ELIMINATOR Hermetic bi-flow filter drier, types DMB and DCB

367.6 KB

DMB filter driers for A/C | DCB filter drier | Danfoss

PDF preview unavailable. Download the PDF instead.

AN142486435382en-000501
023R9532

023R9532

023R9532

023R9532

Installation guide
ELIMINATOR® Hermetic bi-flow filter drier Types DMB and DCB
Refrigerants: A1: R134a, R404A, R407C, R507, R22, R410A. A2L: R32, R444B, R452B, R454B, R1234yf. A3: R290, R600a For other refrigerants, please contact Danfoss representative.
Only solder versions (cu-plated / pure copper) and connection sizes below 25mm are approved for A3 refrigerants. Only connection sizes below 25 mm are approved for A2L.

Temperature range:
-40 ­ 70 °C -40 ­ 160 °F

Max. working pressure: PS / MWP = 46 bar / 667 psig

Installation

Soldering

Indoor coil STF

Outdoor coil

Min.5% Ag

DMB/DCB TGE
Mounting

After charging, mark the system with the refrigerant and the oil used.
Customer best practice will still be needed: · Use wet wrap when installing. · Braze the joints. · Let them cool down. · Clean the brazing /welding area after the installation (remove remaining flux with a brush). · This is an important operation and needs to be done with great care to remove all remaining flux. · Paint / Anti-corrosive needs to cover all open steel parts, areas where the black original paint has been burnt due to brazing and at least 3 cm approx of the copper. · Paint the joints twice.

Danfoss 23Z7016.10
Danfoss 23Z7016.10

Danfoss 23Z7013.10
Danfoss 23Z7013.10

Danfoss 23Z7014.10

Danfoss 23Z7015.10

Danfoss 23Z7014.10

Danfoss 23Z7015.10

© Danfoss | Climate Solutions | 2021.11

AN142486435382en-000501 | 1

