Emerson 1F83H-21PR Programmable Heat Pump Thermostat

This document provides installation and operating instructions for the Emerson 1F83H-21PR 80 Series Programmable Heat Pump Thermostat.

Specifications

Electrical Rating

Battery Power20 to 30 VAC, NEC Class II, 50/60 Hz
Input-Hardwire20 to 30 VAC, NEC Class II, 50/60 Hz
Terminal Load1.5 A per terminal, 2.5A maximum all terminals combined

General Specifications

Setpoint Range45° to 99° F (7° to 37° C)
Rated Differentials (@ 6°F/ Hr)
FastMedSlow
Heat Pump (Heat)0.9°F1.2°F1.7°F
Heat Pump (Cool)0.9°F1.2°F1.7°F
Auxiliary Heat0.5°F0.75°F1.9°F
Operating Ambient32°F to +105°F (0° to +41°C)
Display Temperature Range32°F to +99°F (0 to 37°C)
Operating Humidity90% non-condensing maximum
Shipping Temperature Range-20°F to +150°F (-29° to +65°C)
Thermostat Dimensions3-3/4” H x 6” W x 1-1/8” D

Optional Accessory: Wall Cover-Up Plate F61-2663, 6 3/4” W x 4 1/2” H

Thermostat Installation

Wiring

Refer to equipment manufacturer’s instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. The wiring table below shows typical systems and describes the thermostat terminal functions.

Terminal DesignationsTerminal Function
RPower (24V)
O/BChangeover Terminal-Energized in Cool (O) or Heat (B) for Heat Pump or Damper Systems
YHeat and Cool Mode 1st Stage Compressor
GFan Relay
E*Auxiliary only Heat Mode (Emergency Heat)
CCommon wire for 24V (optional with batteries)
LHeat Pump malfunction / Diagnostic terminal (input signal requires common)
W2*Heat Mode – 2nd stage

*Cut W2/E jumper when separate heat sources are used for W2 and E.

IMPORTANT: For Dual Fuel Heat Pump applications, be sure to turn on the Duel Fuel Logic option (found in the Installer’s Menu).

Leveling Thermostat: Leveling is for appearance only and will not affect thermostat operation.

Precautions

WARNING: Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will burn out thermostat and could cause personal injury and/or property damage.

CAUTION: To prevent electrical shock and/or equipment damage, disconnect electrical power to system, at main fuse or circuit breaker box, until installation is complete.

Battery Location

Premium AA alkaline batteries are required when a C-wire is not available. When a C-wire is available, the batteries provide a back-up source of power, which will maintain the clock in the event of a power outage.

W2/E Jumper Wire

This thermostat electrically connects the W2 and E terminals, eliminating the need for a jumper wire. If your system has separate W2 and E wires, clip the W2/E jumper located on the back of the thermostat to isolate both terminals for independent use.

O/B Terminal Switch

The O/B switch is factory set to the 'O' position, accommodating most heat pump applications that require the changeover relay to energize in Cool. If your heat pump requires the 'B' terminal to energize the changeover relay in Heat, move the O/B switch to the 'B' position.

Installer Menu

The Installer Menu provides access to all system performance options, while the User Menu offers access to settings that do not affect system performance. To access the Installer Menu, press and hold the Menu button for 8 seconds. The display will show item 30. Use the Next and Back buttons to navigate through menu items. Press the ▲ or ▼ buttons to change a setting.

Installer's Menu # (Hold Menu 8 Seconds)DescriptionDefault Setting (flashing icons)Settings (Press ▲ or ▼)
30Heat Cycle Rate (how often the heat will turn on)MEdSLO – slow, MEd – medium, FAS – fast
32Aux Cycle Rate (how often the auxiliary heat will turn on)MEdSLO – slow, MEd – medium, FAS – fast
35Cool Cycle Rate (how often the cooling will turn on)MEdSLO – slow, MEd – medium, FAS – fast
50Compressor Lockout (protects the compressor from short cycling)OFFOn – 5 minute delay, OFF – no delay
60Duel Fuel Logic (turn On when using gas as the auxiliary heat source)OFFOn - gas auxiliary heat, OFF - electric auxiliary heat
65Maximum Heat Limit (maximum set point for heat mode)9947 to 99
66Minimum Cool Limit (minimum set point for cool mode)4545 to 97
74Schedule Type (set as either 7-Day, 5-1-1 Day or Non-Programmable)57 – 7 Day, 5 – 5-1-1 Day, 0 – Non Programmable
76Early Start (starts heating or cooling early so your programmed temperature is reached by the programmed time)OFFOn – start early, OFF – start at program period time
79Fahrenheit or Celsius°F°F – Fahrenheit, °C – Celsius
81Temperature Display Adjustment (adjust the displayed “Room Temperature”)0-5 to +5
83Continuous Display Light (keep the backlight always on – “C” wire required)OFFOn – always on, OFF – momentarily
86Change Air Filter (set up a monthly reminder)OFF1 to 12 – reminder time (months), OFF – no filter reminder
99Keypad Lock (prevent unwanted changes to the thermostat)OFFOn – disable buttons, OFF – all buttons are active

Test Equipment

Turn on power to the system.

Fan Operation

If your system does not have a G terminal connection, skip to Heating System.

  1. Move fan switch to On position. The blower should begin to operate.
  2. Move fan switch to Auto position. The blower should stop immediately.

Heating System

  1. Move System Switch to Heat position. If the auxiliary heating system has a standing pilot, be sure to light it.
  2. Press ▲ to adjust thermostat setting to 1° above room temperature. The heat pump system should begin to operate and the thermostat will indicate Heat On.
  3. Press ▲ to adjust thermostat setting to 3° above room temperature. The auxiliary heat should begin to operate and the thermostat will indicate Heat On Auxiliary.
  4. Press ▼ to adjust thermostat setting 1° below room temperature. The heating system should stop operating and the thermostat should indicate Heat.

Auxiliary System

  1. Move System Switch to Aux position. If the auxiliary heating system has a standing pilot, be sure to light it.
  2. Press ▲ to adjust thermostat setting to 1° above room temperature. The auxiliary heating system should begin to operate and the thermostat will indicate Heat On Auxiliary.
  3. Press ▼ to adjust thermostat setting 1° below room temperature. The auxiliary heating system should stop operating and the thermostat should indicate Heat Auxiliary.

Cooling System

  1. Move System Switch to Cool position.
  2. Press ▼ to adjust thermostat setting 1° below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay (see INSTALLER MENU, item 50).
  3. Press ▲ to adjust thermostat setting to 1° above room temperature. The cooling system should stop operating and the thermostat will indicate Cool.

Note: If "Starting Soon" is shown on the display, the compressor lockout feature is operating. There will be up to a 5 minute delay before the compressor turns on (see INSTALLER MENU, item 50).

CAUTION: To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system. Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.

Using the Thermostat

Thermostat Overview

Before using your thermostat, familiarize yourself with its features, display, and the location/operation of the thermostat buttons and switches.

Thermostat Buttons and Switches

The Display

Image Description: The thermostat's front panel layout is illustrated with numbered components: 1. Fan Switch, 2. System Switch, 3. Backlight Button, 4. Set Correct Time button, 5. Hold a Permanent Temperature button, 6. Cancels Hold button, 7. Raises Temperature Setting button, 8. Access Menu Options button, 9. Lowers Temperature Setting button. The display area is labeled with: 10. Short cycling protection indicator, 11. System mode indicator (Heat, Cool, Aux), 12. Current time display, 13. Battery status indicator, 14. Low battery indicator, 15. Day of the week indicator, 16. Permanent hold indicator, 17. Temperature setpoint display. Navigation buttons are labeled: 19. Next, 21. Back, 22. Exit. Button 20 is for accessing schedule and features. 23. Troubleshooting reference.

Whenever "Replace" appears in the display, new premium brand AA alkaline batteries should be installed. If the house will be unoccupied for an extended period and either " ? " or "Replace" is displayed, install new batteries before leaving.

User Menu

To customize thermostat settings, press the Menu button from the home screen. Use the ▲ or ▼ buttons to highlight Settings and press Next. Use Next and Back to navigate through menu items. Press ▲ or ▼ to change the setting.

User's Menu # (Press Menu button and release)DescriptionDefault Setting (flashing icons)Settings (Press ▲ or ▼)
01Schedule Type (set as either 7-Day, 5-1-1 Day or Non Programmable)57 – 7 Day, 5 – 5-1-1 Day, 0 – Non Programmable
02Early Start (starts heating or cooling early so your programmed temperature is reached by the programmed time)OFFOn – start early, OFF – start at program period time
03Fahrenheit or Celsius°F°F – Fahrenheit, °C – Celsius
04Temperature Display Adjustment (adjust the Room Temperature)0-5 to +5
05Continuous Display Light (keep the backlight always on – “C” wire required)OFFOn – always on, OFF – momentarily
06Change Air Filter (set up a monthly reminder)OFF1 to 12 – reminder time (months), OFF – no filter reminder
07Keypad Lock (prevent unwanted changes to the thermostat)OFFOn – disable buttons, OFF – all buttons are active

Thermostat Operation

Set Current Time and Day

Note: Time icons will flash at initial power up or after a reset.

  1. Press Set Time.
  2. Use ▲ or ▼ to adjust the hour.
  3. Press Next to advance to set the minutes and day of the week.
  4. Press Exit when finished.

The default program is 5-1-1 Day, but can be set up as a 7-Day or Non-Programmable thermostat (refer to the User Menu above).

Thermostat Schedule

Energy Saving Factory Schedule

This thermostat is programmed with the energy saving settings shown in the table below for all days of the week.

WakeLeaveReturnSleep
Heating Schedule6:00 AM - 70°F8:00 AM - 62°F5:00 PM - 70°F10:00 PM - 62°F
Cooling Schedule6:00 AM - 75°F8:00 AM - 83°F5:00 PM - 75°F10:00 PM - 78°F

Note: Thermostat can be programmed on or off the subbase.

Modify the Heating Schedule

  1. Slide the system switch to Heat.
  2. Press Menu.
  3. Press Next to enter the schedule.
  4. The time icons will flash – use ▲ or ▼ to set the time for the start of a period.
  5. Press Next – the set point icons will flash – use ▲ or ▼ to set the temperature for the current period.
  6. Continue to press Next to advance through all periods (Wake, Leave, Return, Sleep) for all days of the week.

Note: Press Back to return to the previous setting. Once all days of the week have been programmed, the thermostat will display "End". Press Exit at any time to save changes and return to the home screen.

Modify the Cooling Schedule

  1. Slide the system switch to Cool.
  2. Repeat steps 2-6 from the heating schedule.

Troubleshooting

SymptomPossible CauseCorrective Action
No Heat/
No Cool/
No Fan
(common problem)
1.) Blown fuse or tripped circuit breaker 1.) Replace fuse or reset breaker.
2.) Furnace power switch to OFF2.) Turn switch to ON.
3.) Furnace blower compartment door panel loose or not properly installed3.) Replace door panel in proper position to engage safety interlock or door switch.
4.) Loose connection to thermostat or system4.) Tighten Connections.
No Heat 1.) System Switch not set to Heat Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within five minutes, the thermostat should make a soft click sound and "Heat On" should appear on the display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.
2.) Loose connection to thermostat or systemVerify thermostat and system wires are securely attached.
3.) Heating System requires service or thermostat requires replacementSee diagnostic steps above.
No Cool 1.) System Switch not set to Cool Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same procedures as diagnostic for "No Heat" condition, except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu (see INSTALLER MENU, item 50).
2.) Loose connection to thermostat or systemVerify thermostat and system wires are securely attached.
3.) Cooling System requires service or thermostat requires replacementSee diagnostic steps above.
Heat, Cool or Fan Runs Constantly Possible short in wiring, thermostat, heat, cool, or fan system. Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists, contact your HVAC service person.
Thermostat Display & Thermometer Disagree Thermostat display requires adjustment. Display can be adjusted +/-5°. See User Menu item 04.
Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing) The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently, but runs for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu (Reference menu items 30 & 35). If an acceptable cycle rate is not achieved, contact your HVAC service person.
"Call for Service" icon appears on display 1.) Heating system is not able to heat the space to within 10 degrees of the setpoint within 2 hours.
2.) Cooling system is not able to cool the space to within 10 degrees of the setpoint within 2 hours.
3.) If "--" is displayed for the Room Temperature, a replacement thermostat is needed.
4.) None of the buttons operate on the thermostat.
5.) If "Call for Service" is flashing, compressor self-diagnostic is detecting an issue with the outdoor unit.
1.) See corrective action for "No Heat".
2.) See corrective action for "No Cool".
3.) Replace thermostat.
4.) Make sure keypad lockout is not turned on (denoted by ?).
5.) Contact a service person to verify the equipment is operating correctly.

Resetting the Thermostat or Thermostat Settings

If the thermostat has good batteries but has a blank display or does not respond to key presses, reset it by removing the batteries for 2 minutes. This reset will not change menu settings or programs. If the condition persists after reinstalling the batteries, replace the thermostat.

To conveniently reset only the schedule and user settings back to factory defaults, press the Menu and Backlight buttons simultaneously and hold until the display goes blank and resets.

HOMEOWNER HELP LINE: 1-800-284-2925

White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co.

Visit us at: www.white-rodgers.com | www.emersonclimate.com

Models: 1F83H-21PR, 80 Series Heat Pump Thermostat

File Info : application/pdf, 4 Pages, 1.06MB

PDF preview unavailable. Download the PDF instead.

A1a6R1a4OqL Adobe InDesign CC 2015 (Macintosh) Adobe PDF Library 15.0

Related Documents

Preview Emerson 1F83H-21PR Programmable Heat Pump Thermostat Installation and Operation Guide
Comprehensive guide for installing and operating the Emerson 1F83H-21PR programmable heat pump thermostat. Covers wiring, installer menu, user menu, thermostat operation, scheduling, and troubleshooting.
Preview Emerson 1F85U-22NP Universal Thermostat Installation and Operating Instructions
Comprehensive guide for installing and operating the Emerson 1F85U-22NP Universal Thermostat. Covers setup, features, troubleshooting, and specifications for optimal home climate control.
Preview Emerson 1F75H-21NP Heat Pump Thermostat Installation and Operation
Comprehensive installation and operating instructions for the Emerson 1F75H-21NP Non-Programmable Heat Pump Thermostat. Covers wiring, installer menu settings, system testing, and troubleshooting.
Preview Emerson 1F75H-211PR Programmable Heat Pump Thermostat Installation and Operation Guide
Comprehensive installation and operating instructions for the Emerson 1F75H-211PR programmable thermostat, designed for heat pump systems. Learn about wiring, installer menu settings, thermostat operation, programming, and troubleshooting.
Preview Emerson 1F83C-11NP Thermostat Installation and Operation Guide
Comprehensive guide for installing and operating the Emerson 1F83C-11NP single-stage thermostat. Covers wiring, thermostat applications, installer and user menus, troubleshooting, and specifications.
Preview Emerson 1F85U-42PR Programmable Thermostat Installation and Operation Guide
Comprehensive guide for installing and operating the Emerson 1F85U-42PR programmable thermostat. Covers wiring, installer menu, user settings, scheduling, and troubleshooting for efficient home climate control.
Preview Emerson Blue Easy Set 1F89EZ-0251 Thermostat Installation and User Guide
Comprehensive guide for installing and using the Emerson Blue Easy Set 1F89EZ-0251 non-programmable thermostat. Learn about its features, pre-set temperatures, installation steps, and troubleshooting.
Preview Emerson 1F75P-21NP PTAC Thermostat Installation and Operating Instructions
Comprehensive guide for installing and operating the Emerson 1F75P-21NP Non-Programmable PTAC Thermostat. Learn about wiring, configuration, features, and troubleshooting.