Bosch DDC Field Installation Guide for Water-to-Air Units

Model Numbers: FHP 560, FHP 583

Document Revision: 8 733 904 851 (2013/05)

Introduction

This manual provides information for installing the FHP 560 and FHP 583 Control Boards, also known as the DDC, on commercial, water-to-air units in the field.

Safety Precautions:

Unpacking and Inspection

Unpack the DDC kit and inspect the contents per Table 1. If any part of the kit appears damaged or missing, or if additional components are required (per Table 2), do not attempt to install the kit. Contact your local distributor for assistance.

Table 1: Kit Contents List

ItemDescriptionQty
ADDC Controller Assembly (includes: Preprogrammed Controller and Wire Harness)1
BController Mounting Screws2
CController Cover2
DCover Screws3
EThermistor, 10K 88" lead3
FSnap Bushing1
GFHP 560/583 User Guide1
HBACView Instruction Manual1
IField Installation Guide1
JCork Tape - White Backing1

Table 1 (Continued): Kit Contents List

ItemDescriptionQty
KInsulation Tape1
LCable Clamp1
MTie-Wraps7

Table 2: Optional Accessories List

ItemDescriptionPart#
NRS-PRO Wall Sensor8733800500
ORS-PLUS Wall Sensor8733800503
PRS-BASE Wall Sensor8733800504
QRS-Humidity Wall Sensor8733800505
R12" Duct Mounted Temperature Probe641-258
SThermistor, 10K 40" lead641-147
TCombo Temperature/Humidity Duct Probe641-257
UBACview Kit641-K31
VBACview Programming Cable641-261
WLON Card641-237
XDDC Input Expansion Module641-264
YUPM I Replacement Kit8733903903
ZUPM II Replacement Kit8733903904

Required Tools and Materials

Unit Preparation

Follow all Electrical Safety and Lockout Procedures in accordance with local, state, and federal regulations.

  1. Remove power from the unit. [!] Adhere to all Electrical Safety and Lockout Procedures.
  2. Locate the front side of the Water-to-Air Heat Pump.
  3. Remove the front-side panel to expose the electrical box.
  4. Locate the Unit Protection Module (UPM) in the electrical box.
  5. Verify part numbers as shown in Figure 1 & 2: Single Compressor UPM-I: 8 733 800 259 or Dual Compressor UPM-II: 8 733 800 260.
  6. If UPM board(s) part numbers do not match the listed numbers, new UPM Board Kits (Table 2) will need to be ordered.

Figure 1 & 2 Description: These figures show the Unit Protection Module (UPM) boards, identifying the UPM Part Number, Freeze Sensor Contacts, and Alarm Contacts.

Mounting the Controller

The controller is mounted externally to the right-side panel of the Heat Pump. Locations are shown on a typical EC360 per Figure 3.

  1. Locate the controller on the right side panel and align the harness with the top access knockout as shown in Figure 4.
  2. Mark and drill holes for mounting the controller as indicated in Figure 3.
  3. If necessary, assemble the harness onto the controller per the wiring diagram in Figure 6.
  4. Use the supplied mounting screws to attach the controller to the right side of the unit.
  5. Route the terminated ends of the harness through the top access knockout port (Figure 4) and into the adjacent electrical box.

Figure 3 Description: This diagram shows a water-to-air unit, indicating the electrical box, front-side panel, right-side panel, and the location for mounting the DDC controller using screws, including the top access knockout.

Figure 4 Description: This diagram illustrates the routing of the wire harness from the DDC controller through the top access knockout into the electrical box on the right-side panel of the unit. It notes that the diagram shows the corner post unfolded for clarity.

Terminal Block Connections

Refer to the wiring diagram in Figure 6 for detailed instructions on wiring the various components. Table 5 provides a general guide for connecting labeled wires:

Table 5: Wiring Chart

LabelQtyWire ColorDescriptionDestination
C1BlueCommonE-Box, Terminal Block
O1BlackReversing ValveE-Box, Terminal Block
Y/Y11BrownStage 1 CoolingE-Box, Terminal Block
Y2/E1Purple (short)(Y2) Stage 2/Economizer, (E) Electric HeatE-Box, Terminal Block
R1Yellow24 VACE-Box, Terminal Block
G1OrangeBlowerE-Box, Terminal Block
H/W1Red (short)(H) Hot Gas Reheat, (W) Electric HeatE-Box, Terminal Block
DATS2Purple (long)Discharge Air Temperature SensorBlower Housing (Air Handler Section)
LWTS2WhiteLeaving Water Temperature SensorHeat Exchanger Leaving Water Pipe
ALR-OUT1WhiteUPM Alarm OutE-Box, UPM Board
ALR-COM1Red (long)UPM Alarm CommonE-Box, UPM Board

Wiring Instructions:

  1. Inside the electrical box, connect power and signal wires to the corresponding terminal block locations per Figure 6, based on unit options.
  2. For DATS and LWTS connections, install the provided thermistors at their respective locations per the chart/table in Figure 5.
  3. Route thermistor wires into the electrical box and connect the terminated ends (female) of the thermistor wires to the terminated ends (male) of the corresponding DATS or LWTS leads from the DDC wire harness.

Wiring the Controller

Refer to Figure 6 for controller connection details.

Figure 6 Description: This is a detailed diagram of the DDC controller board, showing terminal blocks for UPM connections (OUT, COM), sensors (DATS, LWTS), and general wiring (C, O, Y1, Y2, R, G, H/W). It also illustrates connections for BACnet, power, and optional cards like the LON Card and Expansion Card. Specific wiring color codes are noted for options like HGRH, electric heater, and economizer.

Installing the Freeze Sensor

If the unit is already equipped with the freeze sensor option, verify sensor location per Figure 7 and skip these steps.

  1. Route the provided freeze sensor to the refrigeration line of the water coil (Figure 7).
  2. Use the two supplied tie-wraps to mount the sensor (Figure 8).
  3. Use the provided cork tape to wrap the sensor (Figure 9).
  4. Apply the provided pipe insulating tape to ensure good thermal connection to the sensor (Figure 4).
  5. Connect the sensor wires to the UPM board at the locations specified in Figure 1 & 2:
    • For UPM-I units, connect the sensor on the water coil to Freeze 1.
    • For UPM-II units, connect the sensor on the water coil of the first compressor to Freeze 1, and the sensor on the water coil of the second compressor to Freeze 2.

Note: There is no polarity for these wires.

Figure 7 Description: Shows a water coil with the freeze sensor being routed to the refrigeration line, indicating an "old location" and a "relocated freeze sensor" position.

Figure 8 Description: Illustrates the freeze sensor being secured to the pipe using tie-wraps.

Figure 9 Description: Shows the freeze sensor wrapped with cork tape for insulation.

UPM to DDC Alarm Connection

1. Locate the Alarm (ALR) Contacts on the corresponding UPM-I or UPM-II board per Figure 1 & 2.

2. Connect the cables labeled OUT and COM from the DDC wiring harness to the spade connectors labeled OUT and COM on the UPM board.

DDC Wiring Diagrams

Figure 10: DDC Wiring Diagram for FHP 560

This diagram details the wiring for the FHP 560 controller. It includes termination details for remote and RH sensors, CO2 and RH sensors, LWTS, DATS, alarm output, and blower motor/fan status switches. It shows connections to the DDC controller, UPM board, and BACnet MS/TP network. Standard and optional components are listed, with notes on specific terminal usage and field-terminated components.

Figure 11: DDC Wiring Diagram for FHP 583

This diagram details the wiring for the FHP 583 controller. It is similar to the FHP 560 diagram but specific to the FHP 583 model. It includes termination details for sensors, UPM, alarm output, and blower motor/fan status switches, showing connections to the controller, UPM board, and BACnet network. Standard and optional components are listed, with notes on terminal usage and field-terminated components.

Unit Configuration

Figure 12: Unit Configuration - Zone Basic

This schematic diagram illustrates the "Zone Basic" configuration of a water-to-air unit. It shows the airflow path from return air through a filter, heat pump, and to supply air via a supply fan. The diagram highlights the integration of the unit-mounted DDC controller, a reversing valve, and sensors such as the Discharge Air Temperature Sensor (DATS) and Leaving Water Temperature (LWT) sensor. It also indicates control signals for fan enable/disable and compressor enable/disable. Various sensor types (RS-PRO, RS-PLUS, RS-BASE) are shown for zone temperature sensing.

Figure 13: Unit Configuration - Discharge Air Control

This schematic diagram illustrates the "Discharge Air Control" configuration of a water-to-air unit. It is similar to the Zone Basic configuration, showing the airflow path and component integration. The primary focus is on controlling the discharge air temperature, with the DATS sensor playing a key role. It depicts the reversing valve, heat pump, supply fan, and DDC controller, along with control signals for fan and compressor.

Notes

This section is reserved for additional notes and information.

PDF preview unavailable. Download the PDF instead.

im field ddc 201305 8733904851 en us us us FrameMaker 10.0.2 Acrobat Distiller 10.1.5 (Windows)

Related Documents

Preview Bosch AppLoader 6.5 Installation Manual
Step-by-step guide for installing and using Bosch AppLoader 6.5 software to download enabling software for Bosch WSHP DDC Controllers.
Preview Bosch Cool 2000 Portable Air Conditioner User Manual
Comprehensive user manual for the Bosch Cool 2000 portable air conditioner, covering safety, installation, operation, cleaning, maintenance, and troubleshooting. Includes product specifications and environmental information.
Preview Control Air 5830 Hardware User Manual
This manual provides detailed information on the Bosch Control Air 5830, a multi-protocol heat pump controller. It covers specifications, features, components, DDC options, and troubleshooting for efficient HVAC system management.
Preview Bosch Connected Control BCC100 Wi-Fi Thermostat: Installation Guide & User Manual
Comprehensive installation guide and user manual for the Bosch Connected Control BCC100 Wi-Fi Thermostat. Learn how to install, set up, and use your smart thermostat for energy savings and enhanced home comfort.
Preview Bosch IDS Heat Pump Ultra Series Condensing Unit Installation Instructions
Comprehensive installation guide for the Bosch IDS Heat Pump Ultra Series Condensing Unit (Model BOVA60-19), detailing safety procedures, unit setup, refrigerant handling, electrical connections, and troubleshooting for HVAC professionals.
Preview UPM I Unit Protection Module Installation and Operation Manual
Installation and operation manual for the Bosch UPM I Unit Protection Module, detailing its specifications, features, protection mechanisms, DIP switch settings, and operational sequence for HVAC systems.
Preview Bosch Multi-Position Cased Coils Installation Manual
This installation manual provides comprehensive guidance for the Bosch Multi-Position Cased Coils (BMAC Series). It covers essential safety instructions, general product information, detailed installation procedures, drain application guidelines, refrigerant connection specifications, and TXV replacement procedures. The document includes dimensional data, airflow performance charts, and spare parts information.
Preview Bosch SM, CE, BP Series Electric Heat Kit Installation Manual | HK050, HK100, HK150, HK200
Comprehensive installation manual for Bosch SM, CE, and BP Series electric heat kits (HK050, HK100, HK150, HK200). Covers unpacking, component identification, installation procedures, wiring, start-up, and electrical data.