Hisense Hi-Mit II Adapter

Model: HCCS-H64H2C1M

EN INSTALLATION & USER MANUAL

1. Safety Precautions

Please read this chapter thoroughly before installation. The following signal words indicate important information on safety, please observe.

⚠️ WARNING: Hazards or unsafe practices that may result in severe injuries or damages.

⚠️ CAUTION: Hazards or unsafe practices that may result in minor injuries or damages.

WARNING

CAUTION

2. Product Description

2.1 Main features

The Hi-Mit II adapter (referred to as adapter) is used in conjunction with an APP and offers the following main features:

  1. One adapter connects to a maximum of 64 indoor units, 64 outdoor units, and 64 electric meters.
  2. One APP account can create a maximum of 8 groups, with each group connecting up to 4 adapters.
  3. The adapter supports both wired and wireless routers; only one connection type should be selected.
  4. Enables remote control of air conditioners for ON/OFF, Temperature, Mode, Fan, and Louver settings.
  5. Enables remote control of water modules for ON/OFF and Temperature/Mode settings.
  6. Monitors the operational status of air conditioners and water modules, sending alarms for exceptions.
  7. Collects power consumption data of the refrigeration system.
  8. Supports two types of power supply systems; only one type should be selected based on on-site conditions.

System diagram:

The system diagram illustrates connections between Air Conditioning (A/C) units, adapters, electric meters, and routers, supporting both wireless (via WiFi and smartphone) and wired connections. Communication cables include 485 commu. cable, H-NET commu. cable, and Internet cable.

NOTE:

2.2 Description of parts

The adapter features several indicators and connection points:

Reset Button: Located on the unit.

Interfaces and Connections:

InterfaceConnection
6. Power adapter interfaceConnect to power adapter (included in accessories)
7. Internet accessConnect to LAN port of router
8. 485 commu. terminalConnect to 485 commu. port of electric meter
9. H-NET commu. terminalConnect to commu. bus of outdoor/indoor unit
10. Backup power supply terminalConnect to power source of DC12V/1A

CAUTION: Third-party power sources are allowable only when the AC plug fails to comply with local regulations. Ports 6 and 10 should not be used simultaneously as the DC power input in case of power failure.

2.3 General data

ItemParameter
Outer dimension (WxHxD)91x117x31 mm
Net weight0.14kg
Installation locationIndoor
Altitude<5km (refer to manual for low altitude AC adapter)
Quantity of connected indoor unitsmaximum 64
Ambient temperature0°C ~ 40°C
Ambient humidity30%RH ~ 60%RH
Power2.4W
Input power of power adapter100-240V~50/60Hz

3. Installation

3.1 Components list

Upon unpacking, verify that all items are complete and intact:

NOTE: The device includes four AC plugs compatible with British, European, American, and Australian standards, along with two bolts and two expansion plugs.

3.2 On-site preparations

Ensure the following items are ready before installation:

ItemSpecificationRequirements
DC12V power linepreferred: 0.75mm² above, shielded twisted pairNot necessary, applicable only when using DC12V backup power interface.
H-NET commu. cablepreferred: 0.75mm² above, shielded twisted pairNecessary for communication with A/C; commu. distance < 1000m.
485 commu. cablepreferred: 0.75mm² above, shielded twisted pairNot necessary for communication with electric meter; commu. distance < 600m.
Wireless routerpreferred: TP-Link, NetgearNecessary; ensure internet access. For wireless connection, straight line distance < 15m, supports 2.4GHz.
Internet cable100Base-TXNot necessary, applicable only when connecting to internet via cable; commu. distance < 50m.

3.3 On-site confirmation

Select a suitable installation location with customer consent:

3.4 Installation procedure

  1. Drill holes in the selected wall according to the figure (diameter: 6mm, pitch of holes: 44mm).
  2. Insert expansion plugs into the holes and then insert bolts, ensuring 3-5mm protrudes from the expansion plug.
  3. Unscrew the fixing bolts from the adapter's base, remove the bottom cover, and proceed with wiring as per the diagram.

3.5 Electrical wiring

1) Remove the case:

a. Remove rubber plugs and screws.

b. Detach the case by pulling in the direction of the arrow.

2) Connect electric wires according to the diagram:

The diagram shows the adapter (HCCS-H64H2C1M) with connections to the Address DIP switch, Electric meter, Outdoor unit, Indoor unit, Router, and Power adapter. The wiring includes 485 commu. cable, H-NET commu. cable, and Internet cable.

Wiring Requirements:

4. Configuration

4.1 DIP switch setting

When multiple adapters (up to 3) are connected to one H-NET communication cable, DSW1 must be set. The diagram indicates DIP switch positions (ON/OFF) for addresses 0xA0 through 0xA7.

Note: indicates the location of the DIP switch; indicates no attention is needed.

4.2 Electric meter setting

When connecting to a Schneider electric meter, the slave address of the electric meter must be set. Communication parameters default to the electric meter's default settings: Baud rate: 19200, parity: even. Slave address = corresponding refrigerant system number + 1. The setting diagram illustrates this relationship.

4.3 APP download

Search for and install the "Hi-Mit II" App from the Google Play Store or iOS App Store. Recommended smartphone OS: Android 6.0 or iOS 10.0 or later. A QR code is provided for downloading the user manual.

5. Troubleshooting

FailureCause
Power status LED OFFCheck if the power line is connected and power supply is switched on.
WLAN status LED OFFCheck if the router network is normal and if the network cable is disconnected.
System status LED ONAdapter has not yet finished searching.
A/C off-line or out of controlCheck if the H-NET communication distance is within the specified range and if the WiFi signal is normal.
Electric meter off-lineCheck if the 485 communication is within the specified range or disconnected, and if the address setting is proper.

Declarations and Compliance

Declaration of Conformity (EN)

Hereby, Hisense Hitachi declares that the radio equipment Hi-Mit II Adapter complies with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at: http://www.hisense-vrf.com

Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd. No. 218, Qianwangang Road, Economic and Technological Development Zone, Qingdao, China

Konformitätserklärung (DE)

Hiermit erklärt Hisense Hitachi, dass das Funkgerät Hi-Mit II Adapter der Richtlinie 2014/53/EU entspricht. Der vollständige Text der EU-Konformitätserklärung ist unter der folgenden Internetadresse verfügbar: http://www.hisense-vrf.com

Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd. No. 218, Qianwangang Road, Economic and Technological Development Zone, Qingdao, China

Thai Regulatory Notice

กสทช. ผู้ใดมีไว้ในครอบครอง หรือ ใช้ซึ่งเครื่องวิทยุคมนาคม หรือตั้งสถานีวิทยุคมนาคมนี้ ต้องได้รับใบอนุญาตจากเจ้าพนักงานผู้ออกใบอนุญาต หากฝ่าฝืน มาตรา 6 หรือมาตรา 11 มีความผิดตามมาตรา 23 แห่งพระราชบัญญัติวิทยุคมนาคม พ.ศ. 2498 ต้องระวางโทษปรับไม่เกินหนึ่งแสนบาท หรือจำคุกไม่เกินห้าปี หรือทั้งปรับทั้งจำ กสทช. โทรคมนาคม กำกับดูแลเพื่อประชาชน Call Center 1200 (ฟรี)

Correct Disposal of this product

[Recycling Symbol] This marking indicates that this product should not be disposed of with other household wastes. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmentally safe recycling.

FCC Compliance

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Caution: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

To satisfy RF exposure requirements, a separation distance of 20 cm or more should be maintained between the antenna of this device and persons during device operation. To ensure compliance, operations at closer than this distance are not recommended.

ISED Regulatory Compliance (Canada)

This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada's licence-exempt RSS(s). Operation is subject to the following two conditions: (1) This device may not cause interference. (2) This device must accept any interference, including interference that may cause undesired operation of the device.

L'émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d'Innovation, Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : 1) L'appareil ne doit pas produire de brouillage; 2) L'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.

This equipment complies with IC RSS-102 radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body.

Cet équipement est conforme aux limites d'exposition aux radiations IC CNR-102 établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé avec une distance minimale de 20cm entre le radiateur et votre corps.

Company Information

Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd.

Add: No. 218, Qianwangang Road, Economic and Technological Development Zone, Qingdao, China

Website: http://www.hisense-vrf.com

E-mail: export@hisensehitachi.com

The Company is committed to continuous product improvement. We reserve the right, therefore, to alter the product information at any time and without prior announcement.

Document Reference: M00708Q Feb. 2021 V00