A SUBMITTAL PLA-A18EA8 PUZ-A18NKA7 en M1
PLA-A18EA8 & PUZ-A18NKA7
18,000 BTU/H 3' X 3' CEILING CASSETTE 18,000 BTU/H HEAT PUMP UNIVERSAL OUTDOOR
Job Name: System Reference:
Indoor Unit Outdoor Unit

Date:

PLA-A18EA8 PUZ-A18NKA7

INDOOR UNIT FEATURES · Space-efficient ductless installation · Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency · Airflow settings for high and low ceiling applications · Individual vane settings for direct/indirect airflow control or variable airflow patterns · Knockouts for outside-air intake and branch-duct run · Filter indicator signal · Easy-to-clean, washable filter (optional high-efficiency filter available - requires multi-function casement) · Built-in condensate lift mechanism · Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more · Multiple control options available:  kumo cloud® smart device app for remote access  Third-party interface options  Wired or wireless controllers
OUTDOOR UNIT FEATURES · Variable speed INVERTER-driven compressor · Pre-charged with refrigerant volume for piping length up to 70 ft · Low ambient cooling down to 0°F providing 100% capacity · 24-hour continuous operation (cooling mode) · High pressure protection · Fast restart · Superior energy and operational efficiency · Seacoast protection*  External Outer Panel: Phosphate coating + Acrylic-Enamel coating  Fan Motor Support: Epoxy resin coating (at edge face)  Separator Assembly Valve Bed: Epoxy resin coating (at edge face)  Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.  Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing *Seacoast protection standard from 2022 production

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PLA-A18EA8 & PUZ-A18NKA7

test
Cooling at 95°F1 Heating at 47°F2 Heating at 17°F3 Efficiency Electrical
Indoor Unit
Indoor Unit Operating Temperature Range

Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Moisture Removal Sensible Heat Factor Power Factor [208V / 230V] Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Power Factor [208V / 230V] Maximum Capacity Rated Capacity Maximum Power Input Rated Power Input SEER2 EER21 HSPF2 [IV] COP at 47°F2 COP at 17°F at Maximum Capacity3 ENERGY STAR® Certified Voltage, Phase, Frequency Guaranteed Voltage Range Voltage: Indoor - Outdoor, S1-S2 Voltage: Indoor - Outdoor, S2-S3 Short-circuit Current Rating [SCCR] Recommended Fuse/Breaker Size (Oudoor) Recommended Wire Size [Indoor - Outdoor] Power Supply MCA Fan Motor Full Load Amperage Fan Motor Type Airflow Rate at Cooling, Dry Airflow Rate at Cooling, Wet Airflow Rate at Heating, Dry Sound Pressure Level [Cooling] Sound Pressure Level [Heating] Drain Pipe Size Condensate Lift Mechanism, Maximum Distance Coating on Heat Exchanger External Finish Color Unit Dimensions Package Dimensions Unit Weight Package Weight Cooling Intake Air Temp [Maximum / Minimum]* Heating Intake Air Temp [Maximum / Minimum]

BTU/H BTU/H BTU/H
W W Pints/h
% BTU/H BTU/H BTU/H
W W % BTU/H BTU/H W W
V AC V AC V DC
kA A AWG
A A
CFM CFM CFM dB[A] dB[A] In. [mm] In. [mm]
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F °F

18,000 18,000 8,000 1,250 1,250
2.4 0.85 95.3 / 95.3 23,000 19,000 7,900 1,700 1,300 95.8 / 95.8 13,500 11,000 1,390 1,300 25.0 14.4 9.2 4.28 2.85 Yes 208/230, 1, 60 198 - 253 208/230 24
5 15 14 Indoor unit is powered by the outdoor unit 1.0 0.28 DC Motor 460­490­570­600 380­420­530­560 420­460­570­600 28­29­31­32 28­29­31­32 1-1/4 [32] 33-7/16 [850] --
White Munsell 6.4Y 8.9/0.4 33-1/16 x 33-1/16 x 10-3/16 [840 x 840 x 258]
34-19/64 x 35-35/64 x 15 [871 x 903 x 381] 46 [21] 77 [34.8]
90 DB, 72 WB / 66 DB, 61 WB 77 DB / 59 DB

NOTES:

AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

(Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB

3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Conditions

4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. » Wind baffles required to operate below 23°F DB in cooling mode. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PLA-A18EA8 & PUZ-A18NKA7

test
Outdoor Unit
Outdoor Unit Operating Temperature Range Refrigerant Piping

MCA MOCP Fan Motor Full Load Amperage Fan Motor Output Airflow Rate [Cooling / Heating] Refrigerant Control Defrost Method Coating on Heat Exchanger Sound Pressure Level, Cooling1 Sound Pressure Level, Heating2 Compressor Type Compressor Model Compressor Rated Load Amps Compressor Locked Rotor Amps Compressor Oil [Type // Charge] External Finish Color Base Pan Heater Unit Dimensions Package Dimensions Unit Weight Package Weight Cooling Air Temp [Maximum / Minimum]* Heating Air Temp [Maximum / Minimum] Heating Thermal Lock-out / Re-start Temperatures** Type Pre-Charged Refrigerant Amount Maximum Pre-Charged Piping Length Additional Refrigerant Charge Per Additional Piping Length Gas Pipe Size O.D. [Flared] Liquid Pipe Size O.D. [Flared] Maximum Piping Length Maximum Height Difference Maximum Number of Bends

A A A W CFM
dB(A) dB(A)
A A oz.
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F °F °F
Lbs, oz Ft. [m] oz./Ft. [g/m] In.[mm] In.[mm] Ft. [m] Ft. [m]

11.0 28 0.5 46 1590 / 1590 LEV Reverse Cycle Blue Fin Coating*** 44 46 INVERTER-driven twin rotary SNB130FQCMC-L1 7 12.0 FV50S // 16 Ivory Munsell 3Y 7.8/1.1 N/A 31-13/16 (2+7/16) x 11-13/16 x 24-13/16 [809 (+62) x 300 x 630] 37-1/16 x 16-3/16 x 27-7/16 [941 x 411 x 697] 100 [45] 112 [51] 115 DB / 0 DB 70 DB, 59 WB / 12 DB, 14 WB 8 / 12 R410A 4.0, 14.0 70.0 [21.0] 0.2 [19] 1/2 [12.7] 1/4 [6.35] 100 [30] 100 [30] 15

NOTES:

AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

(Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB

3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Conditions

4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. » Wind baffles required to operate below 23°F DB in cooling mode. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT ACCESSORIES: PLA-A18EA8

Control Interface
Remote Sensor Wired Remote Controller
Wireless Remote Controller Casement Condensate Disconnect Switch Filter i-see Sensor® Panel Lineset Shutter Plate Space Panel

3-Pin Connector Airzone ZBS Wired Blueface Principal Controller White Airzone ZBS Wired Blueface Principal Controller White Airzone ZBS Wired Lite Controller White Airzone ZBS Wireless Lite Controller White Airzone ZBS Wireless Think Controller White CN24 Relay Kit IT Extender kumo station® for kumo cloud® Procon BACnet® and Modbus® Interface Remote Operation Adapter Thermostat Interface USNAP Adapter Wireless Interface for kumo cloud® Flush Mount Remote Temperature Sensor Flush Mount Temperature Sensor Remote Temperature Sensor Wireless temperature and humidity sensor for kumo cloud® Deluxe Wired MA Remote Controller Simple Ductless Wired Remote Controller Simple MA Remote Controller Touch MA Controller kumo touchTM RedLINKTM Wireless Controller Lockdown bracket for remote controller Wireless MA Receiver Wireless MA Remote Controller Wireless Remote Contoller Wireless Signal Receiver Panel Multi-function Casement Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H Blue Diamond Sensor Extension Cable -- 15 Ft. Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H (30A/600V/UL) [fits 2" X 4" utility box] - Black (30A/600V/UL) [fits 2" X 4" utility box] - White High Efficiency Filter Element** Grille with 3D i-see Sensor® 100' x 1/4" x 100' / 1/2" Lineset (Twin-Tube Insulation) 15' x 1/4" x 15' / 1/2" Lineset (Twin-Tube Insulation) 30' x 1/4" x 30' / 1/2" Lineset (Twin-Tube Insulation) 50' x 1/4" x 50' / 1/2" Lineset (Twin-Tube Insulation) 65' x 1/4" x 65' / 1/2" Lineset (Twin-Tube Insulation) Shutter Plate Space Panel

NOTES: PAC-SF40RM-E (Unable to use with wireless remote controller)

 PAC-715AD  AZZBSBLUEFACECB  AZZBSBLUEZEROCB  AZZBSLITECB  AZZBSLITERB  AZZBSTHINKRB  CN24RELAY-KIT-CM3  PAC-WHS01IE-E  TAC-WHS01HC-E  PAC-UKPRC001-CN-1  PAC-SF40RM-E  PAC-US445CN-1  PAC-WHS01UP-E  PAC-USWHS002-WF-2  PAC-USSEN002-FM-1  PAC-USSEN001-FM-1  PAC-SE41TS-E  PAC-USWHS003-TH-1  AAR-40MAAU  PAC-SDW01RC-1  PAC-YT53CRAU-J  PAR-CT01MAU-SB  MHK2  RCMKP1CB  PAR-SR32MA-E  PAR-FL32MA-E  PAR-SL101A-E  PAR-SR4LU-E  PAC-SJ41TM-E  X87-721  X86-003  C13-103  COMBI  TAZ-MS303  TAZ-MS303W  PAC-SH59KF-E  PLP-41EAEU  MLS141212T-100  MLS141212T-15  MLS141212T-30  MLS141212T-50  MLS141212T-65  PAC-SJ37SP-E  PAC-SJ38AS-E

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Air Outlet Guide Centralized Drain Pan Control/Service Tool Drain Socket Hail Guards M-NET Converter Mini-Split Wire Mounting Pad
Stand
Wind Baffle

OUTDOOR UNIT ACCESSORIES: PUZ-A18NKA7
Air Outlet Guide Centralized Drain Pan Drain Pan Control/Service Tool M- & P-Series Maintenance Tool Cable Set USB/UART Conversion Cable (Required for all laptop connection) Drain Socket Hail Guard M-NET Converter 14 Gauge, 4 wire MiniSplit Cable--250 ft. roll 14 Gauge, 4 wire MiniSplit Cable--50 ft. roll 16 Gauge, 4 wire MiniSplit Cable--250 ft. roll 16 Gauge, 4 wire MiniSplit Cable--50 ft. roll Condensing Unit Mounting Pad: 16" x 36" x 3" 18" Single Fan Stand 24" Single Fan Stand Condenser Wall Bracket Condenser Wall Bracket - Stainless Steel Finish Outdoor Unit Stand -- 12" High Front Wind Baffle Rear Wind Baffle Side Advanced Wind Baffle

 PAC-SJ07SG-E  PAC-SG63DP-E  PAC-SG64DP-E  PAC-SK52ST  M21EC0397  M21EC1397  MAC-871DS  HG-A5  PAC-SJ96MA-E  S144-250  S144-50  S164-250  S164-50  ULTRILITE1  QSMS1801M  QSMS2401M  QSWB2000M-1  QSWBSS  QSMS1201M  WB-PA4  WB-RE4  WB-SD4

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

(7mm) 1/4 OR MORE
E
SPACE IN THE CEILING

17-11/16(450)

(350) 13-3/4

(SUSPENSION BOLT PITCH)
(660+040)
26 0 (CEILING HOLE)

INDOOR UNIT DIMENSIONS: PLA-A18EA8

n1-1/4''( { MAKE SURE TO SLACK THE ELECTRICAL WIRE LITTLE BIT FOR

1-7/16(37) 3-1/2

OPTIONAL PART:SIGNAL RECEIVER
20(508) (AIR INTAKE HOLE)

CORNER POCKET VANE MOTOR

WALL CEILING GRILLE
GRILLE

INDOOR UNIT

INDOOR UNIT

BETWEEN THE TOP OF UNIT AND CEILING SLAB

F
CEILING HEIGHT

OBSTACLE

118-1/8(3000mm) OR MORE BETWEEN INDOOR UNIT
70-7/8(1800mm) OR MORE FROM FLOOR

(1000mm)

OR MORE
CEILING REMOTE CONTROLLER WIRE ENTRY

FLOOR
(20-45) 13/16 TO 1-3/4 REMOTE CONTROLLER WIRE ENTRY

BRANCH DUCT HOLE

(145) 5-11/16

(CEILING HOLE)
31-5/16 (SUSPENSION BOLT PITCH)

(145) 5-11/16

70° AIR INTAKE GRILLE

REMOTE CONTROLLER TERMINAL BLOCK

(20-45) 13/16 TO 1-3/4
FRESH AIR INTAKE HOLE

(20) 13/16

(20-45) 13/16 TO 1-3/4

(100) 3-15/16

DETAILS OF FRESH AIR INTAKE HOLE

{ 3-15/16({ 100) CUTOUT HOLE

{ 4-15/16({ 125) BURRING HOLE PITCH 120° SELF-TAP 4 SCREWS:3 PLACES

120°

6-1/4 (158)

CEILING

(167)
(155) 6-1/8

CEILING GRILLE

{ 6-7/8({ 175) BURRING HOLE PITCH

70°

SELF-TAP 4 SCREWS:4 PLACES (CONNECTING TO BRANCH DUCT)

{ 5-7/8({ 150) CUTOUT HOLE (CONNECTING TO BRANCH DUCT)

33-1/16(840)

20(508) (AIR INTAKE HOLE)

20-7/8(530) (AIR OUTLET HOLE)

(100) 3-15/16

BRANCH DUCT HOLE

INDOOR UNIT/ OUTDOOR UNIT CONNECTING TERMINAL BLOCK

BRANCH DUCT HOLE

(133) 5-1/4

(20) 13/16

(37) 1-7/16 3-1/2

DRAIN HOLE

(AIR OUTLET HOLE) 20-7/8(530)
COMPANY NAME

AUTO VANE

I-SEE SENSOR CORNER PANEL
EXCEPT DRAIN PIPE CORNER (NEED TO FUNCTION SETTING BY REMOTE CONTROLLER)

{ 5-7/8({ 150) CUTOUT HOLE (CONNECTING TO BRANCH DUCT)
{ 6-7/8({ 175) BURRING HOLE PITCH SELF-TAP 4 SCREWS:4 PLACES (CONNECTING TO BRANCH DUCT)

7-5/8
(222) 8-3/4

BRANCH DUCT HOLE 33-1/16(840)

SUSPENSION BOLT M10 OR W3/8

(60) 2-3/8

MAIN UNIT 24-3/4(628)

2
12/18/24/30/36/42

MODELS 12/18 24/30/36/42

FLARED CONNECTION 1/4F FLARED CONNECTION 3/8F

REFRIGERANT PIPE{ FLARED CONNECTION 1/2F
REFRIGERANT PIPE{ FLARED CONNECTION 5/8F

A

B

CD

(241)

10-3/16 (258)

3(76)

11-1/16 11-3/4

3-1/8

(281)

E

F

10-7/16(265) 137-13/16(3500) OR MORE OR LESS

12(305) 177-3/16(4500) OR MORE OR LESS

DETAILS OF SIGNAL RECEVER
EMERGENCY OPERATION SWITCH <COOLING>AND EMERGENCY UP/DOWN SWITCH<UP>

RECEIVER

OPERATION LAMP

EMERGENCY OPERATION SWITCH <HEATING>AND EMERGENCY UP/DOWN SWITCH<DOWN>
DEFROST/STAND BY LAMP

(170) 6-11/16 (140) 5-1/2

1

THE BOTTOM OF I-SEE SENSOR SUSPENSION BOLT LOWER EDGE

INDOOR UNIT/OUTDOOR UNIT CONNECTING WIRE, POWER SUPPLY WIRE ENTRY

(145) 5-11/16
DRAIN PIPE VP-25 CONNECTION (CONNECTED THE ATTACED DRAIN SOCKET)

GRILLE

CEILING

1/4(6) 5-11/16(145)

4-1/8 (105)

D C

(17+05)

11/16

+3/16 0

7-1/2
A B

(40)

(20-45) 13/16 TO 1-3/4

(100) 3-15/16

(130) 5-1/8

SELF-TAP 4 SCREWS:14 PLACES (CONNECTING TO BRANCH DUCT)
13-3/4×3-15/16(350×100) CUTOUT HOLE (CONNECTING TO BRANCH DUCT)

Specifications are subject to change without notice.

(50-70) 1-15/16 TO 2-3/4
2-5/16 (58)

630 <24-13/16> 320<12-5/8> 8.5 <11/32>

OUTDOOR UNIT DIMENSIONS: PUZ-A18NKA7

404.5<15-15/16>
Air intake Installation bolt pitch
500<19-11/16>

drain hole

ø 42

2-U Shaped notched holes

(Foundation Bolt M10<W 3/8>)

Unit: mm<in>

48<1-29/32>

32.5<1-9/32> 300<11-13/16> 330<13>
360<14-3/16>

Air intake

Air discharge 22.3 <29/32> Handle for moving

40 <1-19/32>

2-10×21 oval hole

(Foundation Bolt M10

<W 3/8>)

22 <7/8>

23.2 <15/16> Terminal connection Left ... Power supply wiring Right ... Indoor/Outdoor wiring
Earth terminal Service panel

492 <19-3/8>

154.5 <6-3/32> 310 <12-7/32>
809 <31-7/8>

2- ø 22.2<7/8> 1/2 conduit hole
62 <2-15/32>

164.5 <6-1/2> 99.5<3-15/16>

Service port

35 ° 43 °

Service panel for charge plug Connection for liquid pipe FLAREø6.35 (1/4F)
Connection for gas pipe FLAREø12.7 (1/2F) 185.5 <7-5/16>

Basically open

Free space around the outdoor unit (basic example)
100mm<3-15/16> or more as long as no obstacle is placed on the rear and right-and-left sides of the unit

FOUNDATION BOLTS
Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts, washers and nut must be purchased locally).
<Foundation bolt height>

Min.100mm <3-15/16>

Min.350mm <13-25/32>

FOUNDATION

Max.
18 mm<23/32>

Min.500mm <19-11/16>

Min.100mm <3-15/16>

2 sides should be open in the right, left and rear side.

PIPING-WIRING DIRECTION
Piping and wiring connection can be made from the rear direction only.

FORM# PLA-A18EA8 & PUZ-A18NKA7 - 202310 Specifications are subject to change without notice.