Installation Guide for kwhiq models including: IQ0304100d1, IQ0304100d1 Direct Connected Three Phase DIN Rail Meter, Direct Connected Three Phase DIN Rail Meter, Connected Three Phase DIN Rail Meter, Three Phase DIN Rail Meter, Phase DIN Rail Meter, DIN Rail Meter, Rail Meter, Meter

Installation manual

Direct connected 3-fase DINrail Meter - Xemex


File Info : application/pdf, 15 Pages, 3.00MB

PDF preview unavailable. Download the PDF instead.

Installation-Manual-IQ0304100d1
Installation Manual
IQ0304100d1
> Direct connected Three Phase DIN rail Meter > 100 Amp MODbus meter > MID certified > Designed for submetering of electrical loads like EV-chargers, PV-Inverters
with high Amps
Contact
www.kwhiq.com info@kwhiq.com +31 (0)73 544 3071

Installation Manual Version 1.0 IQ0304100d1 - meter

Amendment

Version 1.0 1.1

Date 06/03/2023 09/03/2023

Remark Draft

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 2

Installation Manual Version 1.0 IQ0304100d1 - meter

Content

Content

3

MID Certificate

4

Guidelines for safety and installation

5

Safety Instructions

5

Exclusion of liability

5

All Rights Reserved

5

For service and technical support information, please contact

5

Specifications

6

Electrical

6

Environmental

6

Dimensions

6

Wiring diagram

6

Display format

6

General description

7

Front view

7

Button instruction

7

LCD display

8

LCD Scrolling Display Page

8

LCD Information Display Page

9

Installation

10

Mounting

10

Electrical install procedure

11

Communication install procedure

11

Operation

12

Scrolling function

12

Set modbus parameters

12

Modbus registers (partly)

14

Contact information

15

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 3

Installation Manual Version 1.0 IQ0304100d1 - meter
MID Certificate

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 4

Installation Manual Version 1.0 IQ0304100d1 - meter
Guidelines for safety and installation
This installation guide must be consulted in all cases when manipulating parts which are marked with the Caution symbol. The installation and the operation of this device and any maintenance must be carried out by a qualified person in accordance with specific local standards and safety regulations. Failing to obey the "Guidelines for safety and installation", the guarantee no longer applies.
Safety Instructions · Case is sealed, do not open the meter. No warranty if case is opened. · The meter should be installed indoor or in the outdoor electric meter box. · The meter is intended to be installed in a Mechanical Environment `M1', with Shock and Vibrations of low significance, as per
2014/32/EU Directive. · The meter is intended to be installed in Electromagnetic Environment `E2', as per 2014/32/EU Directive.
Exclusion of liability We have checked the contents of this publication and every effort has been made to ensure that the descriptions are as accurate as possible. However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any errors or omissions in the information given. The data in this manual is checked regularly and the necessary corrections will be included in subsequent editions. If you have any suggestions, please let us know.
All Rights Reserved No part of this document can be reproduced or transmitted in any form or by any means without prior written consent of KWHIQ B.V. Burgemeester Burgerslaan 40 5245 NH Rosmalen. The Netherlands.
For service and technical support information, please contact: KWHIQ b.v. Burgemeester Burgerslaan 40. 5245 NH Rosmalen, E-mail: support@kwhiq.com, Website: https://kwhiq.com/

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 5

Installation Manual Version 1.0 IQ0304100d1 - meter

Specifications

Electrical Accuracy Voltage
Current Frequency Power consumption Pulse constant

Active
Reactive
Rated Voltage Voltage with standard Operation voltage range Long-range voltage Rated current Starting current 50Hz ± 2% Voltage circuit Current circuit 1000 imp/kWh(kvarh)

Class B Class 2 2x230(400)V 440V 80% to 120% Un 58/100V to 240/415V 5(100)A 20mA
1W 12VA

Environmental
Operating temperature Operating humidity
Dimensions

-40 ° C to 70 ° C 75% RH (Max 95% RH)

Storage temperature Case protection
Display format

-40 ° C to 70 ° C IP51 Indoor

Wiring diagram

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 6

Installation Manual Version 1.0 IQ0304100d1 - meter

General description
Front view

I

Impulse indication for active energy

J

Impulse indication for reactive energy

K

Far IR

L

Button for data checking

Q

M

Button for data setting

N

SO1 output for active energy (default)

O

SO2 output for reactive energy (default)

I

M

P

RS485 output

Q

LCD screen

N J KO L P

Button instruction Button

Function Short Press: next page
Long press: go to setup menu

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 7

Installation Manual Version 1.0 IQ0304100d1 - meter

LCD display

LCD Scrolling Display Page

20LCD Scrolling Display Page

Page Content

1

Total active energy

2

Forward active energy

3

Reverse active energy

4

Total reactive energy

5

Forward reactive energy

6

Reverse reactive energy

7

First quadrant reactive energy

8

Second quadrant reactive energy

9

Third quadrant reactive energy

10

Fourth quadrant reactive energy

11

Active maximum demand

12

Forward active maximum demand

13

Reverse active maximum demand

14

Reactive maximum demand

15

Forward reactive maximum demand

16

Reverse reactive maximum demand

17

A phase and N-phase voltage

18

B phase and N-phase voltage

19

C phase and N-phase voltage

20

A Phase and B Phase line voltage

21

B Phase and C Phase line voltage

22

C Phase and A Phase Line Voltage

23

Current of A-phase

24

Current of B-phase

25

Current of C-phase

26

Combined active power

27

A-phase active power

28

B-phase active power

29

C-phase active power

30

Combined reactive power

31

A phase reactive power

32

C phase reactive power

33

Combined Apparent Power

34

A phase apparent power

35

B phase apparent power

36

C phase apparent power

37

Combined frequency

38

A phase frequency

39

B phase frequency

40

C phase frequency

41

Combined power factor

42

A phase power factor

43

B Phase power factor

44

C Phase power factor

Unit kWh kWh kWh kWh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh V V V V V V I I I kW kW kW kW kvarh kvarh kvarh kVA kVA kVA kVA Hz Hz Hz Hz Hz Hz Hz Hz

Long press the left button for more than 3 seconds to switch the display page: > Scroll display page > A-phase energy page > B-phase energy page > C-phase energy page > Information page > Scroll display page

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 8

Installation Manual Version 1.0 IQ0304100d1 - meter

LCD Information Display Page

LCD Information Display Page

Page Content

1

12-digit serial number of the meter

2

Modbus communication address

3

Baud rate

4

Parity

5

Stop bit

6

Scrolling time

7

Combination code

8

Demand type & period

9

SO output

Format
000000000000
1-247
6 = 9.600 7 = 19.200 8 = 38.400 9 = 115.200
0=None (default) 1=Odd 2=Even
1=1 bit (default) 2=2 bit
0-99 seconds
1-Total=forward 2-Total=reverse 3-Total =forward+reverse (default) 4-Total=forward-reverse
0=Interval 1=Slip Period=1-30 minutes
800, 1.000, 1.600, etc. above 100, divisible by 96.000

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 9

Installation Manual Version 1.0 IQ0304100d1 - meter
Installation
CAUTION: · Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to
it before working on it. · Always use a properly rated voltage sensing device to confirm that power is off. WARNING: · The installation should be performed by qualified personnel familiar with applicable codes and regulations. · Use insulated tools to install the device. · A fuse, thermal cut-off or single-pole circuit breaker should be fitted on the supply line and not on the neu-
tral Mounting Mount the device in a DIN-rail cabinet
Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized Page 10

Installation Manual Version 1.0 IQ0304100d1 - meter

Electrical install procedure

 2.5 Nm

(A) 0-32 32-65 65-100

(mm2) 1-6 10-14 16-25

(Nm) 0.9-1.2 1.5-2.0 2.0-2.5

Maximum cable size: : 25 mm2

Maximum screw torque: : 2.5 Nm

Communication install procedure
Maximum screw torque: 0.2 Nm:

Maximum cable size: : 2.5 mm2 : 2.5 mm2

Wire the device in accordance to the Wiring Diagram. If the bare wire is visible above the terminal bridge, shorten the stripped part of the wire.

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 11

Installation Manual Version 1.0 IQ0304100d1 - meter

Operation
Scrolling function · Automatic scroll: Every 5 seconds the meter will display the next programmed data page (depending on the setting). · Button scroll: Each short press on the meter button will display the next programmed data page.

Set modbus parameters

By default, the modbus parameters are: Modbus id Baud rate Parity # Stop bits

1 9.600 None 1

Meter settings can be adjusted in two ways: · Manually through the use of the button and display page · Serially through Modbus commands (see Modbus registers).

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 12

Installation Manual Version 1.0 IQ0304100d1 - meter
Manually adjusting meter settings 1. Navigate to the SETUP menu by long pressing the push button (see red circle). In the SETUP menu you can enter a PIN code. By long
pressing the push button you can enter digits. Press briefly to adjust the value of the flashing digit. Use this method to enter the PIN code 0000.

01 100

14 SETUP

14Pin 0000

Default: standard mode

SETUP menu

Pincode

2. Check the following settings in the SETUP menu and change if necessary. Press long to adjust, press briefly to change variables.

01 1D 001

02 9600

03 None

Modbus ID: unique per device on the bus

Baud rate: default `9600' (19200/38400/115200)

Parity: default `None' (odd/even)

04 STOP 1

Stop bit: default `1'

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized

Page 13

Installation Manual Version 1.0 IQ0304100d1 - meter 3. Long press the push button to navigate out of the SETUP menu. Configuration is complete.
04 QUIT

QUIT

Modbus registers (partly)
A selection of the most important modbus registers:

Page Serial Number E-meter

Reg unit UNITLESS

Modbus Reg Address (DEC) 4096

Modbus Reg Address (HEX) 0x1000

Modbus ID
Forward Active Energy
Reverse Active Energy
Forward active Power
Reverse active Power Instantaneous Voltage L1-N Instantaneous Voltage L2-N Instantaneous Voltage L3-N Instantaneous Voltage vector

1-247 kWh kWh Watt Watt Volt
Volt
Volt
Volt

Instantaneous Voltage

Volt

vector

Instantaneous Current L1
Instantaneous Current L2 Instantaneous Current L3 Instantaneous Current vector

Ampère
Ampère Ampère Ampère

4099

0x1003

270

0x010E

280

0x0118

1056

0x0104

Negative Forward Power

1024

0x0400

1026

0x0402

1028

0x0404

1036

0x040C

1038

0x040E

1040
1042 1044 1048

0x0410
0x0412 0x0414 0x0418

Modbus Reg Length 3
1

Modbus Reg Type
12-bit serial number, hexadecimal
8-bit integer

Comment

2

INT32(6+2)

2

INT32(6+2)

2

INT32(5+0)

2

INT32(3+3)

2

INT32(2+3)

2

INT32(2+3)

2

INT32(2+3) [(VA phase - N) +

(VB phase - N) +

(VC phase - N)] / 3

2

INT32(2+3) [(VL1-L2) +

(VL2-L3) +

(VL3-L1)] / 3

2

INT32(2+3)

2

INT32(2+3)

2

INT32(2+3)

2

INT32(2+3)

Copyright KWHIQ - Reproduction and communication of this document is strictly prohibited unless specifically authorized Page 14

Contact information
Contact - NL Burgemeester Burgerslaan 40 5245 NH Rosmalen The Netherlands Phone: +31 73 544 3071
Contact - BE Metropoolstraat 11a B2900 Schoten Belgium Phone: +32 32 01 95 95
Contact - UAE Office 901 HQ Tower (North) Dubai Science Park PO.Box: 478817 Dubai -United Arab Emirates Phone: +971 4 4422 9701
Find us online
www.kwhiq.com info@kwhiq.com



References

Adobe PDF Library 17.0 Adobe InDesign 18.2 (Macintosh)