Instruction Manual for DOLD models including: IK 8810-00 Staircase Lighting Time Switch, IK 8810-00, Staircase Lighting Time Switch, Lighting Time Switch, Time Switch

Staircase Lighting Time Switch IK 8810/003; MINITIMER

Staircase Lighting Time Switch IK 8810/003, MINITIMER

DOLD | Solutions for you

%product-title% – Conrad Electronic Schweiz

%product-title% – Conrad Electronic Suisse


File Info : application/pdf, 2 Pages, 160.39KB

PDF preview unavailable. Download the PDF instead.

fiche-technique-2980053-dold-0057584-ik881041003-minuterie-declairage-descalier-230-vac-1-pcs-plage-temporelle-05-40-min-1
0254933

Installation Technique
MINITIMER Staircase Lighting Time Switch IK 8810/003

Translation of the original instructions

Your Advantages · Energysaving · Increaseoftheservicelifeofthelamps
Features · AccordingtoEN60669-1,EN60669-2-1 · Settingrangeshortpressingofbutton0.5...10minlongpressingof
button2...40min · For4-wirecircuitLonpushbuttonand3-wirecircuitNonpushbutton · Canberetriggered · Withpre-warningshortlybeforeendoftime · Switchforcontinuouslightonunit · Contact:16A · Width17.5mm

Product Description
TheStaircaselightingtimeswitchIK8810/003oftheMINITIMERseries hasanadjustablerunningtimeandcanbeswitchedtocontinuouslightning bymeansofaslideswitch.

Approvals and Markings

Function Diagram
UN L/N

t<1s

t>1s

Warning

L/18

approx. 30s

tv

tv

M12835 Warning

Application
Timedelayedswitchingoffforlights
Function
Ifthebuttonispressedlongerthen1stheadjustedtimewillbemultipied by 4, the timing is retriggerable i.e. if the pushbutton is pressed again during timing the adjusted delay time starts again without interruption. Approx.30sbeforeendoftimingthelightflashesshortlytoindicatethat thelightwillgooff.

approx. 30s

Indication

4 x tv

LED:

Onwhenoutputrelayactivated

Circuit Diagram

Notes
Unitandpushbuttonhavetobeconnectedtothesamephase(seeconnectiondiagram)Theoutputcontactisnotvoltfree.

N L
T
18
NT L 18
M8756
Connection Terminals Terminal designation L N T 18

Signal description Phasevoltage Neutral Controlinputforbuttons Outputcontact

All technical data in this list relate to the state at the moment of edition.We reserve the right

fortechnicalimprovementsandchangesatanytime.

1

13.07.23 en / 761A

Technical Data
Time Circuit
Time range:  Repeat accuracy:

Input

Nominal voltage Voltage range:

UN:

Nominal consumption apparentpower:

effectivepower:

Nominal frequency:

Permitted residual current

caused by glow lamps

in the push buttons

Output
Contacts: Contact opening gap: Thermal current Ith: Switching capacity at lamp load Glowlampload: Short circuit strength max. fuse rating: Mechanical life:

Atpush<1s:0.5...10min atpush>1s:2...40min <1%ofsettingvalue

Standard Type

IK8810.41/003AC230V50/60Hz0.5...10min/2...40min

Articlenumber:

0057584

· Output:

1NOcontact,delay

· NominalvoltageUN: · Timerrange:

AC230V 0.5...10min/2...40min

· Width:

17.5mm

AC230V 0.8...1.1UN 4VA 1W 50/60Hz
max.10glowlampsà1mA
1NOcontact,delay <3mm 16A

Ordering Example IK8810 .41/003AC230V 50/60Hz0.5...10min/2...40min











































Timerange



Nominalfrequency



Nominalvoltage



Contacts



Type

Contact current

Characteristic
I (A) 16 10

1200WatTein/Taus=1s/1s

16AgG/gL

IEC/EN60947-5-1

>106switchingcycles

General Data

Nominal operating mode: Impulseoperation

Temperature range Operation:

-20...+60°C

Storage:

-20...+70°C

Altitude:

2000m

Clearance and creepage

distances Ratedimpulsevoltage/

pollutiondegree:

4kV/2

IEC60664-1

EMC Electrostaticdischarge(ESD): 8kV(air) HF-irradiation:

IEC/EN61000-4-2

80MHz...2.7GHz:

10V/m

IEC/EN61000-4-3

Fasttransients:

2kV

IEC/EN61000-4-4

Surgevoltages

between wiresforpowersupply:

2kV

IEC/EN61000-4-5

betweenwireandground: HFwireguided:

4kV 10V

IEC/EN61000-4-5 IEC/EN61000-4-6

Interferencesuppression:

LimitvalueclassB

EN55011

Degree of protection Housing:

IP40

IEC/EN60529

Terminals:

IP20

IEC/EN60529

Housing: 

ThermoplastwithV0-behaviour accordingtoULsubj.94

Vibration resistance  Climate resistance: Terminal designation:
Wire connection: Crosssection: 

Amplitude0.35mm

frequenzy10...55Hz IEC/EN60068-2-6

20/045/04

IEC/EN60068-1

EN50005

DIN46228-1/-2/-3/-4

2x2.5mm2solidor

2x1.5mm2strandedwirewithsleeve

Insulationofwiresor

sleevelength:

10mm

Wire fixing: 
Fixing torque: Mounting:
Weight:

Flatterminalswithself-lifting

clampingpiece

IEC/EN60999-1

Max.0.8Nm

DINrail

IEC/EN60715

75g

Dimensions Width x Height x Depth:

17.5x90x58mm

-20

0

20

40

Application Examples

IK8810

N

T

L 18
L N

3-wirecircuitNonpushbutton

IK8810

N

T

L 18
L N

T (° C) 60
M9644
M8760_a
M8761_a

4-wirecircuitLonpushbutton

E.Dold&SöhneGmbH&Co.KG·D-78120Furtwangen · Bregstraße 18 · Phone +49 7723 654-0 · Fax +49 7723 654356

dold-relays@dold.com·www.dold.com

2

13.07.23 en / 761A



References