Copeland Compressor Electronics Module User Manual

Introduction

Thank you for purchasing the Copeland compressor electronics module and related kits. This next-generation module offers advanced diagnostics, intelligent protection, and communication features to enhance compressor performance and reliability. It assists contractors and service providers in troubleshooting commercial refrigeration systems by providing valuable information to diagnose issues quickly and accurately, significantly reducing costly downtimes.

Connecting to the Mobile App

Access critical compressor information conveniently via the mobile app. Real-time data and compressor conditions are downloaded to your smartphone, helping service technicians identify potential problems before they occur and prevent system downtimes. Historical data aids in analyzing and resolving issues in the field.

The module stores running data every 20 seconds, retaining approximately 72 hours of effective running time. Data is not recorded during compressor downtime. Old data is overwritten by new data upon restart. It is recommended to select specific time periods for downloading historical data to manage download times.

Step 1: Search for "Copeland Electronics Module" in your device's app store (iOS App Store or Android Google Play) and install it.

Step 2: Enable Bluetooth on your device, search for the Copeland electronics module, and pair with "Emerson xxxxxxxx" (where xxxxxxxx is the serial number on the module sticker).

Product Features and Technical Specifications

The control module monitors the refrigeration scroll compressor's operation using various sensors. If an unsafe condition is detected, it shuts down the compressor by de-energizing the contactor coil and displays an alarm code.

The module is available in two versions: Plus 5 and Plus 4, designed for different compressor platforms.

Module Product Specifications

Module Part Number571-0106-00571-0107-00
Type CodePlus 5Plus 4
T1/T2 Power Supply & Frequency115-240 Vac, 50-60Hz115-240 Vac, 50-60Hz
Allowable Voltage Range97-264 Vac97-264 Vac
T1/T2 Low Voltage Trip90/170 Vac90/170 Vac
T1/T2 Low Voltage Reset95/185 Vac95/185 Vac
Power Consumption25 VA25 VA
M1/M2 Contact Rating2.5A, 240Vac2.5A, 240Vac
Alarm Contact Rating2.5A, 240Vac2.5A, 240Vac
Solenoid Valve Contact Rating0.4A, 240Vac0.4A, 240Vac
Motor Temperature Overheat Trip Resistance> 4.5KΩ ± 25%NA
Open Motor Thermistor Trip Resistance>220KΩNA
Shorted Motor Thermistor Trip Resistance<40ΩNA
Motor Temperature Reset Resistance< 2.75KΩNA
Reset Time After Motor Trip30 minutesNA
Ambient temperature range-30° to 70°C-30° to 70°C
ApprovalsUL, CEUL, CE
Protection ClassIP20IP20

Terminal Designations

TerminalDescription571-0106-00 Plus 5571-0107-00 Plus 4
T1/T2Module power supply, 115-240 VAC, 50-60Hz
L1/L2/L3Phase inputs corresponding to compressor input power L1-L2-L3
M1/M2Normally open control circuit contacts; M2-M1 should be wired in series with the compressor contactor coil
A/BCompressor start/stop demand signal, from low pressure switch or thermostat
ValveSolenoid valve terminal (For oil return in Rack application)
DPTConnect to motor and scroll discharge port temperature sensors
DLTConnect to discharge line temperature sensor
VIT/VOTVapor in sensor and vapor out sensor terminal (EVI compressor is required)
OLSOil level sensor terminal (Optional, required in single unit or rack application)
EXVEXV terminal
AlarmAlarm terminal, output to buzzer
TTLFor PC interface and RS485 communication (Requires a separated transition board)
RecallRecall button to display diagnosis data via LED

Key Functions

Key Functions571-0106-00 Plus 5571-0107-00 Plus 4
Motor protection
Motor temperature overheat protection
Locked rotor protection
Motor missing phase protection
Reverse phase protection
Advanced protection
Discharge temperature overheat protection
Compressor running short cycling protection
Module low voltage protection
Injection control via EXV
Liquid injection control
Vapor injection control
Oil level management (To be released)
Oil level protection via oil level sensor
Oil return via solenoid valve
Diagnosis & data management
LED matrix display running status and alarm history
Read the running information
Download history data (total 72 hours effective running time data storage)
Communication
Alarm terminal output to buzzer
Bluetooth connection to mobile phone
PC interface or RS485 communication via TTL terminal (To be released)

Dip-Switch Setting

The dip-switch settings configure compressor discharge temperature control targets, oil level control enablement, and injection control modes (liquid or vapor injection superheat target).

Plus 5 Module: 571-0106-00

LocationBit 1Bit 2Bit 3Bit 4
OFFDischarge port temperature control target at 120°C (OFF)Disable oil level control (OFF)Disable injection (ON-OFF)Vapor Injection 5K Superheat (OFF-OFF)
ONDischarge line temperature control target at 110°C (ON)Enable oil level control (ON)Liquid Injection (ON-ON)Vapor Injection 10K Superheat (OFF-ON)

Plus 4 Module: 571-0107-00

LocationBit 1Bit 2Bit 3Bit 4
OFFDischarge line temperature control target at 110°C (OFF)Disable oil level control (OFF)Disable Injection (ON-OFF)Vapor Injection 5K Superheat (OFF-OFF)
ONDischarge line temperature control target at 95°C (ON)Enable oil level control (ON)Liquid Injection (ON-ON)Vapor Injection 10K Superheat (OFF-ON)

Typical Application Examples

Compressor modelsBit 1Bit 2Bit 3Bit 4Typical applications
Plus 5 Module: 571-0106-00
ZFI96, ZFI122, ZFI140Discharge port temperature control target at 120°CDisable oil level controlOFFOFFVapor Injection 5K SuperheatDPT + Vapor Injection 5K (Default factory setting)
Discharge port temperature control target at 120°CDisable oil level controlOFFONVapor Injection 10K SuperheatDPT + Vapor Injection 10K (for glide-refrigerants)
Discharge port temperature control target at 120°CEnable oil level controlONOFFVapor Injection 5K SuperheatDPT + Vapor Injection 5K + Oil Level Control
Discharge port temperature control target at 120°CDisable oil level controlONONDisable InjectionDPT + Disable Injection (Default factory setting)
ZB150, ZB190, ZB220Discharge port temperature control target at 120°CDisable oil level controlOFFOFFVapor Injection 5K SuperheatDPT + Disable Injection (for customers who do not use Copeland EVI control kits)
Discharge port temperature control target at 120°CDisable oil level controlOFFONVapor Injection 10K SuperheatDPT + Disable Injection + Oil Level Control
Discharge port temperature control target at 120°CEnable oil level controlONOFFVapor Injection 5K SuperheatDPT + Liquid Injection (enable liquid injection to suction line)
Discharge port temperature control target at 120°CDisable oil level controlONONDisable InjectionDPT + Liquid Injection (Default factory setting)
Plus 4 Module: 571-0107-00
ZFI09-ZFI81Discharge line temperature control target at 110°CDisable oil level controlOFFOFFVapor Injection 5K SuperheatDLT + Vapor Injection 5K (Default factory setting)
Discharge line temperature control target at 110°CDisable oil level controlOFFONVapor Injection 10K SuperheatDLT + Vapor Injection 10K (for glide-refrigerants)
Discharge line temperature control target at 110°CEnable oil level controlONOFFVapor Injection 5K SuperheatDLT + Vapor Injection 5K + Oil Level Control
Discharge line temperature control target at 110°CDisable oil level controlONONDisable InjectionDLT + Disable Injection (for customers who do not use Copeland EVI control kits)
ZSI06-ZSI21Discharge line temperature control target at 110°CDisable oil level controlOFFOFFLiquid injectionDLT 110°C + Liquid Injection (Default factory setting)
Discharge line temperature control target at 95°CEnable oil level controlONOFFLiquid injectionDLT 95°C + Liquid Injection
Non-functionalDisable oil level controlOFFONDisable InjectionDisable Injection + Oil Level Control
ZB58-ZB114Non-functionalEnable oil level controlONONDisable InjectionNon-functional

Alarm Code Definition and Troubleshooting Reference

This section details alarm codes, their descriptions, fault conditions, and troubleshooting steps for both Plus 5 and Plus 4 modules.

Alarm LED CodeFault TypeDescriptionPlus 5Plus 4Fault ConditionTrouble shooting reference
0ONNormal operationNANANANA
0FlashNormal compressor power offNANANANA
1Flash TripDischarge temperature overheating> control target +15°C; 10 minutes reset time after trip1/ Check refrigerant charge, system leaks. 2/ Check superheat, expansion valve, suction tube insulation. 3/ Check pressures, low/high pressure switches. 4/ Inspect liquid/vapor injection system, EXV for damage/blockage. 5/ Check compressor current, potential wear due to oil loss.
2Flash TripDischarge temperature sensor short circuit< 500Ω; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
3Flash WarningDischarge temperature sensor open circuit> 1000KΩ; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
4Flash WarningVapor in temperature sensor short circuit< 500Ω; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
5Flash WarningVapor in temperature sensor open circuit> 500KΩ; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
6Flash WarningVapor out temperature sensor short circuit< 500Ω; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
7Flash WarningVapor out temperature sensor open circuit> 500KΩ; 10 minutes reset time after trip1/ Check sensor connection to module. 2/ Check sensor wiring continuity, replace sensor.
8Flash TripModule input voltage is low< 170/95V; 5 minutes reset time after trip1/ Check supply voltage. 2/ Replace module.
9Flash LockoutModule internal faultModule malfunction1/ Reset power supply. 2/ Replace module.
AFlash WarningModule internal Bluetooth component fault5 times consecutive communication error1/ Reset power supply. 2/ Replace module.
CFlash LockoutModule version faultInternal configuration fault1/ Replace module.
EFlash TripMotor temperature sensor overheating> 4.5KΩ; 30 minutes reset time after trip1/ Check supply voltage. 2/ Check refrigerant charge and superheat. 3/ Check compressor operating envelope. 4/ Check contactor.
FFlash LockoutMotor temperature sensor overheating lockout5 times consecutive trip1/ Check supply voltage. 2/ Check refrigerant charge and superheat. 3/ Check contactor.
GFlash TripMotor temperature sensor short circuit< 40Ω; 30 minutes reset time after trip1/ Check sensor connection to module.
HFlash LockoutMotor temperature sensor open circuit> 220KΩ; 30 minutes reset time after trip1/ Check sensor connection to module.
JFlash TripPhase missing5 minutes reset time after trip1/ Check incoming power supply. 2/ Check fuses/breakers. 3/ Check contactor.
KFlash LockoutPhase missing lockout5 minutes reset time after trip1/ Check incoming power supply. 2/ Check fuses/breakers. 3/ Check contactor.
LFlash LockoutPhase reverse lockoutPhase Reverse1/ Check incoming phase sequence. 2/ Check contactor. 3/ Change module phasing wires L1-L2-L3.
MFlash WarningCompressor forced runningModule detected trip error but compressor still running1/ Check contactor contacts. 2/ Check M1-M2 output shorting. 3/ Check if control wiring bypasses M1-M2.
NFlash WarningCompressor short cycling warning (Default)Compressor running <1 min for 1 cycle, >48 cycles in 24 hrs1/ Check refrigerant charge and pressure control setting. 2/ Check thermostat setting.
PFlash LockoutCompressor short cycling lockout (Manual configuration)Compressor running <1 min for 1 cycle, >48 cycles in 24 hrs1/ Check refrigerant charge and pressure control setting. 2/ Check thermostat setting.

Liquid Injection and Vapor Injection Control Kits

Copeland offers liquid injection and vapor injection control kits with 1.8m or 4.5m wire lengths.

Liquid Injection Control Kits

Part number with 1.8m wire length(1)Part number with 4.5m wire lengthApplicable ZSI modelsEXV valve orifice size (Identification code)
562-0471-00NAZSI06-ZSI21Ø1.3mm (TS113C03)
(1) 562-0471-00 is included in ZSI compressor bill of materials (BOM536/539)

Vapor Injection Control Kits

Part number with 1.8m wire lengthPart number with 4.5m wire lengthApplicable ZFI modelsEXV valve orifice size (Identification code)
562-0471-01562-0471-02ZFI09-ZFI26Ø1.3mm (TS113C03)
562-0471-03562-0471-04ZFI36-ZFI39Ø1.65mm (TS116C03)
562-0471-05562-0471-06ZFI50-ZFI59Ø1.65mm (TS116C03)
562-0471-07562-0471-08ZFI68-ZFI81Ø1.8mm (TS118C03)
562-0460-00562-0460-01ZFI96-ZFI140Ø2.4mm (TS124C03)

Injection Control Kits BOM Breakdown

Injection Control KitsPart number with 1.8m wire lengthApplicable Compressor ModelsPart number with 4.5m wire length
ZSI06-ZSI21ZFI09-ZFI26ZFI36-ZFI39ZFI50-ZFI59ZFI68-ZFI81ZFI96-ZFI140
1 Control module562-0471-00562-0471-01562-0471-03562-0471-05562-0471-07562-0460-00
571-0107-00571-0107-00571-0107-00571-0107-00571-0107-00with Comp
2 Module bracket074-1855-00074-1855-00074-1855-00NANANA
3 Blots group521-0355-00521-0355-00521-0355-00NANANA
4 DLT/DPT sensor543-0317-00543-0317-00543-0317-00543-0317-00543-0317-00with Comp
5 Vapor in/out sensorNA043-0285-00043-0285-00043-0285-00043-0285-00043-0285-00
6 EXV filter013-0212-00013-0212-00013-0212-00013-0212-00013-0212-00013-0212-00
7 EXV-coil023-0111-00023-0111-00023-0111-00023-0111-00023-0111-00023-0111-00
8 EXV-valve010-0240-00010-0240-00010-0240-01010-0240-01010-0240-02010-0240-03
9 Gland Cable - single holeNANANA036-1868-00036-1868-00036-1868-00
10 Gland Cable - 7 holesNANANA036-1869-00036-1869-00036-1869-00
11 Tube for sensor028-3998-00028-3998-00028-3998-00028-3998-00028-3998-00028-3998-00
12 Spring clip032-0962-00032-0962-00032-0962-00032-0962-00032-0962-00032-0962-00
13 Pin connector group521-0398-00521-0398-00521-0398-00521-0398-00521-0398-00521-0398-00

Module Installation and Field Retrofit

Module Installation

ZFI20-39, ZSI06-21: The module is installed in a separate bracket box and fixed into the condensing unit system.

Module Bracket: Two holding tabs secure the module in the compressor terminal box or the module bracket box. To remove, depress the holding tabs and lift the module.

ZFI50-81: For ZFI50-81 Summit scroll compressors, this module can be installed in the compressor terminal box.

ZB150-220, ZFI96-140: For these large scroll compressors, the module is shipped already installed in the compressor terminal box.

Field Retrofit Steps

The new generation Copeland compressor electronics modules are intended for field retrofits of older ZSI liquid injection, ZFI vapor injection, large ZFI scroll P47 CoreSense, and vapor injection control modules.

ZS106-ZS121

ZFI20-ZFI81

ZFI96-ZFI140

Wiring Diagrams

The following diagrams illustrate recommended wiring configurations for various compressor models and module types.

Plus 4 Single Phase Wiring Diagram (ZSI06-ZSI14 Compressor)

This diagram shows the connections for a single-phase compressor using the Plus 4 module, including power supply, control signals, sensors (DLT, VIT/VOT), and output for alarms and EXV.

Plus 4 Three Phase Wiring Diagram (ZSI06-ZSI21, ZFI09-ZFI81 Compressor)

This diagram details the wiring for three-phase compressors with the Plus 4 module, covering power inputs (L1, L2, L3), control circuits, sensors, and communication interfaces.

Plus 5 Wiring Diagram (ZFI96-ZFI140 Compressor)

This diagram illustrates the wiring for three-phase compressors with the Plus 5 module, featuring connections for power, motor phases, sensors (DPT, VIT/VOT), control signals, and communication ports.

Note: Always refer to the specific wiring diagram applicable to your compressor model and module version. Ensure all connections are made according to the diagram for safe and proper operation.

Contact Information

For inquiries or support, please refer to the contact details provided on the cover page of the original document. Key contact regions include Asia Pacific, Australia, China (Beijing, Guangzhou, Shanghai), India (Mumbai, Pune), Egypt, Japan, Middle East & Africa, Philippines, South Africa, Saudi Arabia, South Korea, Thailand, and United Arab Emirates.

Visit Copeland.com for more information.

PDF preview unavailable. Download the PDF instead.

user-manual-copeland-compressor-electronics-module-en-sg-8049968 Adobe PDF library 17.00

Related Documents

Preview ZF Refrigeration Scroll Compressors: Low Temperature Applications with R407A, R407F, R448A, R449A
Technical information on Emerson Copeland ZF Refrigeration Scroll Compressors for low temperature applications using refrigerants R407A, R407F, R448A, and R449A. Covers liquid injection, vapor injection (EVI), and wet vapor injection, including component details, installation, and operating envelopes.
Preview Copeland™ Compressor Electronics for Stream Compressors: Replacement Guide for CoreSense™ Diagnostics
A technical guide from Emerson's Application Engineering Europe on replacing CoreSense™ Diagnostics with Copeland™ Compressor Electronics for Stream Compressors. Covers differences, parts removal, installation steps, connections, and wiring diagrams.
Preview Copeland Scroll ZSI Compressor for Refrigeration Applications
Comprehensive catalog detailing Copeland Scroll ZSI compressors for refrigeration applications, featuring CoreSense technology, liquid injection, performance tables, technical data, and application guidelines.
Preview Emerson Copeland Scroll™ ZFKQ Compressors: Technical Specifications for Refrigeration
Discover the Emerson Copeland Scroll™ ZFKQ series compressors, engineered for high efficiency and reliability in low-temperature refrigeration applications. Featuring advanced technology for frozen food and critical cooling, with detailed technical specifications, performance data, and operating envelopes.
Preview Copeland Scroll Compressor Field Guide
A comprehensive reference guide for Emerson's Copeland Scroll compressors, detailing mobile app features, refrigerants, oils, product families, nomenclature, and manufacturing information for HVACR professionals.
Preview Copeland Scroll Compressors ZP*K6 Series: Application Engineering Bulletin AE4-1400 R2
Technical bulletin detailing the application, features, safety, and service procedures for Emerson's Copeland Scroll ZP*K6 R-410A compressors, covering installation, operation, and troubleshooting for HVAC/R systems.