BX62

Table 101.
Model TWE051 TWE072 TWE076 TWE101

High static fan motors - constant volume air handlers

Motor
High Static Motor 1 HP (.75kW)
High Static Motor 1.5 HP (1.13 kW)
High Static Motor 1.5 HP (1.13 kW)
High Static Motor 2 HP (1.5 kW)

Motor Sheave Turns
Open 0 1 2 3 4 5 0 1 2 3 4 5 0 1 2 3 4 5 0 1 2 3 4 5

Nominal RPM
1122 1066 1010 954 898 842 912 866 820 775 729 683 912 866 820 775 729 683 810 769 729 688 648 607

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

98

SS-PRC029Y-EN

Performance Data

Table 101.
Model TWE101 TWE126 TWE156 TWE156 TWE201 TWE201

High static fan motors - constant volume air handlers (continued)

Motor
High Static Motor with Field Supplied
Components 2 HP (1.5 kW)
High Static Motor 2 HP (1.5 kW)
High Static Motor 3.5 HP (2.6 kW)
High Static Motor with Field Supplied
Components 3.5 HP (2.6 kW)
High Static Motor 5 HP (3.75 kW)
High Static Motor with Field Supplied
Components 5 HP (3.75 kW)

Motor Sheave Turns
Open 0 1 2 3 4 5 0 1 2 3 4 5 0 1 2 3 4 5 6 0 1 2 3 4 5 6 0 1 2 3 4 5 6 0 1 2 3 4 5 6

Nominal RPM

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

1092 1035 977 920 862 805 912 866 825 785 744 683 853 824 794 765 735 705 676 1014 979 932 885 838 803 803 1078 1036 993 950 907 864 822 1096 1067 1036 1004 973 941 926

Variable Pitch (2.8 - 3.8 Fixed Pitch (6.0 Inch

Inch Pitch Diameter), Pitch Diameter),

0.875 Inch Bore,

1.0 Inch Bore,

Single Groove,

Single Groove,

Browning 1VP44

Browning AK64

N/A

N/A

N/A

N/A

Variable Pitch (3.4 - 4.4 Fixed Pitch (6.6 Inch

Inch Pitch Diameter), Pitch Diameter),

1.125 Inch Bore,

1.4375 Inch Bore,

Single Groove,

Single Groove,

Browning 1VP50

Browning BK72

N/A

N/A

Variable Pitch (2.8 - 3.8 Fixed Pitch (10.4 Inch

Inch Pitch Diameter), Pitch Diameter),

1.125 Inch Bore, Single 1.4375 Inch Bore,

Groove, Browning

Single Groove,

1VP44

Browning BK110

Browning A50 N/A N/A
Browning BX58 N/A
Browning BX62

SS-PRC029Y-EN

99

Performance Data

Table 102.
Model TWE072
TWE076
TWE126

Ultra high static fan motors - constant volume air handlers

Motor
Ultra High Static Motor 2 HP (1.5 kW)
Ultra High Static Motor 2 HP (1.5 kW)
Ultra High Static Motor 3.5 HP (2.6 kW)

Motor Sheave Turns
Open 0 1 2 3 4 5 -- 0 1 2 3 4 5 -- 0 1 2 3 4 5 6

Nominal RPM
1122 1034 946 859 771 683
-- 1122 1034 946 859 771 683
-- 1014 979 944 909 874 838 803

Required Field Supplied Components

Motor Sheave

Blower Sheave

Belt

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Table 103. Discharge plenum and grille assembly throw distance -- air handler -- ft (m)

Unit Model No.
TWE051 TWE072 TWE076 TWE101 TWE126 TWE156 TWE201

CFM
1800 2000 2200 2400 1800 2000 2200 2400 2250 2500 2750 3000 3025 3350 3675 4000 3750 4200 4650 5100 4500 5000 5500 6000 6000 6680 7350 8030

m3/h
3060 3395 3737 4074 3061 3400 3739 4078 3823 4249 4671 5098 5139 5692 6245 6795 6370 7137 7902 8666 7644 8497 9346 10195 10195 11348 12488 13645

Louver angle Deflection Position (ft)

Straight

20°

40°

55°

46

37

29

22

48

43

33

24

51

50

36

25

44

58

41

28

47

34

28

24

49

37

30

26

50

40

32

28

52

43

35

29

51

41

33

28

53

45

36

30

56

49

39

31

58

53

42

32

57

44

36

32

60

48

39

32

63

52

43

33

67

57

47

35

44

27

25

38

45

31

28

48

47

36

31

57

50

40

34

67

46

34

30

22

49

39

34

25

53

45

37

28

58

50

41

31

53

43

36

28

57

48

40

31

62

52

44

33

65

57

47

35

Louver angle Deflection Position (m)

Straight

20°

40°

55°

14.0

11.3

8.8

6.7

14.6

13.1

10.1

7.3

15.5

15.2

11.0

7.6

13.4

17.7

12.5

8.5

14.0

10.3

8.3

8.0

14.7

11.2

9.0

8.3

15.3

12.2

9.8

8.5

15.9

13.1

10.6

8.8

15.4

12.4

10.0

8.6

16.2

13.6

10.9

9.0

16.9

14.9

11.9

9.4

17.7

16.2

12.8

9.9

17.4

13.4

10.8

9.6

18.3

14.7

12.0

9.7

19.3

16.0

13.2

10.0

20.3

17.3

14.4

10.5

13.4

8.1

7.5

11.7

13.7

9.5

8.5

14.5

14.3

10.9

9.5

17.4

15.2

12.3

10.5

20.5

14.1

10.5

9.2

6.6

14.9

12.0

10.3

7.6

16.2

13.6

11.4

8.5

17.7

15.1

12.5

9.3

16.0

13.1

10.9

8.6

17.5

14.5

12.1

9.4

18.8

16.0

13.3

10.0

19.8

17.4

14.5

10.5

100

SS-PRC029Y-EN

Performance Data

Table 103. Discharge plenum and grille assembly throw distance -- air handler -- ft (m) (continued)

Unit Model No.

CFM

m3/h

Louver angle Deflection Position (ft)

Straight

20°

40°

55°

Louver angle Deflection Position (m)

Straight

20°

40°

55°

7500

12742

62

52

44

33

18.8

16.0

13.3

10.0

8350

14187

67

59

49

36

20.4

18.0

14.9

11.0

TWE251

9200

15631

73

65

54

40

22.3

19.8

16.5

12.2

10050

17075

78

70

59

43

23.8

21.3

18.0

13.1

Note: Throw distance values are based on a terminal velocity of 75 fpm (0.38 m/s).

Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw factor as follows:

for 50 FPM (0.25 m/s) terminal velocity, multiply by 1.50 throw factor;

for 100 FPM (0.51 m/s) terminal velocity, multiply by 0.75 throw factor;

for 150 FPM (0.76 m/s) terminal velocity, multiply by 0.50 throw factor.

Table 104. Static pressure drop through accessories (inches of water column) -- air handler

Unit Model
No.

Return Grille CFM m3/h
in. wc Pascal

Discharge

2"

Plenum &

Electric Heaters (kW)

MERV Grille(b)

13

5­10

15­20

25­30

35­50

Filter in. wc Pascal

in. wc Pascal in. wc Pascal in. wc Pascal in. wc Pascal

1400 2379 0.09 23.60 0.19 0.16 41.10 0.06 16.20 0.05 13.70 0.09 23.60 --

--

TWE051 1700 2889 0.14 34.90 0.24 0.24 60.60 0.09 23.90 0.08 20.20 0.14 34.90 --

--

2000 3398 0.18 45.70 0.29 0.33 83.80 0.13 33.00 0.13 33.00 0.19 48.30 --

--

1600 2718 0.03 9.51 0.12 0.11 28.91 0.03 7.47 0.03 7.47 0.06 14.94 0.06 14.94

TWE072 2000 3398 0.04 14.70 0.15 0.18 45.20 0.03 7.47 0.05 12.45 0.08 19.93 0.10 24.91

2400 4078 0.06 21.11 0.19 0.26 65.07 0.04 9.96 0.07 17.44 0.11 27.40 0.15 37.36

2000 3398 0.06 14.70 0.15 0.18 45.20 0.03 6.80 0.05 13.50 0.08 19.20 0.10 26.00

TWE076 2500 4248 0.09 22.90 0.20 0.28 70.60 0.04 10.60 0.08 21.20 0.12 30.00 0.16 40.60

3000 5098 0.13 33.00 0.25 0.40 101.60 0.06 15.20 0.12 30.50 0.17 43.20 0.23 58.40

2600 4418 0.05 11.70 0.15 0.28 72.10 0.04 10.10 0.09 21.80 0.13 31.90 0.17 43.60

TWE101 3300 5607 0.07 18.90 0.20 0.46 116.20 0.06 16.20 0.14 35.10 0.20 51.30 0.28 70.20

4000 6797 0.11 27.80 0.25 0.67 170.70 0.09 23.80 0.20 51.60 0.30 75.40 0.41 103.20

3200 5436 0.04 10.20 0.12 0.10 25.60 0.01 2.50 0.02 5.00 0.03 7.50 0.04 10.00

TWE126 4000 6797 0.06 15.90 0.15 0.16 39.90 0.02 5.00 0.03 7.50 0.04 10.00 0.06 15.00

4800 8156 0.09 22.90 0.19 0.23 57.50 0.03 7.50 0.03 7.50 0.06 15.00 0.08 20.00

4000 6797 0.07 16.90 0.15 0.15 38.40 0.02 3.80 0.03 6.80 0.05 13.50 0.08 19.20

TWE156 5000 8496 0.10 26.50 0.20 0.24 60.00 0.04 10.60 0.04 10.60 0.08 21.20 0.12 30.00

6000 10195 0.15 38.10 0.25 0.34 86.40 0.06 15.20 0.06 15.20 0.12 30.50 0.17 43.20

5200 8836 0.07 18.40 0.17 0.30 73.80 0.04 10.60 0.04 10.60 0.08 21.10 0.13 31.70

TWE201 6650 11300 0.12 30.20 0.23 0.46 114.90 0.07 17.30 0.07 17.30 0.14 34.50 0.21 51.80

7800 13254 0.16 41.50 0.28 0.63 156.10 0.10 23.80 0.10 23.80 0.19 47.50 0.29 71.30

7500 12742 0.15 37.70 0.27 0.58 144.60 0.09 21.80 0.09 21.80 0.18 44.10 0.26 65.90

TWE251 8350 14187 0.18 45.60 0.30 0.72 178.60 0.11 27.10 0.11 27.10 0.22 54.00 0.33 81.10

Notes: 1. 2.

9200 15631 0.22 53.60 0.34 0.87 216.80 0.13 32.40 0.13 32.40 0.26 64.50 0.39
Return air filter ESP included in Fan Performance Table data. On discharge plenum and grille - at louver opening angle of 42 degrees. For ESP at other angle openings, see accessory installation instruction.

96.90

Table 105. Auxiliary electric heat capacity -- air handler

Unit Model No.

No. of Total kW Stages

Stage 1

Stage 2

Total

kW Input Btu Output kW Input Btu Output kW Input Btu Output

5.00

1

TWE0514DA, 0724DB,

9.96

1

0764DA/B, 1014DA/B

14.96

1

24.92

2

TWE0724DB, 0764DA/B, 1014DA/B

34.88

2

5.00 9.96 14.96 14.96
19.92

17,065 33,993 51,058 51,058
67,987

-- -- -- 9.96
14.96

-- -- -- 33993
51058

5.00 9.96 14.96 24.92
34.88

17,065 33,993 51,058 85,051
119,045

SS-PRC029Y-EN

101

Performance Data

Table 105. Auxiliary electric heat capacity -- air handler (continued)

Unit Model No.

No. of Total kW Stages

Stage 1

Stage 2

Total

kW Input Btu Output kW Input Btu Output kW Input Btu Output

10.00

1

TWE1264DB, 1564DB,

19.92

1

2014DB, 2514DB

29.92

2

49.84

2

10.00 19.92 19.92 29.92

34,130 67,987 67,987 102,117

-- -- 10.00 19.92

-- -- 34130 67987

10.00 19.92 29.92 49.84

34,130 67,987 102,117 170,104

Note: Heaters are rated at 240V, 480V and 600V. For other than rated voltage, capacity = (Voltage/Related Voltage)2 x Rated Capacity

102

SS-PRC029Y-EN

Zone Controls

Zone Sensors
Zone Sensors are the building occupant's comfort control devices. Zone sensors are required for SZVAV applications. The following zone sensor options are available for units with Symbio 700 control.

Manual Changeover

Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever.

Manual/Automatic Changeover

Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers.

Manual/Automatic Changeover

Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers.

Integrated ComfortTM System

Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated ComfortTM system.

Remote Sensor

Sensor(s) available for all zone sensors to provide remote sensing capabilities.

Conventional Thermostats
Note: All thermostats may be used with Symbio 700 units.

Non-Programmable Thermostats

TCONT102* (1H/1C)

Auto-changeover Backlit Display and Keys Filter Reminder Keypad Lock

Common terminal not required

TCONT103* (2H/1C) Common terminal required

Auto-changeover Backlit Display & Keys Filter Reminder Keypad Lock Outdoor Temp Sensor Available

TCONT402* (3H/2C) Common terminal required

Auto-changeover Backlit Display & Keys Filter Reminder Keypad Lock Outdoor Temp Sensor Included

Programmable Thermostats

TCONT202* (1H/1C) Common terminal preferred, not required

5/2 or 5/1/1 Programming Actual and Setpoint temps displayed simultaneously

TCONT203* (4H/2C) Common terminal preferred, not required

5/2 or 5/1/1 Programming Actual and Setpoint temps displayed simultaneously

TCONT302* (4H/2C) Common terminal preferred, not required

Interactive touchscreen Large display Real time clock

TCONT303* (4H/2C) Humidity Sensor Common terminal preferred, not required

Interactive touchscreen Large display Real time clock Built-in humidity sensor

SS-PRC029Y-EN

103

Electrical Data

Cooling Condenser

Table 106. Electrical characteristics -- compressor and condenser fan motors -- 50 Hz

Tons

Unit Model Number

Volts

Compressor Motors
Compressor 1 Compressor 2 Phase RLA LRA RLA LRA No.
(Amps) (Amps) (Amps) (Amps)

Condenser Fan Motor

Amps

Volts

Phase FLA (Ea.)

LRA (Ea.)

TTA0604DA 380/415

3

8.0

67.0

N/A

N/A

1 380/415

3

1.3

4.2

5

TTA0604DD 380/415

3

5.4

38.0

5.4

38.0

1 380/415

3

1.3

4.2

TTA0764DA 380/415

3

12.9

98.0

N/A

N/A

1 380/415

3

1.3

4.2

6.25

TTA0764DD 380/415

3

6.0

43.0

6.0

43.0

1 380/415

3

1.3

4.2

TTA1014DD 380/415

3

7.2

52.0

7.2

52.0

1 380/415

3

2.7

9.5

8.33

TTA1014DC 380/415

3

7.8

52.0

7.8

52.0

1 380/415

3

2.7

9.5

10.4 TTA1264DD 380/415

3

11.4

75.0

11.4

75.0

1 380/415

3

2.7

9.5

TTA1564DD 380/415

3

12.9

98.0

12.9

98.0

1 380/415

3

2.7

9.5

13

TTA1564DC 380/415

3

12.9

98.0

12.9

98.0

1 380/415

3

2.7

9.5

TTA2014DD 380/415

3

16.5 140.0 14.8 130.0 1 380/415

3

2.7

9.5

16.7

TTA2014DC 380/415

3

18.6 142.0 18.6 142.0 1 380/415

3

2.7

9.5

20.9 TTA2514DC 380/415

4

19.2 147.0 19.2 147.0 1 380/415

3

2.7

9.5

Note: Electrical characteristics reflect nameplate values and are calculated in accordance with UL specifications.

Table 107. Unit wiring -- condensing units -- 50 Hz

Tons
5 6.25 8.33 10.4
13 16.7 20.9

Unit Model Number
TTA0604DA TTA0604DD TTA0764DA TTA0764DD TTA1014DD TTA1014DC TTA1264DD TTA1564DD TTA1564DC TTA2014DD TTA2014DC TTA2514DC

Volts
380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415 380/415

Minimum Circuit
Ampacity 11 13 17 15 19 20 28 34 34 41 47 49

Maximum Fuse or Circuit Breaker Size 15 15 30 20 25 25 35 45 45 50 60 60

104

SS-PRC029Y-EN

Air Handler

Table 108. Electrical characteristics -- standard motor -- 50 Hz air handler

Tons 4.6

Unit Model Number
TWE0514DA

No. 1

Volts 380-415

Standard Evaporator Fan Motor

Phase

HP

Amps

FLA

LRA

3

0.75

1.5

8.2

6

TWE0724DB

1

380-415

3

6.25 TWE0764DA, B

1

380-415

3

8.33 TWE1014DA, B

1

380-415

3

1.00

2.5

17.0

1.00

2.5

17.0

1.50

3.5

26.2

10.4

TWE1264DB

1

380-415

3

2.00

3.2

35.0

13

TWE1564DB

1

380-415

3

2.00

4.6

39.3

16.7

TWE2014DB

1

380-415

3

3.50

8.0

43.2

20.9

TWE2514DB

1

380-415

3

5.00

7.5

71.0

MCA
2 3 3 4 4 6 10 9

Electrical Data
MOP 15 15 15 15 15 15 15 15

Table 109. Unit wiring with electric heat (single point connection) -- air handlers

Ton Used With

Heater Model No.

Heater Unit Power Control

kW Rating Supply

Stages

BAYHTRN405*

3.13

380/3/50

1

BAYHTRR410*

6.25

380/3/50

1

BAYHTRR415*

9.37

380/3/50

1

BAYHTRN425*

15.63

380/3/50

2

4.6

TWE0514DA

BAYHTRN405*

3.74

415/3/50

1

BAYHTRR410*

7.46

415/3/50

1

BAYHTRR415*

11.17

415/3/50

1

BAYHTRN425*

18.64

415/3/50

2

BAYHTRN405*

3.13

380/3/50

1

BAYHTRR410*

6.25

380/3/50

1

BAYHTRR415*

9.37

380/3/50

1

BAYHTRN425*

15.63

380/3/50

2

6

TWE0724DB

BAYHTRN405*

3.74

415/3/50

1

BAYHTRR410*

7.46

415/3/50

1

BAYHTRR415*

11.17

415/3/50

1

BAYHTRN425*

18.64

415/3/50

2

BAYHTRN405*

3.13

380/3/50

1

BAYHTRR410*

6.25

380/3/50

1

BAYHTRR415*

9.37

380/3/50

1

BAYHTRN425*

15.63

380/3/50

2

6.25 TWE0764DA, B

BAYHTRN405*

3.74

415/3/50

1

BAYHTRR410*

7.46

415/3/50

1

BAYHTRR415*

11.17

415/3/50

1

BAYHTRN425*

18.64

415/3/50

2

Min Circuit Ampacity

Max Fuse or Circuit Breaker Size

8

15

14

15

20

20

32

35

8

15

15

15

21

25

34

35

9

15

15

20

21

25

33

35

10

15

16

20

23

25

36

40

9

15

15

20

21

25

33

35

10

15

16

20

23

25

36

40

SS-PRC029Y-EN

105

Electrical Data

Table 109. Unit wiring with electric heat (single point connection) -- air handlers (continued)

Ton Used With

Heater Model No.

Heater Unit Power Control

kW Rating Supply

Stages

BAYHTRN405*

3.13

380/3/50

1

BAYHTRR410*

6.25

380/3/50

1

BAYHTRR415*

9.37

380/3/50

1

BAYHTRN425*

15.63

380/3/50

2

BAYHTRN435*

21.86

380/3/50

2

8.33 TWE1014DA, B

BAYHTRN405*

3.74

415/3/50

1

BAYHTRR410*

7.46

415/3/50

1

BAYHTRR415*

11.17

415/3/50

1

BAYHTRN425*

18.64

415/3/50

2

BAYHTRN435*

26.08

415/3/50

2

BAYHTRP410*

6.25

380/3/50

1

BAYHTRP420*

12.5

380/3/50

1

BAYHTRP430*

18.76

380/3/50

2

BAYHTRP450*

31.26

380/3/50

2

10.4 TWE1264DB

BAYHTRP410*

7.46

415/3/50

1

BAYHTRP420*

14.92

415/3/50

1

BAYHTRP430*

22.38

415/3/50

2

BAYHTRP450*

37.29

415/3/50

2

BAYHTRP410*

6.25

380/3/50

1

BAYHTRP420*

12.5

380/3/50

1

BAYHTRP430*

18.76

380/3/50

2

BAYHTRP450*

31.26

380/3/50

2

13

TWE1564DB

BAYHTRP410*

7.46

415/3/50

1

BAYHTRP420*

14.92

415/3/50

1

BAYHTRP430*

22.38

415/3/50

2

BAYHTRP450*

37.29

415/3/50

2

BAYHTRP410*

6.25

380/3/50

1

BAYHTRP420*

12.5

380/3/50

1

BAYHTRP430*

18.76

380/3/50

2

BAYHTRP450*

31.26

380/3/50

2

16.7 TWE2014DB

BAYHTRP410*

7.46

415/3/50

1

BAYHTRP420*

14.92

415/3/50

1

BAYHTRP430*

22.38

415/3/50

2

BAYHTRP450*

37.29

415/3/50

2

Min Circuit Ampacity

Max Fuse or Circuit Breaker Size

10

15

16

20

22

25

33

35

45

50

10

15

17

20

23

25

36

40

49

50

16

20

28

30

40

40

63

70

17

20

30

30

43

45

69

70

18

20

30

30

41

45

65

70

19

20

32

35

45

45

71

80

22

25

34

35

46

50

69

70

23

25

36

40

49

50

75

80

106

SS-PRC029Y-EN

Electrical Data

Table 109. Unit wiring with electric heat (single point connection) -- air handlers (continued)

Ton 20.9

Used With TWE2514DB

Heater Model No.

Heater Unit Power Control

kW Rating Supply

Stages

BAYHTRP410*

6.25

380/3/50

1

BAYHTRP420*

12.5

380/3/50

1

BAYHTRP430*

18.76

380/3/50

2

BAYHTRP450*

31.26

380/3/50

2

BAYHTRP410*

7.46

415/3/50

1

BAYHTRP420*

14.92

415/3/50

1

BAYHTRP430*

22.38

415/3/50

2

BAYHTRP450*

37.29

415/3/50

2

Min Circuit Ampacity

Max Fuse or Circuit Breaker Size

21

25

33

35

45

50

69

70

22

25

35

40

48

50

74

80

SS-PRC029Y-EN

107

Jobsite Connections
SymbioTM Controls
Wiring shown with dashed lines is to be furnished and installed by the customer. All customer supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.
Figure 7. SymbioTM jobsite connections
Disconnect Switch (By Others) See Note 1

B
Electric Heat Accessory

Air Handler

C

E

B D
A

Disconnect Switch (By Others) See Note 1
Disconnect Switch (By Others)

T'stat Zone Sensor See Note 2 See Note 2
Power Wires A. 3 wires, line voltage for 3 phase, (2 wires for single phase) 1 grounding wire B. 3 wires, line voltage for 3 phase, (2 wires for single phase) 1 grounding wire Control Wires C. Cooling only (or Cooling with Heat) thermostat: 4 to 7 wires depending on stages of cooling and electric heat D. Wiring between indoor and outdoor unit: 5 to 11 wires depending on unit control options* E. Zone Sensor: 4 to 7 wires depending on zone sensor model* Communication signal wires require shielded twisted pairs. Use factory-supplied 165 ft. length of Comlink cable with a PVC jacket, 18/1 PR, stranded shield, 25 PF/FT plenum rated for the field communication signal wiring. Notes:
1. When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.
2. ***Choose only one of the following; Thermostat, Mechanical Zone Sensor, Programmable Zone Sensor Panel or BAS Zone Sensor.
Important: For the EDC switch to be functional and thereby facilitate reliable unit operation, make the EDC connections from the indoor to the outdoor control boxes.

108

SS-PRC029Y-EN

Jobsite Connections

Table 110. Recommended thermostat wire size

Wire Size

Maximum Wire Length

(Gauge)

Physical distance between Unit & T'stat

22

30 Feet

20

50 Feet

18

75 Feet

16

125 Feet

14

200 Feet

Table 111. Zone sensor module wiring
Distance from Unit to Control 0-150 feet (0-45.7 m) 151-240 feet (46-73.1 m) 241-305 feet (73.5-117.3 m) 386-610 feet (117.7-185.9 m) 611-970 feet (186.2-295.7 m)

Recommended Wire Size 22 gauge (0.33 mm2) 20 gauge (0.50 mm2) 18 gauge (0.75 mm2) 16 gauge (1.31 mm2) 14 gauge ( 2.08 mm2)

SS-PRC029Y-EN

109

Dimensional Data

Cooling Condenser
Figure 8. 5, 6.25 ton condensing, single compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 2 FOR CLEARANCE) HAIL GUARD (OPTIONAL)
SUCTION LINE LIQUID LINE

4 5/16" (109)
1 5/16" (33) LINE VOLTAGE CONTROL WIRING

35 15/16" (913)
WITH HAIL GUARD 33 15/16" (863)

SEE NOTE 1 REFRIGERANT GUAGE ACCESS

35 3/8" (898)
27 13/16" (706)

16 5/16" (415)
9 5/16" (236)
2 13/16" (72) 3 3/16" (81)

1/16" (1.2)
6" (152)

3" (76)

SERVICE PANEL

39 1/16" (993)

CONTROL WIRING (OPTIONAL)

20 15/16"
(531) 17 7/16"
(442) 11 13/16"
(300)

21 11/16" (551)
33 13/16" (859)

6" (152)

SERVICE PANEL SIDE

1 7/8" (47) 2 7/8" (74)

40 15/16" (1039)
42" (1067) WITH HAIL GUARD

7/16" (11.11) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

34 3/4" 40 3/4" (886) (1036)

BOTTOM OF UNIT

1 13/16" (47)

2 5/16" (59)
27 11/16" (704)

2 5/16" (59)

110

SS-PRC029Y-EN

Dimensional Data

Figure 9. 5, 6.25 ton condensing, dual compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 2 FOR CLEARANCE) HAIL GUARD (OPTIONAL)
SUCTION LINE LIQUID LINE

4 5/16" (109) 1 5/16" (33)
LINE VOLTAGE

35 15/16" (913)
WITH HAIL GUARD 33 15/16" (863)

SEE NOTE 1 REFRIGERANT GUAGE ACCESS

CONTROL WIRING

6 3/8" (162)

9 5/16" (236)

35 3/8" (898)
27 13/16" (706)

11 5/16" (288)

7 13/16" (199)
2 1/4" (57) 4 3/8" (111)

1/16" (1.2)
6" (152)

3" (76)

SERVICE PANEL

39 1/16" (993)

CONTROL WIRING (OPTIONAL)

20 15/16"
(531) 17 7/16"
(442) 11 13/16"
(300)

21 11/16" (551)
33 13/16" (859)

6" (152)

SERVICE PANEL SIDE

1 7/8" (47) 2 7/8" (74)

40 15/16" (1039)
42" (1067) WITH HAIL GUARD

7/16" (11.11) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

34 3/4" 40 3/4" (886) (1036)

BOTTOM OF UNIT

1 13/16" (47)

2 5/16" (59)
27 11/16" (704)

2 5/16" (59)

SS-PRC029Y-EN

111

Dimensional Data

Figure 10. 8.33 ton condensing, manifolded compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4

HAIL GUARD (OPTIONAL)

HAIL GUARD (OPTIONAL)

SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 2 FOR CLEARANCE)
LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 1/4" (109) 1 1/4" (33)
CONTROL WIRING

35 3/8" (898)
27 13/16" (706)
16 5/16" 9 5/16" (415) (236)

2 13/16" (72) 3 3/16" (81)

6" (152)

40" (1015) WITH HAIL GUARD 37 15/16" (964)
SERVICE PANEL

39 1/16" (993)

CONTROL WIRING (OPTIONAL)

20 15/16" (531) 17 7/16" (442) 11 13/16"
(300)

1 7/8" (47) 2 7/8" (73)

25 11/16" (653)
37 11/16" (958)

6" (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 7/8" (1293) 52" (1320) WITH HAIL GUARD

3" (76)

SERVICE PANEL SIDE

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

44 3/4" 50 3/4" (1137) (1290)

BOTTOM OF UNIT

1 11/16" (43)

2 3/16" (56)
31 11/16" (805)

1 11/16" (43)

112

SS-PRC029Y-EN

Dimensional Data

Figure 11. 8.33 ton condensing, dual compressor ­ in (mm)

SEE NOTE 3 SERVICE PANEL
SEE NOTE 4

HAIL GUARD (OPTIONAL)

NOTES: 1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2) 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT 4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 2 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 5/16" (109) 1 5/16" (33)
CONTROL WIRING

40" (1015) WITH HAIL GUARD 37 15/16" (964)

6 3/8" (162)

9 5/16" (236)

35 3/8" (898) 27 13/16" (706)

11 5/16" (288)

7 13/16" (199) 2 1/4" (56) 4 3/8" (110)

[288]

6" (152)

SERVICE PANEL
25 11/16" (653)
37 11/16" (958)

39 1/16" (993)

CONTROL WIRING (OPTIONAL)

20 15/16" (531) 17 3/8" (441) 11 13/16"
(300)

1 7/8" (47) 2 7/8" (73)

6" (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 3/4" (1290) 52" (1320) WITH HAIL GUARD

3" (76)

SERVICE PANEL SIDE

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

44 3/4" 50 3/4" (1137) (1290)

BOTTOM OF UNIT

1 11/16" (43)

2 3/16" (56)
31 11/16" (805)

1 11/16" (43)

SS-PRC029Y-EN

113

Dimensional Data

Figure 12. 10.4 ton condensing, dual compressor ­ in (mm)

SEE NOTE 2 SERVICE PANEL
SEE NOTE 3

HAIL GUARD (OPTIONAL)

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 1 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

LINE VOLTAGE

SUCTION LINE LIQUID LINE

4 5/16" (109) 1 5/16" (33)
CONTROL WIRING

40" (1015) WITH HAIL GUARD 37 7/8" (962)

6 3/8" 9 5/16"

(162)

(236)

41 3/8" (1050) 33 13/16" (859)

11 3/8" (288)

7 7/8" (199) 2 1/4" (56) 3 3/16" (80)

[288]

6" (152)

SERVICE PANEL
25 11/16" (653)
37 11/16" (958)

45" (1145)

CONTROL WIRING (OPTIONAL)

26 15/16" (684) 23 7/16" (595) 14 5/16"
(363)

1 7/8" (47) 2 7/8" (73)

6" (152)

SEE NOTE 1 REFRIGERANT GAUGE ACCESS
50 7/8" (1293) 52" (1320) WITH HAIL GUARD

3" (76)

SERVICE PANEL SIDE

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

44 3/4" 50 3/4" (1137) (1290)

BOTTOM OF UNIT

1 11/16" (43)

2 3/16" (56)
31 11/16" (805)

1 11/16" (43)

114

SS-PRC029Y-EN

Dimensional Data

Figure 13. 13, 16.7 ton condensing, dual compressor ­ in (mm)

SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 3 DETAIL A
SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 1 FOR CLEARANCE)

SERVICE PANEL

95 7/16" (2424) WITH HAIL GUARD

CONTROL WIRING

14 5/16" (364)

LINE VOLTAGE

10 1/8" (257)

HAIL GUARD (OPTIONAL)
WITHOUT HAIL GUARD (UNIT COIL)

3/8" (10)

46 1/64" (1169) WITH HAIL GUARD
44" (1118)

HAIL GUARD (OPTIONAL)

HAIL GUARD

35 7/16"

(OPTIONAL)

(900) 40 11/16"

24 5/8" 27 1/8" (625) (689)

(1033) 44 3/4" (1137)

SUCTION LINES LIQUID LINES

13 1/2" (343)

93 1/32" (2363)

10 9/16" (268)
12 11/16" (322)
35 1/16" (891)

8 5/8" (219) 3/16" (5)

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

1/16" (2)

9" (229)

25 5/8" (651)

9" (229)

9 3/16" (233)
7 1/16" (179) 6 9/16" (167)

SERVICE PANEL SIDE

LINE VOLTAGE

BOTTOM OF UNIT

3 3/16 (81)

87" (2210)
93 3/8" (2372)

SUCTION LINES

REFRIGERANT ACCESS

41 9/16" (1056)
36 15/16" (938)

14 1/2" 12 5/8" (368) (321)
4 1/4" 5 5/8" (108) (143)

SUCTION LINES

2 5/16" 6 15/16" (59) (176)

37 1/16" 34 5/8" (941) 31 7/8" (879) (810) 20 1/16" 14 1/2" (510) (368)
LIQUID LINES
9 1/4 (235) 6 5/8 (168) 6 5/16 (160) 3 11/16 (94) 3 3/8 (86) 15/16 (24)

SS-PRC029Y-EN

115

Dimensional Data

Figure 14. 13, 16.7 ton condensing, manifolded compressor ­ in (mm)

SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 3 DETAIL A
SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 1 FOR CLEARANCE)

SERVICE PANEL

95 7/16" (2424) WITH HAIL GUARD

CONTROL WIRING

14 5/16" (364)

LINE VOLTAGE

10 1/4" (260)

HAIL GUARD (OPTIONAL)
WITHOUT HAIL GUARD (UNIT COIL)

3/8" (10)

46" (1168) WITH HAIL GUARD
44" (1118)

HAIL GUARD (OPTIONAL)

SUCTION LINES
LIQUID LINES
13 9/16" (344) 93 11/32" (2363)

10 9/16" (268)
35 1/16" (891)

12 1/4" (311)
11 1/8" (283)
3/16" (5)

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

HAIL GUARD

35 7/16"

(OPTIONAL)

(900) 40 11/16"

(1033) 44 3/4"

(1137)

1/16" (2)

9" (229)

25 5/8" (651)

9" (229)

9 3/16" (233)
7 1/16" (179) 6 9/16" (167)

SERVICE PANEL SIDE

LINE VOLTAGE

BOTTOM OF UNIT

3 3/16 (81)

87" (2210)
93 3/8" (2372)

SUCTION LINES

REFRIGERANT ACCESS

41 9/16" (1056)
36 15/16" (938)

14 1/2" 12 9/16" (368) (321)
4 1/4" 5 5/8" (108) (143)

SUCTION LINES

2 5/16" 6 15/16" (59) (176)

37 1/16" 34 5/8"(941) 31 7/8" (879) (810) 20 1/16" 14 1/2" (510) (368)
LIQUID LINES
9 1/4 (235) 6 5/8 (168) 6 5/16 (160) 3 11/16 (94) 3 3/8 (86) 15/16 (24)

116

SS-PRC029Y-EN

Dimensional Data

Figure 15. 20.9 ton condensing, manifolded compressor ­ in (mm)

SEE NOTE 2

NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

HAIL GUARD (OPTIONAL)

SERVICE PANEL
SEE NOTE 3 DETAIL A SERVICE CLEARANCE 48" (1219.2) (SEE NOTE 1 FOR CLEARANCE)

HAIL GUARD (OPTIONAL)

CONTROL WIRING LINE VOLTAGE

14 3/16" (360) 10 1/8" (257)

3/8" (10)

HAIL GUARD (OPTIONAL)

45 15/16" (1166)
44 3/16" (1122)

41 7/16" 50 3/4" (1052) (1289)
46 11/16" 12" (1186) (304)

3" (76)

SUCTION LINE LIQUID LINE

10 7/16" (266)

13 5/8"

35 3/16"

(346)

(893)

93 1/4" (2369)

OPTIONAL REAR ACCESS DIMENSIONAL DETAIL
SERVICE PANEL SIDE

BOTTOM OF UNIT
87" (2211) 93" (2363)

10 1/4" (260)

9" (229)

25 5/8" (651)

9" (229)

7/16" (11.1) DIA. ISOLATOR MOUNTING HOLES (OUTSIDE HOLES - 4 PLACES)

4 5/8" (118)
34 5/8" (880) 4 5/8" (118)
2 3/16" (55)

LINE VOLTAGE CONTROL WIRING
SUCTION LINE
REFRIGERANT GAUGE ACCESS
14 1/2" (368)
4 3/16" (107) LIQUID LINE
8 1/4" (210)

9 1/16" (230) 7" (177) 6 1/2" (164)
40 5/8" (1032)43 1/16"
(1093) 37 7/8" 24 3/8"(962) (620)
13/16" (21) 1 9/16" (40) 6 3/16" (157)
FRONT DETAIL A DIMENSIONAL DETAIL

SS-PRC029Y-EN

117

Dimensional Data

Air Handler

Figure 16. 4.6 ton air handler, single circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.

0.50" (12.7) DUCT FLANGE 1" (25.4) HEIGHT
6 15/16" (176.2)

22 5/8" (574.7)
16 1/4" (412.8)

0.77" (19.6)

NOTES: 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT. 4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

24 1/16" (611.2)

SUPPLY OPEN

37 15/16" (963.6)

HEATER CONTROL AND SINGLE POWER ENTRY WIRES
HEATER VENTILATION
LINE VOLTAGE

6 7/8" (174.6)
22 5/8" (574.7)

CONTROL WIRING
CONTROL BOX ACCESS PANEL
1 11/16" (42.9)
DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)

7 9/16" (192.1)

12 7/16" (315.9)

2 5/16" (58.7)

3 9/16" (90.5)

3 7/16" (87.3)
10 1/8" (265.5) 16 7/16" (417.8)

2 3/4" (69.9)

REMOTE BULB TXV 1 3/8" (34.9) O.D. SUCTION LINE

SIDE RETURN
32 1/2" (825.5)
COPPER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION

BOTTOM RETURN
32 1/2" (825.5)

13 5/16" (338.14)
1 3/4" (44.45)
2 3/4" (69.9)

20 1/16" (509.6)
FILTER ACCESS PANEL 32" (813) MIN. DISTANCE BOTH SIDE

12" 13 9/16" (304.8) (344.5)
0.99" (25.15) 1 3/8" (34.9)

13 9/16" 12" (344.5) (304.8)
0.99" (25.15) 1 3/8" (34.9)

SEE NOTES 2,3,4

LIQUID LINES SEE NOTES 2,3,4
1 1/8" (28.6)
3" (76.2)

3 3/16" (81)
35 5/8" (904.9)

(4) - HOLE FOR HORIZONTAL SUSPENSION

SUPPLY OPENING

(4) - HOLE FOR HORIZONTAL SUSPENSION

34 9/16" 48 1/16" (877.9) (1220.8)

SIDE RETURN

BOTTOM RETURN

10 7/16" (265.1)

BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

FILTER
SIDE RETURN SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

118

SS-PRC029Y-EN

Dimensional Data

Figure 17. 6.25 ton air handler, single circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.

25 1/2"

DUCT FLANGE 1" (25.4) HEIGHT

(647.7)
16 1/4" (412.8)

0.70" (17.8)

11 11/16" (296.8)

NOTES: 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT. 4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

24 1/16" (611.2)

SUPPLY OPEN

47 1/2" (1206.5)

HEATER CONTROL AND SINGLE POWER ENTRY WIRES
HEATER VENTILATION
LINE VOLTAGE CONTROL WIRING
CONTROL BOX ACCESS PANEL
1 3/16" (30.2) DRAIN CONNECTION
FOR HORIZONTAL (SEE NOTE 2,3,5)

12 5/16" 8 5/16" (312.7) (211.1)

6 13/16" (173)
25 1/2" (647.7)

2 1/4" (57.15)
3 1/2" (89.4) 10 9/16" (268.5)

16 9/16" (420.9)

16 1/16" (408)
1 9/16" (39.7) 2 3/4" (69.85)

REMOTE BULB TXV SUCTION LINE

22 7/8" (581)

20" 16 11/16" 17 7/16" (508)
(423.9) (442.9)

SIDE RETURN

16 7/8" (428.6)

BOTTOM RETURN

42" (1066.8)

1 13/16" (46)
2 3/4" (69.85)

42" (1066.8)

COPPER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION

17 3/8" 16 11/16" (441.3) (423.9)

FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH SIDE
LIQUID LINES SEE NOTES 2,3,4
1 3/16" (30.16)
6 3/4" (171.45)

3 5/8" (92.1) 1 11/16" (42.9)

45 1/8" (1146.2)

(4) - HOLE FOR HORIZONTAL SUSPENSION

1 9/16" (39.7) 3 1/2" (88.9)

SEE NOTES 2,3,4

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

54 1/16" 36 7/8" (1373.2) (936.6)
10 7/16" (265.1)

SIDE RETURN
BOTTOM RETURN SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

BOTTOM RETURN
FILTER
SIDE RETURN SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

SS-PRC029Y-EN

119

Dimensional Data

Figure 18. 8.33 ton air handler, single circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.

NOTES:

1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).

25 1/2" (647.7)

2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO

DUCT FLANGE 1" (25.4) HEIGHT

16 1/4" (412.8)

0.70" (17.8)

SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.

5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

19 11/16"

(500.1)

24 1/16" (611.2)

SUPPLY OPEN

63 1/2" (1612.9)
15 15/16" (404.8)

HEATER CONTROL AND SINGLE POWER ENTRY WIRES

20 5/16" 16 5/16" (515.9) (414.3)

HEATER VENTILATION

6 13/16" (173)

LINE VOLTAGE CONTROL WIRING

25 1/2" (647.7)

2 1/4" (57.2) 3 1/2" (89.4)

1 11/16" (42.9)
2 3/4" (69.8)

SIDE RETURN
58" (1473.2)

16 7/8" (428.6)

BOTTOM RETURN

1 13/16" (46)
2 3/4" (69.8)

58" (1473.2)

CONTROL BOX ACCESS PANEL DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
1 3/16" 22 7/8" (30.2) (581)
FILTER ACCESS PANEL 22" (559) MIN. DISTANCE BOTH SIDE
LIQUID LINES SEE NOTES 2,3,4
1 3/16" (30.2)
6 3/4" (171.45)

10 9/16" (268.5) 16 9/16"
(420.9)
REMOTE BULB TXV
SUCTION LINE

16 11/16" 17 3/8" (423.9) (441.4)

20" (508)

1 11/16" (42.9) 3 5/8" (92.1)

COPPER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION
17 3/8" 16 11/16" (441.3) (423.9)
3 5/8" (92.1) 1 11/16" (42.9)

SEE NOTES 2,3,4

63 1/2" (1613)
61 1/8" (1552.6)

(4) - HOLE FOR HORIZONTAL SUSPENSION
SIDE RETURN

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

BOTTOM RETURN

36 7/8" 54 1/16" (936.63) (1373.2)
10 7/16" (265.1)

BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

FILTER
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

120

SS-PRC029Y-EN

Dimensional Data

Figure 19. 8.33 ton air handler, dual circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.

DUCT FLANGE 1" (25.4) HEIGHT
19 11/16" (500.1)

25 1/2" (647.7)
16 1/4" (412.7)

0.70" (17.8)

NOTES: 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT. 4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

24 1/16" (611.2)

SUPPLY OPEN

63 1/2" (1613)
15 15/16" (404.8)

HEATER CONTROL AND SINGLE POWER ENTRY WIRES

20 5/16" 16 5/16" (515.9) (414.3)

HEATER VENTILATION

6 13/16" (173)

LINE VOLTAGE

25 1/2" (647.7)

CONTROL WIRING

2 1/4" (57.15) 3 1/2" (89.4)

1 11/16" (42.9)
2 3/4" (69.8)

SIDE RETURN
58" (1473.2)

16 7/8" (428.6)

BOTTOM RETURN

1 13/16" (46)
2 3/4" (69.8)

58" (1473.2)

CONTROL BOX ACCESS PANEL DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
1 3/16" 22 7/8" (30.2) (581)
FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH SIDE
LIQUID LINES SEE NOTES 2,3,4
1 3/16" (30.2) 6 3/4" (171.45)
54 1/16" 36 7/8" (1373.2) (936.6)
10 7/16" (265.1)

10 9/16" (268.5) 16 9/16"
(420.9)
(2) REMOTE BULB TXV
SUCTION LINE

11"

13 11/16" (279.4) (347.7)

16 1/4" 16 11/16" 19" (412.8) (423.9) (482.6)

20" (508)

1 5/16" (33.4) 1 5/8" (41.3) 3 5/8" (92.1)

COPPER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION

20 1/16" 16 3/4" 16 1/4" (509.6) (425.5) (412.8)

13 3/4" (349.3)

1 5/16" (33.3) 1 5/8" (41.3) 3 5/8" (92.1)

SEE NOTES 2,3,4

61 1/8" (1552.6)

(4) - HOLE FOR HORIZONTAL SUSPENSION
SIDE RETURN

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

BOTTOM RETURN

BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

FILTER
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

SS-PRC029Y-EN

121

Dimensional Data

Figure 20. 10.4, 13 ton air handler, dual circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.

DUCT FLANGE 1" (25.4) HEIGHT

29 1/16" (738.2)
16 5/16" (414.3)

2 7/8" (73)

NOTES: 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO

SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING

12 3/8" (314.3)

DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF

DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.

SUPPLY

5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

OPEN

54 15/16" (1395.4)

SUPPLY OPEN

79 9/16" (2020.9)
17 7/8" (454)

SIDE RETURN

SIDE RETURN

19 1/2" (495.3) BOTTOM RETURN

BOTTOM RETURN

HEATER CONTROL AND SINGLE POWER ENTRY WIRES

12 1/8" (308)

3 5/16" (84.1)
2 3/4" (69.8)

4 5/16" (109.5)

74 1/8" (1882.8)

3 7/16" (87.3) 2 3/4" (69.8)

74 1/8" (1882.8)

LINE VOLTAGE CONTROL WIRING

29 1/16" (738.2)

4 1/4" (108) 23 5/8" (600.6)

CONTROL BOX ACCESS PANEL
DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
1 1/4" 25 1/8" (31.8) (638.2)

30 1/16" (763.7 )

(2) REMOTE BULB TXV SUCTION LINE

15 13/16" 18 5/16"18 11/16" 12" (304.8) (401.6) (465.1) (474.7)

21 1/2" (546.1)

22" (558.8)

COPPER LIQUID LINE FIELD CONNECTION

COPPER SUCTION LINE FIELD CONNECTION

21 1/2" (546.1)

18 11/16" (474.6)

18 3/8" 15 13/16" (466.7) (401.64)

FILTER ACCESS PANEL 32" (813) MIN. DISTANCE BOTH SIDE
LIQUID LINES SEE NOTES 2,3,4
1 3/16" (30.2) 9 5/8" (244.5)

1 5/16" (33.3) 2 1/8" (54) 2 7/16" (62) 4 1/4" (108)
79 5/8" (2022.5) 77 3/16" (1960.6)

2" (50.8) 2 5/16" (58.7) 4 1/8" (104.8)

SEE NOTES 2,3,4

(4) - HOLE FOR HORIZONTAL SUSPENSION
SUPPLY OPENING BOTTOM RETURN

(4) HOLE FOR HORIZONTAL SUSPENSION

SIDE RETURN

69 1/16" 48" (1754.2) (1219.2)

FILTER

11 7/16" (290.5)

BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

122

SS-PRC029Y-EN

Dimensional Data

Figure 21. 16.7, 20.9 ton air handler, dual circuit ­ in (mm)

Note: Duct flange is a field-installed accessory.
31 1/8" (790.6)

DUCT FLANGE 1" (25.4) HEIGHT

16 5/16" (414.3)

4 15/16" (125.4)

18 7/8" (479.4)

SUPPLY OPEN

NOTES: 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS). 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT. 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT. 4. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 5. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

54 15/16" (1395.4)

92 9/16" (2351.1)

20 15/16" (531.8)

SIDE RETURN

SIDE RETURN

20 15/16" BOTTOM RETURN
(531.8)

BOTTOM RETURN

HEATER CONTROL AND SINGLE POWER ENTRY WIRES
6 7/16" (163.5)

LINE VOLTAGE

31 1/8" (790.6)

CONTROL WIRING

18 5/8" (473.1)

3" (76.2) 4 3/4" (120.6)

4 1/4" (108)

83 1/8" (2111.4)

2 15/16" (74.6) 4 3/4"
(120.6)

83 1/8" (2111.4)

CONTROL BOX ACCESS PANEL
DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
1 3/16" 28 1/2" (30.2)
(724)
FILTER ACCESS PANEL 32" (813) MIN. DISTANCE BOTH SIDE
LIQUID LINES SEE NOTES 2,3,4
1 11/16" (42.9)
9 5/8" (244.5)

31 7/16" (798.6)

25 1/4" (640.6)
REMOTE BULB TXV
SUCTION LINE

COPPER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION

25 1/2"

12 7/8"15 7/8" (327) (403.2)

18 3/8"19 1/8"21 3/8"21 13/16" (466.7)(485.8)(542.9) (554)

(647.7)

25 1/2" (647.7) 21(51534/1)6"1(49815/.88)"1(48636/.87)"1(45073/.82")

1 11/16" (42.9) 1 15/16" (49.2) 3 3/8" (85.7) 4" (101.6)
92 9/16" (2351.1) 89 3/16" (2265.4)

(4) - HOLE FOR HORIZONTAL SUSPENSION

1 9/16" (39.7) 1 7/8" (47.6) 3 1/4" (82.5) 3 7/8" (98.4)

SEE NOTES 2,3,4

SUPPLY OPENING

(4) HOLE FOR HORIZONTAL SUSPENSION

SIDE RETURN

71 7/8" 50 13/16" (1825.6) (1290.6)
11 7/16" (290.5)

SIDE RETURN BOTTOM RETURN

FILTER

SUPPLY VERTICAL RETURN HORIZONTAL / RETURN VERTICAL

BOTTOM RETURN

SUPPLY HORIZONTAL RETURN VERTICAL / RETURN HORIZONTAL

SS-PRC029Y-EN

123

Dimensional Data
Accessories
Figure 22. Rubber isolator accessory dimensions

Table 112. Rubber isolator accessory dimensions ­ in (mm)

Model No.

L

W

H

A

B

C

D

BAYISLT004 3-1/8 (79.375) 1-3/4 (44.45) 1-1/4 (31.75) 1-1/4 (31.75) 3/8 (9.525) 2-3/8 (60.325) 3/8 (9.525)

BAYISLT005 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525)

3 (76.2)

3/8 (9.525)

BAYISLT009 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525)

3 (76.2)

3/8 (9.525)

BAYISLT010 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525)

3 (76.2)

3/8 (9.525)

BAYISLT013 2-1/4 (57.15) 2 (50.8)

3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7)

BAYISLT014 2-1/4 (57.15) 2 (50.8)

3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7)

BAYISLT015 2-1/4 (57.15) 2 (50.8)

3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7)

BAYISLT012 BAYISLT015(a)

3 (76.2) 3 (76.2)

2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35) 2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35)

5/8 (15.875) 5/8 (15.875)

3/4 (19.05) 3/4 (19.05)

BAYISLT016

3 (76.2) 2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35) 5/8 (15.875) 3/4 (19.05)

E 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
-- -- -- -- -- --

Note: BAYISLT015 contains a quantity 2 of the 2-1/4 x 2 x 3 isolators and quantity of 3 of the 3 x 2-1/4 x 4-1/2 isolators.

124

SS-PRC029Y-EN

Figure 23. Spring isolator accessory dimensions ­ in (mm)

Dimensional Data

Figure 24. Electric heater accessory for 4.6-8.3 ton air handlers ­ in (mm)

SS-PRC029Y-EN

125

Dimensional Data
Figure 25. Electric heater accessory for 10.4-20.9 ton air handlers ­ in (mm)

126

SS-PRC029Y-EN

Figure 26. Hot water coil accessory ­ in (mm)

1" (25.4)
K

H DUCT OPENING

Dimensional Data
J DUCT OPENING
N
DUCT FLANGE 16" (406.4)

P M

1" (25.4)
3" (76.2) DIA. HOLE FOR "Q"
(RETURN)

C
F B

L
3 7/8" (98.4)

2 1/8" (54)

"D" # HOLES EQUALLY SPACED AT "E" APART
A

1/4" (6.3) DIA. "G" HOLES

3" (76.2) DIA. HOLE FOR "Q" (SUPPLY)

AIR HANDLER MATING SURFACE

Note: Duct flange available as kit. See accessories chapter for details.

Table 113. Hot water coil accessory ­ in (mm)

Model No.

A

B

C

BAYWATR027 38.14 (969) 22.74 (576) 13.74 (349)

D 5 (127)

E 9 (229)

BAYWATR028 47.74 (1213) 25.74 (654) 15.95 (405)

5 (127)

10.84 (275)

BAYWATR029 63.84 (1621) 25.74 (654) 15.95 (405)

6 (152)

11.84 (301)

BAYWATR030 79.74 (2025) 29.18 (741) 14.36 (365)

8 (203)

10.85 (276)

BAYWATR031 Model No. BAYWATR027

92.74 (2356) J
12 (305)

31.24 (793) K
6 (152)

16.48 (419) L
4.94 (125)

8 (203) M
7.79 (198)

10.85 (276) N
2.88 (73)

BAYWATR028

18 (457)

8.88 (225)

8.45 (215)

10.27 (261)

2.88 (73)

BAYWATR029

18 (457)

13.88 (352)

8.45 (215)

10.03 (255)

2.88 (73)

BAYWATR030

18 (457)

14.25 (362)

6.86 (174)

9.91 (252)

1.88 (48)

F 13.65 (347)

G 16 (406)

H 26 (660)

17.17 (436)

16 (406)

30 (762)

17.16 (436)

18 (457)

36 (914)

19.67 (500)

22 (559)

51 (1295)

19.67 (500)

22 (559)

P

Q

10.24 (260) 2 NPT (51) NPTI

7.77 (197) 7.58 (192) 7.41 (188)

2.5 NPTI (64) NPTI
2.5 NPTI (64) NPTI
2.5 NPTI (64) NPTI

64 (1626)

SS-PRC029Y-EN

127

Dimensional Data

Table 113. Hot water coil accessory ­ in (mm) (continued)

Model No.

J

K

L

M

BAYWATR031

18 (457)

14.25 (362)

8.98 (228)

9.88 (251)

Note: Hot Water Coil Dimensions - inches (millimeters)

Figure 27. Steam coil accessory ­ in (mm)

N 3.75 (95)

P 7.38 (187)

Q
2.5 NPTI (64) NPTI

Note: Duct flange available as kit. See accessories chapter for details.

Table 114. Steam coil accessory ­ in (mm)

Model No.

A

B

C

D

E

F

G

H

J

K

BAYWATR022 38.14 (969) 22.74 (577) 14.32 (364)

BAYWATR023 BAYWATR024 BAYWATR025 BAYWATR026

47.74 (1212)
63.84 (1621)
79.74 (2025)
92.74 (2355)

25.74 (654) 20.14 (511) 25.74 (654) 20.14 (511) 29.18 (741) 18.55 (471) 31.24 (793) 20.67 (525)

5 (127) 5 (127) 6 (152) 8 (203) 8 (203)

9 (229) 13.67 (347) 16 (406) 10.88 (276) 11.17 (284) 10.84 (275) 17.17 (436) 16 (406) 10.88 (276) 11.17 (284) 11.87 (301) 17.16 (436) 18 (457) 13.70 (348) 10.57 (268) 10.85 (275) 19.67 (500) 22 (559) 12.11 (308) 10.05 (255) 10.85 (275) 19.67 (500) 22 (559) 14.23 (361) 10.01 (254)

2 (51) 2 (51) 2.5 (64) 2.5 (64) 2.5 (64)

128

SS-PRC029Y-EN

Table 114. Steam coil accessory ­ in (mm) (continued)

Model No.

L

M

N

P

Q

R

BAYWATR022 1.5 (38) 26 (660) 12 (305) 6 (152) 2.87 (73) 9.95 (253)

BAYWATR023 2 (51)

30 (762) 18 (457) 8.87 (225) 2.87 (73) 9.95 (253)

BAYWATR024 2 (51)

36 (914) 18 (457) 13.87 (352) 2.87 (73) 9.13 (232)

BAYWATR025 2 (51) 51 (1295) 18 (457) 14.12 (359) 1.87 (48) 8.61 (219)

BAYWATR026 2 (51) 64 (1626) 18 (457) 14.12 (359) 3.75 (95) 8.58 (218)

Figure 28. Discharge plenum and grille accessory

Dimensional Data

C

A B

Table 115. Discharge plenum and grille dimensions ­ no heat ­ in (mm)

Unit TWE051 TWE072, TWE076

Model No.(a) BAYPLNM015 BAYPLNM016

A 37.94 (963.6) 47.5 (1206.5)

B 21.94 (557.2) 24.99 (634.7)

TWE101

BAYPLNM017 63.5 (1612.9)

TWE126, TWE156 BAYPLNM018(b) 79.5 (2019.3)

24.99 (634.7) 27.63 (701.8)

TWE201, TWE251 BAYPLNM019(b) 92.5 (2349.5) 30.43 (772.9)

TWE051

BAYPLNM020 37.91 (962.9) 21.91 (556.5)

TWE076 TWE126

BAYPLNM021 BAYPLNM022

47.5 (1206.5) 63.5 (1612.9)

24.99 (634.7) 24.99 (634.7)

(a) When installed horizontally, plenum/water coil must be self-supported. (b) For use with hydronic heat or no heat.

C 28 (711.2) 28 (711.2) 28 (711.2) 22 (558.8) 24 (609.6) 14.75 (374.65) 14.75 (374.65) 14.75 (374.65)

SS-PRC029Y-EN

129

Dimensional Data
Figure 29. Discharge plenum and grille accessory

C
A

B

Table 116. Discharge plenum and grille dimensions (for use with electric heat) ­ in (mm)

Tons
TWE051 TWE072, TWE076 TWE101
TWE126, TWE156 TWE201, TWE251

Model No. BAYPLNM030 BAYPLNM031 BAYPLNM032 BAYPLNM033
BAYPLNM034

A 38.07 (967) 47.86 (1216) 63.86 (1622) 80.14 (2036)
92.96 (2361)

B 22.69 (576.3) 25.69 (652.5) 25.69 (652.5) 29.10 (739.1)
31.10 (789.9)

C 29.05 (738) 29.05 (738) 29.05 (738) 35.11 (892)
35.05 (890)

Figure 30. Subbase accessory ­ in (mm)

Table 117. Subbase dimensions ­ in (mm)

Tons
TWE051
TWE072, TWE076 TWE101
TWE126, TWE156 TWE201, TWE251

Model No. BAYBASE009 BAYBASE010 BAYBASE011 BAYBASE012
BAYBASE013

A 38 (965.2) 47.5 (1206.5) 63.5 (1612.9) 79.5 (2019.3)
92.5 (2349.5)

B 22.63 (574.8) 25.51 (648.0) 25.52 (648.2) 29.04 (737.6)
31.14 (791.0)

130

SS-PRC029Y-EN

Weights

Cooling Condenser

Table 118. TTA R-410A unit and corner weights -- kg (50 Hz)

Shipping Net Max

Corner Weights

Tons Model No. Max (kg)

(kg)

1

2

3

4

TTA0604DA

146

109

30

33

16

30

5

TTA0604DD

154

122

37

37

24

24

TTA0764DA

155

133

36

44

23

30

6.25

TTA0764DD

170

139

41

41

29

28

TTA1014DD

196

170

48

59

33

30

8.33

TTA1014DC

214

188

49

76

39

24

10.4 TTA1264DD

227

201

52

70

34

45

TTA1564DD

363

312

70

110

51

82

13

TTA1564DC

365

313

61

116

46

91

TTA2014DD

394

318

70

108

55

86

16.7

TTA2014DC

398

345

108

98

68

71

20.9 TTA2514DC

457

384

129

107

98

50

Figure 31. TTA060, 076, 101
#3

Figure 32. TTA156, 201, 251
#4

#1 #2
ASCECREVSICSE

#4
#1

#3

ASCECREVSICSE

#2

ASCECREVSICSE

LIFTING HOLES (BOTH SIDES)

LIFTING HOLES (BOTH SIDES)

SS-PRC029Y-EN

131

Weights

Air Handler
Table 119. Constant volume air handler (TWE) -- unit and corner weights - (50 Hz)

1

2

3

4.6 TWE0514DA

285

6

TWE0724DB

385

6.25 TWE0764DA/B

385

8.33 TWE1014DA/B

441

10.4 TWE1264DB

753

13 TWE1564DB

752

16.7 TWE2014DB

912

20.9 TWE2514DB

993

4

1

2

3

4

232

55

71

51

55

54

67

50

61

323

67

99

75

82

56

92

87

88

323

67

99

75

82

56

92

87

88

393

77 121 110 85

79 118 77 119

676

168 192 181 135 196 164 145 171

675

167 192 181 135 196 163 145 171

818

258 168 161 231 256 181 146 235

899

211 229 184 275 272 176 228 223

Figure 33. Vertical -- TWE051, 072, 076, 101 Control Box Access

Top View
Figure 34. Vertical -- TWE126, 156, 201, 251 Control Box Access

Top View Figure 35. Horizontal -- TWE051, 072, 076, 101
Top View

Control Box Access
132

SS-PRC029Y-EN

Figure 36. Horizontal -- TWE126, 156, 201, 251 Top View
Control Box Access

Weights

SS-PRC029Y-EN

133

Weights

Accessories
Table 120. Accessory weights (net lbs.)

Unit Used
w/ Tons
5

Discharge

Discharge

Plenum Discharge Plenum

and Grille Plenum and Grille

with and Grille with

Electric

Hot Water

Hydronic without Electric Return Air Heat Min/

Coil Steam Coil Heat

Heat

Heat

Grille

Max

86

94

63

58

115

3

32/43

Subbase 14.4

Oversized Motor 31

RIS Isolator
Floor Mount
2

6.25

116

131

78

73

160

5

27/45

19.4

48

2

8.33

165

148

97

92

195

7

27/45

23.5

50

2

10.4

211

234

--

230

235

10

79/100

28.4

80

2

13

211

234

--

230

235

10

79/100

28.4

80

2

16.7

242

261

--

145

265

12

79/100

31.7

88

2

20.9

242

261

--

145

265

12

79/100

31.7

--

2

Unit Used
w/ Tons
5

RIS Isolator Suspended Mount
9

Steel Spring Isolator Floor Mount
12

Steel Spring Isolator Suspended Mount
6

6.25

6

12

6

8.33

7

12

6

10.4

7

12

6

13

7

12

6

16.7

9

12

6

20.9

9

12

6

Hail Guard
21 21 28 33 55 55 71

Control Transformer
4
4
4
4
4
4
4

Expansion Low Sensors Module Ambient

--

13

13

--

13

13

--

13

13

--

13

13

--

2

2

--

2

2

--

2

2

Service Valve
5 5 5 5 5 5 5

134

SS-PRC029Y-EN

Mechanical Specifications

Condensing Units
Standard Features
General
· Weatherproofed steel mounting/lifting rails · Hermetic scroll compressors · Microchannel condenser coils · Fans and motors · Standard operating range 50-125°F (min. 0°F with low ambient accessory) · Nitrogen holding charge · Capacities and efficiencies for split systems are rated within the scope of the Air-
Conditioning, Heating, & Refrigeration Institute (AHRI) certification program and display the AHRI Standard 340-360 (I-P) mark. This standard applies to units between 65,000 and 250,000 btu/hr. · Capacities and efficiencies for split system cooling condensers are rated within the scope of the Air-Conditioning, Heating, & Refrigeration Institute (AHRI) certification program and display the AHRI Standard 365 (I-P) mark. This standard applies to cooling units between 135,000 and 250,000 btu/hr.
Casing
· Zinc coated, heavy gauge, galvanized steel · Weather resistant baked enamel finish · Meets ASTM B117, 672 hour salt spray test · Removable single side maintenance access panels · Lifting handles in maintenance access panels · Unit base provisions for forklift and/or crane lifting
Refrigeration System - Single Compressor (TTA0604DA, TTA0764DA, TTA1014DA)
· Single refrigeration circuit with integral subcooling circuit · Single direct drive hermetic scroll compressor · Suction gas-cooled motor w/ ± 10% voltage utilization range of unit nameplate voltage · Crankcase heater · Internal temperature and current sensitive motor overloads · No compressor suction and/or discharge valves (reduced vibration/sound) · Factory installed liquid line filter drier · Phase loss/reverse rotation monitor · External high pressure cutout device · External low pressure cutout device · Evaporator defrost control · Loss of charge protection (discharge temperature limit)
Refrigeration System - Dual Compressor (TTA0604DD, TTA0764DD, TTA1014DD, TTA1264DD, TTA1564DD, TTA2014DD)
· Two (2) separate and independent refrigerant circuits · Each refrigeration circuit equipped with integral subcooling circuit · Front or rear refrigerant line connections (TTA156**D/201**D) · Two (2) direct drive hermetic scroll compressor · Suction gas-cooled motors w/ ± 10% voltage utilization range of unit nameplate voltage · Crankcase Heaters · Internal temperature and current sensitive motor overloads · Factory installed liquid line filter driers · Phase loss/reverse rotation monitor

SS-PRC029Y-EN

135

Mechanical Specifications
· No compressor suction and/or discharge valves (reduced vibration/sound) · External high pressure cutout devices · External low pressure cutout devices · Evaporator defrost control · Loss of charge protection (discharge temperature limits)
Refrigeration System - Dual Manifolded Compressors (TTA1014DC, TTA1564DC, TTA2014DC, TTA2514DC)
· Single refrigerant circuit with integral subcooling circuit · Two (2) direct drive hermetic scroll compressor · Suction gas-cooled motors w/ ± 10% voltage utilization range of unit nameplate voltage · Crankcase Heaters · Internal temperature and current sensitive motor overloads · No compressor suction and/or discharge valves (reduced vibration/sound) · Factory installed liquid line filter drier · Phase loss/reverse rotation monitor · External high pressure cutout devices · External low pressure cutout devices · Evaporator defrost control · Loss of charge protection (discharge line thermostats) · Front or rear refrigerant line connections (TTA1564DC/2014DC/2514DC only)
Condenser Coil (Microchannel)
· Microchannel coils burst tested by the manufacturer · Coils shall be leak tested to ensure the pressure integrity · Factory pressure and leak tested to 660 psig · Perforated steel hail guards available (factory installed option or field installed accessory)
Condenser Fan
· 26" or 28" propeller fan(s) · Direct drive · Statically and dynamically balanced
Condenser Motor(s)
· Permanently lubricated totally enclosed or open construction · Built-in current and thermal overloads · Ball or sleeve bearing type
Controls
· Centralized microprocessor · Indoor and outdoor temperature sensors drive algorithms, making decisions for all heating,
cooling, and ventilation · Integrated anti-short cycle timer · Integrated time delay between compressors · Completely internally wired · Colored and keyed connectors and colored wires · Contactor pressure lugs or terminal block · Unit external mounting location for disconnect device · Single point power entry · Front or rear electrical connections (TTA1564DC/D, 2014DC/D, 2514DC only)
Factory Installed Options
Hail Guards
· Condenser coil protection from hail, vandals, etc. · Perforated, painted galvanized steel

136

SS-PRC029Y-EN

Mechanical Specifications
· Factory or field installed
Complete CoatTM Microchannel Condenser Coil
· Available on Microchannel units only · Cathodic, epoxy-type, electro-disposition coating formulated for high edge build · Coating provides excellent resistance and durability to corrosive effects of alkalies, acids,
alcohols, petroleum, seawater, salty air and other corrosive environments
BACnet Communication Options
· BACnet MS/TP -BACnet IP · Allows unit communication with Trane or generic BACnet building automation controls
Advanced Diagnostics and LonTalk Communication Interface
· Factory or field installed · Allows unit communication as a Tracer Lon® device · Allows unit communication with generic LonTalk® Network building automation controls
Field Installed Options
Low Ambient (Fan ON/OFF)
· Provides unit cooling operation to outdoor ambient of 0°F · Low cost solution · Discharge pressure controls condenser fan operation
Service Valves
· Liquid line service valve (with gauge port) · Suction line service valve (with gauge port)
Vibration Isolators
· Neoprene-in-shear or spring flex choice · Reduce vibration transmission to building structures, equipment, and adjacent spaces · Reduce noise transmission to building structures, equipment, and adjacent spaces
Hot Gas Bypass
· Provides capacity modulation solution
Zone Sensor
· Interfaces with microprocessor units · Manual or automatic programmable · System malfunction lights · Remote sensor options
Thermostat
· 1H/1C available · 2H/1C available · Manual or automatic changeover available · Programmable and non-programmable solutions available
LonTalk Communication Interface
· Factory or field installed · Allows unit communication as a Tracer Lon® device · Allows unit communication with generic LonTalk® Network building automation controls

SS-PRC029Y-EN

137

Mechanical Specifications
Air Handlers
Standard Features
General
· Completely factory assembled · Convertible for horizontal or vertical configuration · Convertible for cooling only or heat pump application · Convertible for left or right external connections (refrigerant and/or electrical) · Convertible for front or bottom air return · Nitrogen holding charge
Casing
· Zinc coated, heavy gauge, galvanized steel · Weather resistant baked enamel finish · Access panels with captive screws · Completely insulated with foil faced, cleanable, fire retardant, permanent, odorless glass fiber
material · Captured or sealed insulation edges · Electrical connection bushings or plugs · Refrigerant connection bushings or plugs · Withstand elevated internal static pressure
Refrigeration System
· Single or dual circuit · Distributor(s) · Thermal expansion valves (TXVs)
Evaporator Coil
· 3/8" internally enhanced copper tube mechanically bonded to lanced aluminum plate fins · Factory pressure and leak tested to 449 psig. · Draw-through airflow · Dual circuits are interlaced/intertwined · Double sloped, removable, cleanable, composite drain pan · Four drain pan positions
Indoor Fan
· Double inlet, double width, forward curved, centrifugal type fan · Dual fans on 10.4 ­ 20.9 ton air handlers · Adjustable belt drive · Permanently lubricated bearings
Indoor Motor
· Adjustable motor sheaves (constant volume units) · Thermal overload protection · Permanently lubricated bearings · Meet energy policy of 1992 (EPACT) · Optional oversized motors for high static applications
Controls
· Completely internally wired · Colored and keyed connectors, colored wires · Magnetic indoor fan contactor · Detachable low voltage connectors · Single point power entry · Evaporator defrost control

138

SS-PRC029Y-EN

Mechanical Specifications
Filters
· Access from side coil panels · Filters slide on rack · One inch (1"), throwaway filters on 4.6 - 8.33 ton units · Filter rack convertible to two inch (2") capability on 4.6 - 8.33 ton units · Two inch (2"), throwaway filters on 10.4 - 16.7 ton units
Field Installed Options
Electric Heaters
· Heavy duty nickel chromium elements · Installs directly on fan discharge · One or two stage control (dependent upon capacity) · Single point power entry · Terminal strip connections · Heaters
­ Internally wye connected ­ Automatic line break high limit controls with secondary single action disc limits
Hydronic Heat Coils
· One row steam · Two row hot water · Installs directly on fan discharge · Heavy gauge sheet metal casing matches air handler · Convertible for horizontal or vertical configurations
Discharge Plenums and Grilles
· Vertical, free discharge applications · Heavy gauge sheet metal casing matches air handler · Satin-finished, 4-way adjustable louver grilles
Return Air Grilles
· Vertical, free discharge applications · Satin-finished, non-adjustable louver grilles · Replaces front lower access panel
Mounting Sub-Base
· Vertical floor mount configuration requirement · Heavy gauge sheet metal casing matches air handler · Provides additional clearance for condensate drain trapping · Required when isolators are used
Vibration Isolators
· Neoprene-in-shear or spring flex choice · Floor or suspended applications · Reduce vibration transmission to building structures, equipment, and adjacent spaces · Reduce noise transmission to building structures, equipment, and adjacent spaces
Oversize Motors
· High static applications · Motor, sheaves, belt included
Filters
· 2 inch, MERV 13 high efficiency filters

SS-PRC029Y-EN

139

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

SS-PRC029Y-EN 10 Sep 2021 Supersedes SS-PRC029W-EN (April 2021)

©2021 Trane


PDFlib PDI 9.0.6 (C /Win64) PTC Arbortext Publishing Engine