69-2576
Wiring Configuration

ADVANCED MODELS (HE150/HE250/HE300)

INSTALLATION ADDENDUM

G OR W
2
C
HumidiPRO

C

R

U

U

S

OUTDOOR

S

SENSOR

AIR PROVING DEVICE
1
POWER IN

LEFT LEFT
1 HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN. HE300 USES A LINE CORD PLUG.
CONNECT G TO HUMIDIFY WHEN THERE IS A FAN CALL. 2 CONNECT W TO HUMIDIFY WHEN THERE IS A HEAT CALL.
NEVER CONNECT BOTH. CONNECT C WHEN USING G OR W. M35152
Fig. 1. Wiring HumidiPRO (H6062) to humidify only with a call for Heat or Fan.

FROM HUMIDITY CONTROL

1
POWER IN

RIGHT LEFT
1 HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN. HE300 USES A LINE CORD PLUG. M35153
Fig. 2. Wiring TrueIAQ, VisionPRO IAQ, or Prestige, using the intelligent control to program humidity calls with heat, cool, or on demand.

69-2576-06

WIRING CONFIGURATION

1 G (THERMOSTAT)

R G (FURNACE)

HumidiPRO

C

R

U

U

S

OUTDOOR

S

SENSOR

2
POWER IN

RIGHT RIGHT
1 ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G. IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION AND ROUTE THROUGH HUMIDIFIER AS SHOWN.
2 HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN. HE300 USES A LINE CORD PLUG. M35154
Fig. 3. Wiring to force the HVAC system fan on whenever humidity is needed (on demand).

1 G (THERMOSTAT) HumidiPRO

R

C R

U

U

G (FURNACE)

S

OUTDOOR

S

SENSOR

AIR PROVING DEVICE
2 POWER IN

LEFT RIGHT

1 ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G. IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION AND ROUTE THROUGH HUMIDIFIER AS SHOWN.

2 HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN.

HE300 USES A LINE CORD PLUG.

M35155

Fig. 4. Wiring to force fan on and prove airflow in the duct.

69-2576--06

2

BASIC MODELS (HE100/HE200)

WIRING CONFIGURATION
H8908 HUM/U WIRE
HUM/U WIRE

M24734
Fig. 5. Wiring connections on the H8908 humidistat.

HUMIDIFIER

OTHER WIRE(S) TO HVAC/FAN WHEN NECESSARY

M35804

Fig. 6. Wiring H8908 humidistat.

FAN CONTROL

L1 (HOT)
POWER SUPPLY
L2 1

FURNACE FAN MOTOR

TRANSFORMER

C 24V CONSTANT R REQUIRED U U S OUTDOOR SENSOR S
2
HUMIDIFIER

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 24 VAC WIRING.
Fig. 7. Wiring HumidiPRO with fan interlock.

M34570A

3

69-2576--06

WIRING CONFIGURATION

L1 (HOT)
POWER SUPPLY
L2 1

FAN CONTROL TRANSFORMER
2 DPST SWITCHING RELAY

C 24V CONSTANT R REQUIRED U U S OUTDOOR SENSOR S
HUMIDIFIER

HL C

2-SPEED FAN MOTOR

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 24 VAC WIRING.

M34571A

Fig. 8. Wiring HumidiPRO with 2-speed fan motor.

C 24V CONSTANT R REQUIRED U U S OUTDOOR SENSOR S

AIR PRESSURE SWITCH/SAIL SWITCH

C 24V CONSTANT R REQUIRED
U
U
S OUTDOOR SENSOR S

CURRENT SENSING RELAY

LO

C

HI

L2 L1 1 (HOT)

HUMIDIFIER

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M34572A

Fig. 9. Wiring HumidiPRO with current sensing relay.

L2 L1 1 (HOT)
HUMIDIFIER 1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M34573A
Fig. 10. Wiring HumidiPRO with air proving device.