Thermostat Control Units: Fan operation must be proven via contact closure across terminals 7TB2-3 and 7TB2-4. Once fan is proven and the unit is ...

6 days ago — SAFETY WARNING. Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of.

il y a 7 jours — SAFETY WARNING. Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of.


File Info : application/pdf, 32 Pages, 1.28MB

PDF preview unavailable. Download the PDF instead.

SS-SVX007B-EN 08022023
Installation, Operation, and Maintenance
DDC Controller Options Remote Split System Units and Remote Chillers
Air-Cooled Condensing Units

BAYDDCU600
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2023

SS-SVX007B-EN

Introduction

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

©2023 Trane

SS-SVX007B-EN

Introduction
WARNING Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below: · Before installing/servicing this unit, technicians MUST put on all PPE required for the work
being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE. · When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions. · If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury. · All Trane personnel must follow the company's Environmental, Health and Safety (EHS)
policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies. · Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

SS-SVX007B-EN

3

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Receipt of Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Field Supplied and Installed Items (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Field Supplied and Installed Items (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Unit Control (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Unit Control (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Occupancy Switch Notes (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Outdoor Air Temperature Sensor Notes (AHU and Chiller) . . . . . . . . . . . . . . . . 6 Occupied Sequence of Operation (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Supply Fan Control Notes (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 General Control Notes (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 General Control Notes (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Backplate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Diagnostics Rewiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 20 to 30T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 20 to 30T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 40 to 60T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 40 to 60T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 80 to 120T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 80 to 120T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Startup Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 AHU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Object Data Points List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 20 to 30T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 40 to 60T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 80 to 120T (AHU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 20 to 30T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 40 to 60T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 80 to 120T (Chiller) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

4

SS-SVX007B-EN

Overview
Receipt of Kit
Inspect the unit for damage. Check internal components for damage. If inspection reveals damage or material shortages, file a claim with the shipper immediately. Specify the type and extent of the shipping damage on the Bill of Lading before signing. It is the responsibility of the purchasing contractor to file the freight claim; failure to do so makes the purchaser financially responsible for shipping damage. Do not install a damaged unit without approval from the appropriate Trane sales representative.
Field Supplied and Installed Items (AHU)
· Zone Sensor with Setpoint (CV or VAV control units only) · Discharge Air Temperature Sensor (VAV control units only) · Conventional Thermostat (field supplied, thermostat controlled units Only) · Outdoor Air Temperature Sensor (factory-wired, field-installed) · Occupancy Contacts (CV or VAV control units) · Evaporator Fan Interlock
Field Supplied and Installed Items (Chiller)
· Chiller Enable Contacts · Chiller Leaving Water Temperature Sensor · Circulating Pump Control Circuit · Flow Switch · Circulating Pump Interlock · Freezestat
Unit Control (AHU)
· This unit will control based on field application and set by jumper position. Default is Thermostat Control.
· This unit is designed to operate at ambient temperatures above 40°F. When the outside air (OA) temperature is below 40°F as read by the outdoor air temperature sensor on UI11, all compressors will be commanded off.
· All default values and setpoints are adjustable using the Tracer TU service tool.
Unit Control (Chiller)
· If the outdoor air temperature is within the ambient temperature window (40° and 125°F adjustable), the chiller will be allowed to operate.
· Upon a chiller-enable signal, the unit controller will stage compressors to maintain the leaving water temperature at setpoint (45°F adjustable).
· Chiller may be remotely disabled regardless of local enable by setting Chiller Disable BAS (Binary Value 1) to Disabled.
· If leaving-water temperature is at or below 36°F (adjustable if the correct percent solution of glycol is in the system), the UC controller will go into freeze protection lockout.

SS-SVX007B-EN

5

Overview
Occupancy Switch Notes (AHU)
· An occupancy switch must be field wired to 7TB2-12 and 7TB2-13 for proper operation. · When the occupancy switch is closed the unit will be occupied. When the occupancy switch is open
the unit will be unoccupied. · Occupancy may be communicated to the unit via Multi-state Value 2, but the unit control must be set
to BAS. See points list for additional details.
Outdoor Air Temperature Sensor Notes (AHU and Chiller)
· The outdoor air (OA) sensor is factory wired to the UC controller and is supplied with enough wire to reach the mounting point.
· Use the bracket that is included in the unit to mount the OA sensor to the air entering side of the condenser coils.
Occupied Sequence of Operation (AHU)
1. Thermostat Control Units: Fan operation must be proven via contact closure across terminals 7TB2-3 and 7TB2-4. Once fan is proven and the unit is in occupied mode, a field-supplied thermostat or sequencer will call on compressors with contact closures across universal inputs UI1 to UI6. Normally, open contacts for compressor staging will be wired to terminals 7TB2-5 to 7TB2-11 for cool calls 1 to 6, respectively.
2. Constant Air Volume (CV) Control Units: Fan operation must be proven via contact closure across terminals 7TB2-3 and 7TB2-4. A fieldinstalled space temperature sensor with setpoint (BAYSENS075A) must be wired to 7TB2-16 to 7TB218 according to the wiring diagram. Once fan is proven and the unit is in occupied mode, the compressors will be controlled by the Tracer UC600 to maintain space temperature at setpoint.
3. Variable Air Volume (VAV) Control Units: Fan operation must be proven via contact closure across terminals 7TB2-3 and 7TB2-4. A fieldinstalled discharge air temperature sensor (10K, Type II thermistor) must be wired to 7TB2-14 and 7TB2-15 according to the wiring diagram. Once fan is proven and the unit is in occupied mode, the compressors will be controlled by the Tracer UC600 to maintain discharge air temperature at setpoint. Default value is 55°F.
Supply Fan Control Notes (AHU)
The supply fan is controlled by others. Fan status must be hardwired to the Tracer UC600 across terminals 7TB2-3 and 7TB2-4 for proper operation.

6

SS-SVX007B-EN

Overview
General Control Notes (AHU)
· Unit controls shall maintain minimum on and off timers to protect compressors from short cycling. · Factory safeties (for example, High/Low pressure, temperature) are re-wired to allow for monitoring
and diagnostic capability with the Tracer UC600. The only factory components that are replaced by the DDC controller are compressor on/off timers. · In unoccupied cooling mode, this unit will stage compressors to maintain temperature at unoccupied cooling setpoint. · The Tracer UC600 will monitor safety status and lock out compressors if a safety trips three consecutive times in one hour. This hard lockout must be reset by cycling power to the unit. A soft lockout will occur if a high-pressure or low-pressure safety trips and will shut the circuit's compressors off for at least three minutes. The safety resets itself. · Tracer UC600 will maintain a 3-minute inter-stage timer when ramping stages of cooling up and down. · Cool Calc P-Gain may need to be adjusted on startup to optimize cooling operation.
General Control Notes (Chiller)
· Unit controls shall maintain minimum on and off timers to protect compressors from short cycling. · Factory safeties (for example, High/Low pressure, temperature) are rewired to allow for monitoring
and diagnostic capability with the Tracer UC600. The only factory components replaced by the DDC controller are compressor on/off timers. · Pump Interlock, Flow Switch, and Freezestat must be field-wired in series with Chiller Enable to allow chiller operation. Circulating Pump Control is optional.
· The Tracer UC600 will monitor safety status and lock out compressors if a safety trips three consecutive times in one hour. This hard lockout must be reset by cycling power to the unit. A soft lockout will occur is a high-pressure or low-pressure safety trips and will shut the circuit's compressors off for at least three minutes. The safety resets itself.
· Tracer UC600 will maintain a three-minute inter-stage timer when ramping stages of cooling up and down.
· Cool Calc P-Gain may need to be adjusted on startup to optimize chiller operation.

SS-SVX007B-EN

7

Backplate Installation
WARNING Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Important: Turn off main unit disconnect and lockout / tag out power supply.
1. For 20 to 60 ton units, unplug connector 7P1 and 7P2. For 80 to 120 ton units unplug connectors 7P1, 7P2, and 7P3.

2. Cut wire ties to free wires connected to components on the control panel. 3. Remove the screws that fasten the back plate to the main control panel. Discard back plate.

8

SS-SVX007B-EN

Backplate Installation
4. Install the new back plate to the main electrical panel with provided sheet metal screws. On 80 to 120 ton units, install timers 7U5 and 7U6 in top left corner of back plate. Connect wires 58C to 7U5-1, 100B to 7U5-2, 36AW to 7U5-3, 71C to 7U6-1, 101B to 7U6-2, and 36AV to 7U6-3. Reference CST Supplied wiring diagram (lines 81 to 88).
Note: Plug in new connector(s) 7P1, 7P2 (and 7P3 where applicable) into existing receptacle.

SS-SVX007B-EN

9

Diagnostics Rewiring Instructions
20 to 30T (AHU)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, then splice with wires 1552G and 1559A respectively. Reference line 80 on BAYDDCU601A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 92 on BAYDDCU601A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 57E from 1TB3-1 and splice with 1557A. Reference line 92 on BAYDDCU601A.60.00.
b. Connect wire 1552H to 1TB3-1. Reference line 83 on BAYDDCU601A.60.00. c. Remove wire 61P from 1TB3-2 and rewire to 1TB3-7. Reference line 83 on BAYDDCU601A.60.00. d. Remove wire 98A from 1TB2-2 and splice with wire 1598A. Reference line 83 on
BAYDDCU601A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 94 on BAYDDCU601A.60.00. 3. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 92 to
94 on BAYDDCU601A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 109 to
112 on BAYDDCU601A.60.00
20 to 30T (Chiller)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, then splice with wires 1552G and 1559A respectively. Reference line 80 on BAYDDCU602A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 92 on BAYDDCU602A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 57E from 1TB3-1 and splice with 1557A. Reference line 92 on BAYDDCU602A.60.00.
b. Connect wire 1552H to 1TB3-1. Reference line 83 on BAYDDCU602A.60.00. c. Remove wire 61P from 1TB3-2 and rewire to 1TB3-7. Reference line 83 on BAYDDCU602A.60.00. d. Remove wire 98A from 1TB2-2 and splice with wire 1598A. Reference line 83 on
BAYDDCU602A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 94 on BAYDDCU602A.60.00. 3. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 92 to
94 on BAYDDCU602A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 109 to
112 on BAYDDCU602A.60.00

10

SS-SVX007B-EN

Diagnostics Rewiring Instructions
40 to 60T (AHU)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, then splice with wires 1552G and 1559A respectively. Reference line 80 on BAYDDCU603A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 92 on BAYDDCU603A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 57E from 1TB3-1 and splice with 1557A. Reference line 92 on BAYDDCU603A.60.00.
b. Connect wire 1552H to 1TB3-1. Reference line 83 on BAYDDCU603A.60.00. c. Remove wire 61P from 1TB3-2 and rewire to 1TB3-7. Reference line 83 on BAYDDCU603A.60.00. d. Remove wire 98A from 1TB2-2 and splice with wire 1598A. Reference line 83 on
BAYDDCU603A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 94 on BAYDDCU603A.60.00. 3. Circuit 2 High Pressure Cutout: a. Remove wires 71A and 72A from 1TB4-3 and 1TB4-6, then splice with wires 1552J and 1572A
respectively. Reference line 85 on BAYDDCU603A.60.00. b. Connect wire 1572B to 1TB4-6. Reference line 112 on BAYDDCU603A.60.00 4. Circuit 2 Low Pressure Cutout: a. Remove wire 70E from 1TB4-2 and splice with 1570A. Reference line 112 on
BAYDDCU603A.60.00. b. Connect wire 1552K to 1TB4-2. Reference line 86 on BAYDDCU603A.60.00. c. Remove wires 74R 1TB4-5 and rewire to 1TB4-3. Reference line 86 on BAYDDCU603A.60.00. d. Remove wire 99A from 1TB4-8 and splice with wire 1599A. Reference line 86 on
BAYDDCU603A.60.00. e. Run wire 1574R from 1TB4-5 to 1TB4-8. Reference line 109 on BAYDDCU603A.60.00. 5. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 92 to
94 on BAYDDCU603A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 109 to
112 on BAYDDCU603A.60.00

SS-SVX007B-EN

11

Diagnostics Rewiring Instructions
40 to 60T (Chiller)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, and splice with wires 1552G and 1559A, respectively. Reference line 80 on BAYDDCU604A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 92 on BAYDDCU604A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 57E from 1TB3-1 and splice with 1557A. Reference line 92 on BAYDDCU604A.60.00.
b. Connect wire 1552H to 1TB3-1. Reference line 83 on BAYDDCU604A.60.00. c. Remove wire 61P from 1TB3-2 and re-wire to 1TB3-7. Reference line 83 on
BAYDDCU604A.60.00. d. Remove wire 98A from 1TB2-2 and splice with wire 1598A. Reference line 83 on
BAYDDCU604A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 94 on BAYDDCU604A.60.00. 3. Circuit 2 High Pressure Cutout: a. Remove wires 71A and 72A from 1TB4-3 and 1TB4-6, and splice with wires 1552J and 1572A,
respectively. Reference line 85 on BAYDDCU604A.60.00. b. Connect wire 1572B to 1TB4-6. Reference line 112 on BAYDDCU604A.60.00 4. Circuit 2 Low Pressure Cutout: a. Remove wire 70E from 1TB4-2 and splice with 1570A. Reference line 112 on
BAYDDCU604A.60.00. b. Connect wire 1552K to 1TB4-2. Reference line 86 on BAYDDCU604A.60.00. c. Remove wires 74R 1TB4-5 and re-wire to 1TB4-3. Reference line 86 on BAYDDCU604A.60.00. d. Remove wire 99A from 1TB4-8 and splice with wire 1599A. Reference line 86 on
BAYDDCU604A.60.00. e. Run wire 1574R from 1TB4-5 to 1TB4-8. Reference line 109 on BAYDDCU604A.60.00. 5. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 92 to
94 on BAYDDCU604A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 109 to
112 on BAYDDCU604A.60.00

12

SS-SVX007B-EN

Diagnostics Rewiring Instructions
80 to 120T (AHU)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, and splice with wires 1552J and 1559A, respectively. Reference line 80 on BAYDDCU605A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 93 on BAYDDCU605A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 100F from 1TB3-1 and splice with 15100A. Reference line 93 on BAYDDCU605A.60.00.
b. Connect wire 1552K to 1TB3-1. Reference line 93 on BAYDDCU605A.60.00. c. Remove wire 61P from 1TB3-2 and re-wire to 1TB3-7. Reference line 83 on
BAYDDCU605A.60.00. d. Remove wire 98J from 1TB2-2 and splice with wire 1598J. Reference line 83 on
BAYDDCU605A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 100 on BAYDDCU605A.60.00. 3. Circuit 2 High Pressure Cutout: a. Remove wires 71A and 72A from 1TB4-3 and 1TB4-6, and splice with wires 1552L and 1572A,
respectively. Reference line 85 on BAYDDCU605A.60.00. b. Connect wire 1572B to 1TB4-6. Reference line 118 on BAYDDCU605A.60.00 4. Circuit 2 Low Pressure Cutout: a. Remove wire 101F from 1TB4-2 and splice with 15101A. Reference line 118 on
BAYDDCU605A.60.00. b. Connect wire 1552M to 1TB4-2. Reference line 86 on BAYDDCU605A.60.00. c. Remove wires 74R 1TB4-5 and re-wire to 1TB4-3. Reference line 86 on BAYDDCU605A.60.00. d. Remove wire 99J from 1TB4-8 and splice with wire 1599J. Reference line 86 on
BAYDDCU605A.60.00. e. Run wire 1574R from 1TB4-5 to 1TB4-8. Reference lines 110-111 on BAYDDCU605A.60.00. 5. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 96 to
98 on BAYDDCU605A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 1110
to 114 on BAYDDCU605A.60.00

SS-SVX007B-EN

13

Diagnostics Rewiring Instructions
80 to 120T (Chiller)
Reference CST Supplied Wiring Diagram for details regarding this section. 1. Circuit 1 High Pressure Cutout:
a. Remove wires 58A and 59A from 1TB3-7 and 1TB2-4, and splice with wires 1552J and 1559A, respectively. Reference line 80 on BAYDDCU606A.60.00.
b. Connect wire 1559B to 1TB2-4. Reference line 93 on BAYDDCU606A.60.00. 2. Circuit 1 Low Pressure Cutout:
a. Remove wire 100F from 1TB3-1 and splice with 15100A. Reference line 93 on BAYDDCU606A.60.00.
b. Connect wire 1552K to 1TB3-1. Reference line 93 on BAYDDCU606A.60.00. c. Remove wire 61P from 1TB3-2 and re-wire to 1TB3-7. Reference line 83 on
BAYDDCU606A.60.00. d. Remove wire 98J from 1TB2-2 and splice with wire 1598J. Reference line 83 on
BAYDDCU606A.60.00. e. Run wire 1561P from 1TB3-2 to 1TB2-2. Reference line 100 on BAYDDCU606A.60.00. 3. Circuit 2 High Pressure Cutout: a. Remove wires 71A and 72A from 1TB4-3 and 1TB4-6, and splice with wires 1552L and 1572A,
respectively. Reference line 85 on BAYDDCU606A.60.00. b. Connect wire 1572B to 1TB4-6. Reference line 118 on BAYDDCU606A.60.00 4. Circuit 2 Low Pressure Cutout: a. Remove wire 101F from 1TB4-2 and splice with 15101A. Reference line 118 on
BAYDDCU606A.60.00. b. Connect wire 1552M to 1TB4-2. Reference line 86 on BAYDDCU606A.60.00. c. Remove wires 74R 1TB4-5 and re-wire to 1TB4-3. Reference line 86 on BAYDDCU606A.60.00. d. Remove wire 99J from 1TB4-8 and splice with wire 1599J. Reference line 86 on
BAYDDCU606A.60.00. e. Run wire 1574R from 1TB4-5 to 1TB4-8. Reference lines 110 to 111 on BAYDDCU606A.60.00. 5. Reset Relay Disconnect: a. Disconnect wires 53B and 53C from 1TB2-8 and splice together to isolate. Reference lines 96 to
98 on BAYDDCU606A.60.00 b. Disconnect wires 66B and 66C from 1TB4-1 and splice together to isolate. Reference lines 1110
to 114 on BAYDDCU606A.60.00

14

SS-SVX007B-EN

Startup Instructions

AHU

1. The mode of operation (Thermostat, CV or VAV) is determined by jumpers J1 and J2 on UI9 and UI10. Control selection is made according to the following:
a. If J1 and J2 are either both in place or both removed, the unit will operate as Thermostat controlled and Compressors will be enabled/disabled based on inputs UI1 ­ UI6 according to the wiring diagrams.
b. If J1 is removed or cut and J2 remains in place, the unit will operate as Constant Volume (CV) and the compressors will be controlled to satisfy space temperature at local setpoint.
c. If J1 is in place and J2 is removed or cut, the unit will operate as Variable Air Volume (VAV) and the compressors will be controlled to satisfy discharge air temperature at setpoint. A discharge air temperature sensor (10k Type II thermistor) is required for the unit to operate correctly. See wiring diagram.

2. Once the new panel is installed, wiring reconnected and mode of operation set, restore power to the unit and verify correct operation.
3. Because the refrigeration safeties were rewired through a relay and UC monitoring, each safety should be checked for wiring accuracy. Circuit compressors will be locked out after three safety trips within a one-hour period. Power must be cycled off and on at the unit disconnect to reset the hard lockout.
a. Pull wire on Circuit 1 High Pressure Cutout (4S1) and verify relay 7K8 relay denergizes, and circuit 1 compressor(s) shut down immediately.
b. Pull wire on Circuit 1 Low Pressure Cutout (4S5) and verify relay 7K9 relay deenergizes, and circuit 1 compressor(s) shut down immediately.
c. Pull wire on Circuit 2 High Pressure Cutout (4S2) and verify relay 7K10 relay deenergizes, and circuit 2 compressor(s) shut down immediately.
d. Pull wire on Circuit 2 Low Pressure Cutout (4S6) and verify relay 7K11 deenergizes, and circuit 2 compressor(s) shut down immediately.
e. Remaining split-system RAUJ will follow standard startup procedure.

SS-SVX007B-EN

15

Startup Instructions

Chiller

1. Once the new panel is installed, wiring reconnected and mode of operation set, restore power to the unit and verify correct operation. Do not enable unit yet!
2. Verify the Freeze Setpoint (Analog Value 10) is set to an appropriate value for the fluid type being used in the chiller. Default value is 36°F for straight water.
3. Verify the Low Ambient Lockout Setpoint is set to the proper value. Default value is 40°F. This value may be adjusted lower if low ambient damper option is installed. Setpoint adjustment is accomplished by adjusting analog constant in the "Setpoints" program.
4. Since the refrigeration safeties were re-wired through a relay and UC monitoring, each safety should be checked for wiring accuracy. Circuit compressors will be locked out after 3 safety trips within a 1hour period. Power must be cycled off and on at the unit disconnect to reset the hard lockout.
a. Pull wire on Circuit 1 High Pressure Cutout (4S1) and verify relay 7K8 relay deenergizes, and circuit 1 compressor(s) shut down immediately.
b. Pull wire on Circuit 1 Low Pressure Cutout (4S5) and verify relay 7K9 relay deenergizes, and circuit 1 compressor(s) shut down immediately.
c. Pull wire on Circuit 2 High Pressure Cutout (4S2) and verify relay 7K10 relay deenergizes, and circuit 2 compressor(s) shut down immediately.
d. Pull wire on Circuit 2 Low Pressure Cutout (4S6) and verify relay 7K11 deenergizes, and circuit 2 compressor(s) shut down immediately.
5. Enable Circulating pump and verify 7K1 relay energizes. If 7K1 does not energize, verify all field installed safeties (flow switch, freezestat, motor overloads, etc.) are not tripped and wired properly.
6. After a few moments the Tracer UC600, Cool Calc should start ramping up and enabling compressors. The Cool Calc P-Gain (Analog Value 3) may need to be adjusted based on water flow, chiller load, to avoid excessive cycling or over/undershooting setpoint.
7. Remaining chiller startup will follow standard RAUJ startup procedure.

16

SS-SVX007B-EN

Wiring Diagrams
See attached wiring diagrams for further reference.

SS-SVX007B-EN

17

Object Data Points List
20 to 30T (AHU)

Instance

Object Name

1

Discharge Air Temperature

2

Space Temperature Local

3

Space Temperature Setpoint Local

4

Outdoor Air Temperature

1

Active CoolCoil Control Sensor

2

Active CoolCoil Control Setpoint

3

Cooling Capacity Request TC

4

Cooling Capacity Status

5

Cooling PID Maximum Value

6

Cooling PID Output

7

Cooling Stages Requested TC

8

Discharge Air Cooling Setpoint BAS

9

Discharge Air Cooling Setpoint Max BAS

10

Discharge Air Temperature Setpoint Active

11

Discharge Air Temperature Setpoint BAS

12

Discharge Air Temperature Setpoint Local

13

Local Setpoint High Limit

14

Local Setpoint Low Limit

15

Occupied Cooling Setpoint

16

Occupied Heating Setpoint

17

Occupied Offset

18

Occupied Standby Offset

19

Optional CoolCoil Control Command

20

Space Temperature Active

21

Space Temperature BAS

22

Space Temperature Setpoint Active

23

Space Temperature Setpoint BAS

24

Unoccupied Cooling Setpoint

25

Unoccupied Heating Setpoint

26

Cooling Capacity Request CV

27

Cooling Capacity Request VAV

28

Cooling Stages Requested CV

29

Cooling Stages Requested VAV

Point Reference Analog Inputs
UI12.analogValue UI13.analogValue UI14.analogValue UI11.analogValue
Analog Values

Read/Write

Description

Read Read Read Read

Field Installed Field Installed Field Installed

Read Read Read Read Read Read Read Read/Write
Read/Write Read
Read/Write
Read/Write
Read/Write
Read/Write Read/Write Read/Write Read/Write
Read/Write Read Read Read Read
Read/Write Read/Write Read/Write
Read Read Read Read

Default: 55°F Range: 50-125°F Default: 65° Range: 50-85°F
Default: 65°F Range: 50-120°F Default: 70°F Range: 50-120°F Default: 80°F Range: 60-90°F Default: 65° Range: 45-75°F Default: 72° Default: 68°F Default: 2°F Range: 0-18°F Default: 4°F Range: 0-18°F
Default: 70°F Range: 45-95°F Default: 80°F Default: 60°F

18

SS-SVX007B-EN

Object Data Points List

Instance

Object Name

101 Cool Control P-Gain

Point Reference

102 Discharge Air Temperature Setpoint P-Gain
103 Circuit 1 HPCO Fail Count 104 Circuit 1 LPCO Fail Count

1

Supply Fan Status

2

Occupancy Status

3

Constant Volume Mode Input

4

VAV Mode Input

5

Cool 1 Call

6

Cool 2 Call

9

Circuit 1 High Pressure Cutout

10

Circuit 1 Low Pressure Cutout

1

Compressor 1A Command

Binary Inputs UI8.binaryValue UI7.binaryValue UI9.binaryValue UI10.binaryValue UI1.binaryValue UI2.binaryValue XM.30.1.UIO1.binaryValue XM.30.1.UIO2.binaryValue
Binary Outputs
BO1.binaryValue

2

Compressor 1B Command

1

Active CoolCoil Control Sensor Failed

2

Circuit 1 Lockout BAS

3

Circuit 2 Lockout BAS

4

Diagnostic: Space Temperature Source Failure

5

Economizer Interlock OK

6

Fan Latch

7

Heat Cool Mode Active

8

Mixed Air Low Limit Active

9

Night Heat Cool

10

Startup Delay Completed

11

Cooling Enabled

12

CV Mode Active

13

VAV Mode Active

14

Thermosat Mode Active

15

Low OA Temp Cutout

16

Compressor 1A Command CV

17

Compressor 1B Command CV

18

Compressor 1A Command TC

19

Compressor 1B Command TC

20

Compressor 1A Command VAV

21

Compressor 1B Command VAV

32

Circuit 1 Soft Lockout

33

Circuit 1 Hard Lockout

BO2.binaryValue Binary Values
Multistate Values

Read/Write Read/Write
Read/Write Read Read

Default: 1.5 Range: 0.5-25
Default: 4 Range: 0-10

Description

Read Read Read Read Read Read Read Read

Field Installed
Field Installed Field Installed

Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read Read/Write Read/Write
Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read/Write Read/Write Read Read

Default: Off Default: Off
Default: Off Default: Off

SS-SVX007B-EN

19

Object Data Points List

Instance

Object Name

1

DX Staging Status

2

Heat Cool Mode Request

3

Heat Cool Mode Status

4

Occupancy Request

5

Occupancy Status

20

Point Reference

Read/Write Read Read
Read Read/Write
Read

Description 1: Normal 2: Start Interval Active 3: Shutdown Delay Active 4: Subtract Suspended 1: Auto 2: Heat 3: Morning Warm-up 4: Cool 5: Night Purge 6: Pre Cool 7: Off 8: Test 9: Emergency Heat 10: Fan Only 11: Free Cool 12: Ice-Making 13: Maximum Heat 14: Economizer 15: Dehumidify 16: Calibrate 1: Auto 2: Heat 3: Morning Warm-up 4: Cool 5: Night Purge 6: Pre Cool 7: Off 8: Test 9: Emergency Heat 10: Fan Only 11: Free Cool 12: Ice-Making 13: Maximum Heat 14: Economizer 15: Dehumidify 16: Calibrate 1: Occupied 2: Unoccupied 3: Occupied Bypass 4: Occupied Standby 5: Auto 1: Occupied 2: Unoccupied 3: Occupied Bypass 4: Occupied Standby 5: Auto

SS-SVX007B-EN

Object Data Points List

Instance

Object Name

6

Unit Operation

100 Unit Information
40 to 60T (AHU)

Instance

Object Name

1

Discharge Air Temperature

2

Space Temperature Local

3

Space Temperature Setpoint Local

4

Outdoor Air Temperature

1

Active CoolCoil Control Sensor

2

Active CoolCoil Control Setpoint

3

Cooling Capacity Request TC

4

Cooling Capacity Status

5

Cooling PID Maximum Value

6

Cooling PID Output

7

Cooling Stages Requested TC

8

Discharge Air Cooling Setpoint BAS

9

Discharge Air Cooling Setpoint Max BAS

10

Discharge Air Temperature Setpoint Active

11

Discharge Air Temperature Setpoint BAS

12

Discharge Air Temperature Setpoint Local

13

Local Setpoint High Limit

14

Local Setpoint Low Limit

15

Occupied Cooling Setpoint

16

Occupied Heating Setpoint

17

Occupied Offset

18

Occupied Standby Offset

19

Optional CoolCoil Control Command

20

Space Temperature Active

21

Space Temperature BAS

22

Space Temperature Setpoint Active

SS-SVX007B-EN

Point Reference

Read/Write Read Read

Description 1: Thermostat 2: Constant Volume 3: None 4: Variable Volume 5: Thermostat 1: Version: 1 2: CID: 464/471/491/498/630/1183/1185/1191/

Point Reference Analog Inputs
UI12.analogValue UI13.analogValue UI14.analogValue UI11.analogValue
Analog Values

Read/Write

Description

Read Read Read Read

Field Installed Field Installed Field Installed

Read Read Read Read Read Read Read Read/Write
Read/Write Read
Read/Write
Read/Write
Read/Write
Read/Write Read/Write Read/Write Read/Write
Read/Write Read Read Read Read

Default: 55°F Range: 50-125°F Default: 65° Range: 50-85°F
Default: 65°F Range: 50-120°F Default: 70°F Range: 50-120°F Default: 80°F Range: 60-90°F Default: 65° Range: 45-75°F Default: 72° Default: 68°F Default: 2°F Range: 0-18°F Default: 4°F Range: 0-18°F

21

Object Data Points List

Instance

Object Name

23

Space Temperature Setpoint BAS

24

Unoccupied Cooling Setpoint

25

Unoccupied Heating Setpoint

26

Cooling Capacity Request CV

27

Cooling Capacity Request VAV

28

Cooling Stages Requested CV

29

Cooling Stages Requested VAV

101

Cool Control P-Gain

Point Reference

102

Discharge Air Temperature Setpoint P-Gain

103

Circuit 1 HPCO Fail Count

104

Circuit 1 LPCO Fail Count

105

Circuit 2 HPCO Fail Count

106

Circuit 2 LPCO Fail Count

1

Supply Fan Status

2

Occupancy Status

3

Constant Volume Mode Input

4

VAV Mode Input

5

Cool 1 Call

6

Cool 2 Call

7

Cool 3 Call

8

Cool 4 Call

9

Circuit 1 High Pressure Cutout

10

Circuit 1 Low Pressure Cutout

11

Circuit 2 High Pressure Cutout

12

Circuit 2 Low Pressure Cutout

1

Compressor 1A Command

Binary Inputs UI8.binaryValue UI7.binaryValue UI9.binaryValue UI10.binaryValue UI1.binaryValue UI2.binaryValue UI3.binaryValue UI4.binaryValue XM.30.1.UIO1.binaryValue XM.30.1.UIO2.binaryValue XM.30.1.UIO3.binaryValue XM.30.1.UIO4.binaryValue
Binary Outputs
BO1.binaryValue

2

Compressor 1B Command

BO2.binaryValue

3

Compressor 1C Command

BO3.binaryValue

4

Compressor 2A Command

1

Active CoolCoil Control Sensor Failed

2

Circuit 1 Lockout BAS

3

Circuit 2 Lockout BAS

4

Diagnostic: Space Temperature Source Failure

5

Economizer Interlock OK

6

Fan Latch

7

Heat Cool Mode Active

8

Mixed Air Low Limit Active

BO4.binaryValue Binary Values

Read/Write

Description

Read/Write

Default: 70°F Range: 45-95°F

Read/Write Default: 80°F

Read/Write Default: 60°F

Read

Read

Read

Read

Read/Write

Default: 1.5 Range: 0.5-25

Default: 4 Read/Write Range: 0-10

Read

Read

Read

Read

Read Read Read Read Read Read Read Read Read Read Read Read

Field Installed
Field Installed Field Installed Field Installed Field Installed

Read Read Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read Read/Write Read/Write
Read Read Read Read Read

Default: Off Default: Off

22

SS-SVX007B-EN

Instance

Object Name

9

Night Heat Cool

10

Startup Delay Completed

11

Cooling Enabled

12

CV Mode Active

13

VAV Mode Active

14

Thermosat Mode Active

15

Low OA Temp Cutout

16

Compressor 1A Command CV

17

Compressor 1B Command CV

18

Compressor 1A Command TC

19

Compressor 1B Command TC

20

Circuit 3 Lockout BAS

21

Circuit 4 Lockout BAS

22

Compressor 2A Command CV

23

Compressor 2A Command TC

24

Compressor 2B Command CV

25

Compressor 2B Command TC

26

Compressor 1A Command VAV

27

Compressor 1B Command VAV

28

Compressor 2A Command VAV

29

Compressor 2B Command VAV

32

Circuit 1 Soft Lockout

33

Circuit 1 Hard Lockout

34

Circuit 2 Soft Lockout

35

Circuit 2 Hard Lockout

1

DX Staging Status

2

Heat Cool Mode Request

SS-SVX007B-EN

Object Data Points List

Point Reference Multistate Values

Read/Write Read Read Read Read Read Read Read Read Read Read Read
Read/Write Default: Off Read/Write Default: Off
Read Read Read Read Read/Write Default: Off Read/Write Default: Off Read Read Read Read Read Read

Description

Read Read

1: Normal 2: Start Interval Active 3: Shutdown Delay Active 4: Subtract Suspended 1: Auto 2: Heat 3: Morning Warm-up 4: Cool 5: Night Purge 6: Pre Cool 7: Off 8: Test 9: Emergency Heat 10: Fan Only 11: Free Cool 12: Ice-Making 13: Maximum Heat 14: Economizer 15: Dehumidify 16: Calibrate

23

Object Data Points List

Instance

Object Name

3

Heat Cool Mode Status

4

Occupancy Request

5

Occupancy Status

6

Unit Operation

100

Unit Information

80 to 120T (AHU)

Instance

Object Name

1

Discharge Air Temperature

2

Space Temperature Local

3

Space Temperature Setpoint Local

4

Outdoor Air Temperature

1

Active CoolCoil Control Sensor

2

Active CoolCoil Control Setpoint

24

Point Reference

Read/Write

Description

1: Auto

2: Heat

3: Morning Warm-up

4: Cool

5: Night Purge

6: Pre Cool

7: Off

Read

8: Test 9: Emergency Heat

10: Fan Only

11: Free Cool

12: Ice-Making

13: Maximum Heat

14: Economizer

15: Dehumidify

16: Calibrate

1: Occupied

2: Unoccupied

Read/Write 3: Occupied Bypass

4: Occupied Standby

5: Auto

1: Occupied

2: Unoccupied

Read

3: Occupied Bypass

4: Occupied Standby

5: Auto

1: Thermostat

2: Constant Volume

Read

3: None

4: Variable Volume

5: Thermostat

Read

1: Version: 1 2: CID: 464/471/491/498/630/1183/1185/1191/

Point Reference Analog Inputs
UI12.analogValue UI13.analogValue UI14.analogValue UI11.analogValue
Analog Values

Read/Write

Description

Read Read Read Read

Field Installed Field Installed Field Installed

Read Read

SS-SVX007B-EN

Object Data Points List

Instance

Object Name

3

Cooling Capacity Request TC

4

Cooling Capacity Status

5

Cooling PID Maximum Value

6

Cooling PID Output

7

Cooling Stages Requested TC

8

Discharge Air Cooling Setpoint BAS

9

Discharge Air Cooling Setpoint Max BAS

10

Discharge Air Temperature Setpoint Active

11

Discharge Air Temperature Setpoint BAS

12

Discharge Air Temperature Setpoint Local

13

Local Setpoint High Limit

14

Local Setpoint Low Limit

15

Occupied Cooling Setpoint

16

Occupied Heating Setpoint

17

Occupied Offset

18

Occupied Standby Offset

19

Optional CoolCoil Control Command

20

Space Temperature Active

21

Space Temperature BAS

22

Space Temperature Setpoint Active

23

Space Temperature Setpoint BAS

24

Unoccupied Cooling Setpoint

25

Unoccupied Heating Setpoint

26

Cooling Capacity Request CV

27

Cooling Capacity Request VAV

28

Cooling Stages Requested CV

29

Cooling Stages Requested VAV

101

Cool Control P-Gain

102

Discharge Air Temperature Setpoint P-Gain

103

Circuit 1 HPCO Fail Count

104

Circuit 1 LPCO Fail Count

105

Circuit 2 HPCO Fail Count

106

Circuit 2 LPCO Fail Count

1

Supply Fan Status

2

Occupancy Status

3

Constant Volume Mode Input

4

VAV Mode Input

Point Reference
Binary Inputs UI8.binaryValue UI7.binaryValue UI9.binaryValue UI10.binaryValue

Read/Write

Description

Read

Read

Read

Read

Read

Read/Write Default: 55°F Range: 50-125°F

Read/Write

Default: 65° Range: 50-85°F

Read

Default: 65°F Read/Write Range: 50-120°F

Read/Write

Default: 70°F Range: 50-120°F

Read/Write

Default: 80°F Range: 60-90°F

Read/Write

Default: 65° Range: 45-75°F

Read/Write Default: 72°

Read/Write Default: 68°F

Read/Write Default: 2°F Range: 0-18°F

Default: 4°F Read/Write Range: 0-18°F

Read

Read

Read

Read

Default: 70°F Read/Write Range: 45-95°F

Read/Write Default: 80°F

Read/Write Default: 60°F

Read

Read

Read

Read

Read/Write

Default: 1.5 Range: 0.5-25

Read/Write

Default: 4 Range: 0-10

Read

Read

Read

Read

Read Read Read Read

Field Installed

SS-SVX007B-EN

25

Object Data Points List

Instance

Object Name

5

Call 1 Call

6

Call 2 Call

7

Call 3 Call

8

Call 4 Call

9

Call 5 Call

10

Call 6 Call

11

Circuit 1 High Pressure Cutout

12

Circuit 1 Low Pressure Cutout

13

Circuit 2 High Pressure Cutout

14

Circuit 2 Low Pressure Cutout

1

Compressor 1A Command

Point Reference UI1.binaryValue UI2.binaryValue UI3.binaryValue UI4.binaryValue UI5.binaryValue UI6.binaryValue
XM.30.1.UIO1.binaryValue XM.30.1.UIO2.binaryValue XM.30.1.UIO3.binaryValue XM.30.1.UIO4.binaryValue
Binary Outputs
BO1.binaryValue

2

Compressor 1B Command

BO2.binaryValue

3

Compressor 1C Command

BO3.binaryValue

4

Compressor 2A Command

BO4.binaryValue

5

Compressor 2B Command

XM30.BO1.binaryValue

6

Compressor 2C Command

XM30.BO2.binaryValue

1

Active CoolCoil Control Sensor Failed

2

Circuit 1 Lockout BAS

3

Circuit 2 Lockout BAS

4

Diagnostic: Space Temperature Source Failure

5

Economizer Interlock OK

6

Fan Latch

7

Heat Cool Mode Active

8

Mixed Air Low Limit Active

9

Night Heat Cool

10

Startup Delay Completed

11

Cooling Enabled

12

CV Mode Active

13

VAV Mode Active

14

Thermosat Mode Active

15

Low OA Temp Cutout

16

Compressor 1A Command CV

17

Compressor 1B Command CV

18

Compressor 1A Command TC

19

Compressor 1B Command TC

20

Circuit 3 Lockout BAS

21

Circuit 4 Lockout BAS

22

Compressor 1C Command CV

23

Compressor 1C Command TC

Binary Values

Read/Write

Read

Field Installed

Read

Field Installed

Read

Field Installed

Read

Field Installed

Read

Field Installed

Read

Field Installed

Read

Read

Read

Read

Read Read Read Read Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read Read/Write Default: Off Read/Write Default: Off
Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read/Write Default: Off Read/Write Default: Off Read Read

Description

26

SS-SVX007B-EN

Instance

Object Name

24

Compressor 2A Command CV

25

Compressor 2A Command TC

26

Compressor 5 Lockout BAS

27

Compressor 6 Lockout BAS

28

Compressor 2B Command TC

29

Compressor 2B Command CV

30

Compressor 2C Command TC

31

Compressor 2C Command CV

32

Circuit 1 Soft Lockout

33

Circuit 1 Hard Lockout

34

Circuit 2 Soft Lockout

35

Circuit 2 Hard Lockout

36

Compressor 1A Command VAV

37

Compressor 1B Command VAV

38

Compressor 1C Command VAV

39

Compressor 2A Command VAV

40

Actuator Type

41

Compressor 2B Command VAV

42

Compressor 2C Command VAV

1

DX Staging Status

2

Heat Cool Mode Request

Object Data Points List

Point Reference Multistate Values

Read/Write Read Read
Read/Write Default: Off Read/Write Default: Off
Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read

Description

Read Read

1: Normal 2: Start Interval Active 3: Shutdown Delay Active 4: Subtract Suspended 1: Auto 2: Heat 3: Morning Warm-up 4: Cool 5: Night Purge 6: Pre Cool 7: Off 8: Test 9: Emergency Heat 10: Fan Only 11: Free Cool 12: Ice-Making 13: Maximum Heat 14: Economizer 15: Dehumidify 16: Calibrate

SS-SVX007B-EN

27

Object Data Points List

Instance

Object Name

3

Heat Cool Mode Status

4

Occupancy Request

5

Occupancy Status

6

Unit Operation

100

Unit Information

20 to 30T (Chiller)

Instance

Object Name

1

Outdoor Air Temperature

2

Leaving Water Temperature

1

Leaving Water Temp Setpoint BAS

2

Cool Calc

3

Cool Calc P-gain

4

Circuit 1 HPCO Fail Count

28

Point Reference

Read/Write

Description

1: Auto

2: Heat

3: Morning Warm-up

4: Cool

5: Night Purge

6: Pre Cool

7: Off

Read

8: Test 9: Emergency Heat

10: Fan Only

11: Free Cool

12: Ice-Making

13: Maximum Heat

14: Economizer

15: Dehumidify

16: Calibrate

1: Occupied

2: Unoccupied

Read/Write 3: Occupied Bypass

4: Occupied Standby

5: Auto

1: Occupied

2: Unoccupied

Read

3: Occupied Bypass

4: Occupied Standby

5: Auto

1: Thermostat

2: Constant Volume

Read

3: None

4: Variable Volume

5: Thermostat

Read

1: Version: 1 2: CID: 464/471/491/498/630/1183/1185/1191/

Point Reference Analog Inputs
UI2.analogValue UI3.analogValue
Analog Values

Read/Write Description

Read Read

Field Installed

Read/Write Read
Read/Write Read

SS-SVX007B-EN

Object Data Points List

Instance 5 6 7 10

Object Name Circuit 1 LPCO Fail Count Circuit 2 HPCO Fail Count Circuit 2 LPCO Fail Count Freeze Setpoint

1

Chiller Enable

9

Circuit 1 High Pressure Cutout

10

Circuit 1 Low Pressure Cutout

1

Compressor 1A Command

2

Compressor 1B Command

1

Chiller Disable BAS

2

Low Ambient Lockout

3

High Ambient Lockout

4

Warning-Low Fluid Temp

5

Circuit 1 Hard Lockout

6

Circuit 1 Soft Lockout

7

Circuit 2 Hard Lockout

8

Circuit 2 Soft Lockout

9

Compressor 1 Call

10

Compressor 2 Call

15

Freeze Avoidance Lockout 1

16

Freeze Avoidance Lockout 2

40 to 60T (Chiller)

Instance

Object Name

1

Outdoor Air Temperature

2

Leaving Water Temperature

1

Leaving Water Temp Setpoint BAS

2

Cool Calc

3

Cool Calc P-gain

4

Circuit 1 HPCO Fail Count

5

Circuit 1 LPCO Fail Count

6

Circuit 2 HPCO Fail Count

7

Circuit 2 LPCO Fail Count

10

Freeze Setpoint

1

Chiller Enable

9

Circuit 1 High Pressure Cutout

SS-SVX007B-EN

Point Reference
Binary Inputs UI1.binaryValue XM.30.2.UIO1.binaryValue XM.30.2.UIO2.binaryValue
Binary Outputs BO1 (Relay).binaryValue BO2 (Relay).binaryValue
Binary Values

Read/Write Read Read Read R/W

Description

Read Read Read

Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read/Write Read Read Read Read Read Read Read Read Read Read Read

On=Chiller Disabled

Point Reference Analog Inputs
UI2.analogValue UI3.analogValue
Analog Values
Binary Inputs UI1.binaryValue XM.30.2.UIO1.binaryValue

Read/Write

Description

Read Read

Field Installed

Read/Write Read
Read/Write Read Read Read Read Read

Read Read

29

Object Data Points List

Instance

Object Name

10

Circuit 1 Low Pressure Cutout

11

Circuit 2 High Pressure Cutout

12

Circuit 2 Low Pressure Cutout

1

Compressor 1A Command

2

Compressor 1B Command

3

Compressor 2A Command

4

Compressor 2B Command

1

Chiller Disable BAS

2

Low Ambient Lockout

3

High Ambient Lockout

4

Warning-Low Fluid Temp

5

Circuit 1 Hard Lockout

6

Circuit 1 Soft Lockout

7

Circuit 2 Hard Lockout

8

Circuit 2 Soft Lockout

9

Compressor 1 Call

10

Compressor 2 Call

11

Compressor 3 Call

12

Compressor 4 Call

15

Freeze Avoidance Lockout 1

16

Freeze Avoidance Lockout 2

80 to 120T (Chiller)

Instance

Object Name

1

Outdoor Air Temperature

2

Leaving Water Temperature

1

Leaving Water Temp Setpoint BAS

2

Cool Calc

3

Cool Calc P-gain

4

Circuit 1 HPCO Fail Count

5

Circuit 1 LPCO Fail Count

6

Circuit 2 HPCO Fail Count

7

Circuit 2 LPCO Fail Count

10

Freeze Setpoint

1

Chiller Enable

9

Circuit 1 High Pressure Cutout

30

Point Reference XM.30.2.UIO2.binaryValue XM.30.2.UIO3.binaryValue XM.30.2.UIO4.binaryValue
Binary Outputs BO1 (Relay).binaryValue
BO2 (Relay).binaryValue
BO3 (Relay).binaryValue
BO4 (Relay).binaryValue Binary Values

Read/Write Read Read Read

Description

Read Read Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read/Write Read Read Read Read Read Read Read Read Read Read Read Read Read

On=Chiller Disabled

Point Reference Analog Inputs
UI2.analogValue UI3.analogValue
Analog Values
Binary Inputs UI1.binaryValue XM.30.2.UIO1.binaryValue

Read/Write

Description

Read Read

Field Installed

Read/Write Read
Read/Write Read Read Read Read R/W

Read Read

SS-SVX007B-EN

Instance

Object Name

10

Circuit 1 Low Pressure Cutout

11

Circuit 2 High Pressure Cutout

12

Circuit 2 Low Pressure Cutout

1

Compressor 1A Command

2

Compressor 1B Command

3

Compressor 2A Command

4

Compressor 2B Command

5

Compressor 1C Command

6

Compressor 2C Command

1

Chiller Disable BAS

2

Low Ambient Lockout

3

High Ambient Lockout

4

Warning-Low Fluid Temp

5

Circuit 1 Hard Lockout

6

Circuit 1 Soft Lockout

7

Circuit 2 Hard Lockout

8

Circuit 2 Soft Lockout

9

Compressor Call 1

10

Compressor Call 2

11

Compressor Call 3

12

Compressor Call 4

13

Compressor Call 5

14

Compressor Call 6

15

Freeze Avoidance Lockout 1

16

Freeze Avoidance Lockout 2

Object Data Points List

Point Reference XM.30.2.UIO2.binaryValue XM.30.2.UIO3.binaryValue XM.30.2.UIO4.binaryValue
Binary Outputs
BO1 (Relay).binaryValue
BO2 (Relay).binaryValue
BO3 (Relay).binaryValue
BO4 (Relay).binaryValue
XM.32.1.BO1 (Relay).binaryValue
XM.32.1.BO2 (Relay).binaryValue
Binary Values

Read/Write Read Read Read

Description

Read Read Read Read Read Read

3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off
3 Minute On 5 Minute Off

Read/Write Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read

On=Chiller Disabled

SS-SVX007B-EN

31