BACnet Quick Start Guide
1 ­ W ire Network Connection
M S/ TP

A

TCP/ IP

A ­ Ethernet Port Lights

c.pCO M ini Cont roller

2 ­ Adjust BACnet Network Settings
M enu Structure Reference M ain M enu
Ct rl Variables Advanced Login Net w ork Set tings

2.1 ­ Ent er User Password

2.2 ­ BACnet M S/ TP Set tings 2.2 ­ BACnet IP Set t ings

Ethernet Port Lights Green: Connect ed Yellow : On = 100M bps Off = 10 M bps

3 ­ Command Unit Operation 1. Enable Unit 2. Cont rol Occupancy 3. Reset Alarms 4. Global Alarm Not ification 5. Cont rol Temperature Set point (o p t io n al)

Object
BV-2 BV-3 BV-4 BV-19

Object Nam e
Syst em_Enable BM S_Occupancy_Com mand Reset _All_Alarms Global_Alarm

AV-1 Tem perat ure_Set point

Object Descript ion
M ast er syst em enable/ disable point . Occupancy Command Alarm Reset Command Alarm Notificat ion (any alarm by default ) Set s the act ive t emperat ure set-point based on mode of operat ion (space set point , ret ur n setpoint or supply setpoint ). Not applicable for out side reset .

M UA BACnet Quick St art Guide

Act ive Text

Inact ive Text

Variable Type

Enabled

Disabled

Uno ccu p i ed

Occu pi ed

Reset

Nor m al

Alar m

Nor m al

Default = 72°F M in = 50°F; M ax = 100°F

January 2023

Document 485941 BACnet Int egrat ion Guide for
M akeup Air Systems
Reference Guide for BACnet Int egrat ion
Please read and save t hese inst ruct ions for fut ure reference. The information in t his guide assumes t he cont roller was already configured wit h BACnet based on t he original sales configuration. If t he cont roller does not have BACnet enabled, please cont act t he equipment represent ative t o get t he necessary licensing and configuration files t o allow BACnet communication t o be used.

M UA_01.001 Rev 2 Document Date: 01/ 2023
Basic Unit Int egration Below are the basic int egrat ion functions available on all equipment regardless of cont rol mode. Some feat ures are unit configurat ion dependent (heat ing t ype, cooling t ype, et c.). The cont roller's BM S point s list is st atic regardless of configurat ion to accommodat e field configurat ion changes, however, not all point s are applicable every unit . Once the required sensors are inst alled in t he equipment , the only mandat ory requirement s to make the unit operat ional are to enable t he unit , if it hasn't been enabled manually at t he cont roller, and to command occupancy as desired.

Object

Variable

De script ion

Active Text

Inactive Text

Unit Enable/ Disable Operation

If desired, t he unit can be enabled and disabled by the BM S syst em. In disabled mode, cert ain saf ety sequences may operat e t o prot ect the

building and/ or equipment but general heat ing, cooling and vent ilat ion operat ion will not funct ion.

BV-2 Syst em_Enable

M ast er syst em enable/ disable command

Enabled

Disabled

Unit Occupancy Control

By default , t he unit occupancy is expect ed t o be commanded by t he BM S occupancy point . Alt ernat ively, t he unit occupancy can be cont rolled

by an int ernal schedule, set t o always unoccupied, always occupied or cont rolled by a digit al input by changing t he occupancy m ode select ion

at t he cont roller. If t he cont roller is configured f or warm-up/ cool-dow n mode, aft er t he occupancy com mand is received t he unit will run in

unoccupied recirculat ion mode unt il reaching t he occupied t emperat ure set point or t he warm-up/ cool dow n t ime expires (default 30 minut es)

at which point the cont roller will ent er nor mal occupied mode operat ion.

BV-3 BM S_Occupancy_Command

Building Occupancy Command

Unoccupied

Occu p i ed

Alarms

The following point s allow t he not ificat ion of any alarm and t he last alarm t riggered to be r ead, as w ell as act ive alarms that t o be manually

reset remot ely. See t he unit 's full BM S point s list if specific alarm monit oring or t rending is desired.

BV-4 Reset _All_Alarms

Alarm Reset Command

Reset

Nor m al

BV-19 Global_Alarm

Global Alarm

Alarm

Nor m al

IV-9 Lat est Alm

M ost recent act ive alarm

See Alarm Table (0 = No Act ive Alarm)

M onitoring Unit Operation

Unit status

AV-41 Unit _St at us_M ode

Unit Operat ion M ode/ St at e

See St at us M ode Table

Fans and Dampers

BI-1

Exhaust _Fan_1_St at us_Digit al_Input

Exhaust Fan 1 St at us

Act ive

Inact ive

BI-2

Supply_Fan_1_St at us_Digit al_Input

Supply Fan 1 St at us

Act ive

Inact ive

AV-62 Out side_Airflow_M ask

Percent age of Out side Airflow

Real (%)

AV-63 Supply_Fan_Speed_Analog_Out put

Supply Fan Speed Analog Out put

Real (%)

Cooling

IV-15* Cooling_is_On (Bit 20)

Indicat es t hat the unit is cooling

Act ive

Inact ive

AV-43 Cooling_1_Ramp_Capacit y

Cooling Ramp 1 St at us Value

Real (%)

Heating

IV-15* Heat ing_is_On (Bit 21)

Indicat es t hat the unit is heat ing

Act ive

Inact ive

AV-46 Heat ing_Capacit y

Heat ing Ramp

Real (%)

Filters

IV-13* (Bit 3)

Filt er_Alarm_Digit al_Input

Filt er Alarm Digit al Input St at us

Alarm

Nor m al

Refrigeration System s

IV-10* (Bit 3)

Compr essor _1_Enable_Digit al_Out put

Compr essor 1 Enable Digit al Out put

Act ive

Inact ive

IV-10* (Bit 4)

Compr essor _2_Enable_Digit al_Out put

Compr essor 2 Enable Digit al Out put

Act ive

Inact ive

AV-64 M odulat ing_Compressor_Analog_Out put _BM S M odulat ing Compressor Analog Out put

Real (%)

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 1

Object

Variable

Chilled W ater Systems

AV-58 Chilled_Wat er_1_Valve_Analog_Out put

Evaporative Cooling Systems

IV-10* Evap_Valve_Enable_Digit _Out put (Bit 16)

IV-10* Evap_Pump_Enable_Digit _Out put (Bit 17)

Hot W ater Systems

AV-60 Hot _Wat er _Valve_1_Analog_Out put

IG Furnaces

IV-10* (Bit 7)

Furnace_1_St age_1_Digit al_Out put

IV-10* (Bit 8)

Furnace_1_St age_2_Digit al_Out put

IV-10* (Bit 9)

Furnace_2_St age_1_Digit al_Out put

IV-10* (Bit 10) Furnace_2_St age_2_Digit al_Out put

IV-10* (Bit 11)

Furnace_3_St age_1_Digit al_Out put

AV-61 M od_Gas_Furnace_1_Analog_Out put

Electric Post-Heat

IV-10* (Bit 15)

Elect ric_Heat er_St art _St op_Digit al_Out put

AV-59 Elect ric_Heat er_1_Analog_Out put

Direct Gas Burner

IV-10* Direct _Gas_Heat ing_Enable_Digit al_Out put
(Bit 14)

Sensor Values (w hen equipped)

AI-1 Space_Temp_Analog_Input

AI-2 Supply_Temp_Analog_Input

AI-3 Out side_Air_Temp_Analog_Input

AI-9 Space_St at ic_Pressure_Analog_Input

AI-10 Supply_Duct _St at ic_Pressure_Analog_Input

AI-11 Space_CO2_1_Analog_Input

AI-12 Ret urn_CO2_Analog_Input

AV-56 OAD_CFM _BM S

Active Setpoint s

AV-42 Supply_Temperat ure_Calculat ed_Set point

* Please see Binary Tables.

De script ion
Chilled Wat er 1 Valve Analog Out put
Evaporat ive Cooling Valve Enable Evaporat ive Cooling Pump Enable
Hot Wat er Valve 1 Analog Out put
Furnace 1 St age 1 Digit al Out put Furnace 1 St age 2 Digit al Out put Furnace 2 St age 1 Digit al Out put Furnace 2 St age 2 Digit al Out put Furnace 3 St age 1 Digit al Out put M od Gas Fur nace 1 Analog Out put
Elect ric Heat er Digit al Out put Elect ric Heat er 1 Analog Out put
Direct Gas Enable Digit al Out put
Space Air Temperat ure Supply(discharge) Air Temperat ure Out side Air Temperat ure Space St at ic Pressure Supply Duct St at ic Pressure Space 1 CO2 ppm Ret urn CO2 ppm Out door Air Damper CFM Act ive Supply Temperat ure Set point

Active Text

Inactive Text

Real (%)

Act ive Act ive

Inact ive Inact ive

Real (%)

Act ive

Inact ive

Act ive

Inact ive

Act ive

Inact ive

Act ive

Inact ive

Act ive

Inact ive

Real (%)

Real (%)

Act ive

Inact ive

Real (°F) Real (°F) Real (°F) Real (" wc) Real (" wc) Real (ppm) Real (ppm) Real (cfm)
Real (°F)

Unpacking Int eger Words to Binary Values Binary values can be combined to creat e an int eger word. By doing t his, more informat ion is available t o t he BM Sin a smaller number of point s and less net work traffic. These int eger words need t o be "unpacked" once t he BM S receives t he value.

Object

Variable

Packed Integer W ords

IV-10 Digit al_Out put _Word

IV-11 Cooling_Alarm_Word

IV-12 Device_Offline_Word

IV-13 Device_Alarm _Word

IV-14 Heat ing_Alarm_Word

IV-15 Unit _St at us_Word

De script ion
Digit al Out put Enables Cooling Device Alarms Device Communicat ion Alarms Device Alarms Heat ing Device Alarms Unit St at us Word

Reference Table
Bit Packed Word - See Binary Tables Bit Packed Word - See Binary Tables Bit Packed Word - See Binary Tables Bit Packed Word - See Binary Tables Bit Packed Word - See Binary Tables Bit Packed Word - See Binary Tables

To unpack the int eger word int o t he binary values, t he integer needs to be convert ed t o a binary number. The int egers in t he program are 32-bit , meaning up to 32 binary values are packed int o t he integer. Each bit can eit her be a 0 (Inact ive) or a 1 (Active).
The BM Sfront end may have a solut ion already int act t o pull individual bit s from an int eger. A " read bit " function looks t o return what value a cert ain bit is in an int eger. Bit number are 0-31 in a 32-bit int eger wit h 0 being t he low est bit and t he furt hest t o t he right in t he binary not at ion of the number. Bit 31 would be t he largest bit and t he furthest t o t he left in binary notat ion.

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 2

If t he front end does not have a " read bit " or "bit ext ract" f unct ion, t he binary value of individual bit s can be det ermined by continually dividing t he quotient of t he int eger by 2, the remainder of t he division is t he value of t he bit (0 or 1). A funct ion called M odulo or " mod" and is commonly used to ret urn t he remainder of int eger division.

Equat ion: x = (round down(a/ 2b) )mod 2

· x is Boolean value for bit b, where 0 is inactive and 1 is active. · a is the int eger word value · b is t he bit of the binary number used as an exponent · The result of a/ 2b should round down t o a whole number, t runcating t he decimal. For example, 5/ 21 is 2.5,
however, only t he 2 is used.

Exam ple:

If t he Device_Offline_Word (IV-12) is a decimal value of 11, t he binary value would be 1011. This binary value would mean that Space Thermost ats 1, 2, and 4 are offline. The rest of t he bit s in t he binary number would be a Boolean value of 0. (Please see Binary Tables.)

· Bit 0 = 11/ 20 mod 2...t his result s in a Boolean of 1 or Active for bit 0. · Bit 1 = 11/ 21 mod 2...t his result s in a Boolean of 1 or Active for bit 1. · Bit 2 = 11/ 22 mod 2...t his result s in a Boolean of 0 or Inactive for bit 2. · Bit 3 = 11/ 23 mod 2...t his result s in a Boolean of 1 or Active for bit 3.

Bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Val 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

1

1

M odifying Equipment Operat ion In addit ion t o commanding unit occupancy, some syst em level sequences may require feedback from t he BM S. Common BM Sadjusted sequences include it ems like supply air t emperature reset control, demand cont rol vent ilat ion for mult iple zones, and duct st atic pressure reset .

HEATING AND COOLING OPERATION SETPOINTS

Object

Variable

De script ion

Active Text

Inactive Text

Adjusting Temperature Setpoints

Cont roller Provided Sequences ­ Occupied M ode

The cont roller has several st and-alone supply air temperat ure cont rol modes wit h set point s that can be modified by the BM S. These modes include a

st at ic supply air t emperat ure set point (no-reset) or allows for t he supply air temperat ure setpoint to be reset based on out side air t emperat ure, space

t emperat ure, or retur n air t emperat ure.

IV-1 Temperat ure_Reset _M ode

Commands t he reset mode during occupied oper at ion .

1 = No Reset , 2 = Space Reset 3 = Ret urn Reset, 4 = Out side Reset

Set s the t emperat ure set point based on mode

AV-1 Temperat ure_Set point

of operat ion (space set point , ret urn set point or supply set point ).

Real, Default = 72°F * M in = 50°F; M ax = 120°F

Not applicable for out side reset.

Heat / Cool Set pt Deadband w hen Space or

Real, Default = 4°F

AV-2 Temperat ure_Heat _Cool_Deadband

Ret urn reset cont rol is act ive. Ht g Set pt = Temp Set pt - Deadband / 2

M in = 0.1°F; M ax = 20°F [Space/ Ret urn Heat ing = 70°F,

Clg Set pt = Temp Set pt - Deadband / 2

Space/ Ret urn Cooling = 74°F]

Cont roller Provided Sequences ­ Unoccupied M ode

When the unoccupied mode of operat ion is set t o night set back t emperat ure, normal operat ion wit h unoccupied setpoint s, or recirculat ion wit h

unoccupied set point s, t he following set point s cont rol unoccupied heat ing and cooling operat ion. If night set back is select ed as t he Unoccupied M ode

of operat ion, t he reset mode will not be available to change at t he cont roller and should be set to Space Reset (2).

IV-2 Temperat ure_Reset _M ode_Unoccupied

Commands t he reset mode during occupied oper at ion .

1 = No Reset , 2 = Space Reset 3 = Ret urn Reset, 4 = Out side Reset

Set s the t emperat ure set point based on mode

AV-3 Temperat ure_Set point _Unoccupied

of operat ion (space set point , ret urn set point or supply set point ).

Real, Default = 72.5°F * M in = 50°F; M ax = 120°F

Not applicable for out side reset.

* Typical range for st andard configurat ion unit, please verify at point min and max propert ies.

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 3

Object

Variable

De script ion

Heat / Cool Set pt Deadband w hen Space or

AV-4

Ret urn reset cont rol is act ive. Temperat ure_Heat _Cool_Deadband_Unoccupied Unooc Clg Set pt = Deadband / 2 + Temp Set pt

Unocc Ht g Set pt = Deadband / 2 - Temp Setpt

BM SCont r olled Sequences

BM S cont rol over reset writ e t o t emp set point and have mode in No reset.

Active Text

Inactive Text

Real, Default = 15°F

M in = 0.1°F; M ax = 40°F

[Space/ Ret urn Heat ing = 65°F,

Space/ Ret urn Cooling = 80°F]

AIRFLOW OPERATION SETPOINTS

Object

Variable

De script ion

Active Text

Inactive Text

Airflow Setpoints

Airflow operat ion of supply fan, exhaust fan, and mixing dampers may use set point s from duct pressur e, space pressur e, CO2 sensors, or airflow

measuring st at ions t o properly cont rol airflow in an applicat ion. The Out side Air Damper M inimum Set point Occupied applies t o all unit s wit h

modulat ing out side air dampers. The setpoint is used t o est ablish an absolut e minimum posit ion for vent ilat ing t he space w hile allowing ot her cont r ol

modes t o open t he damper furt her as necessary. Out door and recirculat ing air dam pers operat e inversely using t he same signal.

AV-16 Space_St at ic_Pressure_Set point

Space St at ic Pressure Set point

Default = 0.05" w c M in = -0.5" w c; M ax = 0.5" w c

AV-17 Supply_Duct _St at ic_Pressure_Set point

Supply Duct St at ic Pressure Set point

Default = 1.0" w c M in = 0" wc; M ax = 5" wc

AV-18 Space_CO2_Set point

Space CO2 Set point

Default = 1,000 ppm M in = 0 ppm; M ax = 5,000 ppm

AV-19 Out side_Air_Damper _M inimum_Set point _Occ Out side Air Damper M inim um Set point Occupied

Default = 35% M in = 0%; M ax = 100%

BM SWat chdog Enabled Control

BM S W ATCHDOG

When direct ly commanding fans speeds, damper posit ions, or sending sensor values, the unit cont roller requires the BM SWat chdog point t o be writ t en t o on a recurring basis. This tells the unit controller that t he BM S is st ill actively com m u n i cat in g.

Object

Variable

De script ion

Active Text

Inactive Text

BM S W atchdog

The BM S Wat chdog must be writ t en to True (1) regularly t o verify communicat ion is est ablished between t he unit cont roller and t he BM S headend

syst em. If t he BM S Wat chdog value r emains False(0) for longer t han the Timeout Delay (15 minut es, adjust able), an alarm is generat ed and t he

cont r oller falls back t o local cont rol and sensor values, as applicable, inst ead of using BM S com manded values.

BV-1 BM S_Wat chdog

BM S Wat chdog command

Act ive

Inact ive

BV-20 BM S_Wat chdog_Act ive

St at us of t he BM S wat chdog ping.

Act ive

Inact ive

CONTROLLING AIRFLOW DEVICES
If desired, t he speeds and posit ions of airflow devices can be cont rolled directly using BACnet commandable point s. To cont rol t he devices via the BM S, t he BM SWat chdog requirement s must be sat isfied.

Object

Variable

De script ion

Active Text

Inactive Text

Fan Controls

Fan speeds can be cont rolled direct ly t hough BM S point s. The binary point s enable t he BM S t o t ake cont rol and t he analog values command the

speeds as a percent age bet ween t he allowed minim um and maximum values set in t he cont roller.

Supply Fan

BV-14 SF_Cont rol_Source_BM S

Allows t he BM S t o cont r ol supply fan speed

BM S

Local

AV-38 SF_Cont rol_Signal_BM S

Supply Fan Command Speed

Real (%) * M in=50%; M ax=100%

Outdoor Air/ Recirculation Air Damper Control

The out door air damper posit ion can be cont r olled direct ly by t he BM S to adjust the mixt ure of out door air and recirculat ion air on unit s configured for

recirculat ion. M inimum and maxim um values for occupied and unoccupied mode set at the unit cont r oller are enforced.

BV-15 OAD_Cont r ol_Source_BM S

Allows t he BM S t o cont r ol OAD posit ion

BM S

Local

AV-39 OAD_Cont r ol_Signal_BM S

Out side Air Damper Cont r ol Signal via BM S

Real (%) M in=0%; M ax=100%

* Typical range for st andard configurat ion unit, please verify at point min and max propert ies.

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 4

SENDING SENSOR VALUES

Sensor values required for sequence operat ion can be sent t o t he cont roller over dedicat ed BM S point s in place of a sensor wired t o the cont roller (local sensor). When values are communicated to t he cont roller over BM S, t he BM S Wat chdog must be satisfied. If t he wat chdog isn't sat isfied, t he controller revert s to the local sensor (if inst alled and valid) t o cont rol the unit or falls back t o local cont rol unt il t he BM S wat chdog is sat isfied.

Object

Variable

De scrip t ion

Active Text

Inactive Text

BM S W riteable Sensor Values

To writ e the sensor values over BM S, first command t he cont roller t o use t he BM Svalue using t he corresponding binary value and t hen use the corresponding analog value t o send t he sensor value.

Sensor Sources

BV-6 Out side_Temp_Source_BM S

Out side Temp Source Select ion

BM S

Local

BV-9 Space_1_CO2_Source_BM S

Space 1 CO2 Source Select ion

BM S

Local

BV-10 Ret urn_CO2_Source_BM S

Ret urn CO2 Source Select ion

BM S

Local

BV-12 Space_St at ic_Source_BM S

Space St at ic Source Select ion

BM S

Local

BV-13 Space_Temp_Source_BM S

Space Temp Source Select ion

BM S

Local

Sensor Values

AV-30 Out side_Temp_from_BM S

Out side Temp from BM S

Real (°F)

AV-33 Space_1_CO2_from_BM S

Space 1 CO2 from BM S

Real (ppm)

AV-34 Ret urn_CO2_from _BM S

Ret urn CO2 fr om BM S

Real (ppm)

AV-36 Space_St at ic_from_BM S

Space St at ic from BM S

Real (" w c)

AV-37 Space_Temp_from_BM S

Space Temp from BM S

Real (°F)

M enu Structure Reference M ain M enu Cont rol Variables Advanced Net work Set tings Advanced Set tings

Advanced BACnet Set tings
Addit ional set tings can be accessed in t he BACnet Advanced Set t ings menu including BACnet Broadcast M anagement Device (BBM D) configuration, relinquish default set t ings, Change of Value (COV) increment s and rest oring binary text values.

BBM D CONFIGURATION

To configure the cont roller t o operate wit h a BACnet Broadcast M anagement Device (BBM D) on IP networks, go t o t he advanced BACnet set t ings menu and ent er t he IP address of t he BBM D, foreign device configurat ion, and t ime t o live set tings.

COV INCREM ENTS

BACnet COV is an opt ional portion of BACnet t hat support s providing new values/ informat ion only aft er an increase or decrease of t he value is at least t he list ed COV increment . The controller's COV increment s are based on t he unit of measure. All variables wit h t he same unit of measure share t he same COV increment value. Values can be adjust ed on t his screen, or by writing t o t he COV increment propert y of any BACnet object .

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 5

RELINQUISH DEFAULT SETTINGS BINARY TEXT

When t he Ret urn t o Default funct ion is enabled, t he present value will not overwrite t he relinquish default value and on a loss of power t he controller will boot wit h last saved default values inst ead of last w rit ten values. This must also be enabled for t he BACnet Comm Loss relinquish default t o w ork.
When t he Enable Relinquish Default funct ion is enabled any value in t he priorit y array for binary values or analog values w ill be cleared if a communicat ion loss is det ect ed. All commandable point s will revert t o t he relinquish default value.
Communication loss is det ermined based on t he BM SWat chdog. The wat chdog funct ion must be enabled. The funct ion will execut e 5 minutes aft er t he wat chdog st at us goes inact ive.
This m ay be desired if t he BM Sis running a reset routine on t he set point s and would like t o revert t o a default st at e if communicat ion is lost. It is recommended t o be used wit h ret urn t o default enabled, and a known relinquish default is saved. When t his box is checked by a user, t he controller will write t he present value of variables t o t he relinquish default for all binary and analog value BACnet object s t hat are comm andable. The funct ion operat es in t he background and t akes approximately 30 seconds t o complet e.
This is desired t o save any Test and Balance set t ings adjust ed locally on t he cont roller t o be t he BACnet r elinquish default values. Alt ernatively, t hese values could be read and writ t en t o t he relinquish default variables by t he BM Ssyst em.
If for any reason, t he st ate text is missing from binary objects, checking t his box will cause the controller t o re-writ e t he act ive and inactive t ext values.

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 6

M UA Reference Tables

STATUS M ODE TABLE
The following analog values can appear in t he point t o t ell the building aut omat ion the current mode of operat ion of the unit . Values may rotat e every t hree seconds.

Analog Value
0 1 2 3 5 6 7 8 9

M ode
Off/ St andby Unoccupied St art Occupied St art Opening Dampers Dampers Open Fan St art Delay Exhaust Fan St art Supply Fan St art St art up Delay

Status M ode Table (AV-41)

Analog Value

M ode

10

Syst em On

11

Soft Shut dow n

12

Syst em Disabled

13

Remot e Of f

14

Syst em Shut down Alarm

18

Unit Of f Flow Act ive

19

Fans Only

20

Eco n o m i zi n g

Analog Value
21 22 30 31 32 33 35 36

M ode
Cooling Heat ing Over r ides Expansion Offline Occupancy Overridden M ax Vent Sequence Act ive M orning Sequence Act ive Wint er Ramp Act ive

ALARM TABLE This table displays the lat est alarm t hat is active in the unit cont roller.

Alarm Table - Latest Alarm (IV-9)

0 No Act ive Alarms

27 IG Furnace 1 Combust Fan High Pressure Sw it ch

1 Supply Fan Run St at us Not Proven

28 IG Furnace 1 Ignit ion Cont roller Alarm

2 Exhaust Fan Run St at us Not Proven

29 IG Furnace 1 Pressure Sw it ch Fault Alarm

3 Filt ers are Dirt y Replace Filt ers

30 IG Furnace 1 Combust Fan Proving Alarm

4 Cond Drain Pan Full Check Drain

31 IG Furnace 1 M ax Retries

5 High Supply Duct St at ic Pressur e

32 IG Furnace 1 High Limit Trip

6 Out side Air Temp Sensor Value Not Valid

33 IG Furnace pCOe 1 Offline

7 Space Temperat ure Sensor Value Not Valid

34 IG Furnace 1 IC Fault Check IC->pCOe Wiring

8 Supply Air Temperat ure Sensor Value Not Valid

35 IG Furnace 1 Combust ion Fan Alarm

9 Out side Air GreenTrol Offline or Flow Error

36 IG Furnace pCOe 2 Offline

10 Hi/ Low Pressure Swit ch Circuit A

37 IG Furnace 2-No Flam e Alarm Aft er 3 Tries

11 Hi/ Low Pressure Swit ch Circuit B

38 IG Furnace 2 M ax Retries

12 Space CO2 Sensor Value Not Valid

39 IG Furnace 2 Ignit ion Cont roller Alarm

13 Ret urn CO2 Sensor Value Not Valid

40 IG Furnace 3-No Flam e Alarm Aft er 3 Tries

14 Space St at ic Pressure Sensor Value Not Valid

41 IG Furnace 3 M ax Retries

15 Supply Duct St at Press Sensor Value Not Valid

42 IG Furnace 3 Ignit ion Cont roller Alarm

16 Supply Air Temperat ure Low Limit Shut down

43 DG Flame Saf eguard General Refer ence

17 Supply Air Temperat ure High Limit Shut down

44 DG Flame Safeguard M anual Reset at FSG

18 Space High St at ic Pres Shut down

45 DG Pilot Flame Alarm Did Not Pr ove

19 BM S Offline Wat chdog is FALSE

46 DG Heat ing Saf ety Check Circuit

20 BACnet License Not Inst alled

47 DG Flame Saf eguard Check Funct ionalit y

21 Space Ther most at 1 Sensor Offline

48 DG Burner Diff erent ial Check Pressure

22 Space Ther most at 2 Sensor Offline

51 M ult i Devices per Ch Cont act Tech Support

23 Space Ther most at 3 Sensor Offline

52 Comp M aint enance Alarm Run Hours Set point Reached

24 Space Ther most at 4 Sensor Offline

54 Non-Volat ile M emory Er Cont act Tech Support

25 IG Furnace 1-No Flam e Alarm Aft er 3 Tries

55 Cooling Exp Boar d pCOe 3 Offline

26 IG Furnace 1 - Large No Flam e Aft er 3 Tries

59 Exp Boar d 4 St at us Board is Offline

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 7

BIT-PACKED INTEGER W ORD TABLES The following t ables are used t o unpack int eger words int o Boolean values.

Bit

Digit al_Out put _W ord

0 Supply Fan St art 1 Exhaust Fan St art 2 Exhaust Relief Enable 3 Compr essor 1 St art

4 Compr essor 2 St art 5 Condenser Fan St art 6 7 Furnace 1 St art 8 Furnace 1 St age 2 St art

9 Furnace 2 St art

10 Furnace 2 St age 2 St art

Digital Output Table (IV-10)

Bit

Digit al_Out put _W ord

Bit

11 Furnace 3 St art

22

12

23

13 Damper Act uat or Power Enable

24

14 Direct Gas St art

25

15 Elect ric Heat St art

26

16 Evaporat ive Cooling Valve Enable

27

17 Evaporat ive Cooling Pump Enable

28

18

29

19

30

20

31

21

Cooling Alarm Table (IV-11)

Bit

Cooling_Alarm_W ord

Bit

Cooling_Alarm_W ord

Bit

0 Circuit A High/ Low Pr essure Swit ch Alarm

11

22

1 Circuit B High/ Low Pr essure Swit ch Alarm

12

23

2

13

24

3

14

25

4

15

26

5

16

27

6

17

28

7

18

29

8

19

30

9

20

31

10

21

Device Offline Table (IV-12)

Bit

Device_Offline_W ord

Bit

Device_Offline_W ord

Bit

0 Space T-St at 1 Offline

11

22

1 Space T-St at 2 Offline

12

23

2 Space T-St at 3 Offline

13

24

3 Space T-St at 4 Offline

14

25

4 IG Furnace Cont roller 1 Offline

15

26

5 IG Furnace Cont roller 2 Offline

16

27

6 Cooling Cont roller Offline

17

28

7 GreenTrol Out side Air Offline

18

29

8 BM S Offline Alarm

19

30

9 Permanent M emory - Too M any Writ es

20

31

10

21

Digit al_Out put _W ord Cooling_Alarm_W ord Device_Offline_W ord

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2

Page | 8

Bit

Device_Alarm _W ord

0 Supply Fan Alarm

1 Exhaust Fan Alarm

2 Drain Pan Alarm

3 Filt er Alarm

4 GreenTrol OAD AFM S Alarm

5 Out side Air Temp Sensor Alarm

6 Space CO2 Sensor Alarm

7 Supply Air Temp Sensor Alarm

8 Space Temperat ure Sensor Alarm

9 Supply Temp Low Limit Alarm

10 Supply Temp High Limit Alarm

Device Alarms Table (IV-13)

Bit

Device_Alarm _W ord

Bit

11 Supply High Duct St at ic Alarm

22

12 Supply Duct St at ic Sensor Alarm

23

13 Space St at ic Pressure Sensor Alarm

24

14 Space High St at ic Alarm

25

15 Ret urn CO2 Sensor Alarm

26

16

27

17 Shut down Input Alarm

28

18

29

19

30

20

31

21

Device_Alarm _W ord

Bit

Heat ing_Alarm _W ord

0 DG Flame Safeguard General Refer ence

1 DG Flame Safeguard M anual Reset at FSG

2 DG Pilot Flame Alarm Did Not Pr ove

3 DG Heat ing Saf ety Check Circuit

4 DG Flame Safeguard Check Funct ionalit y

5 DG Burner Diff erent ial Check Pressure

6 General IG Furnace Alarm

7 IG Furnace 1 No flame Alarm Aft er 3 Tries

8 IG Furnace 1 Large No Flame Aft er 3 Tries

IG Furnace 1 Combust Fan High Pressure

9

Swit ch

10 IG Furnace 1 Ignit ion Cont roller Alarm

Heating Alarm Table (IV-14)

Bit

Heat ing_Alarm _W ord

11 IG Furnace 1 Pressure Sw it ch Fault Alarm 12 IG Furnace 1 Combust Fan Proving Alarm 13 IG Furnace 1 M ax Retries

14 IG Furnace 1 High Limit Trip

15 IG Furnace 1 IC fault Check Furnace Wiring

16 IG Furnace 1 Combust ion Fan Alarm

17 IG Furnace 2-No Flam e Alarm Aft er 3 Tries

18 IG Furnace 2 M ax Retries 19 IG Furnace 2 Ignit ion Cont roller Alarm

20 IG Furnace 3-No Flam e Alarm Aft er 3 Tries

21 IG Furnace 3 M ax Retries

Bit

Heat ing_Alarm _W ord

22 IG Furnace 3 Ignit ion Cont roller Alarm

23

24

25

26

27

28

29

30

31

Bit

Unit _St at us_W ord

0 Off/ St andby

1 Unoccupied St art

2 Occupied St art

3 Opening Dampers 4 Dampers Open 5 Fan St art Delay 6 Exhaust Fan On

7 Supply Fan On

8 Syst em On 9 Soft Shut dow n 10 Syst em Disabled

Unit Status W ord Table (IV-11)

Bit

Unit _St at us_W ord

11 Remot e Of f

12 Syst em Shut down Alarm

13 Supply Fan Only

14 Exhaust Fan Only 15 Purge M ode (Supply and Exhaust Only) 16 Case Heat Act ive 17 Fans Only

18 Economizing

19 Energy Recovery Act ive 20 Cooling 21 Heat ing

Bit

Unit _St at us_W ord

22 Dehumidifying

23 Hot Gas Reheat Act ive

24 HGRH Purging

25 Dehum w/ Heat 26 Energy Recovery Defrost Act ive 27 Heat Pump Defrost Act ive 28 M orning Warm Up/ Cool Down Act ive

29 Wint er Ramp Act ive

30 31 Overrides Act ive

BACnet Int egrat ion Guide ­ M UA_01.001 Rev 2