Installation and Operating Instructions Addendum

High Efficiency Condensing Combi Boiler

99,000 & 125,000 Btu/hr Models

160,000 & 199,000 Btu/hr Models

This addendum replaces the version found in the High Efficiency Condensing Combi Boiler 99,000 & 120,000 Btu/hr and 160,000 & 199,000 Btu/hr Installation and Operating Instructions dated April 2022.

Page 2

  • 1 x Propane Conversion Kit: Part # P-081034 (99,000 Btu/hr) or Part # P-081054 (125,000 Btu/hr) or Part # P-081744 (160,000 Btu/hr) or Part # P-081014 (199,000 Btu/hr)

Page 1-18

⚠️ NOTE

Combustion air connection may be moved from one side to the other:

  • Remove the retaining clip screws then lift tab at back of plug and rotate 1/8th of a turn counter-clockwise to remove from top of cabinet.
  • Remove the retaining clip by removing both screws then lift tab at back of combustion air connection and rotate 1/8th of a turn counter-clockwise to remove from top of cabinet.
  • Reinstall plug and combustion air connection in the desired locations then rotate 1/8th of a turn clockwise until tab latches into the top of the cabinet.
  • Reinstall the retaining clip over the combustion air connection tab and secure with two screws. Reinstall two screws in the top of the cabinet near the plug.

Page 3-4

PROPANE ORIFICE CHART

MODELORIFICE SIZE
99,000 Btu/hr327
125,000 Btu/hr392
160,000 Btu/hr440
199,000 Btu/hr535

NATURAL GAS ORIFICE CHART

MODELORIFICE SIZE
99,000 Btu/hr415
125,000 Btu/hr480
160,000 Btu/hr580
199,000 Btu/hr660

Document Number: 900-804, August 2022