GENERAL DESCRIPTION:

X7-WIFI
· Commercial Grade Wi-Fi Thermostat · Gas/Electric to 2H/2C, Heat Pump to 3H/2C · Humidity Sensing and Control · CO2 Sensing and Control Ready · Advanced Remote Sensor Bus · Two Configurable · Full Color Touchscreen · 7 Day Programmable ~ 4 Events/Day · 80 Additional Event Schedules · BACnet/IP and Modbus TCP/IP Included
Complete Stand-Alone Solution

The X7-WIFI is a Wi-Fi color touchscreen thermostat with an advanced remote sensor bus, designed for new or

replacement commercial and residential applications. Use the X7 for either conventional and heat pump applications

(Gas/Elect 2H/2C, HP 3H/2C), along with humidification, fresh air damper, IAQ controls and more. The X7 also has a

revolutionary accessory deliver a near-effortless

sselotut pfoor fCyOo2u/rVdOaCilyssecnhseodrsu,leasnd(4theeveNnetstXpDerEdCaTy/)UaLnEd

Wireless up to 80

Sensors. Additional

DirectConnectTM helps Events (40 Special and

40 Calendar Events). The unique scheduling structure also supports the powerful features of adjustable temporary

override times and temperature ranges, occupied and unoccupied events, keypad lockout, and many more features. The

X7-WIFI also includes full BACnet/IP support over Wi-FI, directly on the thermostat.

The X7-WIFI is designed to operate with our CloudConnectTM Online Management software or, for maximum security, behind your firewall using DirectConnectTM or our PCConnectTM Software. Since all HVAC functions are stored in the thermostat, the X7 will continue to operate even during network outages, allowing you to maintain your energy savings. For ultimate control over energy usage, the X7 offers a digital lockout that can permit limited temperature overrides based on your requirements. Our on-board data collection allows for historical review, sub-metering, and run-time reporting.

STANDARD FEATURES:

CloudConnectTM & CloudManagerTM Available

Energy Savings  Efficient Equipment RestartTM randomizes equipment starts to minimize
multiple units turning on simultaneously when there are multiple NetX thermostats at the location  Random Restart on power up staggers restart of HVAC system after a power outage to minimize peak inrush current  Adaptive Recovery for Schedules allows system to achieve desired setpoint at the beginning of the schedule
Monitoring  14 Remote Sensors: up to 6 indoor, 1 humidity, 1 outdoor, and up to 6
auxiliary sensors for monitoring items such as supply air, return air, walk-in refrigerators and freezers, etc.  Accessory Port for CO2/VOC and NetX DECT/ULE Wireless Sensors  2 Digital Inputs for Fault Conditions, including Condensate and Equipment Faults  Occupancy Sensor Input  On-board Data Logging with Sub-Metering Support
Connectivity  CloudConnectTM Internet-Based Cloud Service  PCConnectTM Software Local Network & Port Forwarded Access  DirectConnectTM Integrated Web Server  Integrated NetXTM API, Supports 3rd Party Apps  BACnet/IP and Modbus TCP/IP Embedded  Optional Modbus RTU Interface via NT-485 Module
© 2023 Network Thermostat, Grapevine, TX

Facility Management  4 independent schedules per day  80 Additional Schedules (40 Special and 40 Calendar Events)  Commercial Lockout with Programmable Temporary Override Time and
Temp Adjustment  Email & Text Message Alerting for 4 Recipients  Alerts include Hi/Lo Temps for Indoor, Outdoor, Supply, Return, and Aux
Temps, Inefficient Equipment Runs, Change Filter Notifications, and Two Digital Inputs: 19 Alerts in All
General  Color Selectable Touchscreen Display, Black or White Case  Modes: Heat, Cool, Automatic Changeover  Integrated Humidity Sensor & Humidification and Dehumidification
Control  Fan Selector for Automatic and up to 3-speed Fan Operation*;
Programmable Recirculation Fan  Relay 1 & Relay 2 Flexible Control
 Humidification and Dehumidification Control  Fresh-Air Damper Control  IAQ Equipment Control Control  Auxiliary General Purpose Relays
with Scheduling  Integrated Weather with Current Conditions and
7-Day Forecasts

972-580-8001

P/N 240254-05

SPECIFICATIONS:

Rated Voltage: Rated A.C. / D.C. Current: Temperature Control Range: Thermostat Sensing Range: Minimum Deadband: Humidity Sensing: Humidity Control Range: Dimensions: Equipment Terminations:
Aux Relay Terminations:

20V to 30VAC, 24VAC nominal 0.05 to 0.75 AC / 0.0 to 0.75 DC Amp continuous, per output, surges to 3 Amps maximum Heating: 38 to 88°F (6 to 30°C) in 1° steps Cooling: 60 to 108°F (16 to 40°C) in 1° steps 20 to 124°F (0 to 48°C) Control Accuracy: +/-1°F @ 68°F (0.5°C @ 20°C) 2°F (1°C) Range: 0% - 100% RH Accuracy: ±3% From 10% - 90% Humidify: 10% to 60%RH in 5%RH steps Dehumidify: 35% to 75%RH in 5%RH steps 5.1"H x 4.7"W x 1.15"D (128mm x 119mm x 29mm) R - 24V switching voltage, W1 - Heat1 or Aux/Emer Heat, G - Fan, Y1-Compressor1, Y2 - Compressor2, O/W2 - Heat2 or Rev. Valve in Cooling, B - Rev. Valve in Heating, K/H/D ­ Humidify / Dehumidify / Relay 1 Schedule / Damper / IAQ , K2 ­ Relay 2 Schedule / Damper / IAQ

Power Terminations:

24V(c) - Power Return, 24V - Separate Power (24VAC/DC) requires jumper removal

Input Terminations:

LED1 (Filter Icon Selectable), LED2 (Fault Icon Selectable), CLK1 ( + ), CLK2 ( - ) (Occupancy)

Remote Sensor Terminations: RS+V - Power, RS2 - Return, RS1 - Data

Wireless Radio:

2.4GHz 802.11b/g/n, Security: Open, WEP, WPA-PSK, WPA2-PSK

Accessory Port: Protocols:

SIM port for NetX CO2/VOC Sensor, NetX DECT/ULE Wireless Sensor Network Host Card http, native NetX API, BACnet/IP and Modbus TCP/IP over Wi-Fi

WIRING DIAGRAMS:

INPUT, OCCUPANCY,
SENSOR CONNECTIONS
24Vac INPUT #1 24Vac INPUT #2 OCCUPANCY IN ( + ) OCCUPANCY IN ( ­ ) REMOTE SENSOR BUS - RTN REMOTE SENSOR BUS - DATA REMOTE SENSOR BUS - PWR
RELAY 2, FAN 3

*24V for separate power (24VAC/DC). Requires jumper removal on faceplate.

LED1 LED2 CLK1 CLK2 RS2 RS1 RS+V X2/A X1/B K2

K/H/D Y2 W1 Y1 G R
24V 24V(c)
O/W2 B

HVAC CONNECTIONS

(DE)HUM, RELAY 1, FAN 2 COMPRESSOR #2
HEAT #1 or AUX/EMER HEAT

K/H/D Y2 W1

COMPRESSOR #1

Y1

FAN 24 VAC

G R

COMMON HEAT #2 or AUX/EMER HEAT or REVERSING VALVE

C O B

HVAC Equipment.
Line Voltage
24 Vac Transformer

Note: Check Heat Pump Installation Instructions for reversing valve connection, either `O' or `B'.
TERMINAL FUNCTIONS

LED1 24Vac Input #1 for Filter or other Alert LED2 24Vac Input #2 for Condensate, Fault or other Alert CLK1 For use with External Occupancy Sensor ( + ) CLK2 For use with External Occupancy Sensor ( - )
RS2 Remote Sensor Bus (Power Return) RS1 Remote Sensor Bus (Data) RS+V Remote Sensor Bus (Power) X2/A N/A X1/B N/A
K2 Programmable Auxiliary Relay 2, FAN 3

K/H/D Humidification or Dehumidification, Aux. Relay 1, or FAN 2

Y2

Energizes compressor for second stage cooling, or for heat pumps, either second stage heating or cooling

W1

Energizes heater for first stage heating, or for heat pumps, aux/emer heat

Y1 Energizes compressor for first stage cooling, or for heat pumps, either first stage heating or cooling

G Energizes fan circuit with a call for heating or cooling

R Independent Switching Voltage from HVAC equip

24V 24Vac

24V(c) 24Vac Common

O/W2

Energizes heater for second stage heating, or for heat pumps, energizes the reversing valve in cooling mode

B Energizes the reversing valve in heating mode

