Installation Guide for Danfoss models including: DMB, Eliminator Hermetic Bi Flow Filter Drier, DMB Eliminator Hermetic Bi Flow Filter Drier, DCB
DMB filter driers for A/C | DCB filter drier | Danfoss
023R9532 023R9532 023R9532 023R9532 Installation guide ELIMINATOR® Hermetic bi-flow filter drier Types DMB and DCB Refrigerants: A1: R134a, R404A, R407C, R507, R22, R410A. A2L: R32, R444B, R452B, R454B, R1234yf. A3: R290, R600a For other refrigerants, please contact Danfoss representative. Only solder versions (cu-plated / pure copper) and connection sizes below 25mm are approved for A3 refrigerants. Only connection sizes below 25 mm are approved for A2L. Temperature range: -40 70 °C -40 160 °F Max. working pressure: PS / MWP = 46 bar / 667 psig Installation Soldering Indoor coil STF Outdoor coil Min.5% Ag DMB/DCB TGE Mounting After charging, mark the system with the refrigerant and the oil used. Customer best practice will still be needed: · Use wet wrap when installing. · Braze the joints. · Let them cool down. · Clean the brazing /welding area after the installation (remove remaining flux with a brush). · This is an important operation and needs to be done with great care to remove all remaining flux. · Paint / Anti-corrosive needs to cover all open steel parts, areas where the black original paint has been burnt due to brazing and at least 3 cm approx of the copper. · Paint the joints twice. Danfoss 23Z7016.10 Danfoss 23Z7016.10 Danfoss 23Z7013.10 Danfoss 23Z7013.10 Danfoss 23Z7014.10 Danfoss 23Z7015.10 Danfoss 23Z7014.10 Danfoss 23Z7015.10 © Danfoss | Climate Solutions | 2021.11 AN142486435382en-000501 | 1Danfoss A/S Adobe PDF library 15.00