Instruction Manual for DELTA models including: Magic Cube LFP Battery System, Magic, Cube LFP Battery System, LFP Battery System, Battery System, System

magic cube leaflet EN 20240301

[PDF] LFP Battery System / Magic Cube - Delta Electronicsfilecenter.deltaww.com › download

LFP Battery System / Magic Cube

16 apr 2024 — Delta's Magic Cube battery system is designed for grid-scale and medium to large-scale industrial energy storage applications. Built.6 pagine

[PDF] LFP Battery System / Magic Cube - Delta Electronics

Magic Cube battery system is high energy density, offering scalability from 708 kWh to 7.7 MWh. This flexibility allows it to accommodate varying spatial and ...


File Info : application/pdf, 6 Pages, 4.34MB

PDF preview unavailable. Download the PDF instead.

Products-202404161937218538
Energy Storage System Solution
LFP Battery System / Magic Cube
 Rotational design of standard 10ft shipping container for easy transportation and installation  Built-in fire protection system and meeting UL 9540A safety test standard  Battery system with built-in site controllers, offering flexible scalability from 708kWh to 7.7MWh

Ancillary Services

Solar-Plus Storage

Energy-Heavy Industries

Microgrids

Fully-Integrated Battery Solutions
Redefining Safety and Performance with Effortless Installation, Remarkable Scalability, and Integrated Fire Protection System

Delta's Magic Cube battery system is designed for grid-scale and medium to large-scale industrial energy storage applications. Built on a standard 10ft shipping container with unique designs and simple installation procedure, the battery system can be rapidly deployed. Magic Cube battery system is high energy density, offering scalability from 708 kWh to 7.7 MWh. This flexibility allows it to accommodate varying spatial and capacity requirements for different sites, optimizing land utilization. In addition, Magic Cube

features a redundant communication support for the field site with built-in site controllers, enhancing the communication stability of the energy storage system. It also incorporates several environmental sensors and a fire protection system to ensure the safety of the energy storage system.

Features

High Energy Density with Flexible Scalability Configuration
High energy density, effectively utilizing land resources Flexible configuration ranging from 708 kWh to 7.7 MWh battery capacity

Built-in Fire Protection System Enhancing Inherent Safety
Real-time cell monitoring: temperature, voltage, and current of each cell
Dual-redundant environmental sensors: smoke, temperature, humidity, hazardous gas, and flood
Fire protection system: detection system, off-gas ventilation system, aerosol and fire sprinkler system

Easy Transportation and Installation

Integrated Control and Monitoring

Whole-container transport without the need to dismantle battery modules
Rotational design of standard 10ft shipping container
Containers connected by flexible duct connectors on the top, tolerating positioning errors and reducing on-site installation time

Built-in site controllers seamlessly integrating battery and PCS without the need for additional space
Built-in Human-Machine Interface (HMI): on-site access to real-time field information
Dual-redundant communication: enhancement of communication stability and monitoring efficiency

Product Configuration and Design

Battery System Battery Zone

Container Connector
· Flexible duct connector design for flexible installation · Quick installation of busbars, auxiliary power cables
and communication cables

Embedded HVAC
· Built-in air conditioner for better heat management · Cooler installation is not required, saving both space and cost

Battery Container

Quick Wiring Design
· Onsite work can be performed without opening containers to avoid the risk of exposure to water vapor and foreign particles
· Simplified wiring allows for shorter work duration, allowing for shorter work duration

AIO (All-In-One) Container
Auxiliary Power and Control Zone DC Power Distribution Zone

Reinforced Storage Container
· Three-layer structure composed of double steel plate and fireproof rock wool boards (fire retardant up to 60 minutes)
· Cables and wires in accordance with IEC 6033
· IEEE 693 Recommended Practice for Seismic Design of Substations
· Corrosion protection in ISO 12944 C5M (Optional for C5H enclosure)
· Access control for vandalism prevention

Battery Container

1.4 MWh Battery Container

Redundancy Detection System
· Smoke detectors · Hazardous gas detectors · Temperature sensors · Door sensors · Flood detectors · Humidity sensors
Battery Module Protetcion
· Real-time monitoring of each battery cell · Big data for aging/abnormality detection · Insulation design of battery module · Built-in fuse · Cell balancing mechanism

Fire Safety Protection
· Off-gas ventilation system · Aerosol · Fire sprinkler system · Fire alarm horn & strobe
Safety Certification
· UL 9540A · UL 1973 · IEC 62619 include fire propagation · UN38.3 · IEC 60730

Software Interface
Human Machine Interface (HMI)
Easy Commissioning On-site view of real-time information on the battery system
Real-time Monitoring Operation information, environment status, UPS status, warnings, and battery information (ex. SOC, SOH, voltage, current, temperature), etc
Convenient Maintenance Service mode option enables technicians to maintain the battery system easily

Battery Management System (BMS)
Clear Overview of Battery Status Intuitive UI for real-time display of battery string parameters
Quick Diagnosis and Debugging Easy access to error codes, database, daily logs, and entry records

System Overview Battery Analysis Reports

Specifications ­ Battery System

Model Name
Battery System Specification Battery Cell DC Voltage Range Per String Configuration Per String Modules Installed Capacity DC Usable Capacity Rated Power Max. Charging/Discharge Current Recommend DoD Aux. Power Environment Environment Condition Altitude Operating Temperature Environment Humidity Storage Temperature Ingress Protection Corrosion Resistance Container Standard Seismic Level Monitoring & Operating Measurement Accuracy HMI BMS Log BMS Power Backup Time Calibration Safety Protection Fire Safety Equipment Detection Sensor (Per Container) Mechanical Information Dimension (W x D x H) Weight

EBSU-CE2818S22P00 Battery System (6 Containers with 22 Strings Battery) LFP 280Ah Cell 1069 ­1400 Vdc 396S-1P 18 Modules 7788 kWh 6666 kWh 3333 kW @0.5CP 3080A 90% 220/380 Vac (3P4W) +/-5% (source: OVC II)

EBSB-CE2818S4P00 Battery Container with 4 Strings Battery
1416 kWh 1212 kWh 606 kW @0.5CP

Outdoor < 2000m -30 to +50 0 ­ 100 % RH (No condensing) 1 month: -20 ~ +45, <70% RH humidity; 1 year: 0 ~ +35, <70% RH humidity IP54; Type 3R, NEMA 3R compliance Comply with Severity-1 (IEC 60068-2-52); Pass 720-hour salt mist test (ISO 9227), ISO 12944 Level C5M ISO 668 IEEE 693 (Tai-power, 0.5G, 2% damping)

Voltage: ± 0.5% ; Current: ± 1% ; Temperature: ± 2 ; SOC: Ù5% Display of the information on the battery system 90 days UPS power backup for 60 minutes Built-in NTP server

Off-gas ventilation system, aerosol and fire sprinkler system Temperature (x2), smoke (x2), gas (x2), flood (x2), humidity (x4), door (x4)

2438 × 2990 × 2896mm (Per Container) < 16,000kg (Per Container)

More Information

Delta Electronics
16 Tungyuan Road, Chungli Industrial Zone, Taoyuan City 32063, Taiwan TEL: +886 3 4526107 EISBG.Marketing@deltaww.com www.deltaww.com

2024 / 02



References