OMRON NX1P Machine Automation Controller

Compact package-type machine automation controller

Key Features

System Configuration

The NX1P2 CPU Unit forms the core of the system, connecting to various NX Units via the CPU Rack. This configuration allows for flexible expansion and customization to meet specific automation needs. The system supports EtherNet/IP and EtherCAT network configurations for communication with other devices and systems.

Basic System Configuration Diagram:

The diagram illustrates the NX1P2 CPU Unit connected to NX Units within a CPU Rack. An Option Board can be added to the CPU Unit. The EtherCAT network configuration shows connections to slave terminal units, servo drives, encoder input slaves, and general-purpose slaves. An EtherNet/IP network is also shown.

Interpreting Model Numbers

Model numbers for the NX1P2 CPU Units follow a specific structure, indicating features such as control engine, synchronized motion control axes, and built-in I/O. For example, NX1P2-9024DT indicates a specific configuration.

No. Item Symbol Specifications
1 Type P DC power supply model with built-in I/O
2 Control engine 9 Motion control axes
3 Synchronized motion control axes * 0
2
4
No motion control axis (Single-axis position control axes only)
2 axes
4 axes
4 Built-in I/O 24 24 (14 inputs, 10 outputs)
5 Built-in input type D DC inputs
6 Built-in output type T
T1
NPN transistor outputs
PNP transistor outputs

* The number of synchronized motion control axes when "2 Control engine" is "1". When "2 Control engine" is "9", "3 Synchronized motion control axes" is always "0" but there is no synchronized motion control axis.

Ordering Information

The following table provides details on the NX-series NX1P2 CPU Units, including their program memory capacity, used motion control axes, I/O points, and available models.

Product Name Program Memory capacity for variables Maximum number of used real axes Used motion control servo axes *1 Used single-axis position control servo axes *1 Total number of built-in I/O points Number of input points Number of output points Model
NX1P2 CPU Unit 1.5 MB
32 KB (Retained during power interruptions) or 2 MB (Not retained during power interruptions)
8 axes 4 axes 4 axes 40 points 24 points 16 points NX1P2-1140DT
NX1P2-1140DT1
6 axes 2 axes 4 axes 24 points 14 points 10 points NX1P2-1040DT
NX1P2-1040DT1
4 axes 0 axes 4 axes 24 points 14 points 10 points NX1P2-9024DT
NX1P2-9024DT1

Note: One NX-END02 End Cover is provided with the NX1P2 CPU Unit.

*1. The following table shows the enabled functions.

Motion control function Single-axis position control Motion control servo axes Single-axis position control servo axes
Single-axis synchronized control Yes Yes Yes No
Single-axis velocity control Yes Yes Yes No
Single-axis torque control Yes Yes Yes No
Multi-axes coordinated control Yes Yes Yes * No

* You can use only the MC_MoveVelocity (Velocity Control) instruction.

*2. With the load short-circuit protection.

Option Boards (For CPU Units)

Option Boards enhance the functionality of the CPU Unit by adding serial communication or analog I/O capabilities.

Product Name Specification Supported protocol Model
Serial Communications Option Board One RS-232C port. Transmission distance: 15 m. Connection type: Screwless clamping terminal block (9 terminals) Host link, Modbus-RTU master, and no-protocol NX1W-CIF01
One RS-422A/485 port. Transmission distance: 50 m. Connection type: Screwless clamping terminal block (5 terminals) NX1W-CIF11
One RS-422A/485 port (isolated). Transmission distance: 500 m. Connection type: Screwless clamping terminal block (5 terminals) NX1W-CIF12
Analog I/O Option Board Analog input: 2 (Voltage input: 0 to 10 V; Current input: 0 to 20 mA). Connection type: Screwless clamping terminal block (5 terminals) NX1W-ADB21
Analog output: 2 (Voltage output: 0 to 10 V). Connection type: Screwless clamping terminal block (3 terminals) NX1W-DAB21V
Analog input: 2/Analog output: 2 (Voltage input: 0 to 10 V; Current input: 0 to 20 mA; Voltage output: 0 to 10 V). Connection type: Screwless clamping terminal block (8 terminals) NX1W-MAB221

NX Units

Up to eight NX Units can be connected to an NX1P2 CPU Unit, providing a modular and expandable system. Various types of NX Units are available, including Digital Input Units, Digital Output Units, Digital Mixed I/O Units, High-speed Analog Input Units, Analog Input Units, and Analog Output Units.

Digital Input Units

These units are used for inputting digital signals into the controller. They are available in various configurations, including NPN and PNP types, with different numbers of points and connection methods.

Product Name Number of points Internal I/O common Rated input voltage I/O refreshing method ON/OFF response time Model
DC Input Unit 4 points NPN/PNP 12 to 24 VDC Switching Synchronous I/O refreshing and Free-Run refreshing 20 µs max./400 µs max. NX-ID3317
NX-ID3343
NX-ID3417
NX-ID3443
NPN/PNP 24 VDC Input refreshing with input changed time only * 100 ns max./100 ns max. NX-ID3344
NX-ID3444
DC Input Unit (Screwless Clamping Terminal Block, 12 mm Width) 8 points NPN/PNP 24 VDC Switching Synchronous I/O refreshing and Free-Run refreshing 20 µs max./400 µs max. NX-ID4342
NX-ID4442
DC Input Unit (M3 Screw Terminal Block, 30 mm Width) 16 points NPN/PNP 24 VDC Switching Synchronous I/O refreshing and Free-Run refreshing 20 µs max./400 µs max. NX-ID5342
NX-ID5442
DC Input Unit (For both NPN/PNP, 16 points) 16 points For both NPN/PNP 24 VDC Switching Synchronous I/O refreshing and Free-Run refreshing 20 µs max./400 µs max. NX-ID5142-1
DC Input Unit (MIL Connector, 30 mm Width) 32 points For both NPN/PNP 24 VDC Switching Synchronous I/O refreshing and Free-Run refreshing 20 µs max./400 µs max. NX-ID5142-5
NX-ID6142-5
AC Input Unit (Screwless Clamping Terminal Block, 12 mm Width) 4 points For both NPN/PNP 200 to 240 VAC, 50/60 Hz (170 to 264 VAC, ±3 Hz) Free-Run refreshing 10 ms max./40 ms max. NX-IA3117

* To use input refreshing with input changed time, the EtherCAT Coupler Unit with unit version 1.1 or later and the Sysmac Studio version 1.07 or higher are required.

Digital Output Units

These units provide digital outputs for controlling actuators and other devices. They are available in various configurations, including transistor output units and relay output units.

Product Name Number of points Internal I/O common Maximum value of load current Rated voltage I/O refreshing method ON/OFF response time Model
Transistor Output Unit 2 points NPN/PNP 0.5 A/point, 1 A/Unit 24 VDC Output refreshing with specified time stamp only * 300 ns max./300 ns max. NX-OD2154
NX-OD2258
4 points NPN 0.5 A/point, 2 A/Unit 12 to 24 VDC 0.1 ms max./0.8 ms max. NX-OD3121
PNP 24 VDC 300 ns max./300 ns max. NX-OD3153
NX-OD3256
NX-OD3257
NX-OD3268
Transistor Output Unit (Screwless Clamping Terminal Block, 12 mm Width) 8 points NPN/PNP 0.5 A/point, 4 A/Unit 12 to 24 VDC (NPN)
24 VDC (PNP)
Switching Synchronous I/O refreshing and Free-Run refreshing 0.1 ms max./0.8 ms max. (NPN)
0.5 ms max./1.0 ms max. (PNP)
NX-OD4121
NX-OD4256
Transistor Output Unit (M3 Screw Terminal Block, 30 mm Width) 16 points NPN/PNP 0.5 A/point, 5 A/Unit 12 to 24 VDC (NPN)
24 VDC (PNP)
Switching Synchronous I/O refreshing and Free-Run refreshing 0.1 ms max./0.8 ms max. (NPN)
0.5 ms max./1.0 ms max. (PNP)
NX-OD5121
NX-OD5256
NX-OD5121-1
NX-OD5256-1
Transistor Output Unit (For both NPN/PNP, 16 points) 16 points For both NPN/PNP 12 to 24 VDC (NPN)
24 VDC (PNP)
Switching Synchronous I/O refreshing and Free-Run refreshing 0.1 ms max./0.8 ms max. (NPN)
0.5 ms max./1.0 ms max. (PNP)
NX-OD5121-5
NX-OD5256-5
Transistor Output Unit (MIL Connector, 30 mm Width) 32 points NPN/PNP 0.5 A/point, 2 A/common, 4 A/Unit 12 to 24 VDC (NPN)
24 VDC (PNP)
Switching Synchronous I/O refreshing and Free-Run refreshing 0.1 ms max./0.8 ms max. (NPN)
0.5 ms max./1.0 ms max. (PNP)
NX-OD6121-5
NX-OD6256-5
NX-OD6121-6
Relay Output Unit (Screwless Clamping Terminal Block, 12 mm Width/24 mm Width) 2 points N.O. 250 VAC/2 A (cosφ=1)
250 VAC/2 A (cosφ=0.4)
24 VDC/2 A
Free-Run refreshing 15 ms max./15 ms max. NX-OC2633
8 points N.O. 250 VAC/2 A (cosφ=1)
250 VAC/2 A (cosφ=0.4)
24 VDC/2 A
8 A/Unit Free-Run refreshing 15 ms max./15 ms max. NX-OC2733
NX-OC4633

* To use input refreshing with input changed time, the EtherCAT Coupler Unit with unit version 1.1 or later and the Sysmac Studio version 1.07 or higher are required.

Digital Mixed I/O Units

These units combine digital input and output functions in a single unit, offering space and cost savings.

Product Name Number of points Internal I/O common Maximum value of load current Specification Model
DC Input/Transistor Output Unit (MIL Connector, 30 mm Width) Outputs: 16 points
Inputs: 16 points
Outputs: NPN
Inputs: For both NPN/PNP
Outputs: 12 to 24 VDC
Inputs: 24 VDC
I/O refreshing method: Switching Synchronous I/O refreshing and Free-Run refreshing
ON/OFF response time: Outputs: 0.1 ms max./0.8 ms max.; Inputs: 20 µs max./400 µs max.
NX-MD6121-5
DC Input/Transistor Output Unit (Fujitsu Connector, 30 mm Width) Outputs: 16 points
Inputs: 16 points
Outputs: PNP
Inputs: For both NPN/PNP
Outputs: 24 VDC
Inputs: 24 VDC
I/O refreshing method: Switching Synchronous I/O refreshing and Free-Run refreshing
ON/OFF response time: Outputs: 0.5 ms max./1.0 ms max.; Inputs: 20 µs max./400 µs max.
NX-MD6256-5
DC Input/Transistor Output Unit Outputs: 16 points
Inputs: 16 points
Outputs: NPN
Inputs: For both NPN/PNP
Outputs: 12 to 24 VDC
Inputs: 24 VDC
I/O refreshing method: Switching Synchronous I/O refreshing and Free-Run refreshing
ON/OFF response time: Outputs: 0.1 ms max./0.8 ms max.; Inputs: 20 µs max./400 µs max.
NX-MD6121-6

High-speed Analog Input Units

These units are designed for high-speed analog signal acquisition, offering precise measurement capabilities.

Product name Number of points Input range Resolution Input method Conversion time Trigger input section Number of points I/O refreshing method Model
High-speed Analog Input Unit 4 -10 to 10 V
-5 to 5 V
0 to 10 V
0 to 5 V
1 to 5 V
0 to 20 mA
4 to 20 mA
1/64,000 (full scale) Differential input
Other input range: 1/32,000 (full scale)
Differential input 5 μs per channel 4 NPN/PNP Synchronous I/O refreshing NX-HAD401
NX-HAD402

Analog Input Units

These units convert analog signals from sensors and other devices into digital data for processing by the controller.

Product Name Number of points Input range Resolution Conversion value, decimal number (0 to 100%) Specification Over all accuracy (25°C) Input method Conversion time Input impedance Model I/O refreshing method
Voltage Input Unit 2 points -4000 to 4000 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 1 MΩ min. NX-AD2603 Free-Run refreshing
-15000 to 15000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD2604 Selectable Synchronous I/O refreshing or Free-Run refreshing
4 points -10 to +10 V 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 1 MΩ min. NX-AD3603 Free-Run refreshing
-15000 to 15000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD3604 Selectable Synchronous I/O refreshing or Free-Run refreshing
8 points -4000 to 4000 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 1 MΩ min. NX-AD4603 Free-Run refreshing
-15000 to 15000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD4604 Selectable Synchronous I/O refreshing or Free-Run refreshing
Current Input Unit 2 points 0 to 8000 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 250 Ω NX-AD2203 Free-Run refreshing
0 to 30000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD2204 Selectable Synchronous I/O refreshing or Free-Run refreshing
4 points 0 to 8000 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 250 Ω NX-AD3203 Free-Run refreshing
0 to 30000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD3204 Selectable Synchronous I/O refreshing or Free-Run refreshing
8 points 0 to 8000 1/8000 ±0.2% (full scale) Single-ended input 250 µs/point 85 Ω NX-AD4203 Free-Run refreshing
0 to 30000 1/30000 ±0.1% (full scale) Differential Input 10 µs/point NX-AD4204 Selectable Synchronous I/O refreshing or Free-Run refreshing

Analog Output Units

These units convert digital data from the controller into analog signals for controlling devices such as actuators and valves.

Product Name Number of points Input range Resolution Output setting value, decimal number (0 to 100%) Specification Over all accuracy (25°C) Model Conversion time I/O refreshing method
Voltage Output Unit 2 points -4000 to 4000 1/8000 ±0.3% (full scale) NX-DA2603 250 µs/point Free-Run refreshing
-15000 to 15000 1/30000 ±0.1% (full scale) NX-DA2605 10 µs/point Selectable Synchronous I/O refreshing or Free-Run refreshing
4 points -4000 to 4000 1/8000 ±0.3% (full scale) NX-DA3603 250 µs/point Free-Run refreshing
-15000 to 15000 1/30000 ±0.1% (full scale) NX-DA3605 10 µs/point Selectable Synchronous I/O refreshing or Free-Run refreshing
Current Output Unit 2 points 0 to 8000 1/8000 ±0.3% (full scale) NX-DA2203 250 µs/point Free-Run refreshing
0 to 30000 1/30000 ±0.1% (full scale) NX-DA2205 10 µs/point Selectable Synchronous I/O refreshing or Free-Run refreshing
4 points 0 to 8000 1/8000 ±0.3% (full scale) NX-DA3203 250 µs/point Free-Run refreshing
0 to 30000 1/30000 ±0.1% (full scale) NX-DA3205 10 µs/point Selectable Synchronous I/O refreshing or Free-Run refreshing

Temperature Control Units

These units are designed for precise temperature control in industrial processes.

Product Name Number of channels Input type Output Number of output points Specifications Number of CT input points Control type Conversion time I/O refreshing method Model
Temperature Control Unit 2-channel Type 2 Voltage output (for driving SSR) 2 None Standard control NX-TC2405
Voltage output (for driving SSR) 2 None Standard control NX-TC2406
Linear current output 4 None Heating/cooling control 50 ms NX-TC2407
Temperature Control Unit 4-channel Type 4 Universal input (thermocouple, resistance thermometer) Voltage output (for driving SSR) 4 None Standard control NX-TC2408
Voltage output (for driving SSR) 4 None Standard control NX-TC3405
Voltage output (for driving SSR) 4 None Heating/cooling control NX-TC3406
Linear current output 4 None Standard control 50 ms NX-TC3407
NX-TC3408

Temperature Input Units

These units are used for acquiring temperature data from various types of sensors.

Product Name Number of points Input type Resolution Over all accuracy (25°C) Conversion time I/O refreshing method Terminals Model
Thermocouple Input type 2 points Thermocouple 0.1°C max. 250 ms/Unit 16 Terminals NX-TS2101
4 points 0.01°C max. 10 ms/Unit 16 Terminals X 2 NX-TS3101
2 points Thermocouple 0.001°C max. 60 ms/Unit 16 Terminals NX-TS2102
4 points 10 ms/Unit 16 Terminals x 2 NX-TS3102
2 points 0.001°C max. 60 ms/Unit 16 Terminals NX-TS2104
4 points 10 ms/Unit 16 Terminals x 2 NX-TS3104
Resistance Thermometer Input type 2 points Resistance Thermometer 0.1°C max. 250 ms/Unit 16 Terminals NX-TS2201
4 points 10 ms/Unit 16 Terminals x 2 NX-TS3201
2 points Resistance Thermometer (Pt100/Pt1000, three-wire) *2 0.01°C max. 10 ms/Unit 16 Terminals NX-TS2202
4 points 10 ms/Unit 16 Terminals x 2 NX-TS3202
2 points 0.001°C max. 60 ms/Unit 16 Terminals NX-TS2204
4 points 10 ms/Unit 16 Terminals x 2 NX-TS3204

*1. The resolution is 0.2°C max. when the input type is R, S, or W.

*2. The NX-TS2202 and NX-TS3202 only supports Pt100 three-wire sensor.

Heater Burnout Detection Units

These units detect heater burnout by monitoring the current flowing through the heater.

Product Name CT input section Number of inputs Maximum heater current Number of outputs Internal I/O common Control output section Maximum load current Rated voltage I/O refreshing method Model
Heater Burnout Detection Unit 4 50 AAC 4 NPN/PNP 0.1 A/point, 0.4 A/Unit 12 to 24 VDC (NPN)
24 VDC (PNP)
Free-Run refreshing NX-HB3101
NX-HB3201

Load Cell Input Unit

This unit is used for acquiring load cell signals, which are typically used in weighing applications.

Product Name Number of points Standards Conversion cycle I/O refreshing method * Load cell excitation voltage Input range Model
Load Cell Input Unit 1 125 µs • Free-Run refreshing
• Synchronous I/O refreshing
• Task period prioritized refreshing
5 VDC ± 10% -5.0 to 5.0 mV/V NX-RS1201

* Refer to the NX-series Load Cell Input Unit User's Manual (W565) for detailed information on I/O refresh cycle.

Position Interface: Incremental Encoder Input Units

These units are used for acquiring signals from incremental encoders, which provide position feedback.

Product Name Number of channels External inputs Maximum response frequency I/O refreshing method Number of I/O entry mappings Model
Incremental Encoder Input Unit 1 (NPN)
3 (NPN)
1 (PNP)
3 (PNP)
500 kHz • Free-Run refreshing
• Synchronous I/O refreshing
1/1 NX-EC0112
NX-EC0122
NX-EC0132
NX-EC0142
2 (NPN)
2 (PNP)
4 MHz 2/2 NX-EC0212
NX-EC0222
None 500 kHz

Position Interface: SSI Input Units

These units are used for acquiring signals from SSI (Synchronous Serial Interface) encoders.

Product Name Number of channels Input/Output form Maximum data length Encoder power supply Type of external connections Model
SSI Input Unit 1 EIA standard RS-422-A 32 bits 24 VDC, 0.3 A/CH Screwless push-in terminal block (12 terminals) NX-ECS112
2 EIA standard RS-422-A 32 bits 24 VDC, 0.3 A/CH Screwless push-in terminal block (12 terminals) NX-ECS212

Position Interface: Pulse Output Units

These units provide pulse outputs for controlling stepper motors and servo motors.

Product Name Number of channels *1 External inputs External outputs Maximum pulse output speed I/O refreshing method Number of I/O entry mappings Control output interface Model
Pulse Output Unit 1 (NPN)
1 (PNP)
2 (NPN)
2 (PNP)
1 (NPN)
1 (PNP)
500 kpps Synchronous I/O refreshing
Task period prioritized refreshing *2
1/1 Open collector output NX-PG0112
NX-PG0122
5 inputs/CH (NPN)
5 inputs/CH (PNP)
3 outputs/CH (NPN)
3 outputs/CH (PNP)
4 Mpps 2/2 Line driver output NX-PG0232-5
NX-PG0242-5
5 inputs/CH (NPN)
5 inputs/CH (PNP)
3 outputs/CH (NPN)
3 outputs/CH (PNP)
4/4 NX-PG0332-5
NX-PG0342-5

*1. This is the number of pulse output channels.

*2. Unit version 1.2 or later and an NX-ECC203 EtherCAT Coupler Unit are required.

Communications Interface Units

These units provide various communication interfaces for connecting the controller to other networks and devices.

Product Name Serial interface Number of serial ports External connection terminals Communications protocol Model
Communications Interface Unit RS-232C 1 port Screwless Clamping Terminal Block • No-protocol
• Signal lines
NX-CIF101
RS-422A/485 NX-CIF105
RS-232C 2 ports D-Sub connector NX-CIF210

RFID Units

These units are used for reading and writing RFID tags, enabling identification and tracking of products.

Product name Amplifier/Antenna No. of unit numbers used Model
RFID Unit (1Ch) V680 series 1 NX-V680C1
RFID Unit (2Ch) 2 NX-V680C2

IO-Link Master Unit

This unit serves as a master for IO-Link devices, enabling communication with smart sensors and actuators.

Product Name Number of IO-Link ports Specification I/O refreshing method I/O connection terminals Model
IO-Link Master Unit 4 Free-Run refreshing Screwless clamping terminal block NX-ILM400

System Units

System Units provide essential functions such as power supply and connection management.

Product Name Specification Model
Additional NX Unit Power Supply Unit Power supply voltage: 24 VDC (20.4 to 28.8 VDC)
NX Bus power supply capacity: 10 W max.
NX-PD1000
Additional I/O Power Supply Unit Power supply voltage: 5 to 24 VDC (4.5 to 28.8 VDC)
I/O power feed maximum current: 4 A
NX-PF0630
Power supply voltage: 5 to 24 VDC (4.5 to 28.8 VDC)
I/O power feed maximum current: 10 A *
NX-PF0730
I/O Power Supply Connection Unit Number of I/O power terminals: IOG: 16 terminals
Current capacity of I/O power terminal: 4 A/terminal max.
NX-PC0010
Number of I/O power terminals: IOV: 16 terminals
Current capacity of I/O power terminal: 4 A/terminal max.
NX-PC0020
Number of I/O power terminals: IOV: 8 terminals, IOG: 8 terminals
Current capacity of I/O power terminal: 4 A/terminal max.
NX-PC0030
Shield Connection Unit Number of shield terminals: 14 terminals
(The following two terminals are functional ground terminals.)
NX-TBX01

* Use the NX-PF0730 at 4 A or less on the CPU Rack where the NX1P2 CPU Unit is mounted.

EtherCAT Coupler Units

These units enable the connection of NX-series Units and NX-series Safety Units to the EtherCAT network.

Product Name Communications cycle in DC Mode Current consumption Maximum I/O power supply current Model
EtherCAT Coupler Unit *1 250 to 4000 µs *2 1.45 W max. 4 A NX-ECC201
250 to 4000 µs *2 1.25 W max. 10 A NX-ECC202
125 to 10000 µs *2 NX-ECC203

*1. One End Cover NX-END01 is provided with the EtherCAT Coupler Unit.

*2. This depends on the specifications of the EtherCAT master. For example, the values are as follows when the EtherCAT Coupler Unit is connected to the built-in EtherCAT port on an NJ5-series CPU Unit: 500 µs, 1,000 µs, 2,000 µs, and 4,000 µs. Refer to the NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (Cat. No. W505) for the specifications of the built-in EtherCAT ports on NJ/NX-series CPU Units. This also depends on the unit configuration.

Safety CPU Units

These units provide safety functions for machine control, ensuring compliance with safety standards.

Appearance Maximum number of safety I/O points Program capacity Specification Number of safety master connections I/O refreshing method Unit version Model
256 points 512 KB 32 Free-Run refreshing Ver.1.1 NX-SL3300
1024 points 2048 KB 128 Free-Run refreshing Ver.1.1 NX-SL3500

Note: Connect the Safety CPU Unit to the NX1P2 CPU Unit via the EtherCAT Coupler Unit.

Safety Input Units

These units are used for safety-related input signals, such as emergency stop buttons and safety gate switches.

Appearance Number of safety input points Number of test output points Internal I/O common Rated input voltage OMRON special safety input devices Number of safety slave connections I/O refreshing method Unit version Model
4 points 2 points Sinking inputs (PNP) 24 VDC Can be connected. 1 Free-Run refreshing Ver.1.1 NX-SIH400
8 points 2 points Sinking inputs (PNP) 24 VDC Cannot be connected. 1 Free-Run refreshing Ver.1.0 NX-SID800

Note: Connect the Safety Input Unit to the NX1P2 CPU Unit via the EtherCAT Coupler Unit.

Safety Output Units

These units provide safety-related output signals for controlling safety devices such as safety relays and safety contactors.

Appearance Number of safety output points Internal I/O common Maximum load current Rated voltage Number of safety slave connections I/O refreshing method Unit version Model
2 points Sourcing outputs (PNP) 2.0 A/point, 4.0 A/Unit at 40°C, and 2.5A/Unit at 55°C 24 VDC 1 Free-Run refreshing Ver.1.0 NX-SOH200
4 points Sourcing outputs (PNP) 0.5 A/point and 2.0 A/Unit 24 VDC 1 Free-Run refreshing Ver.1.0 NX-SOD400

Note: Connect the Safety Output Unit to the NX1P2 CPU Unit via the EtherCAT Coupler Unit.

NX Unit Power Supply System

Additional NX Unit Power Supply Units may be required when I/O power is supplied from the NX bus to NX Units connected to the CPU Unit.

NX Units Model NX-PF Additional I/O Power Supply Unit required NX Units Model NX-PF Additional I/O Power Supply Unit required
NX-ID3317 Yes NX-AD3208 No
NX-ID3343 Yes NX-AD4203 Yes
NX-ID3344 Yes NX-AD4204 No
NX-ID3417 Yes NX-AD4208 No
NX-ID3443 Yes NX-DA2603 Yes
NX-ID3444 Yes NX-DA2605 Yes
NX-ID4342 Yes NX-DA3603 Yes
NX-ID4442 Yes NX-DA3605 Yes
NX-ID5342 Yes NX-DA2203 Yes
NX-ID5442 Yes NX-DA2205 Yes
NX-ID5142-1 No NX-DA3203 Yes
NX-ID5142-5 No NX-DA3205 Yes
NX-ID6142-5 No NX-TC2405 Yes
NX-ID6142-6 No NX-TC2406 Yes
NX-IA3117 No NX-TC2407 Yes
NX-OD2154 Yes NX-TC2408 Yes
NX-OD2258 Yes NX-TC3405 Yes
NX-OD3121 Yes NX-TC3406 Yes
NX-OD3153 Yes NX-TC3407 Yes
NX-OD3256 Yes NX-TC3408 Yes
NX-OD3257 Yes NX-TS2101 No
NX-OD3268 No NX-TS3101 No
NX-OD4121 Yes NX-TS2102 No
NX-OD4256 Yes NX-TS3102 No
NX-OD5121 Yes NX-TS2104 No
NX-OD5256 Yes NX-TS3104 No
NX-OD5121-1 No NX-TS2201 No
NX-OD5256-1 No NX-TS3201 No
NX-OD5121-5 No NX-TS2202 No
NX-OD5256-5 No NX-TS3202 No
NX-OD6121-5 No NX-TS2204 No
NX-OD6256-5 No NX-TS3204 No
NX-OD6121-6 No NX-HB3101 Yes
NX-OC2633 No NX-HB3201 Yes
NX-OC2733 No NX-RS1201 No
NX-OC4633 No NX-EC0112 Yes
NX-MD6121-5 No NX-EC0122 Yes
NX-MD6256-5 No NX-EC0132 Yes
NX-MD6121-6 No NX-EC0142 Yes
NX-HAD401 Yes NX-EC0212 Yes
NX-HAD402 Yes NX-EC0222 Yes
NX-AD2603 Yes NX-ECS112 Yes
NX-AD2604 No NX-ECS212 Yes
NX-AD2608 No NX-PG0112 Yes
NX-AD3603 Yes NX-PG0122 Yes
NX-AD3604 No NX-PG0232-5 No
NX-AD3608 No NX-PG0242-5 No
NX-AD4603 Yes NX-PG0332-5 No
NX-AD4604 No NX-PG0342-5 No
NX-AD4608 No NX-CIF101 No
NX-AD2203 Yes NX-CIF105 No
NX-AD2204 No NX-CIF210 No
NX-AD2208 No NX-V680C1 Yes
NX-AD3203 Yes NX-V680C2 Yes
NX-AD3204 No NX-ILM400 Yes

Note: Refer to the NX-series NX1P2 CPU Unit Hardware User's Manual (Cat. No. W578) for the NX Unit power supply system.

Automation Software Sysmac Studio

Sysmac Studio is a support software package that provides an integrated development environment for designing, programming, debugging, and maintaining Sysmac NJ/NX-series Controllers.

Configuration

With an NX1P2 CPU Unit, you can connect the Sysmac Studio online in the following ways:

Version Information

Refer to NX-series NX1P2 CPU Unit Hardware User's Manual (W578) for unit versions and corresponding Sysmac Studio versions.

Dimensions

The following diagrams show the dimensions of the NX-series NX1P2 CPU Units and the End Cover.

NX-series NX1P2 CPU Units

NX1P2-140 / NX1P2-9024

Diagrams showing the front, side, and top views of the NX1P2-140 and NX1P2-9024 CPU Units, including dimensions.

End cover NX-END02

Diagram showing the dimensions of the NX-END02 End Cover.

Related Manuals

This section lists related manuals that provide further information on the NX1P2 CPU Unit and its associated products.

Manual name Cat. No. Model numbers Application Description
NX-series NX1P2 CPU Unit Hardware User's Manual W578 NX1P2- Learning the basic specifications of the NX-series NX1P2 CPU Units, including introductory information, designing, installation, and maintenance. An introduction to the entire NX1P2 CPU Unit system is provided along with the following information on the NX1P2 CPU Unit: Features and system configuration, Introduction, Part names and functions, General specifications, Installation and wiring, Maintenance and inspection.
NX-series NX1P2 CPU Unit Built-in I/O and Option Board User's Manual W579 NX1P2- Learning about the details of functions only for an NX-series NX1P2 CPU Unit and an introduction of functions for an NJ/NX-series CPU Unit. Of the functions for an NX1P2 CPU Unit, the following information is provided: Built-in I/O, Serial Communication Option Boards, Analog I/O Option Boards. An introduction of the following functions for an NJ/NX-series CPU Unit is also provided: Motion control functions, EtherNet/IP communications functions, EtherCAT communications functions.
NJ/NX-series CPU Unit Software User's Manual W501 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Learning how to program and set up an NJ/NX-series CPU Unit. Mainly software information is provided. The following information is provided on a Controller built with an NJ/NX-series CPU Unit: CPU Unit operation, CPU Unit features, Initial settings, Programming based on IEC 61131-3 language specifications.
NJ/NX-series Instructions Reference Manual W502 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Learning detailed specifications on the basic instructions of an NJ/NX-series CPU Unit. The instructions in the instruction set (IEC 61131-3 specifications) are described.
CPU Unit Motion Control User's Manual W507 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Learning about motion control settings and programming concepts. The settings and operation of the CPU Unit and programming concepts for motion control are described.
Motion Control Instructions Reference Manual W508 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Learning about the specifications of the motion control instructions. The motion control instructions are described.
NJ/NX-series CPU Unit Built-in EtherCAT® Port User's Manual W505 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Using the built-in EtherCAT port on an NJ/NX-series CPU Unit. Information on the built-in EtherCAT port is provided. This manual provides an introduction and provides information on the configuration, features, and setup.
NJ/NX-series CPU Unit Built-in EtherNet/IP™ port User's Manual W506 NX1P2-, NJ101-, NJ102-, NJ301-, NJ501-, NX701- Using the built-in EtherNet/IP port on an NJ/NX-series CPU Unit. Information on the built-in EtherNet/IP port is provided. Information is provided on the basic setup, tag data links, and other features.
NJ/NX-series Troubleshooting Manual W503 NX1P2-, NJ101-, NJ102- Learning about the errors that may be detected in an NJ/NX-series Controller. Describes concepts on managing errors that may be detected in an NJ/NX-series Controller and information on individual errors.
Sysmac Studio Version 1 Operation Manual W504 SYSMAC-SE2 Learning about the operating procedures and functions of the Sysmac Studio. Describes the operating procedures of the Sysmac Studio.
NX-series EtherCAT® Coupler Unit User's Manual W519 NX-ECC20 Learning how to use an NX-series EtherCAT Coupler Unit and EtherCAT Slave Terminals The following items are described: the overall system and configuration methods of an EtherCAT Slave Terminal (which consists of an NX-series EtherCAT Coupler Unit and NX Units), and information on hardware, setup, and functions to set up, control, and monitor NX Units through EtherCAT.
NX-series Data Reference Manual W525 NX- Referencing lists of the data that is required to configure systems with NX-series Units Lists of the power consumptions, weights, and other NX Unit data that is required to configure systems with NX-series Units are provided.

Terms and Conditions Agreement

Buyers are advised to read and understand the catalog before purchasing products. Consult an OMRON representative for any questions or comments. OMRON provides a limited warranty against defects in materials and workmanship for twelve months from the date of sale. OMRON disclaims all other warranties, express or implied, including warranties of non-infringement, merchantability, or fitness for a particular purpose. Buyer acknowledges that they alone have determined that the Products will suitably meet their intended use. Omron is not liable for claims or expenses based on infringement of intellectual property rights. Buyer's remedy is limited to replacement, repair, or repayment/credit of the purchase price, provided the Products were properly handled, stored, installed, and maintained. Omron is not liable for suitability or unsuitability or results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies, or other materials or substances or environments. Advice, recommendations, or information given orally or in writing do not amend or add to the warranty. See http://www.omron.com/global/ or contact your Omron representative for published information.

Limitation on Liability: OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use: Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Programmable Products: Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof.

Performance Data: Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability.

Change in Specifications: Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product.

Errors and Omissions: Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.

PDF preview unavailable. Download the PDF instead.

nx1p p116-e1 9 4 csm1055399 ?id=3650

Related Documents

Preview OMRON NJ301-1100 CPU Unit: Advanced Automation
Explore the OMRON NJ301-1100, a powerful CPU unit for advanced industrial automation. Discover its specifications, features, and compatible accessories for seamless integration into your control systems.
Preview OMRON NX-series System Units: NX-PD/PF/PC/TBX Datasheet
Datasheet for OMRON NX-series System Units, including Power Supply Units, Power Connection Units, and FG Terminal Expansion Units. Details system configuration, power supply wiring, specifications, and ordering information for models like NX-PD1000, NX-PF0630, NX-PF0730, NX-PC0010, NX-PC0020, NX-PC0030, and NX-TBX01.
Preview Omron Sysmac Library: Advanced Control and Programming Solutions
Explore the Omron Sysmac Library, a collection of software functional components designed to simplify programming for NJ/NX Machine Automation Controllers and Industrial PC Platforms. Discover features for advanced control, motion control, productivity improvement, and reduced setup times.
Preview OMRON NX/GX-series IO-Link System User's Manual
This OMRON user's manual provides comprehensive guidance for implementing IO-Link Systems using NX-series and GX-series IO-Link Master Units. It details system configuration, wiring, parameter settings, I/O data management, communication protocols (EtherCAT, EtherNet/IP), unit functions, startup procedures, and troubleshooting for industrial automation (FA) applications.
Preview OMRON NX-series Digital I/O Units User's Manual
User's Manual for OMRON's NX-series Digital I/O Units, providing detailed information on features, specifications, installation, operation, and troubleshooting for machine automation controllers.
Preview OMRON SYSMAC CJ Series CJ2H-CPU-EIP Software User's Manual
Comprehensive user's manual for the OMRON SYSMAC CJ Series CJ2H-CPU-EIP, detailing software installation, configuration, programming, operation, and troubleshooting for industrial automation.
Preview OMRON NX Series Safety Network Controller: Flexible Production Line Safety
Explore OMRON's NX Series Safety Network Controller for scalable, flexible, and efficient production line safety. Features EtherNet/IP, CIP Safety, EtherCAT, and Sysmac Studio for simplified design and maintenance.
Preview OMRON NX-series Communications Interface Units User's Manual
Comprehensive user's manual for OMRON NX-series Communications Interface Units (NX-CIF101, NX-CIF105, NX-CIF210), detailing specifications, installation, wiring, operation, and troubleshooting for machine automation systems.