Huawei Solar Inverter Conformity and Technical Data

Manufacturer: HUAWEI TECHNOLOGIES CO., LTD.

Product Type: SOLAR INVERTER

Models: SUN2000-100KTL-M2, SUN2000-115KTL-M2

Certificate Number: A3 50564049 0001

Report Number: CN224DKW 001

Date of Issue: 04.11.2022

Certificate of Conformity

This document confirms that a sample of the specified technical equipment has been tested and found to be in accordance with relevant requirements.

The verification of conformity refers to the product mentioned above and confirms its compliance with the assessment requirements. This verification does not imply an assessment of the production of the product and does not permit the use of a TÜV Rheinland mark of conformity.

Product Identification and Standards

Manufacturer: HUAWEI TECHNOLOGIES CO., LTD.

Address: Administration Building, Headquarters of Huawei Technologies Co., Ltd. Bantian, Longgang District, Shenzhen, 518129 Guangdong, P.R. China

Type of Product: SOLAR INVERTER

Model Designation: SUN2000-100KTL-M2, SUN2000-115KTL-M2

Firmware Version: V500R023

Software Version: V500R023C00SPC010

Standards Applied:

  • VDE-AR-N 4105:2018-11
  • DIN VDE V 0124-100 (VDE V 0124-100):2020-06

Test Report Summaries

The document includes summaries and data from various test reports:

  • A3 Grid Code Certificate: Confirms compliance with grid code requirements.
  • E.5 Test Report "System Reactions" for power generation units with feeding current: Details network reaction tests, including rapid voltage changes and flicker.
  • E.6 Certificate of NS protection: Confirms compliance with national protection (NA-Schutz) requirements.
  • E.7 Requirements for the test report for NS protection: Outlines specific protection settings tested, such as overvoltage, undervoltage, and frequency protection.

Technical Data: Network Reaction (E.5)

This section details the system's reaction to network disturbances, including rapid voltage changes and flicker, as well as harmonic emissions.

Rapid Voltage Changes (System Reactions)

The following table shows the system's reaction (represented by 'ki' values) to different voltage change scenarios:

ScenarioModel: SUN2000-100KTL-M2Model: SUN2000-115KTL-M2
Einschalten ohne Vorgabe (zum Primärenergieträger) / Marking operation without default (to primary energy carrier)ki= 1.003ki= 1.106
Einschalten bei Nennbedingungen (des primärenergieträger) / Marking operation at reference conditions (of primary energy carrier)ki= 1.106ki= 1.054
Ausschalten bei Nennleistung / Breaking operation at nominal powerki= 1.054kimax= 1.106
Schlechtester Wert aller Schaltvorgänge / Worst case value of all switching operationskimax= 1.106

Flicker

The following table shows the flicker coefficient (CY) of the system at different network impedance angles (Ψk):

Netzimpedanzwinkel Ψk / Angle of network impedance Ψk30°50°70°85°
Anlagenflickerbeiwert CV / System flicker coefficient CY0.0200.0150.0200.005

Harmonics (Model: SUN2000-115KTL-M2)

The following table details the harmonic current emissions (Iv/In [%]) at various active power levels (P/Pn [%]):

Harmonic numberP/Pn [%]0%10%20%30%40%50%60%70%80%90%100%
1Iv/In [%]0.5600.1860.1090.1210.1450.1390.1200.1140.1150.1260.124
2Iv/In [%]0.6880.1440.0540.0790.1370.0990.1530.1190.1500.1070.101
3Iv/In [%]1.3280.2900.1380.1010.0840.0770.0630.0700.0510.0320.029
4Iv/In [%]0.8340.1850.2030.1390.1810.1120.3310.1840.1180.2750.444
5Iv/In [%]1.1940.2900.1340.0860.0780.0690.0530.0680.0600.0460.048
6Iv/In [%]0.8560.2060.2000.1250.1690.1550.2340.1000.1330.2420.453
7Iv/In [%]0.7960.1850.0860.0560.0460.0360.0280.0190.0250.0260.021
8Iv/In [%]0.4670.0830.0410.0280.0640.1110.0530.0600.0330.0350.066
9Iv/In [%]0.2580.0670.0350.0220.0180.0220.0160.0150.0140.0150.023
10Iv/In [%]0.4290.1100.0630.0810.0990.1290.1340.0860.0770.2050.104
11Iv/In [%]0.2490.0710.0280.0200.0150.0160.0170.0170.0170.0190.013
12Iv/In [%]0.3290.0820.0480.0530.0470.1260.1240.0770.0660.1280.144
13Iv/In [%]0.3980.0830.0410.0270.0250.0260.0200.0220.0140.0160.020
14Iv/In [%]0.6280.0830.0530.0250.0350.0640.0620.0340.0420.0370.037
15Iv/In [%]0.2880.0640.0330.0190.0150.0160.0130.0110.0100.0120.015
16Iv/In [%]0.6550.1340.1110.1380.1480.1810.2100.1440.1160.1190.147
17Iv/In [%]0.2750.0630.0260.0180.0160.0150.0120.0120.0120.0130.010
18Iv/In [%]0.3520.0820.0830.0950.1110.1060.1410.1070.1080.1260.164
19Iv/In [%]0.2380.0500.0250.0200.0170.0160.0140.0120.0130.0120.012
20Iv/In [%]0.6530.0970.0610.0500.0860.0680.0750.0480.0680.0700.065
21Iv/In [%]0.2980.0640.0300.0400.0260.0240.0150.0140.0110.0130.013
22Iv/In [%]0.7230.0940.0790.0990.1510.1700.1730.1590.1290.1080.158
23Iv/In [%]0.3070.0700.0400.0470.0340.0300.0230.0220.0160.0170.010
24Iv/In [%]0.1780.1720.2100.1910.1570.1720.2100.1910.1570.1720.210
25Iv/In [%]0.2640.0610.0310.0210.0160.0150.0190.0150.0140.0120.012
26Iv/In [%]0.6670.1580.0850.0920.1230.2330.2180.2370.2340.2000.160
27Iv/In [%]0.6630.1580.0850.0920.1230.2330.2180.2370.2340.2000.160
28Iv/In [%]0.6670.1550.0420.0220.0160.0150.0120.0130.0150.0210.018
29Iv/In [%]0.9590.1740.0740.0920.1350.2030.1720.1670.1480.1510.186
30Iv/In [%]0.2820.0760.0320.0220.0170.0160.0140.0140.0170.0200.020
31Iv/In [%]0.6630.1580.0850.0920.1230.2330.2180.2370.2340.2000.160
32Iv/In [%]0.2640.0610.0310.0210.0160.0150.0190.0150.0140.0120.012
33Iv/In [%]1.2680.2100.0940.0420.0510.0580.0750.0930.0750.0710.097
34Iv/In [%]0.2660.0590.0300.0200.0180.0140.0130.0130.0170.012
35Iv/In [%]1.2190.1490.0550.0820.1350.1760.1780.1820.1590.1730.204
36Iv/In [%]0.2680.0620.0280.0200.0180.0160.0140.0160.0160.0210.017
37Iv/In [%]0.6480.2490.0920.0840.1400.2190.2080.2230.2330.1940.136
38Iv/In [%]0.2530.0630.0270.0180.0160.0160.0150.0170.0160.0180.021
39Iv/In [%]1.3110.3140.1830.0880.0370.0260.0650.0740.0660.0580.068
40Iv/In [%]0.3640.0860.0350.0200.0150.0160.0140.0150.0200.0270.022

Remark: The maximal value of three phases is selected.

Technical Data: NS Protection (E.6 & E.7)

This section details the requirements and settings for the Network Protection (NA-Schutz) of the solar inverters.

Network Connection Rule: VDE-AR-N 4105: 2018-11 "Erzeugungsanlagen am Niederspannungsnetz" (Requirements for connection and parallel operation of generation plants at the low-voltage grid)

Test Requirement: DIN VDE V 0124-100 (VDE V 0124-100):2020-06 "Netzintegration von Erzeugungsanlagen - Niederspannung" (Test requirements for generation plants intended for connection and parallel operation at the low-voltage grid)

Protection Settings

The following table outlines the tested protection settings for voltage and frequency:

Protection FunctionSettingResponse ValueResponse TimeModel: SUN2000-100KTL-M2Model: SUN2000-115KTL-M2
Spannungsschutz (Überspannungsschutz) / Voltage protection (Overvoltage protection)Einschleusen / Connect1.15 * Un< 100ms1.15 * Un280.4 V< 100ms
Ausschleusen / Disconnect1.25 * Un< 100ms1.1 * Un253.0 V< 100ms
Spannungsschutz (Unterspannungsschutz) / Voltage protection (Undervoltage protection)Einschleusen / Connect0.8 * Un< 100ms0.8 * Un184.8 V< 100ms
Ausschleusen / Disconnect0.7 * Un< 100ms0.7 * Un160.6 V< 100ms
Frequenzschutz (Oberfrequenzschutz) / Frequency protection (Overfrequency protection)Ausschleusen / Disconnect51.5 Hz< 100ms51.5 Hz51.5 Hz< 100ms
Frequenzschutz (Unterfrequenzschutz) / Frequency protection (Underfrequency protection)Ausschleusen / Disconnect47.5 Hz< 100ms47.5 Hz47.5 Hz< 100ms

Note: The test results are based on the time frame of the grid connection rule and refer to the connection and parallel operation of generation plants at the low-voltage grid.

Type NA-Schutz / Type of NS protection: Integrated NS protection (Zugeordnet zu Erzeugungseinheit Typ / Assigned to power generation unit of type: SUN2000-100KTL-M2, SUN2000-115KTL-M2)

Manufacturer of Integrated NS Protection: Xiamen Hengjia Electronic Co., Ltd.

Accreditation and Certification Bodies

The tests and certifications were performed by TÜV Rheinland, an accredited testing and certification body. The accreditation is confirmed by DAkkS (Deutsche Akkreditierungsstelle) under the number D-ZE-14169-01-02.

Certification Body: TÜV Rheinland LGA Products GmbH, Tillystraße 2, 90431 Nürnberg, Germany.

PDF preview unavailable. Download the PDF instead.

media.nl?id=13735036&c=6376560&h=zpmJDWVIEqrEVuMwxYMiMvXqgfZ86eW4lkQAWdN5LaqM49Ud& xt= SZ-LXD-16F-PUB-KMC558 KONICA MINOLTA bizhub C558

Related Documents

Preview Huawei SUN2000 Solar Inverter Technical Reports and Certificates of Conformity
Technical reports and certificates of conformity for Huawei's SUN2000-100KTL-M2 and SUN2000-115KTL-M2 solar inverters, detailing specifications, testing, and compliance with international standards.
Preview Certificate of Conformity for Huawei SUN2000 Series PV Inverters
This document certifies the conformity of Huawei SUN2000 series photovoltaic inverters with technical requirements established in the Norma Técnica de Supervisión (NTS) for electricity generation modules.
Preview Huawei SUN2000 Series Photovoltaic Inverter Certificate of Conformity and Technical Specifications
This document presents the Certificate of Conformity and detailed technical specifications for Huawei SUN2000 series photovoltaic inverters, including models SUN2000-60KTL-M0, SUN2000-100KTL-M1, SUN2000-100KTL-M2, SUN2000-115KTL-M2, and SUN2000-150K-MG0, certified by CERE (Certification Entity for Renewable Energies S.L.). It outlines compliance with technical requirements and provides performance data.
Preview Huawei SUN2000-(100KTL, 110KTL, 115KTL)-M2 User Manual
Comprehensive user manual for the Huawei SUN2000 series solar inverters (100KTL, 110KTL, 115KTL-M2). Covers installation, electrical connections, commissioning, maintenance, troubleshooting, and technical specifications.
Preview Huawei SUN2000-(100KTL, 110KTL, 115KTL)-M2 User Manual
Comprehensive user manual for Huawei SUN2000 series solar inverters (100KTL, 110KTL, 115KTL-M2), covering installation, electrical connections, commissioning, maintenance, and troubleshooting for photovoltaic plant personnel and electricians.
Preview Huawei SUN2000 Inverter Quick Guide: Installation and Operation
A comprehensive quick guide for installing and operating the Huawei SUN2000 series solar inverters, including models SUN2000-100KTL, SUN2000-110KTL, and SUN2000-115KTL-M2. This guide covers essential installation requirements, cable connections, and system powering procedures.
Preview Red Eléctrica Confirmation: Huawei SUN2000-100KTL-M2 MPE Model Validation
Red Eléctrica acknowledges receipt and confirms the validation of Electrical Module (MPE) modeling using Huawei SUN2000-100KTL-M2 series converters, in accordance with Procedimiento de Operación 9 and P.O.12.2 SENP.
Preview Huawei SUN2000 Inverter Maximum Input Power per MPPT
This document details the maximum input power (Pmpp,max) for various Huawei SUN2000 inverter models, crucial for optimizing PV string utilization and preventing power clipping.